Apollo Conbraco DCLF4A, DC4A Installation Manual

INSTALLATION, OPERATION & MAINTENANCE MANUAL
BACKFLOW
BFMM DC4A SBF | EFFECTIVE AUGUST 1, 2016
Model DC4A / DCLF4A
1/2” - 2” Double Check Valve (DC) Backflow Preventer
TABLE OF CONTENTS
Double Check Valve Backow Preventer 1/2” – 2”
Section Page
I Description and Operation ......................................................................3
II Installation .....................................................................................3
III Trouble Shooting Guide.........................................................................5
IV Maintenance Instructions .......................................................................5
V Testing Procedures............................................................................6-7
Parts List
Parts List (1/2”- 2”) .......................................................................... 8-10
Repair Kits
Repair Kits (1/2”- 2” ) ..........................................................................11
2
www.apollovalves.com Customer Service (704) 841-6000
BFMM DC4A SBF
DOUBLE CHECK VALVE BACKFLOW PREVENTER 1/2”  2”
I. DESCRIPTION AND OPERATION
The Double Check Valve (DC) device consists of two independently-acting, spring-loaded check valves. Two resilient seated shut­o valves and four test cocks complete the assembly. Each check is designed to maintain a minimum of 1 psi across the valve during normal operation. If at any time the pressure downstream of the device increases above the supply pressure, both check valves will close to prevent any backow from occurring. The owing and no ow conditions are illustrated in gures 1 and 2. To initiate ow, supply pressure must be sucient to open both checks and overcome friction, normally a minimum of 3 to 5 psi above the downstream pressure.
II. INSTALLATION
A. The DC must be installed in an accessible location to facilitate periodic eld testing and maintenance. B. Flush all upstream piping thoroughly to remove foreign matter prior to installing the device. C. The device should be installed either horizontally or vertical up for ease of maintenance and testing. A clearance between the lower most portion of the device and ood grade or oor should be provided for ease of maintenance. D. When shut-o valves are provided separately, they should be installed with a test cock on the upstream side of the inlet shut­ o valve. E. After installing the assembly and with downstream or #2 shut-o valve closed, pressurize the device and bleed ALL air through test cock #4. Then open #2 shut-o valve.
Customer Service (704) 841-6000 www.apollovalves.com
3
Figure 1
FLOWING CONDITION
Figure 2
NO FLOW CONDITION
NOTE: Pressures shown are for illustrative purposes only and are not necessarily indicative of any actual valve.
4
www.apollovalves.com Customer Service (704) 841-6000
Loading...
+ 8 hidden pages