Thank you for purchasing an MPI series magnetostrictive level sensor from APG. We appreciate your
business and your trust. Please take a few minutes to familiarize yourself with your MPI and this manual.
The MPI level sensors provide highly accurate and repeatable level readings in a wide variety of liquid level
measurement applications. The MPI-F is certied intrinsically safe for installation in hazardous areas by
CSA, ATEX, and IECEx for Class I, Division 1 and Class I, Zones 0 environments. The MPI-F’s exible stainless
steel stem allows for easier installation in extra tall tanks.
Reading your label
Every APG instrument comes with a label that includes the instrument’s model number, part number,
and serial number. Please ensure that the part number on your label matches your order. The following
electrical ratings and approvals are also listed on the label. Please refer to the CSA Certicate of Compliance
at the back of this manual for further details.
8-24 VDC, Imax = 280 mA
Class I, Division 1, Groups C, D, T4; IP65
Class I, Zone 0, Ex/AEX ia, IIB, T4, Ga
Ex ia IIB, T4 ,Ga
(Ta = -40°C to 85°C)
C
US
Intrinsically Safe Wiring Requirements:
U
ATEX Certicate Number: Sira 19ATEX2072X
II 1G
Ex ia IIB T4 Ga
Ta: -40°C to 85°C
U
IECEx SIR 19.0026X
Ex ia IIB T4 Ga
Ta: -40°C to 85°C
= 28 V, Ii = 280 mA, Pi = 0.850 W, L
i
= 28 VDC, Ii = 280 mA, Pi = 0.850 W , Li = 3.50 μH, Ci = 0.374 μF
IMPORTANT: MPI-F level sensor MUST be installed according to drawing 9009451
(Intrinsically Safe Installation Drawing for Hazardous Locations) on page 23 to meet listed
approvals. Faulty installation will invalidate all safety approvals and ratings.
DANGER: OPEN CIRCUIT BEFORE REMOVING COVER or KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE;
AVERTISSEMENT -- COUPER LE COURANT AVANT D’ENLEVER LE COUVERCLE, ou GARDER LE COUVERCLE
FERME TANT QUE LES CIRCUITS SONT SOUS TENSION.
DANGER: WARNING -- EXPLOSION HAZARD -- SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS I, DIVISION 2;
AVERTISSEMENT -- RISQUE D’EXPLOSION -- LA SUBSTITIOND E COMPOSANTSP EUTR ENDRE CE MATERIEL
INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I, DIVISION 2.
DANGER: WARNING -- EXPLOSION HAZARD -- DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS
BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS;
AVERTISSEMENT -- RISQUE D’EXPLOSION -- AVANT DE DECONNECTER L’EQUIPEMENT, COUPER LE COURANT
OU S’ASSURER QUE L’EMPLACEMENT EST DESIGNE NON DANGEREUX.
Warranty and Warranty Restrictions
This product is covered by APG’s warranty to be free from defects in material and workmanship under
normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit
https://www.apgsensors.com/about-us/terms-conditions. Contact Technical Support to receive a Return
Material Authorization before shipping your product back.
Scan the QR code below to read the full explanation of our Warranty on your tablet or smartphone.
Model Number: MPI - _F_ __5__ _____ - _____ _____ - _____ _____ _____ __B__ - _____ - _____ - _____
A B C D E F G H I J K L
A. Stem Type
□ F 7/8 in. diameter Flexible Tubing with Braid, 316L SS
B. Output
□ 5 Modbus RTU, with surge protection, Intrinsically Safe
C. Housing Type
All Housing Die-cast Aluminum, NEMA 4X, IP68, Blue
▲
□ __
Large Housing
□ B Large Housing with window
D. Float 1 (Top Float)
□ Z 5.5h x 3d in. Red Polyurethane (0.65 SG)
□ Y 5.5h x 3d in. Blue Polyurethane (0.94 SG)
□ X 5 in. Round 316L SS (0.52 SG)
□ W 5 in. Round 316L SS (0.92 SG)
□ V 6h x 3d in. Oval 316L SS (0.58 SG)
□ U 6h x 3d in. Oval 316L SS (0.94 SG)
□ T 3 in. Round 316L SS (0.60 SG)
□ S 3 in. Round 316L SS (0.94 SG)
□ M 5.5h x 2d in. Red Polyurethane (0.57 SG)
□ L 5.5h x 2d in. Blue Polyurethane (0.94 SG)
□ J 5h x 3d in. Oval Titanium 2 (0.60 SG)
□ I 5h x 3d in. Oval Titanium 2 (0.92 SG)
□ N None
E. Float 2 (optional)
□ N None
□ Y 5.5h x 3d in. Blue Polyurethane (0.94 SG)
□ W 5 in. Round 316L SS (0.92 SG)
□ U 6h x 3d in. Oval 316L SS (0.94 SG)
□ L 5.5h x 2d in. Blue Polyurethane (0.94 SG)
□ I 5h x 3d in. Oval Titanium 2 (0.92 SG)
F. Mounting Type
□ F Flat Face ANSI Flange 150#
(Sizes: 2, 2.5, 3, 4, 5, 6)
□ R Raised Face ANSI Flange 150#
(Sizes: 2, 2.5, 3, 4, 5, 6)
□ S Tri Clamp
(Sizes: 2, 2.5, 3)
□ P NPT Plug 150#
(Sizes: 2, 2.5, 3, 4)
□ N None
G. Mounting Size
□ __ See Mounting Type for available sizes
H. Mounting Connection
□ W Welded (xed)
□ S Slide with Compression Fitting (adjustable)
I. Stem Material
□ B 316L SS
J. Total Stem Length in Inches
□ __ Min. 120 in. - Max. 300 in.
K. Temperature Sensor Options
□ N None
▲
□ 1D
Digital Temperature Sensor A, 12 in. from bottom of
probe
□ 2D Digital Temperature Sensors A, B
□ 3D Digital Temperature Sensors A, B, C
□ 4D Digital Temperature Sensors A, B, C, D
□ 5D Digital Temperature Sensors A, B, C, D, E
□ 6D Digital Temperature Sensors A, B, C, D, E, F
□ 7D Digital Temperature Sensors A, B, C, D, E, F, G
Note: Temperature sensors B - G are spaced evenly between
A and probe’s zero reference, with minimum of 2 in.
required between temperature sensors.
L. Housing Connection
▲
□ N
None
□ A 3/4” to 1/2” NPT Reducing Threads
□ B Cable Gland (Cable sold separately)
□ M 4-pin M12 Micro Connector Male
□ F 4-pin M12 Micro Connector Female
Note: When connecting MPI
sensors to your system, reversing
A and B connections may be necessary
if sensors do not communicate with
Modbus Master device.
MPI SensorMPI SensorMPI Sensor
Sensor 1
V+
B (TX-)
A (TX+)
GND
Sensor 2
V+
B (TX-)
A (TX+)
GND
Modbus System Wiring with RST-6001 For MPI-F Sensors
Power
Supply
+8-24 Vdc
GND
Use Shielded Cable
Wiring T’s must be located on
controller/supply side of IS barriers.
See Hazardous Installation
Drawing for Intrinsically Safe
Wiring T’s must be located on
controller/supply side of IS barriers.
RST-6001
Modbus
Controller
USB to computer
with APG Modbus
software
Note: An independent +8-24 Vdc
power supply is required when using
an RST-6001 Modbus Controller. The
RST-6001 can only supply ±5 Vdc, not
the +8-24 Vdc required by the MPI.
IMPORTANT: Refer to Chapter 5 for Intrinsically Safe Installation Drawing for Hazard-
Chapter 2: Installation and Removal Procedures and Notes
• Tools Needed
You will need the following tools to install your MPI level sensor:
• Wrench sized appropriately for MPI mounting
• Wrench sized appropriately for conduit connections
• Flat-head screwdriver for wire terminals
• Channel lock pliers for tightening compression tting
• 1/8” Hex Allen wrench for screws on oat stop(s).
• Pliers for bending cotter pin.
• ATEX Stated Conditions of Use
• Under certain extreme circumstances, the non-metalic parts incorporated in the enclosure of this
equipment may generate an ignition-capable level of electrostatic charge. Therefore the equipment
shall not be installed in a location where the external conditions are conducive to the build-up of
electrostatic charge on such surfaces. In addition, the equipment shall only be cleaned with a damp
cloth.
• The enclosure is manufactured from Aluminum. In rare cases, ignition sources due to impact and
friction sparks could occur. This shall be considered during installation.
• Physical Installation Notes
The MPI-F should be installed in an area--indoors or outdoors--which meets the following conditions:
• Ambient temperature between -40°C and 85°C (-40°F to +185°F)
• Relative humidity up to 100%
• Altitude up to 2000 meters (6560 feet)
• IEC-664-1 Conductive Pollution Degree 1 or 2
• IEC 61010-1 Measurement Category II
• No chemicals corrosive to stainless steel (such as NH3, SO2, Cl2)
• Ample space for maintenance and inspection
Additional care must be taken to ensure:
• The probe is located away from strong magnetic elds, such as those produced by motors, transform-
ers, solenoid valves, etc.
• The medium is free from metallic substances and other foreign matter.
• The probe is not exposed to excessive vibration.
• The oat(s) t through the mounting hole. If the oat(s) does/do not t, it/they must be mounted on
the stem from inside the vessel being monitored.
• The oat(s) is/are oriented properly on the stem (See Figure 2.1). MPI-F oats are installed by customer.
properly on the stem, or sensor readings
will be inaccurate and unreliable. Untapered
UP
Figure 2.1
oats will have a sticker indicating the top of
the oat. Remove sticker prior to use.
IMPORTANT: MPI-F level sensor MUST be installed according to drawing 9009451
(Intrinsically Safe Installation Drawing for Hazardous Locations) on page 23 to meet listed
approvals. Faulty installation will invalidate all safety approvals and ratings.
• Physical Installation Instructions
Ensure that all components have been received, including:
• MPI-F sensor head and stem
• Float (or oats, if two oats purchased)
• Optional Slide Mount
• Weight, Clevis Pin, and Cotter Pin
• Assembly drawing
Assemble sensor mounting, oat(s), weight and pins at installation location, if possible.
• Slide mounting option onto stem. Loosen compression cap so it will slide easily on stem.
• Note: If the oats do not t through the tank/vessel mounting hole, mount them on the stem from
inside the vessel being monitored. Then secure the sensor to the vessel.
• Slide oats onto stem. If using two oats, slide the lighter oat on rst. Tops of oats will be indicated
by sticker. After ensure top of oat is toward MPI-F sensor head, remove sticker.
• For sensors with oat stops, refer to the assembly drawing included with the sensor for oat stop
installation locations.
• Insert weight on end of stem. Hold in place with clevis pin.
• Insert cotter pin in clevis pin. Bend ends of cotter pin back to lock pins into place.
Install MPI-F sensor on tank
• When lifting and installing the sensor be sure to minimize the bending angle between the rigid stem at
the top and bottom of the sensor and the exible stem in-between. Sharp bends at those points could
damage the sensor.
• If your sensor’s stem and oats t through the mounting hole, insert the weight and the oats into the
mount opening.
• Carefully unroll and feed the MPI-F sensor stem into the tank. Slide the mount up to the top of the
stem.
• When the weight is on the bottom of the tank, secure the mounting option to the vessel.
• Take any slack out of the exible stem. Tighten the compression tting to hold stem in place.
MPI-F series sensors use standard Modbus RTU protocol (RS-485). The sensors can only operate as slave
devices. Sensor default transmission settings are 9600 Baud, 8 Bits, 1 Stop Bit, No Parity, and require a
minimum delay of 300 ms between transactions. See MPI-F Modbus Register Lists on pages 10 and 11.
NOTE: For more information about Modbus RTU, please visit www.modbus.org.
• Modbus Programming with RST-6001 and APG Modbus Software
An APG RST-6001 Modbus Controller can be used in tandem with APG Modbus software to program and
control up to 20 MPI-F series sensors. Through APG Modbus, you can monitor the raw readings from the
sensor, congure the data for distance, level, volume, or weight, and enter measurements for a strapping
chart. See MPI-F Modbus Register Lists on pages 10 and 11.
NOTE: For APG Modbus programming instructions, or to download APG Modbus soft-
ware, please visit www.apgsensors.com/suppport.
• Modbus Register Lists for MPI-F
Input Registers (0x04)
Register Returned Data
30299 Model Type
30300 Raw Top Float Reading (in mm, unsigned)
30301 Raw Bottom Float Reading (in mm, unsigned)
30302 Temperature Reading (in 0C, signed)
30303-30304 Calculated Top Float Reading (in selected Units)
30305-30306 Calculated Bottom Float Reading (in selected Units)
30307 Version
30308 API 18.2 TEMP (in 0C, signed)
NOTE: The Calculated Readings will be returned without a decimal place. In order to
obtain the true result, the Decimal Place setting must be taken into account.
40403 Volume Units 1, 2, 3, 4, 5, 6, 7
40404 Decimal Place 0, 1, 2, 3
40405 †Max Distance 0 to 32,768 mm
40406 Full Distance 0 to 32,768 mm
40407 Empty Distance 0 to 32,768 mm
40408 †Sensitivity 0 to 100
40409 †Pulses 5 to 20
40410 †Blanking 0 to 10,364 mm
40411 NA NA
40412 †Averaging 1 to 50
40413 †Filter Window 0 to 10,364 mm
40414 †Out of Range Samples 1 to 255
40415 †Sample Rate 50 to 1,000 msec.
40416 †Multiplier 1 to 1,999 (1000 = 1.000)
40417 †Oset -10,364 to 10,364 mm
40418 †Pre lter 0 to 10,364 mm
40419 †Noise limit 0 to 255
40420 Temperature Select 0 to 8
40421 †RTD Oset (0C) NA*
40422 †Float Window 0 to 1,000 mm 0=1 oat
40423 †1st Float Oset -10,364 to 10,364
40424 †2nd Float Oset -10,364 to 10,364
40425 †Gain Oset 0 to 255
40426 4 mA Set Point NA*
40427 20 mA Set Point NA*
40428 4 mA Calibration NA*
40429 20 mA Calibration NA*
40430 t1d NA*
40431 t1w NA*
40432 t1t NA*
40433 t2d NA*
40434 t2w NA*
40435 t2t NA*
40436-40437 Parameter 1 Data 0 to 1,000,000 mm
40438-40439 Parameter 2 Data 0 to 1,000,000 mm
40440-40441 Parameter 3 Data 0 to 1,000,000 mm
40442-40443 Parameter 4 Data 0 to 1,000,000 mm
40444-40445 Parameter 5 Data 0 to 1,000,000 mm
40446 Baud Rate 0, 1, 2, 3, 4
40201 Restore to Factory Defaults 1
*These registers are not used by the MPI-F, even though they are labeled in the APG Modbus software.
†Setting is factory calibrated. Do not adjust.
Determines the number of decimal places included in the Calculated Reading(s). The Calculated Reading will
always be returned as a whole number.
For example, a Calculated Reading of 1126.658 (gallons, ft3, etc.) will be returned as follows:
Decimal Place = 0 Volume = 1127 (rounded to nearest whole number)
Decimal Place = 1 Volume = 11267 (divide by 10 to get true result)
Decimal Place = 2 Volume = 112666 (divide by 100 to get true result)
Decimal Place = 3 Volume = 1126658 (divide by 1000 to get true result)
Sets the distance (beginning from the Zero Reference) to the point where the sensor will stop looking for
oat signals, usually the bottom of the stem. A oat beyond the Maximum Distance value will not be detected.
40406 - Full Distance
Sets the positive distance (beginning from the sensor Zero Reference) to the point where the monitored
vessel is considered full.
40407 - Empty Distance
Sets the positive distance (beginning from the Zero Reference) to the point where the monitored vessel is
considered empty (usually the bottom of the stem).
40408 - Sensitivity (Factory Calibrated)
Sets the level of gain that is applied to the returning oat signal.
40409 - Pulses (Factory Calibrated)
Controls the duration of the signal being sent down the magnetostrictive wire.
40410 - Blanking (Factory Calibrated)
Sets the blanking distance, which is the zone from the Zero Reference of the sensor to the point from which
the rst signal will be valid. Signals from a oat in the blanking area will be ignored.
40412 - Averaging (Factory Calibrated)
Sets the number of qualied received oat signals to average for the raw reading. Qualied received signals
are placed in a rst-in, rst-out buer, the contents of which are averaged for the raw reading. The larger
the number of qualied received signals being averaged, the smoother the reading will be, and the slower
the reading will be to react to quickly changing targets.
Determines the physical range (0 - 10,364 mm) of qualied received signals, based on the current raw
reading. Signals beyond the +/- Filter Window range of the current reading will not qualify unless the
average moves. Signals outside the extents of the Filter Window are written to the Out of Range samples
buer (Holding Register 40414). See Figure 3.1.
Window = 300 mm
Out of Range Samples = 10
All samples
Samples are rejected within
this area unless they persist
for 10 consecutive samples
Min. ReadingMax. Reading
Current value
of Distance
are accepted
within this area
150 mm150mm
Figure 3.1
Samples are rejected within
this area unless they persist
for 10 consecutive samples
40414 - Out of Range Samples (Factory Calibrated)
Sets the number of consecutive samples outside the Filter Window (Holding Register 40413) necessary to
automatically adjust the current reading and move the Filter Window.
40415 - Sample Rate (Factory Calibrated)
Sets the update rate of the sensor (between 50 - 1000 ms). Shorter time delays allow for quicker sensor
response times to changing levels. Typical setting is 200 ms. Settings under 200 ms are not recommended.
40416 - Multiplier (Factory Calibrated)
Calibrates the distance reading span. The Multiplier is shown by the values 1 - 1999, but these values are
understood to represent 0.001 - 1.999. The default of 1000 (i.e. 1.000) is used for most applications.
Sets the Zero Reference of the sensor, the point from which the calculated distance is measured.
40418 - Pre lter
Denes the physical range (0 - 10,364 mm) of the start up (pre-lter) window. Four sample readings must be
found within the Pre lter window for the MPI sensor to successfully start up.
This register is used for factory diagnostics only.
40419 - Noise limit
Sets the limit for number of signals (0-255) outside the Pre lter range for the MPI at start up. If the Noise
Limit is reached before four readings register within the Pre lter window, the MPI will not start up.
This register is used for factory diagnostics only.
40420 - Temperature Select
Selects the temperature sensor reading to be displayed in Input Register 30302.
MPI-F sensors can accomodate up to seven digital temperature sensors in the stem.
0 = Average of sensors A - G
1 = Digital Temperature Sensor A 5 = Digital Temperature Sensor E
2 = Digital Temperature Sensor B 6 = Digital Temperature Sensor F
3 = Digital Temperature Sensor C 7 = Digital Temperature Sensor G
Sets the distance (0 - 1000 mm) between the rst (i.e. top) oat and the point at which the sensor will begin
looking for the second (bottom) oat. 0 indicates a single oat.
40423 - 1st Float Oset (Factory Calibrated)
Used to calibrate top oat reading (-10,364 - 10,364 mm).
40424 - 2nd Float Oset (Factory Calibrated)
Used to calibrate bottom oat reading (-10,364 - 10,364 mm).
40425 - Gain Oset (Factory Calibrated)
Used to move the centerline of the oat response signal to optimize signal strength (0 - 255).
40446 - Baud Rate
Selects the communication speed between the sensor and the Master Device. All devices on the network
must use the same Baud Rate.
APG Modbus Master and Slave devices default to 9600 Baud.
0 = 9600
1 = 192002 = 38400
3 = 57600
4 = 115200
40201 - Restore To Factory Defaults
Writing a 1 to this Holding Register will erase any settings changes and restore the factory default settings.
Your MPI level sensor is designed to be low maintenance. However, in general, you should:
• Periodically inspect your MPI to ensure the stem and oats are free of any heavy buildup that might
impede the movement of the oats.
• Ensure the housing cover is snuggly secured. If the cover becomes damaged or is misplaced, order a
replacement immediately.
• Repair and Returns
Should your MPI level sensor require service, please contact the factory via phone, email, or online chat. We
will issue you a Return Material Authorization (RMA) number with instructions.
• Phone: 888-525-7300
• Email: sales@apgsensors.com
• Online chat at www.apgsensors.com
Please have your part number and serial number available. See Warranty and Warranty Restrictions for
more information.
IMPORTANT: All repairs and adjustments of the MPI level sensor must be made by the
factory. Modifying, disassembling, or altering the MPI on site is strictly prohibited.
Certificate: 70219727 Master Contract: 237484
Project: 70219727 Date Issued: 2019-03-26
Issued to: Automation Products Group Inc
1025 West 1700 North
Logan, Utah 84321
USA
Attention: Karl Reid
The products listed below are eligible to bear the CSA Mark shown
with adjacent indicators 'C' and 'US' for Canada and US or with adjacent
indicator 'US' for US only or without either indicator for Canada only.
Issued by:
PRODUCTS
CLASS - C225804 - PROCESS CONTROL EQUIPMENT-Intrinsically Safe, Entity - For Hazardous
LocationsCLASS - C225884 - PROCESS CONTROL EQUIPMENT - Intrinsically Safe, Entity-- For Hazardous
Locations - Certified to US Standards
Class I, Division 1, Groups C, D, T4; IP 65*
Class I, Zone 0, Ex/AEx ia, IIB, T4, Ga
Ex ia IIB, T4, Ga
MPI Vibration Sensors, rated 8-24 VDC, Imax = 280 mA; Tamb = -40°C to +85°C, Intrinsically Safe when
1. Under certain extreme circumstances, the non-metallic parts incorporated in the enclosure
capable level of electrostatic charge.
2. T he enclosure is manufactured from Aluminum. In rare cases, ignition sources due to
Standard
Description
C22.2 No. 60079-0:2019
Explosive atmospheres – Part 0: Equipment – General
requirements
C22.2 No. 60079-11:2014
Explosive atmospheres — Part 11: Equipment protection by
intrinsic safety “i”
C22.2 No. 61010-1-12
Safety Requirements for electrical equipment for measurement,
control, and laboratory use – Part 1: General requirements
UL 61010-1:2012
UL Standard for Safety Electrical Equipment For Measurement,
Ed.
UL 60079-0: 2013
Standard for Safety – Explosive Atmospheres – Part 0: Equipment
– General Requirements, Ed. 6
70219727
70219727
Master Contract: 237484
Date Issued: 2019-03-26
Conditions of Acceptability:
of this equipment may generate an ignitionTherefore the equipment shall not be installed in a location where the external conditions
are conducive to the build-up of electrostatic charge on such surfaces. In addition, the
equipment shall only be cleaned with a damp cloth.
impact and friction sparks could occur. This shall be considered during installation.
3. IP 65 is not a part of the hazardous location ratings and is tested separately.
APPLICABLE REQUIREMENTS
Control, and Laboratory Use; Part 1: General Requirements, 3rd.
Standard for Safety – Explosive Atmospheres – Part 11:
70219727
70219727
Master Contract: 237484
Date Issued: 2019-03-26
Equipment Protection by Intrinsic Safety “I”, Ed. 6
MARKINGS
The manufacturer is required to apply the following markings:
Products shall be marked with the markings specified by the particular product standard.
Products certified for Canada shall have all Caution and Warning markings in both English and French.
Additional bilingual markings not covered by the product standard(s) may be required by the Authorities Having
Jurisdiction. It is the responsibility of the manufacturer to provide and apply these additional markings, where
applicable, in accordance with the requirements of those authorities.
The products listed are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and
US (indicating that products have been manufactured to the requirements of both Canadian and U.S. Standards) or
with adjacent indicator 'US' for US only or without either indicator for Canada only.
1. Manufacturer’s name or registered trade mark;
2. Model Number as in the PRODUCTS section, above;
3. Serial number S/N XXXXXX;
4. “Install per document 9005491”
5. Ambient Temperature Rating: as specified in the PRODUCTS section above;
6. DC Power Symbol as per Table 1, IEC 61010-1:
7. Hazardous Location Designation: As specified in PRODUCTS section above;
8. IP 65 (Only for STEM Type Type E, G, R, F and T).
9. Certificate number: CSA19CA70219727
Nameplate adhesive label material approval information:
1. The following markings are provided on a UL Recognized adhesive nameplate (also used
previously on CSA certificate 2397437) manufactured by Zebra Technologies International, LLC,
Material: Z-Ultimate 4000T, printed with a resin ribbon manufactured by
Zebra Technologies
International LLC, Material: 5100 Premium Resin Ribbon, at a maximum service temperature of
135°C or higher.