APG RCU-7000 User Manual

Page 1
AUT OMATION
Operator’s Manual
PRODUCTS
GROUP, INC.
Power Relay Unit for Pump Control
Rev . A1, 4/07
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • E-mail: sales@apgsensors.com
Page 2
RCU-7000 Series Rev . A1, 4/07
Table of Contents
Warranty .............................................................................................................3
Introduction ......................................................................................................4
Speci cations ....................................................................................................5
Dimensions ........................................................................................................6
Description of Controls .................................................................................6
Operating Characteristics of Relay Units ................................................7
Principle of Operation ...................................................................................8
Installation .........................................................................................................9
Electrical Connection and Adjustment ................................................11
Maintenance and Inspection ...................................................................15
Troubleshooting ........................................................................................... 16
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
2
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 3
Rev . A1, 4/07 RCU-7000 Series
Warranty and Warranty Restrictions
APG warrants its products to be free from defects of material and workmanship and will, without charge, replace or repair any equipment found defective upon inspection at its factory, provided the equipment has been returned, transportation prepaid, within 24 months from date of shipment from factory.
THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES NOT EXPRESSLY SET FORTH HEREIN, WHETHER EXPRESSED OR IMPLIED BY OPERATION OF LAW OR OTHERWISE INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
No representation or warranty, express or implied, made by any sales representative, distributor, or other agent or representative of APG which is not specifi cally set forth herein shall be binding upon APG. APG shall not be liable for any incidental or consequential damages, losses or expenses directly or indirectly arising from the sale, handling, improper application or use of the goods or from any other cause relating thereto and APG’s liability hereunder, in any case, is expressly limited to the repair or replacement (at APG’s option) of goods.
Warranty is specifi cally at the factory. Any on site service will be provided at the sole expense of the Purchaser at standard fi eld service rates.
All associated equipment must be protected by properly rated electronic/ electrical protection devices. APG shall not be liable for any damage due to improper engineering or installation by the purchaser or third parties. Proper installation, operation and maintenance of the product becomes the responsibility of the user upon receipt of the product.
Returns and allowances must be authorized by APG in advance. APG will assign a Return Material Authorization (RMA) number which must appear on all related papers and the outside of the shipping carton. All returns are subject to the fi nal review by APG. Returns are subject to restocking charges as determined by APG’s “Credit Return Policy”.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
3
Page 4
RCU-7000 Series Rev . A1, 4/07
• Introduction
This relay unit, model RCU-7000 series, may be used with any APG level sensor, such as models ELS, FL, FT, SLS and LF. If the level sensing  oat switch has dry contacts, the RCU-7000 will increase the contact rating capacity. The RCU-7000 is used for control functions such as latching for pump operation or alarm setpoints.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
4
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 5
Rev . A1, 4/07 RCU-7000 Series
• Specifi cations
Operation Versions
RCU-7000: Standard
RCU-7100: High Sensitivity
Characteristics
Power Supply: 90 -132 VAC/180 - 264 VAC, 50/60 Hz
Power Consumption: 1.5 VA max.
Output Signal: SPDT relay contact
Contact Rating: 240 VAC, 5 A; 30 VDC, 5 A
Power Source to Sensor: 8 VAC, 5 mA max.
Cable Length between
Sensors and Relay Units: RCU-7000 - 3,000 ft. (max.);
RCU-7100 - 300 ft. (max.)
Operation Resistance: See Table 1 and 2
Reset Resistance: See Table 1 and 2
Alarm Indicator: Red LED
Power Indicator: Green LED
Environmental
Temperature: 32 to 120°F (0 to 50°C)
Storage Temperature: -4 to 160°F (-20 to 70°C)
Humidity 85% RH max.
Physical Attributes
Housing: ABS
Dimensions: 2 in. x 3 1/8 in. x 4 in.
Mounting Method: 11 pin socket
Weight: 0.62 lb. (280 g)
Speci cations are subject to change without notice for improvement.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
5
Page 6
RCU-7000 Series Rev . A1, 4/07
• Dimensions - in./mm
• Description of Controls
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
6
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 7
Rev . A1, 4/07 RCU-7000 Series
• Operating Characteristics of Relay Units
Table 1 Relay Actuation
RCU-7000 (Standard) Select Switch Mode H. ON side L. ON side Operating resistance (between E0 and E2) 4 Ký or less energize de-energize Reset resistance (between E0 and E2) 15 Ký or more de-energize energize
RCU-7100 (High Sensitivity) Select Switch Mode H. ON side L. ON side Operating resistance (between EO and E2) 50 Ký or less energize de-energize Reset resistances (between E0 and E2) 100 Ký or more de-energize energize
Table 2 Relay Actuation of Latch
RCU-7000 (Standard) Operating/Reset Resistance Select Switch Mode Between E0 and E1 Between E0 and E2 H. ON side L. ON side 1 15 Ký or more 15 Ký or more de-energize energize 2 4 Ký or less 15 Ký or more de-energize energize 3 4 Ký or less 4 Ký or less energize de-energize 4 4 Ký or less 15 Ký or more energize de-energize 5 15 Ký or more 15 Ký or more de-energize energize
RCU-7000 (High Sensitivity) Operating/Reset Resistance Select Switch Mode Between E0 and E1 Between E0 and E2 H. ON side L. ON side 1 100 Ký or more 100 Ký or more de-energize energize 2 50 Ký or less 100 Ký or more de-energize energize 3 50 Ký or less 50 Ký or less energize de-energize 4 50 Ký or less 100 Ký or more energize de-energize 5 100 Ký or more 100 Ký or more de-energize energize
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
7
Page 8
RCU-7000 Series Rev . A1, 4/07
Figure 3: Relay Action
• Principle of Operation
Figure 4: Wiring Schematic
The RCU-7000 is designed to replace the dry contact rating of the level sensing  oat switch. The RCU-7000 can also input two point levels for pump control either for  lling or emptying.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
8
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 9
Rev . A1, 4/07 RCU-7000 Series
• Installation
After unpacking, open shipping cartons of unit and inspect the units for shipping damage. If there is evidence of damage, notify the carrier immediately. Also verify the contents for properly ordered units.
Unpacking
This relay unit has been thoroughly inspected and carefully packed at the factory to prevent from damage during shipment. When unpacking, care must be taken not to damage the instrument with mechanical shock. After unpacking, visually check the instrument exterior for damage.
Note the following points:
• Remove the relay unit from the package carefully. Also, take out the socket from the package if ordered.
• Model number of the relay is indicated on the nameplate. Check it to be sure if it is as required.
• Check exterior for damage. If there is, contact APG.
Installation Location
This relay unit should be installed in an area with the following conditions:
1. Provide ample space for maintenance/inspection.
2. Low relative humidity and no exposure to moisture.
3. No corrosive gases. (Such as HN
, SO2, C12, etc)
S
4. No excessive vibration.
Installation of Relay Unit
This relay unit installation method depends on the mounting type, either 11
pin socket or DIN rail.
The socket (Omron 11PFA) for relay unit is optional.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
9
Page 10
RCU-7000 Series Rev . A1, 4/07
Surface Mounting with Socket
Drill 2-4.5 dia. mounting holes with 15 mm deep or tap A-M4 threads. See
drawing.
Surface Mounting Method
Rail Mounting with DIN Rail (35 mm)
DIN Rail Mounting Method
APG...Providing tailored solutions for measurement applications
10
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Automation Products Group, Inc.
Page 11
Rev . A1, 4/07 RCU-7000 Series
• Electrical Connection and Adjustment
Wiring Diagram for High or Low Level Alarm
High level alarm (Select SW: H.ON side) (a) When the l (b) When the l
switch actuate, relay energize.
1
switch de-actuate, relay de-energize.
1
Low level alarm (Select SW: L. ON side) (a) When the l (b) When the l
switch actuate, relay de-energize.
1
switch de-actuate, relay energize.
1
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
11
Page 12
RCU-7000 Series Rev . A1, 4/07
Wiring Diagram for Dual Level Empty/Fill
Out ow control (Select Sw: H. ON side) (a) When the l (b) When the l (c) When the l (d) When the l
switch actuate as level falls, relay energize.
1
switch de-actuate as level rises, relay energize.
1
switch de-actuate as level rises, relay de-energize.
2
switch actuate as level falls, relay de-energize.
2
In ow control (Select Sw: L. ON side) (a) When the l (b) When the l (c) When the l (d) When the l
switch actuate as level falls, relay energize.
2
switch de-actuate as level rises, relay energize.
2
switch de-actuate as level rises, relay de-energize.
1
switch actuate as level falls, relay de-energize.
1
12
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 13
Rev . A1, 4/07 RCU-7000 Series
Pump Control Wiring Diagram with Low and High Level Alarms (FL Sensor)
Pump Control Wiring Diagram with Low and High Alarms (ELS Sensor)
Caution: To avoid malfunction, the E1 contact must be connected to lower
switch. Actuation direction of switch must be set same direction.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
13
Page 14
RCU-7000 Series Rev . A1, 4/07
(a) When the l4 switch actuate as level rises, relay (no. 3) energize. (b) When the l
switch de-actuate as level falls, relay (no. 1) energize.
1
(c) Relay (no. 2) may be used for control functions such as latching for pump
control.
Caution: Actuation direction of all switches must be “upper ON” (NO) WARNING: Earth terminal “4” shall be grounded. If it is not grounded, you
will get an electric shock.
Wiring Diagram for Dual Pumps Emptying with High Alarm (ELS Sensor)
Note the following points:
• Do not connect the multiple relay units to same level switch. Relay units will malfunction.
• Power supply must be connected in phase
(• To avoid malfunction, the wiring distance should be used within
speci cations. (Refer to Speci cations). If the wiring distance exceed speci cations, the relay unit may be malfunction by tray capacitance between cables or noise.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
14
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 15
Rev . A1, 4/07 RCU-7000 Series
• Maintenance and Inspection
The following annual servicing tasks should be carried out on the sensor
and relay unit.
(1) Remove the sensor from tank carefully. (2) Ensure there is no damage. (3) If sediment or other foreign matters are stained on sensor, clean the
sensor.
(4) Make contact between E0 and E2, and check the relay unit operation. (5) Spare parts should be ordered from APG, whose address appears on
the title page.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
15
Page 16
RCU-7000 Series Rev . A1, 4/07
• Troubleshooting
Problem
Relay unit de-energize with level change
Possible Causes
• Miswiring between sensor and relay unit
• Set for improper select switch (Select SW) mode of relay unit
Remedies
• Ensure the wiring is correct.
• Change the select switch mode (H ON/L ON).
Problem
Relay unit energize with level changes
Possible Causes
• Miswiring between sensor and relay unit
• Set for improper select switch (Select SW) mode of relay unit
• A ection by stray capacitance
Remedies
• Ensure the wiring is correct.
• Change the select switch mode (H ON/L ON).
• Rewire as short as possible
Problem
Relay Chatter
Possible Causes
• Miswiring between sensor and relay unit
Remedies
• Ensure the wiring is correct.
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
16
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 17
Rev . A1, 4/07 RCU-7000 Series
Notes
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
17
Page 18
RCU-7000 Series Rev . A1, 4/07
Notes
18
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 19
Rev . A1, 4/07 RCU-7000 Series
Notes
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
19
Page 20
AUT OMATION
PRODUCTS
GROUP, INC.
APG...Providing tailored solutions for measurement applications
Automation Products Group, Inc.
Tel: 1/888/525-7300 1/435/753-7300 Fax: 1/435/753-7490
e-mail: sales@apgsensors.com
www.apgsensors.com
Automation Products Group, Inc.
1025 W. 1700 N.
Logan, UT 84321
Loading...