654105-000
INSTRUCTION MANUAL
AA-51 SERIES, INCANDESCENT LIGHTING FIXTURES
EGS Electrical Group • 7770 North Frontage Road • Skokie, Illinois 60077
Rev. C 08/28/01 Page 1
INSTALLATION AND MAINTENANCE DATA SHEET
The fixture unit MUST BE installed with one of the following
mounting hoods for safe operation.Failure to use fixture
unit with one of the following mounting hoods voids warranty as well as the U.L. Listing and creates the risk of fire
or explosion.
DIRECTIONS FOR FIXTURE
INSTALLATION
Use the installation drawing as a guide. Install mounting
hood first as all wiring connections are made in the mounting
hood. The fixture unit requires no internal wiring
connections.
1. Remove the connection bloc k (VPT-7) from the mounting
hood by loosening (but not removing) the two Phillips
head screws.T urn connection bloc k counter-cloc kwise to
remove.
2. When using ceiling (AAC- ) or short bracket (AASB-),
mounting hoods, threaded adapter (59064050000) can
be removed by lifting gasket (59064034000) to access
set screw.
• Loosen set screw and turn adapter counter-clockwise for
easier access to junction box.
3. Install mounting hood to conduit system (and/or
wall or ceiling). If usi ng pendant, secure the hood to
the conduit system with the set screw.
4. Pull supply wires from the conduit into the junction box.
• Use supply wire rated 110° C minimum.
5. Secure threaded adapter (where applicable) to junction
box and tighten all set screws. Make connection of supply wires to the VPT-7 connection block by attaching
“hot“ voltage lead to the brass terminal and common
"neutral" lead to silver terminal.
6. Secure VPT-7 connection block to threaded adapter or
mounting hood by slipping over Phillips head screws;
turning clockwise and tightening screws.
7. Install lamp into fixture unit. See directions under "Lamp
Installation Instructions."
8. Inspect threads of mounting hoods and of the fixture
unit to be sure they are clean and free of damage.
Inspect globe for any chips, scratches or cracks.
CAUTION
9. Thread the fixture unit into mating threads of mounting
hood until tight against gasket of mounting hood.Locking
spring of fixture unit should engage with notches on
mounting hood.
10. Install guard and/or reflector if desired. Check tightness
of set screws and all threaded joints.Activate supply circuit to test fixture.
KEEP THIS MANUAL FOR FUTURE REFERENCE
AA-51 Series lighting fixtures for Hazardous
Location.
Class I, Div. 1 & 2, Groups A, B, C, D
Suitable for Group A, when used with Pendant Mount Only
Class II, Div. 1, and 2, Groups F and G
Class III
WARNING GENERAL
1. DO NOT MODIFY UNIT IN ANY W AY. Modification may
affect safety and reliability.
2. Improper use or failure to follow these instructions could
result in serious injury or proper ty damage.
3. Operator should be instructed in the safe and proper
usage and maintenance of this product.
WARNING ELECTRICAL
1. Disconnect electrical power before installation, adjust-
ment and maintenance.
2. DO NOT overload; the amperage and voltage indicated
on the name plate must not be exceeded.
3. Check continuity before connecting electrical power.
4. All installations must comply with applicable local and/or
National Electrical Code.
5. Before installing check fixture unit nameplate and carton
labels to be sure you have correct fixture and mounting
hood. Circuit must be deactivated before installing fix-
ture.
CAUTION GENERAL
1. All AA-51 Series Fixtures are to be mounted ver tically
with lamp base up.
• FREE OF
CHIPS OR
CRACKS
Chipped, scratched or cracked
globes will fail. Replace any
such defective lamp housing.
The AA-51 fixture MUST BE installed with:
FIGURE 1
AAP-50, AAP-75
Pendant Hood - ONLY
*Group A with this hood.
(One Hub) Rigid or flexible
mounting.
AAC-50, AAC-75
Ceiling Hood (Four hubs
three close-up plugs)
AASB-50, AASB-75
Short Wall Bracket Hood
(Two hubs one close-up
plug)
IMPORTANT: Remove all unused conduit plugs
and reinstall with pipe sealant.