Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 7CD, 9EFG
Applications
• Manual motor starters are available to meet any plant
installation requirement.
• They may be used to install a variety of electrical wiring devices
and comes complete with covers and dead-end or feed-thru
hub arrangements. Available with or without the heater.
• Complete units are ideal for manual starting of small Vac or
Vdc motors in locations made hazardous by the presence of
ammable vapors, gases or combustible dust.
Features
• Easily readable operator handle with provisions for padlocking
in the ON or OFF position.
• Cast in hubs.
• Interchangeable heater units.
Standard Materials
• Body and cover: malleable iron
• Sealing chamber: copperfree (4/10 of 1% max.) aluminum
• Operating handle: nylon
Standard Finishes
• Body and cover: gray epoxy powder coat
Options
• For Aluminum Backbox and Cover add sufx -SA.
• Starters are furnished with one interchangeable heater. Select
heater number from heater selection table and add appropriate
sufx to catalog number. For example, a complete catalog
number with Allen-Bradley motor starter and Allen-Bradley
0-17 amp heater: EPS2199-P1.
✢ Cutler-Hammer is a registered trademark of Eaton Corporation.
Ordering Instructions: Starters and starter cover assemblies are furnished with one interchangeable heater. Select heater number from heater selection
table and add appropriate suffix to catalog number. For example, a complete catalog number with Cutler-Hammer motor starter and Cutler-Hammer heater:
EDS11101-W1. Available in aluminum — add suffix -SA.
324
Page 3
Contender™ Series Factory Sealed Manual Motor Starters
Allen-Bradley is a registered trademark of Rockwell Automation.
Ordering Instructions: Starters are furnished with one interchangeable heater. Select heater number from heater selection table and add appropriate suffix
to catalog number. For example, a complete catalog number with an Allen-Bradley motor starter and an Allen-Bradley heater: EDS1199-P5. Available in
aluminum; add suffix -SA.
325
Page 4
Contender™ Series Factory Sealed Manual Motor Starter and Contactor Heaters
Allen-Bradley and Cutler-Hammer ✢ heaters and starters are not interchangeable with each other.
NEC/CEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 7CD, 9EFG
The ”Full Load Motor Current” listed in the tables below are ratings
which determine the proper heat element that should be used with
the EDS Series starters. Refer to motor nameplate for its full load
motor current. It is our recommendation that for normal conditions
the heater element selected should have a capacity of 20 to 25%
greater than the full load current of the motor. This applies to
standard +40 °C (+104 °F) temperature rise motors. For +50 °C
(+122 °F) rise motors, a heater not greater than 115% full load
current should be selected.
Allen-Bradley
✢ Cutler-Hammer is a registered trademark of Eaton Corporation.
Allen-Bradley is a registered trademark of Rockwell Automation.
Full Load Motor
Current (Amp)
0.17P10.40-0.430.50W1
0.21P20.44-0.480.55W2
0.25P30.49-0.530.61W3
0.32P40.54-0.580.67W4
0.39P50.59-0.640.74W5
0.46P60.65-0.710.81W6
0.57P70.72-0.780.89W7
0.71P80.79-0.870.98W8
0.79P90.88-0.951.10W9
0.87P100.96-1.031.20W10
0.98P111.04-1.151.30W11
1.08P121.16-1.271.45W12
1.19P131.28-1.351.60W13
1.30P141.36-1.511.70W14
1.43P151.52-1.671.90W15
1.58P161.68-1.832.10W16
1.75P171.84-1.992.30W17
1.88P182.00-2.232.50W18
2.13P192.24-2.472.80W19
2.40P202.48-2.713.10W20
2.58P212.72-2.953.40W21
2.92P222.96-3.273.70W22
3.09P233.28-3.594.10W23
3.32P243.60-3.994.50W24
3.77P254.00-4.395.00W25
4.16P264.40-4.795.50W26
4.51P274.80-5.266.00W27
4.93P285.27-5.836.60W28
5.43P295.84-6.397.30W29
6.03P306.40-7.038.00W30
6.83P317.07-7.748.80W31
7.72P327.75-8.469.70W32
8.24P338.47-9.3510.60W33
8.90P349.36-10.3011.70W34
9.60P3510.31-11.3512.90W35
10.80P3611.36-12.4714.20W36
12.00P3712.48-13.6715.60W37
13.50P3813.68-15.1217.10W38
15.20P3915.13-16.0018.60W39
Add Suffix
Contender/EDSContender
However, due to the difference between full load motor currents of
various motor manufacturers of the same size motors, the above
information is approximate.
If selection of heater element is uncertain as might be in the
case of a motor subject to frequent starting and
it is advisable to contact
representative giving full particulars, such as motor horsepower,
voltage, phase cycles, name or manufacturer or pertinent data that
may aid in the selection of the proper heater element.
Cutler-Hammer ✢
Full Load Motor
Current (Amp)
the starter manufacturer or his local
Heater Rating
(Amp)
intermittent load,
Add Suffix
326
Page 5
Contender™ Series Factory Sealed Manual Motor Starter Mounting Bodies