APG LFP-V-2A, LFP-V-2B, LFP-V-2F, LFP-V-2P LVP-V Manual

Page 1
AUTOMATION
Operator’s Manual
PRODUCTS
GROUP, INC.
Model LFP-V
Miniature Level Switch
Doc #9004722 / Part #200437
Rev. A2, 11/19
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • E-mail: sales@apgsensors.com
Page 2
Model LFP-V Rev. A2, 11/19
Table of Contents
Warranty ..................................................................................3
Introduction ............................................................................. 4
Specications ...........................................................................4
Installation ...............................................................................5
Wiring .......................................................................................7
Automation Products Group, Inc.
2
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 3
Rev. A2, 11/19 Model LFP-V
Warranty and Warranty Restrictions
This product is covered by APG’s warranty to be free from defects in material and workmanship under normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit https://www.apgsensors.com/about-us/terms-conditions. Contact Technical Support to receive a Return Material Authorization before shipping your product back.
Scan the QR code below to read the full explanation of our Warranty on your tablet or smartphone.
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
3
Page 4
Model LFP-V Rev. A2, 11/19
• Introduction
The miniature magnetic level sensors are used for liquid level detection. They have been designed for reliable operation in small tanks and containers. Their rugged design and careful engineering make them the optimum solution for OEM and large volume applications.
• Specications
Operational Versions
LFP-V-2A ..................................polycetal stem and buna oat
LFP-V-2B ...................................brass stem and buna oat
LFP-V-2F ...................................PVDF stem and PVDF oat
LFP-V-2P ...................................polypropylene stem and
polypropylene oat
Characteristics
Switch Rating (resistive load) (50 VA):
Max contact rating ..................50 VA AC; 50 W DC
Max current .............................0.5 A AC; 0.5 A DC
Max voltage .............................300 V AC; 300 V DC
Life expectancy .......................107 operations (at 12 VDC, 5 mA)
Max temperature range ........-14 to 194°F (-10 to 90°C)
for LFP-V-2A, LFP-V-2B, and LFP-V-2P
-4 to 175°F (-20 to 80°C)
for LFP-V-2F-300
-14 to 104°F (-10 to 40°C)
for LFP-V-2F-1000
Max pressure ..........................145 psi (10 bar) for LFP-V-2A,
LFP-V-2B, LFP-V-2F-1000, and LFP-V-2P
28.4 psi (1.96 bar) for LFP-V-2F-300
Min SG ......................................0.6 for LFP-V-2A, LFP-V-2B
0.85 for LFP-V-2F-300 and LFP-V-2P
0.9 for LFP-V-2F-1000
Automation Products Group, Inc.
4
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 5
Rev. A2, 11/19 Model LFP-V
Generic LFP (Nohken)
• Installation
Environment
The LFP should be installed in an area that meets the following conditions:
• Within the specied temperature range.
• Located away from any strong magnetic eld.
• Located away from drop, splash or vapor around the lead wire egress. Note: Apply the proper sealing compound over the lead wire egress if necessary. Liquid penetration may ruin insulation.
• Clean liquid, free from any foreign matter.
• Ample space for maintenance/ inspection.
Location
DO NOT locate near liquid inlets/
outlets.
NC NO
If there is surface wave motion, use a
time delay relay to dampen the switch
action.
A B
H
OFF
ON
ON
OFF
Ø
Point of operation in SG = 1.0 (water) 2A 2B 2P 2F-1000 NC-A:
Falling switch closes at
NC-B:
Rising switch opens at NO-A: NO-B:
Falling switch opens at Rising switch closes at
24.5 21.5 20.0 19.0
23.0 20.0 18.5 17.5
22.5 19.5 17.0 16.5
21.0 18.0 15.5 15.0
Size of oat ø25xH25 ø25xH25 ø25xH25 ø25xH25
Note: Standard switch operation is NC (switch closes as the level falls). Switch action can be reversed by inverting the oat. The direction of close is marked on the oat.
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
5
Page 6
Model LFP-V Rev. A2, 11/19
Installation
Install the LFP vertically with the lead wires up and down.
4
3
2
1
1. Flange: Open holes (as necessary) through top of tank. Insert
oat and tighten the nut. Be sure to use a suitable gasket, O-ring, or thread tape. Use a 1/4” pipe for extension, if necessary.
2. Threaded: Use R1/8” or G1/8” female thread in top of tank. Use suitable O-ring or thread tape.
3. Bulkhead: Drill a 10 mm (0.4”) hole in tank top. Insert and tighten the nut. Use a suitable O-ring or thread tape.
4. Terminal Box: Provide G2” female mounting boss. Use suitable O-ring or thread tape.
Note: After assembling the extension pipe, check insulation (100 MW or more) and switch operation. Improper assembly or seal may result in damage or injury.
Automation Products Group, Inc.
6
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Page 7
Rev. A2, 11/19 Model LFP-V
• Wiring
Wiring should be in accordance with all local codes. Lead wires are 22 AWG, UL listed. We recommend the use of solderless lugs for
connection.
Black
Switch Rating (Resistive)
• Max capacity 50 VA, 50 W
• Max current 0.5 A AC, 0.5 A DC
Black
• Max voltage 300 VAC, 300 VDC
Note: Max pull-load of the lead wire is 20 N. Excessive pulling or kinking of the lead wire may break the switch.
Caution!
Protection for electrical surges:
Overvoltage
Reed switches are not designed for the direct starting of inductive loads such as motors, contactors, solenoid valves, and so on. They are susceptible to damage from overvoltages. DO NOT EXCEED THE CONTACT RATINGS. Contact should be wired to miniature relays, suppressors or similar devices.
Overcurrent
Momentary surge current may be produced by switching lamps or stray capacity from long cable length, consequently welding the reed switch. Contact should be wired to a relay unit, coils in series, or suppressors.
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
7
Page 8
AUTOMATION
PRODUCTS
GROUP, INC.
Automation Products Group, Inc.
Tel: 1/888/525-7300 1/435/753-7300 Fax: 1/435/753-7490
e-mail: sales@apgsensors.com
www.apgsensors.com
Automation Products Group, Inc.
1025 W. 1700 N.
Logan, UT 84321
Loading...