APG PT-500 Operating Manual

Page 1
APG
PT-500 Modbus Series
User Manual
Doc #9003999
R
Part #200245
Rev C, 07/19
Page 2
Table of Contents
Introduction ................................................................................................................ iii
Warranty and Warranty Restrictions .................................................................... iv
Chapter 1: Specications and Options.....................................................................1
Dimensions ........................................................................................................................................1
Specications ...................................................................................................................................2
Model Number Congurator .......................................................................................................... 3
Electrical Pinout Table, Power Supply Table, and System Wiring Diagrams.....................4
Chapter 2: Installation and Removal Procedures and Notes ..............................5
Tools Needed .....................................................................................................................................5
Mounting Instructions ................................................................................................................... 5
Electrical Installation ..................................................................................................................... 5
Removal Instructions .....................................................................................................................6
Chapter 3: Programming ............................................................................................6
Modbus Programming .................................................................................................................... 6
Modbus Programming with RST-6001 and APG Modbus Software ...................................... 6
PT-500 Modbus Register Lists .................................................................................................. 7-9
PT-500 Modbus Sensor Parameters - L5 pressure series ...................................................... 10
PT-500 Modbus Sensor Parameters - L31 level series ........................................................... 10
PT-500 Modbus Application Parameters - L31 level series ............................................. 11-15
Chapter 4: Maintenance ...........................................................................................16
General Care .................................................................................................................................... 16
Vent Tube Drying ......................................................................................................................16-17
Repair and Returns ........................................................................................................................ 17
NOTE: Wiring information in this User Manual is specic to the Modbus Series of the
PT-500. If you have a 0-5V, mV/V, or 4-20 mA Series sensor, please consult the factory at 1-888-525-7300, or our website at www.apgsensors.com/support, for the appropriate
manual for your sensor.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 3
Introduction
Thank you for purchasing a PT-500 modbus series submersible pressure transmitter from APG. We appreciate your business! Please take a few minutes to familiarize yourself with your PT-500 and this manual.
PT-500 submersible pressure transmitters oer reliability in harsh industrial conditions. The small size, integrated electronics, wide operating temperature range, and durability make the PT-500 the perfect
instrument for static and dynamic pressure measurement.
Reading your label
Every APG instrument comes with a label that includes the instrument’s model number, part number, serial number, and a wiring pinout table. Please ensure that the part number and pinout table on your label
match your order.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
iii
Page 4
Warranty and Warranty Restrictions
This product is covered by APG’s warranty to be free from defects in material and workmanship under
normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit
https://www.apgsensors.com/about-us/terms-conditions. Contact Technical Support to receive a Return
Material Authorization before shipping your product back.
Scan the QR code below to read the full explanation of our Warranty on your tablet or smartphone.
iv
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 5
Chapter 1: Specications and Options
[91.4mm]
[8.0mm]
• Dimensions
0.99"
[25.1mm]
1/2" NPT
1.00"
[25.4mm]
REMOVABLE
SENSOR CAGE
ASSEMBLY
1.67"
[42.4mm]
3.60"
PT-500 with Reusable Cage
0.99"
[25.1mm]
1/2" NPTM
0.89"
[22.5mm]
0.89"
[22.5mm]
6.47"
[164.4mm]
7.36"
[186.9mm]
0.95"
[24.1mm]
0.89"
[22.5mm]
6.30"
[160.0mm]
7.19"
[182.5mm]
NON-REMOVABLE
CAGE ASSEMBLY
1.65"
[41.9mm]
1/2" NPTM
1.00"
[25.4mm]
3.60"
[91.4mm]
PT-500 with Welded Anti-snag Cage
0.99"
[25.1mm]
0.89"
[22.5mm]
1/2" NPTM
1.00"
[25.4mm]
0.31"
1.98"
[50.3mm]
PT-500 with Tri-clover
Sanitary Fitting
1.00"
[25.4mm]
1/2" NPTM
Ø.188" THRU
PROTECTIVE NOSE CONE
1.00"
[25.4mm]
5.08"
[129.0mm]
5.96"
[151.5mm]
PT-500 with Removable Plastic
Nose Cone
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
4.93"
[125.2mm]
1.44"
[36.6mm]
7.25"
[184.2mm]
1
Page 6
Specications
Performance
Pressure Ranges 0 to 250 PSI
Digital Output Modbus RTU, 4-wire RS-485
Over Pressure 2X FSO Burst Pressure 3.0X FSO 1 Year Stability 0.75% FSO
Accuracy
Linearity, Hystereses & Repeatability ±0.25% of Full Scale (BFSL) up to ±0.1% of Full Scale ±1.0% for ≤ 1 psi Thermal Zero Shift @ 70 °F ±0.045% FSO/°C (±0.025% FSO/°F) Thermal Span Shift @ 70 °F ±0.045% FSO/°C (±0.025% FSO/°F)
Environmental
Operating Temperature -40 to 85°C / -40 to 185°F
Compensated Temperature
≤ 10 psi: 0º - 60ºC / 32º - 140ºF > 10 psi: -10º - 70ºC / 14º - 158ºF
Maximum Submersible Depth 575 ft / 175.25 m / 250 psi
Electrical
Supply Voltage (at sensor) 5-28 VDC Current Draw 2 mA max.
Protection Reverse Polarity and Surge (per IEC 61000-4-5)
Load Limitation R Startup Time 200 ms
= ((Vs-12V)/0.02A)-(0.042Ω per ft. of cable)
(max)
Materials of Construction
Wetted Materials 316L Stainless Steel Anti-snag Cage 316L Stainless Steel Cable Urethane, PVC, or Hytrel
Protective Nose Cone Delrin Seal Viton ETP-s
Mechanical
Pressure Connection See model number congurator for complete list
Cable Tensile Strength Up to 200 pounds
Patents
US Patent No. 7,787,330
2
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 7
Model Number Congurator
Model Number: PT-500_____ - _____ - _____ - _____ - _____ - _____ - _____ - _____ - _____
A B C D E F G H I
A. Cable Type
□ -▲ Urethane - Blue □ B Hytrel .31” Ø - Black C PVC - Black D Hytrel .25” Ø - Black
B. Pressure Range
Specify range in desired unit of measure
__________ Max Water Depth
575 ft. (175.25 m), 250 psi
C. Standard Units of Measure
PSI FTH2O
INH2O MMH2O
D. Pressure Type (Venting) Range
G Gauge (open vent tube) -- 0 - 250 psi A Absolute (sealed vent tube) -- 10 - 200 psi S Sealed (sealed vent tube) -- 4 - 20 psi
F. NPTM
E0▲ 1/2” NPTM tting for conduit,with pigtail □ E5 Pigtail without conduit connection
G. Process Connection
P1▲ 1/2” NPTM with removable plastic nose cone □ P5 1/4” NPTF P37 Welded Cage (anti-snag 1 piece tting) P38 1-1/2” tri-clover with 3/4” diaphragm P39 Reusable Cage (includes P38 tting)
H. Accuracy
Greater than 1 PSI
N0▲ ±0.25% □ N1 ±0.25% with NIST certication N2 ±0.1% with NIST certication
1 PSI and Below
N3 ±1% N4 ±1% with NIST certication
E. Output
L1
L3 0-5V, 4-wire* L9 10 mV/V, 4-wire* L12 1-5V, 4-wire* L21 1-10V, 4-wire*
L5 Modbus RTU, 4-wire RS-485*†
Pressure reading only
L31 Modbus RTU, 4-wire RS-485 *† Level calculations, tank volume
Note: *Indicates this option does not yet have CSA
Approvals.
Note: †Indicates Field Adjustable Zero feature is not
included.
4-20 mA, 2-wire
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
I. Cable Length
(specify length of cable needed in feet)
Note: ▲Indicates this option is standard.
3
Page 8
Electrical Pinout Table, Supply Power Table, and System Wiring Diagrams
PT-500 Modbus Series Pinout Table PT-500 Modbus Series Supply Power Table
Modbus
Red + Power
Black - Power
Pigtail
Green B (TX-)
White A (TX+)
Shield Case Gnd
Modbus System Wiring
Power Supply
Master Device
Note: PT-500 modbus sensors use reversed TX+/TX- pins. When connecting to your system, ensure continuity of TX- to TX- and TX+ to TX+, rather than A to A and B to B.
+5-28 Vdc
GND
RS-485 A (TX+)
RS-485 B (TX-)
120 Ω
terminating resistor
Use Shielded Cable
PT-500 modbus series sensor
Sensor 1
V+
B (TX-)
A (TX+)
GND
Modbus
Power Supply 5-28 VDC
PT-500 modbus series sensor
Sensor 2
V+
B (TX-)
A (TX+)
GND
PT-500 modbus series sensor
Sensor 3
V+
B (TX-)
A (TX+)
GND
120 Ω terminating
resistor at last sensor
Modbus System Wiring with RST-6001
Modbus
+5-28 Vdc
GND
A
B
-5V
+5V
Equivalent 120 Ω
terminating resistor internal to RST-6001
PT-500 modbus series sensor
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
USB to computer with APG Modbus software
4
Power Supply
RST-6001
Controller
Note: An independent +5-28 Vdc power supply is required when using an RST-6001 Modbus Controller. The RST-6001 can only supply ±5 Vdc, not the +5-28 Vdc required by the modbus series PT-500.
Sensor 1
V+
B A
GND
Use Shielded Cable
PT-500 modbus series sensor
Sensor 2
V+
B
A
GND
PT-500 modbus series sensor
Sensor 3
V+
B A
GND
120 Ω terminating
resistor at last sensor
Page 9
Chapter 2: Installation and Removal Procedures and Notes
• Tools Needed
Wrench sized appropriately for your PT-500’s process or conduit connection.
Thread tape or sealant compound for threaded connections.
Mounting Instructions
Your PT-500 can be mounted in three ways: via NPT process connection, free-hanging suspension, or con­duit mounted. Mounting your pressure transducer is easy if you follow a few simple steps:
Never over-tighten the sensor. In all cases, tighten the sensor as little as possible to create an adequate
seal.
Always use thread tape or sealant compound on tapered threads. Wrap thread tape in the opposite direction of the threads so it does not unravel as you screw the sensor into place. Unraveling can cause uneven distribution and seal failure.
Always start screwing in your sensor by hand to avoid cross-threading. Thread failure can be a problem if you damage threads by over-tightening them or by crossing threads.
For suspension mounting the PT-500, drill a 3/16” hole into the 1/2” NPTF to 1/2” NPTF hex coupler (P/N 511414) and secure it to the 1/2” NPTM coupler tting of the PT-500. Attach a .060” diameter 316L
SS cable of desired length to the hex coupler and secure the steel cable according to your application
requirements.
NOTE: If your PT-500 has a vent tube, do not seal, cover, or close the vent tube with
anything other than an APG-provided venting cap or desiccant drying cartridge (See Fig­ure 4.1 and 4.2). Unapproved seals or covers will prevent proper sensor operation.
• Electrical Installation
Attach the wires of your PT-500 to your control system according to the pinout table above.
IMPORTANT: APG modbus equipment uses reversed TX+/TX- pins. When making connections between APG equipment, ensure continuity of A to A and B to B pins. When connecting APG modbus equipment to other systems, ensure continuity of TX+ to TX+ and TX- to TX-.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
5
Page 10
• Removal Instructions
Removing your PT-500 from service must be done with care. It’s easy to create an unsafe situation, or damage your sensor, if you are not careful to follow these guidelines:
For sensors installed via NPT process connection, make sure the pressure is completely removed from
the line or vessel. Follow any and all procedures for safely isolating any media contained inside the line
or vessel.
Remove the sensor with an appropriately sized wrench (per your process connection).
For suspended sensors, retrieve the sensor from the vessel. Follow any and all procedures for safely
isolating any media contained inside the line or vessel.
Carefully clean the sensor’s tting and diaphragm of any debris (see General Care) and inspect for
damage.
Store your sensor in a dry place, at a temperature between -40° F and 180° F.
DANGER: Removing your process connected PT-500 Pressure Transmitter while there
is still pressure in the line could result in injury or death.
IMPORTANT: Any contact with the diaphragm can permanently damage the sensor.
Use extreme caution.
Chapter 3: Programming
Modbus Programming
PT-500 L5/L31 modbus series sensors use standard Modbus RTU protocol (RS-485). The sensors can only op­erate as slave devices. Sensor default transmission settings are 9600 Baud, 8 Bits, 1 Stop Bit, No Parity, and
require a minimum delay of 300 ms between transactions to return the contents of all registers. Commands returning fewer registers will require shorter delays. See PT-500 Modbus Register Lists on pages 7 - 9.
NOTE: For more information about Modbus RTU, please visit www.modbus.org.
6
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 11
Modbus Programming with RST-6001 and APG Modbus Software
APG RST-6001 Modbus Controller can be used in tandem with APG Modbus to program and control up to 20 PT-500 L5 or PT-500 L31 sensors. Through APG Modbus, you can monitor the raw readings from the sensor, including level or pressure, temperature and battery voltage, or congure the sensor. See PT-500 Modbus Register Lists on pages 7 - 9.
NOTE: For APG Modbus programming instructions, or to download APG Modbus soft-
ware, please visit www.apgsensors.com/support.
PT-500 Modbus Register Lists
Input Registers (0x04)
Register Returned Data
30299 Model Type 30300 Pressure (L5 - PSI; L31 - mmH2O)
30301 N/A
30302 Temperature Reading (in 0C, signed) 30303-30304 Calculated (raw) 30305-30306 N/A
30307 N/A
30308 Battery Voltage 30309 Trip 1 Status
30310 Trip 2 Status
NOTE: The Calculated Readings will be returned without a decimal place. In order to
obtain the true result, the Decimal Place setting must be taken into account.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
7
Page 12
Holding Registers (0x03) - PT-500 L5 pressure series
Register Function Value Range
40400 Device Address 1 to 247
40401 Units 0-16 40402 Application Type 0 or 8
40403 N/A
40404 Decimal (Calculated) 0 - 3 40405 Max Pressure *0 - 32,000 PSI 40406 Full Pressure 0 - 32,000 PSI 40407 Zero Oset -15,000 - 30,000 PSI 40408 Pressure Decimal 0 - 3 40409 A/D Gain *1, 2, 4, 8, 16, 32, 64, 128
40410 N/A
40411 Parameter Default 0 = No; 1 = Restore Defaults
40412 Averaging 0 - 10
40413 Calibration Value *-32,767 - 32,767 40414 Calibration Flag *0 - 300
40415 Sample Rate 10 to 1000 milliseconds
40416 Scale *0 - 65,535 40417 Oset -20,000 - 20,000 40418 Voltage Oset -20 - 20 40419 Baud Rate 0 - 3 (2400, 9600, 19200) 40420 Parity 0 - 2 (none, even, odd) 40421 Stop Bit 0 - 1 (0 = 1 stop bit; 1 = 2 stop bits) 40422-40423 Pressure X^3 *N/A 40424-40425 Pressure X^2 *N/A 40426-40427 Pressure X^1 *N/A 40428-40429 Pressure X^0 *N/A 40430 Trip 1 Pressure -15,000 - 30,000 PSI 40431 Trip 1 Window 0 - 30,00 PSI 40432 Trip 1 Type 0 - 29 40433 Trip 2 Pressure -15,000 - 30,000 PSI 40434 Trip 2 Window 0 - 30,00 PSI 40435 Trip 2 Type 0 - 29 40436-40437 Multiplier 0.0010 - 99.9999 (oat) 40438-40439 Description A - Z, 0 - 9, /.-,+* (16 char) 40446 Temperature Oset -20 - 20 40447-40448 Temperature X^3 *N/A 40449-40450 Temperature X^2 *N/A 40451-40452 Temperature X^1 *N/A 40453-40454 Temperature X^0 *N/A
*Setting is factory calibrated. Do not adjust.
8
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 13
Holding Registers (0x03) - PT-500 L31 level series
Register Function Value Range
40400 Device Address 1 to 247
40401 Units 1 = Feet, 2 = Inches, 3 = Meters
40402 Application Type 0 - 11 40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level *0 - 65,535 mm 40406 Full Level 0 - 65,535 mm 40407 Zero Oset 0 - 610 mm 40408 N/A 40409 A/D Gain *1, 2, 4, 8, 16, 32, 64, 128 40410 Specic Gravity 1 - 2,000 40411 Parameter Default 0 = No; 1 = Restore Defaults
40412 Averaging 0 - 10
40413 Calibration Value *0 - 65,535 40414 Calibration Flag *0 - 300
40415 Sample Rate 10 to 1000 milliseconds
40416 Scale *0 - 65,535 40417 Oset -20,000 - 20,000 40418 Voltage Oset -20 - 20 40419 Baud Rate 0 - 3 (2400, 9600, 19200) 40420 Parity 0 - 2 (none, even, odd) 40421 Stop Bit 0 - 1 (0 = 1 stop bit; 1 = 2 stop bits) 40422-40423 Pressure X^3 *N/A 40424-40425 Pressure X^2 *N/A 40426-40427 Pressure X^1 *N/A 40428-40429 Pressure X^0 *N/A 40430 Trip 1 Level 0 - 65,535 (mm) 40431 Trip 1 Window 0 - 65,535 (mm) 40432 Trip 1 Type 0 - 29 40433 Trip 2 Level 0 - 65,535 (mm) 40434 Trip 2 Window 0 - 65,535 (mm) 40435 Trip 2 Type 0 - 29 40436-40437 Parameter 1 0 - 1,000,000 (mm) 40438-40439 Parameter 2 0 - 1,000,000 (mm) 40440-40441 Parameter 3 0 - 1,000,000 (mm) 40442-40443 Parameter 4 0 - 1,000,000 (mm) 40444-40445 Parameter 5 0 - 1,000,000 (mm) 40446 Temperature Oset -20 - 20 40447-40448 Temperature X^3 *N/A 40449-40450 Temperature X^2 *N/A 40451-40452 Temperature X^1 *N/A 40453-40454 Temperature X^0 *N/A
*Setting is factory calibrated. Do not adjust.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
9
Page 14
PT-500 Modbus Sensor Parameters - L5 pressure series
40401 - Units
Determines the units of measure for the calculated reading.
0 = PSI 5 = mmH2O† 10 = mmHG‡ 14 = inSW 1 = BAR 6 = cmH2O† 11 = cmHG‡ 15 = ftSW 2 = mBAR 7 = mH2O† 12 = inHG‡ 16 = mSW 3 = kPa 8 = inH2O† 13 = kg/cm 4 = MPa 9 = ftH2O†
All H2O pressure measurements @ 20° C.
All HG pressure measurements @ 0° C.
40402 - Application Type
Determines the units of measure for the calculated reading.
0 = Standard (units selected in 40401 are displayed) 8 = Custom (units selected in 40401 and multiplier in 40436-40437 are used to compute desired
units; description in 40438-40439 is label for measurement)
2
PT-500 Modbus Sensor Parameters - L31 level series
40401 - Units
Determines the units of measure for the calculated reading when Application Type is set to 0, 1, or 7.
1 = Feet 2 = Inches 3 = Meters
40402 - Application Type
Determines the type of calculated reading performed by the sensor. 0 = Distance 1 = Level
2 = Standing Cylindrical Tank with or without Hemispherical Bottom
3 = Standing Cylindrical Tank with or without Conical Bottom 4 = Standing Rectangular Tank with or without Chute Bottom
5 = Horizontal Cylindrical Tank with or without Spherical Ends 6 = Spherical Tank 7 = Pounds (Linear Scaling) 8 = N/A 9 = Vertical Oval Tank 10 = Horizontal Oval Tank
11 = Strapping Chart
10
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 15
40403 - Volume Units
Bottom Radius
Determines the units of measure for the calculated reading when Application Type is set to 2 - 6 or 9 -11.
1 = Feet3 5 = Liters 2 = Million Feet3 6 = Inches3 3 = Gallons 7 = Barrels 4 = Meters3
PT-500 Modbus Application Parameters - L31 level series
Application 0 - Distance
Register Function Value Range
40400 Device Address 1 to 247
40401 Units 1 = Feet, 2 = Inches, 3 = Meters
40402 Application Type 0 40403 Volume Units --
40404 Decimal (Calculated) 0 - 3
Application 1 - Level
Register Function Value Range
40400 Device Address 1 to 247
40401 Units 1 = Feet, 2 = Inches, 3 = Meters
40402 Application Type 1 40403 Volume Units --
40404 Decimal (Calculated) 0 - 3
Application 2 - Volume of Standing Cylindrical Tank ± Hemispherical Bottom
Register Function Value Range
40400 Device Address 1 to 247 40401 Units -- 40402 Application Type 2 40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
Full
Level
Diameter
40436-40437 Tank Diameter 0 - 1,000,000 (mm) 40438-40439 Radius of Bottom Hemisphere 0 - 1,000,000 (mm)
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
or
11
Page 16
Application 3 - Volume of Standing Cylindrical Tank ± Conical Bottom
Register Function Value Range
40400 Device Address 1 to 247 40401 Units -- 40402 Application Type 3 40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
40436-40437 Tank Diameter 0 - 1,000,000 (mm) 40438-40439 Cone Diameter (at bottom of cone) 0 - 1,000,000 (mm) 40440-40441 Length (height) of Cone 0 - 1,000,000 (mm)
Application 4 - Volume of Standing Rectangular Tank ± Chute Bottom
Register Function Value Range
40400 Device Address 1 to 247 40401 Units -- 40402 Application Type 4 40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
Full
Level
Full
Level
Tank X
Diameter
Cone
Diameter
Cone
Length
40436-40437 Tank X Dimension 0 - 1,000,000 (mm) 40438-40439 Tank Y Dimension 0 - 1,000,000 (mm) 40440-40441 Chute X Dimension 0 - 1,000,000 (mm) 40442-40443 Chute Y Dimension 0 - 1,000,000 (mm) 40444-40445 Length (height) of Chute 0 - 1,000,000 (mm)
12
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
or
Chute Length
Chute X
Tank Y
Chute Y
Page 17
Application 5 - Volume of Horizontal Cylindrical Tank ± Hemispherical Ends
Register Function Value Range
40400 Device Address 1 to 247 40401 Units -- 40402 Application Type 5 40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
40436-40437 Tank Length 0 - 1,000,000 (mm) 40438-40439 Tank Diameter 0 - 1,000,000 (mm) 40440-40441 Radius of End Hemispheres 0 - 1,000,000 (mm)
Diameter
End Radius
Length
Application 6 - Volume of Spherical Tank
Register Function Value Range
40400 Device Address 1 to 247 40401 Units --
40402 Application Type 6
40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
40436-40437 Tank Diameter 0 - 1,000,000 (mm)
Full
Level
Full
Level
Diameter
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
13
Page 18
Application 7 - Pounds (Linear Scaling)
Register Function Value Range
40400 Device Address 1 to 247
40401 Units 1 = Feet, 2 = Inches, 3 = Meters
40402 Application Type 7 40403 Volume Units --
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
40436-40437 Multiplier (linear scalar) 0 - 1,000,000 (1000 = 1.000)
Application 9 - Volume of Vertical Oval Tank
Register Function Value Range
40400 Device Address 1 to 247 40401 Units --
40402 Application Type 9
40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
40436-40437 Tank Length 0 - 1,000,000 (mm) 40438-40439 Tank Depth 0 - 1,000,000 (mm) 40440-40441 Tank Width 0 - 1,000,000 (mm)
Full
Level
Width
Depth
Length
14
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 19
Application 10 - Volume of Horizontal Oval Tank
Register Function Value Range
40400 Device Address 1 to 247 40401 Units -- 40402 Application Type 10 40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
40436-40437 Tank Length 0 - 1,000,000 (mm) 40438-40439 Tank Depth 0 - 1,000,000 (mm) 40440-40441 Tank Width 0 - 1,000,000 (mm)
Full
Level
Depth
Width
Length
Application 11 - Strapping Chart (Polynomial Values)
Register Function Value Range
40400 Device Address 1 to 247
40401 Units 1 = Feet, 2 = Inches, 3 = Meters
40402 Application Type 11 40403 Volume Units 1 - 7
40404 Decimal (Calculated) 0 - 3 40405 Max Level (factory set) 40406 Full Level 0 - 65,535 mm
40436-40437 X^3 Coecient 0 - 1,000,000 40438-40439 X^2 Coecient 0 - 1,000,000 40440-40441 X^1 Coecient 0 - 1,000,000 40442-40443 X^0 Coecient 0 - 1,000,000
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
15
Page 20
Chapter 4: Maintenance
General Care
Your PT-500 series pressure transmitter is very low maintenance and will need little care as long as it is
installed correctly. However, in general, you should:
For process connected sensors, keep the transmitter and the area around it generally clean.
Avoid applications for which the transmitter was not designed, such as extreme temperatures, contact
with incompatible corrosive chemicals, or other damaging environments.
Inspect the threads whenever you remove the transmitter from duty or change its location.
Avoid touching the diaphragm. Contact with the diaphragm, especially with a tool, could permanently
shift the output and ruin accuracy.
Clean the diaphragm or the diaphragm bore with extreme care. If using a tool is required, make sure it
does not touch the diaphragm.
IMPORTANT: Any contact with the diaphragm can permanently damage the sensor.
Use extreme caution.
Vent Tube Drying
Condensation in the vent tube can damage the electronics in your sensor, resulting in unreliable readings. APG oers two methods of preventing vent tube condensation: a venting cap, and a desiccant drying
cartridge.
The venting cap is a PVC tube with a hydrophobic patch that allows moisture to pass out of the tube without
allowing water in (See Figure 4.1). The cap is sealed by an o-ring, and is easily installed in the eld.
The desiccant drying cartridge with vent tube adapter absorbs any moisture in the vent tube to keep vapor
from condensing (See Figure 4.2). The installation of the desiccant drying cartridge is quick and easy. Common installation methods are cable tie, Velcro, and cable clamps.
IMPORTANT: Do NOT use desiccant cartridge in the presence of vapors or liquids con-
taining phosphate esters, synthetic lubricants, hydrocarbon solvents, methanol, acetone, lacquer solvents, or other organics.
16
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 21
Figure 4.1
Figure 4.2
NOTE: Desiccant crystals change from blue to pink as they become saturated. Car-
tridge must be replaced when all crystals have saturated.
• Repair and Returns
Should your PT-500 series pressure transmitter require service, please contact the factory via phone, email, or online chat. We will issue you a Return Material Authorization (RMA) number with instructions.
Phone: 888-525-7300
Email: sales@apgsensors.com
Online chat at www.apgsensors.com
Please have your PT-500’s part number and serial number available. See Warranty and Warranty Restrictions for more information.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
17
Page 22
APG
R
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Automation Products Group, Inc.
Loading...