www.apollovalves.com Customer Service (704) 841-6000
BFMM PVB4A
PRESSURE TYPE VACUUM BREAKER 1/2” – 2”
I. DESCRIPTION AND OPERATION
The Apollo PVB4A Series Pressure Type Vacuum Breaker consists of a replaceable check valve cartridge and a unique atmospheric
vent bonnet/oat assembly located between two resilient seated shut-o valves. The modular design allows for unprecedented
ease of inspection and maintenance.
During normal ow conditions, the check valve remains open and the oat seals on the bonnet assembly. A minimum supply
pressure of 10 psig is normally required to fully shut the oat. As the line pressure falls to 1 psig, a spring-loaded atmospheric
vent valve opens, breaking the vacuum and thereby preventing back-siphonage. In the event of exposure to short-term freezing
temperatures, a spring-loaded relief valve in the oat protects the PVB body and internal components from damage. As the
temperature increases above freezing, the relief valve automatically reseats. During normal operating conditions, the relief valve
will not discharge.
NOTE: The freeze resistant feature is for a short term dip in temperature. The PVB should be winterized for extended periods
below freezing.
II. INSTALLATION
Pressure vacuum breaker assembly’s critical level (CL is marked in raised lettering on the body of the PVB) should be installed at
least 12 inches above the highest piping or outlet downstream of the device and with the supply line connected to the bottom of
the device. Install the device in an accessible location to facilitate periodic eld-testing and any required maintenance. Contact
local water authorities for installation/service requirements.
Flush upstream piping thoroughly to remove foreign matter prior to installation. Use pipe dope sparingly on external threads
only. When initially pressurizing the device, some spillage of water from the air inlet may occur.
To winterize the valve:
1. Secure the water source at a location that will not freeze.
2. Open #1 and #2 test cocks to drain the PVB.
3. Place the inlet and outlet isolation ball valves in the halfway open/shut position.
4. If possible, blow the lines clear with pressurized air.
Customer Service (704) 841-6000 www.apollovalves.com
3
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
Figure 1
(FLOWING CONDITION)
Figure 2
(NO FLOW CONDITION)
III. TROUBLE SHOOTING
SYMPTOMCAUSECORRECTIVE ACTION
1. Air inlet fails to open or opens
below 1 psig.
2. Air inlet fails to close.
3. Check valve fails to hold 1 psig.
4. Water continues to ow from test
cock #2 during test #2.
a. Float not moving freely.
b. Float disc sticking to seat.
a. Float not moving freely.
b. Float disc fouled with debris.
a. Check valve fouled with debris.
b. Check valve seat damage.
a. #1 shut-o valve not completely
closed
a. Inspect for fouling debris or
deposits.
b. Clean oat seat area on bonnet
and replace oat disc/turn disc
over.
a. Inspect for fouling debris or
deposits.
b. Clean oat seat area on bonnet
and remove debris.
a. Remove, clean, or replace check
valve.
b. Replace seat
a. Close #1 shut-o valve.
4
www.apollovalves.com Customer Service (704) 841-6000
BFMM PVB4A
IV. MAINTENANCE INSTRUCTIONS 1/2” – 2”
A. Disassembly
1. Close #2 shut-o valve, then close #1 shut-o valve.
2. Bleed pressure from device by opening test cocks #1 and #2.
3. Remove the air inlet canopy by loosening the two screws, rotating the canopy to the left, and lifting up.
4. Unscrew and remove the bonnet and oat assembly. DO NOT USE CANOPY TO UNSCREW BONNET! DAMAGE TO THE
CANOPY MAY OCCUR.
5. Remove oat cage.
6. Push down and turn the spring retainer 90° to remove. Remove the spring. Remove the poppet from the check seat.
CAUTION: Do not use pliers or other tools, which may damage or scratch the plastic stem.
7. Holding the poppet assembly in one hand, remove screw and retaining washer.
8. Remove the seat disc.
9. All parts should be carefully inspected for any damage or excessive wear and thoroughly rinsed in clean water prior to
reassembly. Replace worn parts as necessary.
10. Normally, the check seat need not be removed. If removal is required, rock it back and forth while pulling outward.
B. Assembly
1. If the check seat was removed, install the new o-ring and lubricate with Apollo supplied lubricant, DOW 111, or equal. Line
up the seat with the bore and push it rmly into place.
2. Install new disc in poppet and secure with washer and screw.
3. Place and center the poppet assembly in the check seat.
4. Install the spring onto the poppet, ensure that it is centered around the raised spring pad.
5. Install the spring retainer onto the spring by pushing down into the grooves of the check seat and turning 90°. Ensure spring
retainer pops up about .1” and locks into the lugs. CAUTION: Ensure the spring retainer orientation matches that in the
parts list drawing or the device’s ow will be signicantly restricted.
6. Install oat cage and oat. See drawing for correct orientation.
7. Apply a thin coat of Apollo supplied lubricant, DOW 111 or equal onto o-ring, screw bonnet into body.
8. Test device to insure proper installation.
9. Install air inlet canopy.
Customer Service (704) 841-6000 www.apollovalves.com
5
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
V. TESTING PROCEDURES
Equipment Required: Dierential Pressure Test Kits 40-200-TKU or 40-200 TK5U.
NOTE: These procedures may or may not be approved in all jurisdictions. Consult your local water purveyor for acceptable
test procedures.
Test Setup
1. Obtain permission to shut o the water supply.
2. Determine the direction of ow.
3. Identify and “blow out” test cocks and install appropriate adapters (if necessary).
4. All test kit valves are closed.
IMPORTANT: THE TEST KIT AND HOSE MUST BE HELD AT THE SAME LEVEL AS THE PVB DURING TESTS 1 AND 2.
TEST NO. 1
DOES THE AIR INLET VALVE OPEN WHEN THE PRESSURE IN THE BODY IS AT LEAST 1 PSI ABOVE ATMOSPHERIC PRESSURE? IS
THE AIR INLET VALVE FULLY OPEN WHEN WATER DRAINS FROM THE BODY?
1. Remove air inlet valve canopy.
2. Connect a hose between test cock #2 and the high side connection on the test kit. Open test cock #2.
3. Bleed the high side by opening bleed high valve (high and bypass valves on a 3-valve test kit). Close the bleed high valve
(high valve on 3-valve test kit).
4. Close #2 shut o valve, and then close #1 shut o valve.
5. SLOWLY open the bleed high valve (high valve on 3-valve test kit) no more than 1/4 turn, dropping the pressure slowly. Record pressure reading when the air inlet valve opens. It should be 1PSI or higher. If the air inlet valve does not open
go to step #8.
6. Fully open the bleed high valve (high valve on 3-valve test kit). Check if the air inlet valve is fully open. Close the bleed high
valve (high valve on a 3-valve test kit).
7. Close test cock #2. Disconnect the high hose from test cock #2. Open shut o valve #1. Proceed to Test #2.
8. The #1 shut o valve is leaking. Open and close shut o valve #1 to attempt a better seal. Repeat step #6. If step #6 cannot
be passed go to step #9.
9. SLOWLY open test cock #1 until the gauge reading starts dropping. Record the pressure reading when the air inlet valve opens. (It should be 1 PSI or higher.) Return to step #7. If test cock #1 is fully open and the air inlet valve has not opened,
shut o valve #1 must be repaired or replaced.
TEST NO. 2
DOES THE CHECK VALVE SEAL IN THE DIRECTION OF FLOW WHEN THE INLET PRESSURE IS 1 PSI ABOVE ATMOSPHERIC
PRESSURE? – PRESSURE TIGHT #1 SHUT-OFF VALVE
1. Connect high side hose to test cock #1. Open test cock #1.
2. Bleed the high side by opening the bleed high valve (high valve on a 3-valve test kit). Close the bleed high valve (high valve
on a 3-valve test kit).
3. Close shut o valve #1 then open test cock #2.
4. Record the gauge reading when water stops draining from test cock #2. It should be 1 PSI or higher.
5. Close all test cocks. Open both shut o valves. Remove all test equipment. Replace air inlet valve canopy. Drain test kit.
6
www.apollovalves.com Customer Service (704) 841-6000
BFMM PVB4A
V. TESTING PROCEDURES (continued)
TEST NO. 3
LEAKY #1 SHUT-OFF VALVE
1. Connect a bleed-o valve assembly (not included with test kit) to test cock #1.
2. Connect high side hose to the bleed-o valve. Open test cock #1.
3. Bleed the high side by opening the bleed high valve (high valve on a 3-valve test kit). Close the bleed high valve (high valve
on a 3-valve test kit).
4. Close shut o valve #1, then open test cock #2.
5. Slowly open the bleed-o valve at test cock #1 until the water ow stops draining from test cock #2. Record the gauge
reading. (It should be 1 PSI or higher.) If the ow from test cock #2 cannot be stopped by opening the bleed-o valve, shut
o valve #1 must be repaired or replaced.
6. Close all test cocks. Open both shut o valves. Remove all test equipment. Replace air inlet valve canopy. Drain test kit.
Figure 3
Customer Service (704) 841-6000 www.apollovalves.com
7
INSTALLATION, OPERATION, & MAINTENANCE MANUAL
PARTS LIST (1/2” – 2”)
Figure 4
8
www.apollovalves.com Customer Service (704) 841-6000
Customer Service (704) 841-6000 www.apollovalves.com
1/2” – 3/4”1”1-1/4” – 1-1/2”2”
Size
11
SALES & CUSTOMER SERVICE:
Phone: (704) 841-6000
Fax: (704) 841-6020
www.apollovalves.com
AGENCY AREAS COVERED EMAIL PHONE FAX
Mid South Marketing, Inc. VA/MD/Washington, D.C./WV-East midsouth7@aol.com 804-213-3801 804-213-3802
Pro Marketing, Inc. NC/SC/TN-East sales@promarketinginc.net 864-578-4334 864-578-4889
Spirit Group FL (except Panhandle) info@spiritgroupinc.com 407-291-6035 407-299-0378
REGION
Tim Morales & Associates, Inc. AL/FL Panhandle sales@timmorales.com 251-602-8333 251-602-8339
SOUTHEAST
White Wolf Group GA info@whitewolfgroupinc.com 800-401-4870 888-908-9372
BWC Inc. LA (Commercial Products) chuck@bwcassoc.com 504-734-0229 504-734-3711
Marathon Flow Control TX, OK, KS except Northeast, LA (Industrial) sales@marathonowcontrol.com 214-201-0100 214-201-0104
REGION
Southern Marketing Group MS/TN-West/AR/Bowie Cty.-TX SMG49@bellsouth.net 901-547-0042 901-547-0035
New Tech Marketing MO/Southern IL/Northeast Kansas ntm112@aol.com 618-394-0329 618-394-0427
MIDWESTERN
V.E. Sales Co., Inc. MI (Except Upper Peninsula) tomv@vesalesinc.com 586-774-7760 586-774-1490
Elmco Duddy CA - South tduddy@elmcoduddy.com 626-333-9942 626-855-4811
Gordon & Associates WA, OR, AK, Northern counties ID laura@gordonandassoc.com 360-566-1470 360-566-1478
HC Fletcher CA - North (AB 1953 compliant product) apollosales@hcetcher.com 800-432-7047 949-660-9072
Marshall-Rodeno Associated CO/WY/MT/ID-SE/UT/NV-NE/NM/El Paso-TX trodeno@marshallrodeno.com 303-575-6701 303-575-6706
Romatec CA - North PVF (non AB 1953) apollo@romatec.com 877-530-3530 661-588-3534
REGION
WESTERN
Southwest Valves CA (Waterworks and Fire Protection) d.burell@southwestvalve.com 559-261-2703 559-261-2711
Southwestern Industrial Sales Co. AZ/Nevada-SW eduardop@sw-ind.com 480-458-5838 480-458-5843
Spec Management Group HI msmarch4@cox.net 949-481-4225 949-487-0990
Conroy & Griese Sales, Inc. NY-East/NJ-Nor th iezzi52@aol.com 856-663-4440 856-663-6644
Keith Engle & Associates OEM accounts keith.engle@verizon.net 610-827-9560 610-827-9561
Layden Company NY-Upstate/PA-East/DE/NJ-South joejr@laydencompany.com 610-363-6657 877-529-3361
REGION
NORTHEAST
Urell, Inc. MA/New England States conbraco@urell.com 617-923-9500 617-926-9414
Active Sales Northwest, Inc. OR, WA, Western ID skactive@aol.com 541-726-0320 541-726-1148
Biz Sales Company OH, KY, MI, IN, parts of PA, WV, WI dzavelson@bizpvf.com 216-595-2888 216-595-2899
Fourmation Sales MN/ND/SD/WI-West dean@fourmationsales.com 763-262-4700 763-262-4740
Hall Marketing AL, LA hallmarketing@bellsouth.net 228-547-4637 228-832-6666
J&J Midwest Sales NE, IA, MO, KS john@jandjmidwestsales.com 314-422-8419
Jim Benton & Associates AL, FL Panhandle jim@bentonandassoc.com 205-664-1221 205-664-1277
John Hart FL jhart@lascottings.com 772-595-7773 772-489-4305
Larry Perkins TX - Southern lperkins@lascottings.com 936-443-1096
Marel Enterprises New England, NY, DE, MD, VA, DC, pa rts of PA & WV marelenterprise@gmail.com 631-271-1718 631-427-8558
Marshall-Rodeno Associated CO/WY/MT/ID-SE/UT/NV-NE trodeno@marshallrodeno.com 303-575-6701 303-575-6706
NSC Marketing Group Inc. OK nsc_tulsa@sbcglobal.net 918-627-5340 918-664-1408
IRRI GATI ON O NLY REP S
Pro Marketing, Inc. NC/SC/TN-East sales@promarketinginc.net 864-578-4334 864-578-4889
Sherman Dobbs TX - Northern sdobbs@lascottings.com 469-442-8510 972-417-9733
Southern Marketing Group MS/TN-West/AR/Bowie Cty.-TX SMG49@bellsouth.net 901-547-0042 901-547-0035
Spec Management Group CA-South msmarch4@cox.net 949-481-4225 949-487-0990
VPC Sales AZ chudson@vpcsales.com 661-257-3923 661-257-3928
Agences J. Pierre Sylvain, Inc. Quebec agencespsylvain@golden.net 450-655-9588 450-641-2737
Barclay Sales Ltd. British Columbia bbarclay@barclaysales.com 604-945-1010 604-945-3030
Conbraco Industries, Canada 178 Pennsylvania Ave., Unit 1, Concord, Ontario L4K 4B1 conbraco.canada@conbraco.com 905-761-6161 905-761-6666
D & M Mechanical Sales Ontario/East don@dandmsales.ca 613-384-7084 613-384-3407
Dynamic Agencies, Ltd. Saskatchewan doug.dynamicage@sasktel.net 306-343-1901 306-343-1901
J. Levandier Sales, Inc. Nova Scotia, New Brunswick, Prince Edward
Island & Newfoundland service@jlevandiersales 506-858-1615 506-858-1084
CANADA
Kern Industries, Ltd. Alberta-North kernind@telusplanet.net 780-451-2056 780-454-6687
Kern Industries Calgary, Ltd. Alberta-South marty.yucytus@kernindustries.ca 403-730-7791 403-239-8179
Key to the North Sales Agency, Inc. Ontario-North hmehes@keytothenorth.ca 705-524-6714 705-566-0148
Task Controls, Inc. Ontario infotoronto@taskcontrols.com 416-291-3004 416-754-3481
Tom Beggs Agencies Ltd. Manitoba/NW Ontario tba@mts.net 204-953-1900 204-774-6915
BFMMPVB4A 1/12 3,000 CG
current rep list as of 1/11/12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.