Thanks for purchasing an LPU-2428 loop-powered ultrasonic sensor and RST-4101 programming module from us! We appreciate your business and your trust. Please take a moment to familiarize yourself with the products and this manual before installation. If you have any questions, at any time, don’t hesitate to call us at 888-525-7300.
NOTE: Scan the QR code to the right to see the full user manual on your tablet or smartphone. Or visit
https://www.apgsensors.com/support to nd it on our
website.
Table of Contents
LPU-2428 Loop-Powered Ultrasonic Sensor
Installation Guide
For LPU-2428 & RST-4101
1.Description
2. How To Read Your Label
3. Warranty
4. Dimensions
Description
1
The LPU-2428 loop-powered ultrasonic level sensor provides low-power, non-contact measurement
you can count on. The LPU-2428 is certied for installation in hazardous areas in the US and
Canada by CSA for Class I, Division 1, Groups C & D and Class I, Division 2, Group environments. The default Application setting for the LPU-2428 is Distance, which will work in a wide variety of
settings. Please refer to the full user manual for further conguration settings.
How To Read Your Label
2
Each label comes with a full model number, a part number, and a serial number. The model number for the LPU-2428 will look something like this:
SAMPLE: LPU-2428-C6
5. Installation Guidelines
6. Sensor and System Wiring
7. LPU-2428 Default Application Setting
8. General Care
9. Repair Information
10. Hazardous Location Wiring
R
Automation Products Group, Inc. 1025 W 1700 N Logan, UT 84321 www.apgsensors.com | phone: 888-525-7300 | email: sales@apgsensors.com
Installation Guidelines
5
The LPU-2428 should be installed in an area--indoors or outdoors--which meets the following conditions:
Ambient temperature between -40°C and 60°C (-40°F to +140°F)
Ample space for maintenance and inspection
Additional care must be taken to ensure:
The sensor has a clear, perpendicular sound path to the surface being monitored.
The sensor is mounted away from tank or vessel walls and inlets.
The sound path is free from obstructions and as open as possible for the 9° o axis beam
pattern.
The sensor is tightened by hand to avoid cross-threading.
*Important:
For user interface guide and sensor conguration see the full user manual.
Part # 122950-0030
Doc #9004795 Rev A1
The model number tells you exactly what you have. You can also call us with the model, part, or the
serial number and we can help you.
You’ll also nd all hazardous certication information on the label.
Warranty
3
This product is covered by APG’s waranty to be free from defects in material and workmanship
under normal use and service of the product for 24 months. For a full explanation of our Warranty,
please visit https://www.apgsensors.com/about-us/terms-conditions. Contact Technical Support to recieve a Return Material Authorization before shipping your product back.
Scan the QR code below to read the full explanation of our Warranty on your tablet or smartphone.
Sensor and System Wiring Diagram
6
LPU-2428 & RST-4101 Wiring
Dimensions
4
NON-METALLIC
STRAIN RELIEF
2" NPT
THREADS
3/4" NPT
THREAD S
ø2.00
[50.80 mm]
[184.15 mm]
5.06
[128.59 mm]
7.25
ø2.79
[70.78mm]
2.65
[67.24mm]
For normal operation, connect the provided cable to your control system:
Connect the red wire to +24 VDC.
Connect the black wire to 4-20 mA input. Circuit load resistance + input resistence must be
greater than 150Ω. 249Ω is recommended for optimal signal tranmission.
Refer to drawing 9002747 (section 10) for Intrinsically Safe installation.
Refer to drawing 9002745 (section 10) for Hazardous Location installation.
For programming:
Connect (+) terminal of RST-4101 to +24 VDC supply of sensor (red wire).
Connect (-) terminal of RST-4101 to 4-20 mA signal from sensor (black wire).
Ensure that load resistor is between RST-4101 and control network or PLC, rather than
between sensor and RST-4101.
IMPORTANT: Refer to section 10 for Hazardous Location Wiring.
LPU-2428 Default Application Setting
7
General Care
8
The default Application setting for the LPU-2428 is Distance, which will work in a wide variety of
settings. The LPU-2428 has several additional Application settings that can be congured to meet
your needs.
All of the LPU-2428’s adjustable settings are accessible through the LPU-2428A Software, which is available at https://www.apgsensors.com/support.
Your level sensor is very low maintenance and will need little care as long as it was installed correctly. However, in general, you should periodically inspect your LPU-2428 sensor to ensure the sensor face is free of any buildup that might impede the function of the sensor. If sediment or other foreign matter becomes trapped on the sensor face, detection errors can occur.
If you need to remove the sensor, be sure to store it in a dry place at a temperature between -40° and 180° F.
Repair Information
9
If your LPU-2428 ultrasonic sensor or RST-4101 programming module need repair, contact us via email, phone, or online chat on our website. We will issue you an RMA number with instructions.
Phone: 888-525-7300
Email: sales@apgsensors.com
Online chat at www.apgsensors.com