APG warrants its products to be free from defects of material and workmanship
and will, without charge, replace or repair any equipment found defective upon
inspection at its factory, provided the equipment has been returned,
transportation prepaid, within 24 months from date of shipment from factory .
THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER
WARRANTIES NOT EXPRESSLY SET FORTH HEREIN, WHETHER
EXPRESSED OR IMPLIED BY OPERATION OF LAW OR OTHER WISE
INCLUDING BUT NOT LIMITED T O ANY IMPLIED WARRANTIES OF
MERCHANT ABILITY OR FITNESS FOR A P AR TICULAR PURPOSE.
No representation or warranty, express or implied, made by any sales
representative, distributor, or other agent or representative of APG which is not
specifically set forth herein shall be binding upon APG. APG shall not be liable
for any incidental or consequential damages, losses or expenses directly or
indirectly arising from the sale, handling, improper application or use of the
goods or from any other cause relating thereto and APG’s liability hereunder, in
any case, is expressly limited to the repair or replacement (at APG’s option) of
goods.
Warranty is specifically at the factory. Any on site service will be provided at
the sole expense of the Purchaser at standard field service rates.
All associated equipment must be protected by properly rated electronic/
electrical protection devices. APG shall not be liable for any damage due to
improper engineering or installation by the purchaser or third parties. Proper
installation, operation and maintenance of the product becomes the
responsibility of the user upon receipt of the product.
Returns and allowances must be authorized by APG in advance. APG will
assign a Return Material Authorization (RMA) number which must appear on
all related papers and the outside of the shipping carton. All returns are subject
to the final review by APG. Returns are subject to restocking charges as
determined by APG’s “Credit Return Policy”.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
The RPE/RPX utilizes reed switches in the instrument’s stem and a permanent
magnet in the float. As the float rises or falls with the level of the liquid, the
magnet inside the float act on the reed switches inside the stem and provides a
resistive-chain output. The RPE/RPX is also available with optional
electronics that convert the resistance output into a 4-20mA signal.
4
APG...Providing tailored solutions for measurement applications
When unpacking the instrument, exercise care not to subject the instrument to
mechanical shock. After unpacking, visually inspect the instrument for
damage.
- Environment -
The RPE/RPX series intruments can be installed indoors or outdoors in an
area which meets the following conditions:
1. The ambient temperature does not exceed -400F to 1850F (-400C to 850C).
NOTE: It is recommended that a sun shield be installed over the housing if
exposed to direct sunlight.
2. The medium temperature does not exceed -400F to 1850F (-400C to
850C).
3. Relative humidty up to 100%
4. Pollution Degree 2
5. Measurment Category II
6. Altitude 2000 m or less.
7. Locate the sensor away from strong magnetic fields such as those
produced by motors, transformers, solenoid valves, etc.
8. The medium is free from metallic substances and other foreign matter.
9. No corrosive gases such as NH3, SO2, Cl2, etc.
10. No excessive vibration
11. Ample space for maintenance and inspection.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Do not locate the RPE/RPX sensor near inlets/outlets.
If there is surface wave action, then it may be advisable to use a stilling tube. If
a stilling tube is used, drill vent holes in the tube and use a spacer to assure the
float has free travel inside the tube.
Wave action will cause signal bounce. Use a stilling tube to provide a
smooth output signal.
- Mounting -
The RPE/RPX can be mounted up to 200 from vertical.
1. Flange Mounting
Provide the compatible mating flange on the tank and install using a suitable
gasket.
2. Plug Mounting
Provide the compatible female boss on the tank and install the RPE/RPX with
a suitable gasket, O-ring, or thread tape.