APG DDL Operating Manual

Large Digital Display
Instruction Manual
®
Large Display
Large 1.80" Digits
Dual-Line 6-Digit Display
Readable from up to 100 Feet (30 Meters) Away
Superluminous Sunlight Readable Display
NEMA 4X, IP65 Rated Field Mountable Enclosure
Operating Temperature Range of -40 to 65°C (-40 to 150°F)
0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
Input Power Options Include 85-265 VAC or 12-24 VDC
Isolated 24 VDC Transmitter Power Supply
Signal Input Conditioning for Flow & Round Horizontal Tanks
Programmable Display & Function Keys
Multi-Pump Alternation Control
4 Relays + Isolated 4-20 mA Output Option
Onboard USB & RS-485 Serial Communication
Modbus® RTU Communication Protocol Standard
Program the Meter from a PC with onboard USB and MeterView Pro
Automation Products Group
1025 W 1700 N • Logan UT 84321 USA Tel (435) 753-7300 • Fax (435) 753-7490
Large Digital Display Instruction Manual
Caution: Read complete
instructions prior to installation and
operation of the meter.
Warning: Risk of electric shock or
personal injury.
Warning!
This product is not recommended for life support applications or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at their own risk. Automation Products Group, Inc. shall not be held liable for damages resulting from such improper use.
!
Disclaimer
The information contained in this document is subject to change without notice. Automation Products Group makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
Limited Warranty
Automation Products Group, Inc. warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Automation Products Group’s liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks
Modbus® is a Registered Trademark of Schneider Automation Inc. All other trademarks mentioned in this document are the property of their respective owners.
© 2018 Automation Products Group, Inc. All rights reserved.
www.apgsensors.com
2
Large Digital Display Instruction Manual

Table of Contents

Table of Contents ............................................................ 3
Table of Figures .............................................................. 4
Introduction ..................................................................... 4
Ordering Information ....................................................... 4
Specifications .................................................................. 5
General ................................................................................. 5
Process Input ........................................................................ 5
Relays ................................................................................... 6
Isolated 4-20 mA Transmitter Output ..................................... 6
RS485 Serial Communications Terminal ............................... 6
Modbus® RTU Serial Communications .................................. 6
Digital Input & Output Terminal .............................................. 7
Compliance Information .................................................. 7
Safety .................................................................................... 7
Safety Information ........................................................... 8
Installation ....................................................................... 8
Unpacking ............................................................................. 8
Wall Mounting Instructions .................................................... 9
Mounting Dimensions ....................................................... 9
Pipe Mounting Instructions .................................................. 10
Transmitter Supply Voltage Selection (P+, P-) ..................... 11
Connections ........................................................................ 11
Connectors Labeling ....................................................... 12
Power Connections ......................................................... 12
Signal Connections ......................................................... 13
Modbus RTU Serial Communications ............................. 14
Relay Connections .......................................................... 14
Switching Inductive Loads ............................................... 15
RS485 Output Connections ............................................ 16
Digital I/O Connections ................................................... 18
F4 Digital Input Connections ........................................... 18
4-20 mA Output Connections .......................................... 19
Analog Output Transmitter Power Supply ....................... 19
Interlock Relay Feature ................................................... 19
Setup and Programming ............................................... 20
Overview ............................................................................. 20
Programming Buttons and Status LED Indicators ................ 21
MeterView® Pro Software .................................................... 22
MeterView Pro Installation .............................................. 22
Display Functions & Messages ............................................ 23
Main Menu .......................................................................... 25
Setting Numeric Values ....................................................... 25
Setting up the Meter (setup) ............................................... 26
Setting the Input Signal (Input) ...................................... 27
Setting the Input Units or Custom Tags (units) .............. 27
Setting the Decimal Point (dEc pt) ................................. 28
Programming the Meter (prog) ....................................... 29
Setting the Display Parameter & Intensity (dsplay) ........ 32
Setting the Relay Operation (relay).................................... 33
Setting the Relay Action .................................................. 34
Programming Set and Reset Points ................................ 34
Setting Fail-Safe Operation ............................................. 34
Programming Time Delay ............................................... 34
Relay Action for Loss of 4-20 mA Input (Loop Break) ...... 35
Relay and Alarm Operation Diagrams ................................. 35
High Alarm Operation (Set > Reset) ............................... 35
Low Alarm Operation (Set < Reset) ................................ 35
High Alarm with Fail-Safe Operation (Set > Reset) ......... 36
Low Alarm with Fail-Safe Operation (Set < Reset) .......... 36
Pump Alternation Control Operation ............................... 36
Relay Sampling Operation .............................................. 37
Signal Loss or Loop Break Relay Operation ................... 37
Time Delay Operation .................................................... 37
Relay Operation Details ...................................................... 38
Overview ........................................................................ 38
Relays Auto Initialization ................................................ 38
Fail-Safe Operation ........................................................ 38
Front Panel LEDs ........................................................... 38
Latching and Non-Latching Relay Operation .................. 39
Non-Latching Relay (Auto) ............................................. 39
Non-Latching Relay (A-man) ........................................ 39
Latching Relay (LatcH) .................................................. 39
Latching Relay (Lt-Clr) ................................................ 39
Acknowledging Relays ................................................... 40
Pump Alternation Control Applications (Altern) ............. 40
Setting up the Interlock Relay (Force On) Feature .......... 42
Scaling the 4-20 mA Analog Output (Aout) ......................... 43
Reset Menu (reset) ........................................................... 43
Control Menu (Contrl) ....................................................... 43
Setting up the Password (pass) .......................................... 44
Protecting or Locking the Meter ...................................... 44
Making Changes to a Password Protected Meter ........... 45
Disabling Password Protection ....................................... 45
Advanced Features Menu ................................................... 46
Advanced Features Menu & Display Messages .............. 46
Noise Filter (filter) ...................................................... 48
Noise Filter Bypass (bypass) ......................................... 48
Rounding Feature (round) ............................................. 48
Modbus RTU Serial Communications (serial) .............. 48
Select Menu (SElect) .................................................... 49
Signal Input Conditioning (Functn) ................................. 49
Low-Flow Cutoff (CutofF) .............................................. 51
Analog Output Programming (AoutPr) ........................... 51
Programmable Function Keys User Menu (user) ........... 51
Tare (tare) .................................................................... 52
Internal Source Calibration (ICAL) .................................. 53
Meter Operation ............................................................ 54
Button Operation ................................................................ 54
Function Key Operation ...................................................... 54
Digital Input Operation ........................................................ 54
Maximum/Minimum Readings ............................................. 55
Troubleshooting ............................................................. 56
Diagnostics Menu (diag) .................................................... 56
Determining Software Version ........................................ 56
Reset Meter to Factory Defaults ......................................... 56
Factory Defaults & User Settings .................................... 57
Troubleshooting Tips .......................................................... 58
3
Large Digital Display Instruction Manual
Model Number
Reorder Number
Power
Options Installed
PD2-6000-6H0-AP
DDL-A00
85-265 VAC
No Options
PD2-6000-6H7-AP
DDL-A14
85-265 VAC
4 relays & 4-20 mA output
PD2-6000-7H0-AP
DDL-D00
12-24 VDC
No Options
PD2-6000-7H7-AP
DDL-D14
12-24 VDC
4 relays & 4-20 mA output
Model Number
Description
PDA6260
Pipe Mounting Kit
PDA7485-I
RS-232 to RS-422/485 isolated converter
PDA7485-N
RS-232 to RS-422/485 non-isolated converter
PDA8485-I
USB to RS-422/485 isolated converter
PDA8485-N
USB to RS-422/485 non-isolated converter
PDAPLUG2
Plastic Conduit Plug
PDX6901
Suppressor (snubber): 0.01 µF/470 , 250 VAC

Table of Figures

Figure 1. Meter Mounting Holes ................................................. 9
Figure 2. Meter Dimensions - Side View .................................... 9
Figure 3. Meter Dimensions – Front View .................................. 9
Figure 4. Vertical Pipe Mount Assembly................................... 10
Figure 5. Horizontal Pipe Mount Assembly .............................. 10
Figure 6. Transmitter Supply Voltage Selection ....................... 11
Figure 7. Connector Labeling for Fully Loaded Meter ............... 12
Figure 8. Power Connections ................................................... 12
Figure 9. Transmitters Powered by Internal Supply .................. 13
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered
................................................................................................ 13
Figure 11. Voltage Input Connections ...................................... 14
Figure 12. Relay Connections .................................................. 14
Figure 13. AC and DC Loads Protection .................................. 15
Figure 14. Low Voltage DC Loads Protection .......................... 15
Figure 15. RS-422 or RS-485 Wiring ....................................... 16
Figure 16. RS-485 Two-Wire Multi-Drop Wiring ....................... 17
Figure 17. Connections for RS485 Connector to Serial Converter
............................................................................................... 17
Figure 18. Three-Wire RS485 Connection ............................... 17
Figure 19. Digital Input and Output Connections ..................... 18
Figure 20. F4 Digital Input Connections .................................. 18
Figure 21. 4-20 mA Output Connections ................................. 19
Figure 22. Interlock Connections ............................................. 19
Figure 23. Acknowledge Relays with Function Key or Digital
Input........................................................................................ 40

Introduction

This analog input meter is a multi-purpose, easy to use, large-display digital process meter ideal for level, flow rate, temperature, or pressure transmitter applications. It features large 1.8 inch superluminous LED digits, which can be read in direct sunlight from up to 100 feet (30 meters) away. It is housed in a water­resistant, field-mountable NEMA 4X/IP65 rated enclosure for convenient indoor and outdoor installation.
The meter accepts current and voltage signals (e.g. 4-20 mA, 0-10 V). Three of the programming buttons can be set for custom operation. The analog input can be scaled to display the process in two different scales; for example, the main display could indicate level in feet and the second display could indicate the volume in gallons.
A fully loaded meter comes with four (4) SPDT relays, a 4-20 mA output, two 24 VDC power supplies, five (5) digital inputs and four (4) digital outputs, and RS485 serial communications.
The two or four relays can be used for alarm indication or process control applications such as pump alternation control. The 4-20 mA isolated output, Modbus RTU serial communications, and digital I/O features make this meter an excellent addition to any system.

Ordering Information

Standard Models
Accessories
Manufactured by Precision Digital Corporation, 233 South St, Hopkinton MA 01748 USA
4
Large Digital Display Instruction Manual

Specifications

Display
Main display: 1.8" (46 mm) high, red LEDs 6 digits per line (-99999 to 999999), with lead zero blanking
Display Intensity
Eight user selectable intensity levels
Display Update Rate
5/second (200 ms)
Overrange
Display flashes 999999
Underrange
Display flashes -99999
Display Assignment
Line 1 and line 2 may be assigned to PV1, PV2, PCT, d r-u, d gross, d nt-g, max/min, max & min, set points, units (line 2 only), or Modbus input.
Programming Methods
Four programming buttons, digital inputs, PC and MeterView Pro software, or Modbus registers.
Noise Filter
Programmable from 2 to 199 (0 will disable filter)
Filter Bypass
Programmable from 0.1 to 99.9% of calibrated span
Recalibration
All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Max/Min Display
Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
Password
Three programmable passwords restrict modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs.
Power Options
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC 10%, 15 W max Powered over USB for configuration only.
Isolated Transmitter Power Supply
Terminals P+ & P-: 24 VDC  10%. 12-24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal P+/P- switch). 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
Non-Volatile Memory
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Fuse
Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Normal Mode Rejection
Greater than 60 dB at 50/60 Hz
Isolation
4 kV input/output-to-power line 500 V input-to-output or output-to-P+ supply
Overvoltage Category
Installation Overvoltage Category II: Local level with smaller transient
overvoltages than Installation Overvoltage Category III.
Environmental
Operating temperature range: -40 to 150°F (-40 to 65°C) Storage temperature range: -40 to 185°F (-40 to 85°C) Relative humidity: 0 to 90% non­condensing
Connections
Removable and integrated screw terminal blocks accept 12 to 22 AWG wire.
Enclosure
UL Type 4X, IP65 rated. Polycarbonate & glass blended plastic case, color: gray. Includes four PG11 through-hole conduit openings, with two factory installed PG11, IP68, black nylon threaded hole plugs with backing nuts.
Mounting
Wall Mounting: Four (4) mounting holes
provided for mounting meter to wall. See Wall Mounting Instructions on page 9 for additional details.
Pipe Mounting: Optional pipe mounting kit (PDA6260) allows for pipe mounting. Sold separately. See Pipe Mounting Instructions on page 10 for additional details.
Tightening Torque
Removable Screw Terminals: 5 lb-in
(0.56 Nm) Digital I/O and RS485 Terminals: 2.2 lb-in (0.25 Nm)
Overall Dimensions
10.63" x 12.59" x 4.77" (270 mm x 319.7 mm x 121.2 mm) (W x H x D)
Weight
6.10 lbs (2.76 kg)
Warranty
Please see https://www.apgsensors.com/ about-us/terms-conditions for full warranty statement.
Inputs
Field selectable: 0-20, 4-20 mA, 10 V (0­5, 1-5, 0-10 V), Modbus PV (Slave)
Accuracy
±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
Temperature Drift
0.005% of calibrated span/C max from 0 to 65C ambient,
0.01% of calibrated span/C max from -40 to 0C ambient
Signal Input Conditioning
Linear, square root, programmable exponent, or round horizontal tank volume calculation
Multi-Point Linearization
2 to 32 points for PV or PV1 2 to 8 points for PV2 (Dual-scale Level feature)
Except where noted all specifications apply to operation at +25°C.

General

Process Input

5
Large Digital Display Instruction Manual
Programmable Exponent
1.0001 to 2.9999
Round H Tank
Diameter & Length: 999.999 inch or cm calculates volume in gallons or liters respectively.
Low-Flow Cutoff
0-999999 (0 disables cutoff function)
Decimal Point
Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Calibration Range
Input Range
Minimum Span Input 1 & Input 2
4-20 mA
0.15 mA
10 V
0.01 V
An error message will appear if the input 1 and input 2 signals are too close together.
Input Impedance
Voltage ranges: greater than 500 k Current ranges: 50 - 100 (depending on resettable fuse impedance)
Input Overload
Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
F4 Digital Input Contacts
3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels
Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Rating
4 SPDT (Form C) internal rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP ( 50 W) @ 125/250 VAC for inductive loads
High or Low Alarm
User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
Relay Operation
Automatic (non-latching) and/or manual reset Latching (requires manual acknowledge) with/without clear Pump alternation control (2 to 4 relays) Sampling (based on time) Off (disable unused relays and enable Interlock feature) Manual on/off control mode
Relay Reset
User selectable via front panel buttons or digital inputs
1. Automatic reset only (non-latching), when the input passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (latching)
Note: Front panel button or digital input
may be assigned to acknowledge relays programmed for manual reset.
Noise Suppression
Noise suppression is recommended for each relay contact switching inductive loads; see page 15 for details.
Deadband
0-100% of span, user programmable
Time Delay
0 to 999.9 seconds, on & off relay time delays Programmable and independent for each relay
Fail-Safe Operation
Programmable and independent for each relay.
Note: Relay coil is energized in non-
alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization
When power is applied to the meter, relays will reflect the state of the input to the meter.
Output Source
Process variable (PV), max, min, set points 1-4, Modbus input, or manual control mode
Scaling Range
1.000 to 23.000 mA for any display
range
Calibration
Factory calibrated: 4.000 to 20.000 = 4­20 mA output
Analog Out Programming
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
Accuracy
± 0.1% of span ± 0.004 mA
Temperature Drift
0.4 µA/C max from 0 to 65C ambient,
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply
Terminals I+ & R: 24 VDC  10%. May be used to power the 4-20 mA output or other devices. Refer to Figure 21 on page 19.
All models rated @ 40 mA max.
External Loop Power Supply
35 VDC maximum
Output Loop Resistance
Power
Minimum
Maximum
24 VDC
10
700
35 VDC (external)
100
1200
Compatibility
EIA-485
Connectors
Removable screw terminal connector
Max Distance
3,937' (1,200 m) max
Status Indication
Separate LEDs for Power (P), Transmit (TX), and Receive (RX)
Slave ID
1 – 247 (Meter address)
Baud Rate
300 – 19,200 bps
Transmit Time Delay
Programmable between 0 and 199 ms
Data
8 bit (1 start bit, 1 or 2 stop bits)
Parity
Even, Odd, or None with 1 or 2 stop bits
Byte-To-Byte Timeout
0.01 – 2.54 second
Turn Around Delay
Less than 2 ms (fixed)
Note: Refer to the Modbus Register Tables located at www.apgsensors.com for details.

Isolated 4-20 mA Transmitter Output

Relays

RS485 Serial Communications Terminal

Modbus® RTU Serial Communications

6
Large Digital Display Instruction Manual

Digital Input & Output Terminal

Channels
4 digital inputs & 4 digital outputs
Digital Input Logic High
3 to 5 VDC
Digital Input Logic Low
0 to 1.25 VDC
Digital Output Logic High
3.1 to 3.3 VDC
Digital Output Logic Low
0 to 0.4 VDC
Source Current
10 mA maximum output current
Sink Current
1.5 mA minimum input current
+5 V Terminal
To be used as pull-up for digital inputs only. Connect normally open pushbuttons across +5 V & DI 1-4.
WARNING!
DO NOT use +5 V terminal to power external devices.
UL & C-UL Listed
USA & Canada UL 508 Industrial Control Equipment (United States), C22.2 No. 142 (Canadian National Standard)
UL File Number
E160849
Front Panel
UL Type 4X, NEMA 4X, IP65
Low Voltage Directive
EN 61010-1:2010 Safety requirements for measurement, control, and laboratory use

Compliance Information

Safety

7
Large Digital Display Instruction Manual
Caution: Read complete instructions
prior to installation and operation of the meter.
Warning: Risk of electric shock or personal injury.
Warning!
Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.
!

Safety Information

Installation

There is no need to open the clear plastic front cover in order to complete the installation, wiring, and setup of the meter. All programming is done through the buttons and switches located under the lower door panel and are accessible by removing the single securing screw. Wires should be run through the knockout holes located on the bottom of the meter.
There are a total of four pre-drilled conduit entry holes located at the bottom of the meter. If the need to drill additional holes arises, make sure you will have the clearance necessary for conduit mounting hardware.
Do not disconnect the RJ45 connector found on the right side of the meter wiring board. Doing so will disable the onboard digital I/O, RS-485 serial communications, and M-Link functionality.
Instructions are provided for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 11.

Unpacking

Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier. If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
8
Large Digital Display Instruction Manual

Wall Mounting Instructions

Figure 2. Meter
Dimensions - Side View
Figure 3. Meter Dimensions – Front View
2.63" (67 mm)
4.77"
(121.2 mm)
Mounting Hole Mounting Hole
Front Door Panel Sc rew
10.63" (270 mm)
12.59" (319.7 mm)
10.43" (265 mm)
9.8" (249 mm)
11.14" (283 mm )
The meter can be mounted to any wall using the four provided mounting holes. Note that the bottom mounting holes are located underneath the front door panel. To mount the meter to a wall, follow these instructions.
1. Prepare a section of wall approximately 11″ x 13″ (280 mm x 330 mm) for meter mounting by marking with a pencil the mounting holes (shown in the image to the right) on the wall.
2. Using a drill bit slightly smaller than the girth of the mounting screws, pre-drill holes at the mounting locations previously marked.
3. Insert mounting screws into the four mounting holes and screw them into the pre-drilled holes. Do not overtighten the mounting screws as it is possible that the enclosure could crack and become damaged.
Figure 1. Meter Mounting Holes

Mounting Dimensions

9
Large Digital Display Instruction Manual

Pipe Mounting Instructions

The meter can also be mounted to a pipe using the optional pipe mounting kit (PDA6260). This kit includes two mounting plates, two U-bolts, and the necessary nuts and bolts. To mount the meter to a pipe using the pipe mounting kit accessory, follow these instructions.
1. Secure the mounting plates to the top and bottom (for vertical pipes) or left and right (for horizontal pipes) of the reverse side of the meter enclosure using the provided fasteners. Do not overtighten the fasteners as it could cause damage to the enclosure.
2. Using the provided nuts and U-bolts, secure the mounting plates to the pipe enough torque such that the meter cannot be moved up or down (or side to side).
Figure 4. Vertical Pipe Mount Assembly
Figure 5. Horizontal Pipe Mount Assembly
10
Large Digital Display Instruction Manual

Transmitter Supply Voltage Selection (P+, P-)

Caution
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the meter and ensure personnel safety.
MENU RESET
F1
MAX
F2
ENT ER
F3
All meters, including models equipped with the 12-24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the switch labeled P+/P- must be configured accordingly.
To access the voltage selection jumper:
1. Unplug the meter power.
2. Unscrew and open the front door panel.
3. Locate the P+/P- switch located in the center of the connections board (see diagram below).
4. Flip this switch into the appropriate position for the required transmitter excitation.
Figure 6. Transmitter Supply Voltage Selection

Connections

All connections are made to screw terminal connectors located under the front door panel. Remove the single securing screw in order to access the wiring terminals.
11
Large Digital Display Instruction Manual
Warning!
Do not connect any equipment other than Automation Products Group’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Do not disconnect the RJ45 connector located to the left of the power terminal block. Doing so will disable the onboard digital I/O, RS-485 serial communications, and M-Link functionality.
MENU RESET
F1
MAX
F2
ENTER
F3
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+
-

Connectors Labeling

The connectors’ label, affixed to the inside of the lower door panel, shows the location of all connectors available with requested configuration.
Figure 7. Connector Labeling for Fully Loaded Meter

Power Connections

Power connections are made to a two-terminal connector labeled POWER on Figure 7 on page 12. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
Figure 8. Power Connections
12
Large Digital Display Instruction Manual

Signal Connections

Signal connections are made to a six-terminal connector labeled SIGNAL on Figure 7. The COM (common) terminal is the return for the 4-20 mA and the 10 V input signals.
Current and Voltage Connections
The following figures show examples of current and voltage connections. There are no switches or jumpers to set up for current and voltage inputs. Setup and programming is
performed through the front panel buttons.
Figure 9. Transmitters Powered by Internal Supply
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable fuse. The display may or may not show a fault condition depending on the nature of the overload.
The fuse limits the current to a safe level when it detects a fault condition, and automatically resets itself when the fault condition is removed.
13
Large Digital Display Instruction Manual
-+
+
Voltage
Signal
mA+P-
21 3 54
P+ V+
COM
INPUT SIGNAL
mA+P-
21 3 54
P+ V+
COM
INPUT SIGNAL
3-Wire Voltage
Transducer
Signal
-
C NONO NC NC C
RELAY4 RELAY3
4 36 5 2 1
C NONO NC NC C
RELAY2 RELAY1
4 36 5 2 1
Figure 11. Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.

Modbus RTU Serial Communications

Serial communications connection can be made to the onboard RS485 terminal block or USB connector shown in Figure 7. If RS232 is required, an RS485 to RS232 adapter (PDA7485) may be used. See Ordering Information on page 4 for additional information.

Relay Connections

Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 in Figure 7. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of the corresponding relay. The relays’ C terminals should not be confused with the COM (common) terminal of the INPUT SIGNAL connector.
Figure 12. Relay Connections
14
Large Digital Display Instruction Manual

Switching Inductive Loads

C
R
C
R
Use a diode with a reverse breakdown voltage two to three times the circuit voltage and forward current at least as large as the load current.
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies. Refer to the following circuits for RC network assembly and installation:
Figure 13. AC and DC Loads Protection
Choose R and C as follows: R: 0.5 to 1 Ω for each volt across the contacts C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC network may also be installed across the load. Experiment for best results.
RC Networks Available from Automation Products Group
RC networks are available from Automation Products Group and should be applied to each relay contact switching an inductive load. Part number: PDX6901.
Note: Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Figure 14. Low Voltage DC Loads Protection
15
Large Digital Display Instruction Manual

RS485 Output Connections

An RS-485 connector is provided for the use of advanced Modbus® serial communications. This connector converts the serial output of the meter to balanced, full or half-duplex RS-485 signals. It has a removable screw terminal connector for the RS-485 terminals which includes Transmit Data (DO) and (/DO), Receive Data (DI) and (/DI), and Signal Ground. Baud rates are adjustable and handled by the meter (see Modbus RTU Serial Communications on page 48 for more information).
The RS-485 connector has three diagnostic LEDs: a Power (PWR) LED to show when the adapter is powered properly, a Transmit Data (TX) LED to show when the adapter is sending data out from the PC side, and a Receive Data (RX) LED to show when the adapter is receiving data from the meter.
Installation
Figure 15 shows the connection of a meter to a PC using the RS485 output connector and a PDA7485 RS-232 to RS-422/485 converter in an RS-422 network. Figure 16 shows the connection of several meters to a PC using a PDA7485 RS-232 to RS-422/485 converter in an RS-485 network.
When using more than one meter in a multi-drop mode, each meter must be provided with its own unique address. The meter address (Slave ID) may be programmed between 1 and 247. The transmit delay may be set between 0 and 199 ms. The parity can be set to even, odd, or none with 1 or 2 stop bits.
To change the meter address:
1. Press and hold the Menu button for three seconds to access Advanced Features menu of the meter.
2. Press Up arrow until Serial (SEriaL) menu is displayed and press Enter, Addres is displayed.
3. Press Enter to change meter address using Right and Up arrow buttons. Press Enter to accept.
4. Press Menu button to exit and return to Run Mode.
Figure 15. RS-422 or RS-485 Wiring
Notes:
1. Termination resistors are optional and values depend on the cable length and characteristic
impedance. Consult the cable manufacturer for recommendations.
2. Refer to RS-232 to RS-422/485 Converter documentation for further details.
3. Use shielded cable, twisted-pairs plus ground. Connect ground shield only at one location.
16
Large Digital Display Instruction Manual
Figure 16. RS-485 Two-Wire Multi-Drop Wiring
RS485 Connector to RS-422/485 Serial
Converter Connections
RS-422/485 Serial
Converter
PDA1485 RS-485
Adapter
DO DI DO DI DI DO DI DO
Figure 17. Connections for RS485
Connector to Serial Converter
Notes:
1. Termination resistors are optional and values depend on the cable length and characteristic
impedance. Consult the cable manufacturer for recommendations.
2. Refer to RS-232 to RS-485 Converter documentation for further details.
3. Use shielded cable, twisted-pair plus ground. Connect ground shield only at one location.
Connections
Figure 17 details the wiring connections from the RS-485 connector to an RS-422/485 serial converter (such as the PDA7485 or PDA8485) for a four-wire network.
Three Wire Connection
In order to wire the 5 pins for use as a 3-wire half-duplex RS-485 connection, it is necessary to create a jumper connection between DI – DO and DI- – DO- as shown below.
Figure 18. Three-Wire RS485 Connection
17
Large Digital Display Instruction Manual

Digital I/O Connections

Digital inputs and outputs are provided in order to expand the functionality of the meter. Digital inputs are made via a push button or switch connection to the appropriate digital input connector block and the +5 VDC block. Digital output connections are made by wiring from the appropriate digital output block to the grounding terminal block.
Figure 19. Digital Input and Output Connections

F4 Digital Input Connections

Digital input F4 is also available on the meter. This digital input is connected with a normally open contact across F4 and COM, or with an active low signal applied to F4.
Figure 20. F4 Digital Input Connections
18
Loading...
+ 42 hidden pages