• USB, RS-232, & RS-485 Serial Communication Options
• External 4-Relay & Digital I/O Expansion Modules
• Input Power Options Include 85-265 VAC or 12-24 VDC
• Isolated 24 VDC @ 200 mA Transmitter Power Supply
• Modbus® RTU Communication Protocol Standard
Automation Products Group
1025 W 1700 N • Logan UT 84321 USA
Tel (435) 753-7300 • Fax (435) 753-7490
www.apgsensors.com
Din Mounted Digital Display Instruction Manual
CAUTION: Read complete
instructions prior to
installation and operation
of the meter.
WARNING: Risk of
electric shock or
personal injury.
Warning!
This product is not recommended for life support
applications or applications where malfunctioning could
result in personal injury or property loss. Anyone using this
product for such applications does so at his/her own risk.
Automation Products Group, Inc. shall not be held liable for
damages resulting from such improper use.
!
Disclaimer
The information contained in this document is subject to change without notice.
Automation Products Group makes no representations or warranties with respect to
the contents hereof and specifically disclaims any implied warranties of
merchantability or fitness for a particular purpose.
Limited Warranty
Automation Products Group, Inc. warrants this product against defects in material or
workmanship for the specified period under “Specifications” from the date of
shipment from the factory. Automation Products Group’s liability under this limited
warranty shall not exceed the purchase value, repair, or replacement of the defective
unit.
Registered Trademarks
Modbus® is a Registered Trademark of Schneider Automation Inc. All other
trademarks mentioned in this document are the property of their respective owners.
Connectors Labeling ------------------------------------------ 11
Power Connections-------------------------------------------- 11
Signal Connections -------------------------------------------- 12
Modbus RTU Serial Communications -------------------- 13
Relay Connections -------------------------------------------- 13
Switching Inductive Loads ----------------------------------- 13
F4 Digital Input Connections -------------------------------- 14
4-20 mA Output Connections ------------------------------- 14
Analog Output Transmitter Power Supply --------------- 14
External Relays & Digital I/O Connections -------------- 15
Interlock Relay Feature--------------------------------------- 15
Setup and Programming------------------------------ 16
Overview ----------------------------------------------------------- 16
Front Panel Buttons and Status LED Indicators ------ 16
MeterView® Pro Software ------------------------------------- 17
MeterView Pro Installation ----------------------------------- 17
Display Functions & Messages----------------------------- 18
Main Menu --------------------------------------------------------- 19
Setting Numeric Values --------------------------------------- 19
Setting Up the Meter (setup) -------------------------------- 20
Setting the Input Signal (Input) --------------------------- 20
Setting the Input Units or Custom Tags (units) ------- 21
Setting the Decimal Point (dEc pt) ----------------------- 21
Programming the Meter (prog) ----------------------------- 22
Setting the Display Parameter & Intensity (dsplay) -- 25
Setting the Relay Operation (relay) ---------------------- 26
Setting the Relay Action ------------------------------------- 26
Programming Set and Reset Points----------------------- 26
Setting Fail-Safe Operation --------------------------------- 27
Programming Time Delay------------------------------------ 27
Relay Action for Loss of 4-20 mA Input (Loop Break) 27
Relay and Alarm Operation Diagrams ------------------- 27
High Alarm Operation (Set > Reset) ---------------------- 27
Low Alarm Operation (Set < Reset)----------------------- 27
High Alarm with Fail-Safe Operation (Set > Reset) --- 28
Low Alarm with Fail-Safe Operation (Set < Reset) ---- 28
Pump Alternation Control Operation ---------------------- 29
Relay Sampling Operation ---------------------------------- 29
Signal Loss or Loop Break Relay Operation ------------ 30
Time Delay Operation ---------------------------------------- 30
Scaling the 4-20 mA Analog Output (Aout) ------------- 35
Reset Menu (reset) -------------------------------------------- 36
Control Menu (Contrl) ---------------------------------------- 36
Setting Up the Password (pass)---------------------------- 36
Protecting or Locking the Meter ---------------------------- 36
Making Changes to a Password Protected Meter ----- 37
Disabling Password Protection ----------------------------- 37
Advanced Features Menu ------------------------------------ 38
Advanced Features Menu & Display Messages ------- 38
Noise Filter (filter) ----------------------------------------- 39
Noise Filter Bypass (bypass) ------------------------------- 39
Rounding Feature (round) ---------------------------------- 39
Modbus RTU Serial Communications (serial) ------- 40
Select Menu (SElect) ---------------------------------------- 40
Signal Input Conditioning (Functn) ----------------------- 41
Low-Flow Cutoff (CutofF) ----------------------------------- 42
Analog Output Programming (AoutPr) ------------------- 42
Programmable Function Keys User Menu (user) ----- 42
Tare (tare) ------------------------------------------------------ 43
Internal Source Calibration (ICAL) ------------------------ 44
Meter Operation ------------------------------------------ 45
Front Panel Buttons Operation ----------------------------- 45
Function Keys Operation ------------------------------------- 45
F4 Operation ------------------------------------------------------ 45
Maximum/Minimum Readings ------------------------------ 45
This analog input process meter is a multi-purpose, easy-to-use digital process meter ideal for
level, flow rate, temperature, or pressure transmitter applications. Its superluminous LED digits
make it easily readable in smoke, dust, fog, and, with the optional sunlight readable display,
even direct sunlight. It accepts current and voltage signals (e.g. 4-20 mA, 0-10 V). Three of the
front panel buttons can be custom-programmed for a specific operation. The analog input can
be scaled to display the process in two different scales; for example, the main display could
indicate level in feet and the second display could indicate the volume in gallons.
The basic model includes an isolated 24 VDC transmitter power supply that can be used to
power the input transmitter or other devices. An additional isolated 24 VDC power supply is
included with the 4-20 mA output option. A digital input is standard.
A fully loaded meter has the following: four SPDT relays, 4-20 mA output, and two 24 VDC power
supplies. The meter’s capabilities may be enhanced by adding the following external expansion
modules: four SPST relays (creating an eight-relay process meter), two digital I/O modules with
four inputs and four outputs each, and USB, RS-232 or RS-485 communication adapters.
The eight relays can be used for alarm indication or process control applications such as pump
alternation control. The 4-20 mA isolated output, Modbus RTU serial communications, and digital
I/O options make this meter an excellent addition to any system.
4
Din Mounted Digital Display Instruction Manual
Model Number
Reorder Number
Power
Options
PD6000-6R0-AP
DDD-A00
85-265 VAC
No options
PD6000-6R2-AP
DDD-A02
85-265 VAC
2 relays
PD6000-6R3-AP
DDD-A10
85-265 VAC
4-20 mA output
PD6000-6R4-AP
DDD-A04
85-265 VAC
4 relays
PD6000-6R5-AP
DDD-A12
85-265 VAC
2 relays & 4-20 mA output
PD6000-6R7-AP
DDD-A14
85-265 VAC
4 relays & 4-20 mA output
PD6000-7R0-AP
DDD-D00
12-24 VDC
No options
PD6000-7R2-AP
DDD-D02
12-24 VDC
2 relays
PD6000-7R3-AP
DDD-D10
12-24 VDC
4-20 mA output
PD6000-7R4-AP
DDD-D04
12-24 VDC
4 relays
PD6000-7R5-AP
DDD-D12
12-24 VDC
2 relays & 4-20 mA output
PD6000-7R7-AP
DDD-D14
12-24 VDC
4 relays & 4-20 mA output
Model Number
Reorder Number
Power
Options
PD6000-6H0-AP
DBD-A00
85-265 VAC
No options
PD6000-6H2-AP
DBD-A02
85-265 VAC
2 relays
PD6000-6H3-AP
DBD-A10
85-265 VAC
4-20 mA output
PD6000-6H4-AP
DBD-A04
85-265 VAC
4 relays
PD6000-6H5-AP
DBD-A12
85-265 VAC
2 relays & 4-20 mA output
PD6000-6H7-AP
DBD-A14
85-265 VAC
4 relays & 4-20 mA output
PD6000-7H0-AP
DBD-D00
12-24 VDC
No options
PD6000-7H2-AP
DBD-D02
12-24 VDC
2 relays
PD6000-7H3-AP
DBD-D10
12-24 VDC
4-20 mA output
PD6000-7H4-AP
DBD-D04
12-24 VDC
4 relays
PD6000-7H5-AP
DBD-D12
12-24 VDC
2 relays & 4-20 mA output
PD6000-7H7-AP
DBD-D14
12-24 VDC
4 relays & 4-20 mA output
Model Number
Description
PDA1002
DIN rail mounting kit for two expansion modules
PDA1004
4 SPST (Form A) relays
PDA1044
4 digital inputs & 4 digital outputs (2 may be connected)
PDA1232
RS-232 serial adapter
PDA1485
RS-485 serial adapter
PDA7485-I
RS-232 to RS-422/485 isolated converter
PDA7485-N
RS-232 to RS-422/485 non-isolated converter
PDA8232-N
USB to RS-232 non-isolated converter
PDA8485-I
USB to RS-422/485 isolated converter
PDA8485-N
USB to RS-422/485 non-isolated converter
PDX6901
Suppressor (snubber): 0.01 µF/470 , 250 VAC
Ordering Information
Standard Models
Sunlight Readable Display Models
Accessories
Manufactured by Precision Digital Corporation, 233 South St, Hopkinton MA 01748 USA
5
Din Mounted Digital Display Instruction Manual
Display
Line 1: 0.60" (15 mm) high, red LEDs
Line 2: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero
blanking
Display
Intensity
Eight user selectable intensity levels
Display
Update Rate
5/second (200 ms)
Overrange
Display flashes 999999
Underrange
Display flashes -99999
Display
Assignment
Display lines 1 and 2 may be assigned to PV1,
PV2, PCT, d r-u, d gross, d nt-g, max/min, max
& min, set points, units (display line 2 only), or
Modbus input.
Programming
Methods
Four front panel buttons, digital inputs, PC and
MeterView Pro software, or Modbus registers.
Noise Filter
Programmable from 2 to 199 (0 will disable filter)
Filter Bypass
Programmable from 0.1 to 99.9% of calibrated
span
Recalibration
All ranges are calibrated at the factory.
Recalibration is recommended at least every
12 months.
Max/Min
Display
Max/min readings reached by the process are
stored until reset by the user or until power to the
meter is turned off.
Password
Three programmable passwords restrict
modification of programmed settings.
Pass 1: Allows use of function keys and digital
inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function keys,
and digital inputs.
Power
Options
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or 12-24 VDC 10%, 15 W max
Powered over USB for configuration only.
85-265 VAC models rated @ 200 mA max, 12-24
VDC powered models rated @ 100 mA max, @ 50
mA max for 5 or 10 VDC supply.
Non-Volatile
Memory
All programmed settings are stored in nonvolatile memory for a minimum of ten years if
power is lost.
Fuse
Required external fuse: UL Recognized, 5 A
max, slow blow; up to 6 meters may share one 5
A fuse
Normal Mode
Rejection
Greater than 60 dB at 50/60 Hz
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient overvoltages
than Installation Overvoltage Category III.
Environmental
Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
Connections
Removable screw terminal blocks accept 12 to
22 AWG wire, RJ45 for external relays, digital
I/O, and serial communication adapters.
Enclosure
1/8 DIN, high impact plastic, UL 94V-0, color:
black
Mounting
1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies are
provided.
Tightening
Torque
Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall
Dimensions
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143
mm)
(W x H x D)
Weight
9.5 oz (269 g)
Warranty
Please see https://www.apgsensors.com/aboutus/terms-conditions for full warranty statement.
Inputs
Field selectable:
0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus
PV (Slave)
Accuracy
±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy
range: 10-100% of calibrated span
Temperature
Drift
0.005% of calibrated span/C max from 0 to
65C ambient,
0.01% of calibrated span/C max from -40 to
0C ambient
Signal Input
Conditioning
Linear, square root, programmable exponent, or
round horizontal tank volume calculation
Multi-Point
Linearization
2 to 32 points for PV or PV1
2 to 8 points for PV2 (Dual-scale Level feature)
Programmable
Exponent
1.0001 to 2.9999
Round H Tank
Diameter & Length: 999.999 inch or cm
calculates volume in gallons or liters
respectively.
Low-Flow
Cutoff
0-999999 (0 disables cutoff function)
Decimal Point
Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or
dddddd
Calibration
Range
Input Range
Minimum Span
Input 1 & Input 2
4-20 mA
0.15 mA
10 V
0.01 V
An error message will appear if the input 1 and
input 2 signals are too close together.
Input
Impedance
Voltage ranges: greater than 500 k
Current ranges: 50 - 100 (depending on resettable
fuse impedance)
Input
Overload
Current input protected by resettable fuse, 30
VDC max.
Fuse resets automatically after fault is removed.
F4 Digital Input
Contacts
3.3 VDC on contact. Connect normally open
contacts across F4 to COM.
Specifications
Except where noted all specifications apply to operation at +25°C.
General
Process Input
6
Din Mounted Digital Display Instruction Manual
F4 Digital Input
Logic Levels
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Rating
2 or 4 SPDT (Form C) internal and/or 4 SPST
(Form A) external; rated 3 A @ 30 VDC and
125/250 VAC resistive load; 1/14 HP (≈ 50 W)
@ 125/250 VAC for inductive loads
Noise
Suppression
Noise suppression is recommended for each
relay contact switching inductive loads; see
page 13 for details.
Deadband
0-100% of span, user programmable
High or Low
Alarm
User may program any alarm for high or low trip
point.
Unused alarm LEDs and relays may be disabled
(turn off).
Relay
Operation
Automatic (non-latching) and/or manual reset
Latching (requires manual acknowledge)
with/without clear
Pump alternation control (2 to 8 relays)
Sampling (based on time)
Off (disable unused relays and enable Interlock
feature)
Manual on/off control mode
Relay Reset
User selectable via front panel buttons or digital
inputs
1. Automatic reset only (non-latching), when
the input passes the reset point.
2. Automatic + manual reset at any time (nonlatching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has
cleared (latching)
Note: Front panel button or digital input may be
assigned to acknowledge relays
programmed for manual reset.
Time Delay
0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay
Fail-Safe
Operation
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm
condition.
In case of power failure, relay will go to
alarm state.
Auto
Initialization
When power is applied to the meter, relays will
reflect the state of the input to the meter.
Output Source
Process variable (PV), max, min, set points 1-8,
Modbus input, or manual control mode
Scaling Range
1.000 to 23.000 mA for any display range
Calibration
Factory calibrated: 4.000 to 20.000 = 4-20 mA
output
Analog Out
Programming
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
Accuracy
± 0.1% of span ± 0.004 mA
Temperature
Drift
0.4 µA/C max from 0 to 65C ambient,
0.8 µA/C max from -40 to 0C ambient
Note: Analog output drift is separate from input drift.
Isolated
Transmitter
Power Supply
Terminals I+ & R: 24 VDC 10%. May be used to
power the 4-20 mA output or other devices.
Refer to Transmitter Supply Voltage Selection
(P+, P-) on page 10. All models rated @ 40 mA
max.
External Loop
Power Supply
35 VDC maximum
Output Loop
Resistance
Power supply
Minimum
Maximum
24 VDC
10
700
35 VDC
(external)
100
1200
Slave Id
1 – 247 (Meter address)
Baud Rate
300 – 19,200 bps
Transmit
Time Delay
Programmable between 0 and 199 ms
Data
8 bit (1 start bit, 1 or 2 stop bits)
Parity
Even, Odd, or None with 1 or 2 stop bits
Byte-To-Byte
Timeout
0.01 – 2.54 second
Turn Around
Delay
Less than 2 ms (fixed)
Note: Refer to the Modbus Register Tables located at
www.apgsensors.com for details.
System
Requirements
Microsoft® Windows® XP/Vista/7/8/10
Communications
USB 2.0 (Standard USB A to Micro USB B)
Configuration
Configure meters one at a time
Relays
Isolated 4-20 mA Transmitter Output
Modbus® RTU Serial Communications
MeterView Pro
7
Din Mounted Digital Display Instruction Manual
UL & C-UL Listed
USA & Canada
UL 508 Industrial Control Equipment
UL File Number
E160849
Front Panel
UL Type 4X, NEMA 4X, IP65; panel gasket provided
Low Voltage Directive
EN 61010-1:2010
Safety requirements for measurement, control, and laboratory use
Emissions
EN 55022:2010
Class A ITE emissions requirements
Radiated Emissions
Class A
AC Mains Conducted
Emissions
Class A
Immunity
EN 61326-1:2013
Measurement, control, and laboratory equipment
EN 61000-6-2:2005
EMC heavy industrial generic immunity standard
RFI - Amplitude
Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast
Transients
±2kV AC mains, ±1kV other
Electrostatic
Discharge
±4kV contact, ±8kV air
RFI - Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-Frequency
Magnetic Field
30 A/m 70%V for 0.5 period
Voltage Dips
40%V for 5 & 50 periods
70%V for 25 periods
Voltage Interruptions
<5%V for 250 periods
Compliance Information
Safety
Electromagnetic Compatibility
Note:
Testing was conducted on meters installed through the covers of grounded metal enclosures with
cable shields grounded at the point of entry representing installations designed to optimize EMC
performance.
Declaration of Conformity available at www.apgsensors.com
8
Din Mounted Digital Display Instruction Manual
CAUTION: Read complete
instructions prior to installation
and operation of the meter.
WARNING: Risk of electric
shock or personal injury.
Warning!
Hazardous voltages exist within enclosure.
Installation and service should be performed
only by trained service personnel.
Figure 1. 1/8 DIN Panel Cutout Dimensions
Figure 2. Panel Mounting Details
!
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout
toDIN43700
SquareCorners to0.060"
(1.5mm)MaxRadius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Safety Information
Installation
There is no need to remove the meter from its case to complete the installation, wiring, and setup of
the meter for most applications.
Instructions are provided for changing the transmitter power supply to output 5 or 10 VDC instead of
24 VDC, see page 10.
Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if
any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for
assistance.
Panel Mounting Instructions
•Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1
below, for more details.
• Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
Recommended minimum panel thickness to maintain Type 4X
rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
•Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼"
(6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
• Insert meter into the panel cutout.
• Install mounting brackets and tighten the screws against the panel. To achieve a proper seal, tighten
the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT
OVER TIGHTEN, as the rear of the panel may be damaged.
9
Din Mounted Digital Display Instruction Manual
Figure 3. Meter Dimensions - Side View
Figure 4. Meter Dimensions - Top View
NO
NC
NC
C
NO
C
NO
NC
NC
C
NO
C
+
-
R
Mounting Dimensions
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12-24 VDC power option, are shipped from the factory
configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured
accordingly.
To access the voltage selection jumper:
1. Remove all the wiring connectors.
2. Unscrew the back cover.
3. Slide out the back cover by about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector, for the desired excitation
voltage as shown.
Figure 5. Transmitter Supply Voltage Selection
10
Din Mounted Digital Display Instruction Manual
Use copper wire with 60°C or 60/75°C insulation for all line
voltage connections. Observe all safety regulations. Electrical
wiring should be performed in accordance with all applicable
national, state, and local codes to prevent damage to the
meter and ensure personnel safety.
Warning!
Do not connect any equipment other than Automation
Products Group’s expansion modules, cables, or meters
to the RJ45 M-LINK connector. Otherwise damage will
occur to the equipment and the meter.
Figure 7. Power Connections
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+
-
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter.
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all connectors available with requested
configuration.
Figure 6. Connector Labeling for Fully Loaded Meter
Power Connections
Power connections are made to a two-terminal connector labeled POWER on Figure 6 on page 11. The
meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring
convention.
11
Din Mounted Digital Display Instruction Manual
Signal Connections
Signal connections are made to a six-terminal connector labeled SIGNAL on Figure 6. The COM
(common) terminal is the return for the 4-20 mA and the 10 V input signals.
Current (mA) Connections
The following figures show examples of current connections.
There are no switches or jumpers to set up for current inputs. Setup and programming is performed
through the front panel buttons.
Figure 8. Transmitters Powered by Internal Supply
Figure 9. Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable fuse. The display may or may not
show a fault condition depending on the nature of the overload.
The fuse limits the current to a safe level when it detects a fault condition, and automatically resets itself
when the fault condition is removed.
Voltage (V) Connections
The following figures show examples of voltage connections.
There are no switches or jumpers to set up for voltage inputs. Setup and programming is performed
through the front panel buttons.
Figure 10. Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.
12
Din Mounted Digital Display Instruction Manual
CNONONCNCC
RELAY4RELAY3
436521
CNONO NCNCC
RELAY2RELAY1
436521
C
R
C
R
Use a diode with a reverse
breakdown voltage two to
three times the circuit voltage
and forward current at least as
large as the load current.
Modbus RTU Serial Communications
Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 6. For
interfacing to the meter, use the PDA1232 for RS-232 or the PDA1485 for RS-485. The same port is used
for interfacing with all expansion modules (e.g. external relays, digital I/O).
Relay Connections
Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 on Figure 6.
Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of
the corresponding relay. The relays’ C terminals should not be confused with the COM (common) terminal
of the INPUT SIGNAL connector.
Figure 11. Relay Connections
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent
disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts.
Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased
as complete assemblies. Refer to the following circuits for RC network assembly and installation:
Figure 12. AC and DC Loads Protection
Choose R and C as follows:
R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC network may also be installed across the load.
Experiment for best results.
Figure 13. Low Voltage DC Loads Protection
RC Networks Available from Automation Products Group
RC networks are available from Automation Products Group and should be applied to each relay contact switching an
inductive load. Part number: PDX6901.
Note: Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
13
Din Mounted Digital Display Instruction Manual
12-35 VDC
Power
Supply
+
4-20 mA
Input Meter
-
+
RI-I+
132
RELAY1
321
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
RI-I+
MA OUT
132
RELAY1
321
24 V
MA OUT
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input is connected with a normally open contact
across F4 and COM, or with an active low signal applied to F4.
Figure 14. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT.
The 4-20 mA output may be powered internally or from an external power supply.
Figure 15. 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the
analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
14
Din Mounted Digital Display Instruction Manual
Warning!
Do not connect or disconnect the expansion
modules with the power on!
More detailed instructions are provided with each
optional expansion module.
Figure 16. Expansion Modules & DIN Rail
Mounting Kit
Figure 17. External Relays Module
Connections
12
RLY5RLY6RLY7RLY8
345678
NO C NO C NO C NO C
123456
+5I1I2I3I4 O1
78
O2 O3
910
O4 G
DI 1-4DO 1-4
5 VDCGND
External Relays & Digital I/O Connections
The relay and the digital I/O expansion modules PDA1004 & PDA1044 are connected to the meter using
a CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are
identical and interchangeable; they are used to connect additional modules to the system.
Note: The jumper located between the RJ45 connectors of the PDA1044 must be removed on the second
digital I/O module in order for the system to recognize it as module #2.
Figure 18. Digital I/O Module Connections
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as
interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay. This
feature is enabled by configuring the relay, and relative digital input(s) (see page 35).
In one example, dry interlock contacts are connected in series to one digital input which will be used to
force on (energize) the assigned interlock power relay when all interlock contacts are closed (safe). The
interlock relay front panel LED flashes when locked out. The interlock relay would be wired in-series with
the load (N/O contact). See below.
Figure 19. Interlock Connections
15
Din Mounted Digital Display Instruction Manual
The meter is factory calibrated prior to shipment to read
in milliamps and volts depending on the input selection.
The calibration equipment is certified to NIST standards.
Button
Symbol
Description
LED
Status
Menu
1-8
Alarm 1-8 indicator
Right arrow/F1
1-8
M
Flashing: Relay in
manual control mode
Up arrow/F2
T Flashing: Tare
Enter/F3
1-8
Flashing: Relay
interlock switch open
Note:
F4 is a digital input. Alarms 5-
8 are enabled when relay
expansion module is installed.
Note:
LEDs for relays in manual
mode flash with the “M” LED
every 10 seconds. “M” flashing
by itself indicates Aout –
manual control is used.
Setup and Programming
Overview
There are no jumpers to set for the meter input selection.
Setup and programming is done through the front panel buttons.
After power and input signal connections have been completed and verified, apply power to the meter.
Front Panel Buttons and Status LED Indicators
• Press the Menu button to enter or exit the Programming Mode at any time.
• Press the Right arrow button to move to the next digit during digit or decimal point programming.
• Press or hold the Up-arrow button to scroll through the menus, decimal point, or to increment the
value of a digit.
• Press the Enter button to access a menu or to accept a setting.
• Press and hold the Menu button for three seconds to access the advanced features of the meter.
16
Din Mounted Digital Display Instruction Manual
Note: If you decide to update your MeterView Pro software, once the installation has completed, you
will be asked if you want to update the setup files located on the meter itself. This way, you will always
have the most current version on the meter for future installs.
Warning!
Do not unplug the meter while the new installation files are being written to it. The
meter will display
uwrite
during the process and you will receive an onscreen
notification once the process is complete.
MeterView® Pro Software
The meter can also be programmed using the PC-based MeterView Pro software included with the meter.
This software can be installed on any Microsoft® Windows® (XP/Vista/7/8/10) computer by connecting
the meter’s onboard USB. The meter is powered by the USB connection, so there is no need to wire
anything prior to programming the meter, though USB is intended only for meter configuration.
MeterView Pro Installation
1. Connect one end of the provided USB cable to the meter and the other end to the computer.
The computer will automatically install the driver software it needs to talk to the meter.
Only one meter may be connected at a time.
Attaching multiple meters will cause a
conflict with the meter software.
2. Once the driver is installed, an AutoPlay dialog should appear
for the drive “MAINSTAL.” Click “Open folder to view files.”
If the computer does not display an AutoPlay dialog for the
drive “MAINSTAL,” you should open My Computer and doubleclick on the drive labeled “MAINSTAL.”
3. Double-click on the file named “MAStart.” The program will
open a few windows and install two programs on your
computer. Simply follow the onscreen instructions until you see
one of the dialogs below. If you receive a “User Account
Control” warning, click “Yes.”
4. If there is an update available, click the “Update” button to
install the new version. Otherwise, click “Configure” to begin
programming your meter.
Data logging for one meter at a time is available with MeterView Pro software. More advanced data
acquisition may be accomplished by using any Modbus RTU compliant software. Additional information
regarding configuration and monitoring of the meter using MeterView Pro software is available online.
17
Din Mounted Digital Display Instruction Manual
Display
Parameter
Action/Setting Description
setup
Setup
Enter Setup menu
Input
Input
Enter Input selection menu
nmA
4-20 mA
Set meter for 4-20 mA input
volt
0-10 VDC
Set meter for 10 VDC input
d-SCAL
Dual-scale
Press Enter to select dualscale display for some level
applications (Select Yes or
No)
units
Units
Select the display units/tags
Dec pt
Decimal
point
Set decimal point
PV 1
PV1
PV1 decimal point (Level)
PV 2
PV2
PV2 decimal point (Level)
prog
Program
Enter the Program menu
SCALE
Scale
Enter the Scale menu
SCAL 1
Scale 1
Enter the Scale menu for
PV1
SCAL 2
Scale 2
Enter the Scale menu for
PV2
Cal
Calibrate
Enter the Calibration menu
Inp 1
Input 1
Calibrate input 1 signal or
program input 1 value
Dis 1
Display 1
Program display 1 value
Inp 2
Input 2
Calibrate input 2 signal or
program input 2 value (up to
32 points)
Dis 2
Display 2
Program display 2 value (up
to 32 points)
Error
Error
Error, calibration not
successful, check signal or
programmed value
dsplay
Display
Enter the Display menu
Line 1
Display
Line 1
Press Enter to assign the
Main display parameter
(default: PV)
Line 2
Display
Line 2
Press Enter to assign the
small display parameter
(default: engineering units)
d-Inty
Display
intensity
Set display intensity level
from 1 to 8
RELaY
Relay
Enter the Relay menu
RLY 1
Relay 1
Relay 1 setup
Act 1
Action 1
Set relay 1 action
Auto
Automatic
Set relay for automatic reset
A-nman
Automanual
Set relay for automatic &
manual reset any time
LatCH
Latching
Set relay for latching
operation
Display
Parameter
Action/Setting Description
Lt-CLr
Latchingcleared
Set relay for latching
operation with manual reset
only after alarm condition
has cleared
Altern
Alternate
Set relay for pump
alternation control
Sanmpl
Sampling
Set relay for sampling
operation
OFF
Off
Disable relay and front
panel status LED (Select Off
to enable Interlock feature)
Set 1
Set 1
Program set point 1
RSt 1
Reset 1
Program reset point 1
RLY 2
Relay 2
Relays 2-8 setup
Note: Relays 5-8 are shown,
only if expansion relay
module is installed.
FaiLSF
Fail-safe
Enter Fail-safe menu
FLS 1
Fail-safe 1
Set relay 1 fail-safe
operation
on
On
Enable fail-safe operation
off
Off
Disable fail-safe operation
FLS 2
Fail-safe 2
Set relays 2-8 fail-safe
operation
DeLAY
Delay
Enter relay Time Delay
menu
DLY 1
Delay 1
Enter relay 1 time delay
setup
On 1
On 1
Set relay 1 On time delay
OFF 1
Off 1
Set relay 1 Off time delay
DLY 2
Delay 2
Enter relays 2-8 time delay
setup
break
Loop break
Set relay condition if loop
break detected
ignore
Ignore
Ignore loop break condition
(Processed as a low signal
condition)
On
On
Relay goes to alarm
condition when loop break is
detected
Off
Off
Relay goes to non-alarm
condition when loop break is
detected
Aout
Analog
output
Enter the Analog output
scaling menu
Dis 1
Display 1
Program display 1 value
Out 1
Output 1
Program output 1 value (e.g.
4.000 mA)
Dis 2
Display 2
Program display 2 value
Out 2
Output 2
Program output 2 value (e.g.
20.000 mA)
reset
Reset
Press Enter to access the
Reset menu
Display Functions & Messages
The meter displays various functions and messages during setup, programming, and operation. The following table
shows the main menu functions and messages in the order they appear in the menu.
18
Din Mounted Digital Display Instruction Manual
Display
Parameter
Action/Setting Description
Rst Hi
Reset high
Press Enter to reset max
display
Rst Lo
Reset low
Press Enter to reset min
display
Rst HL
Reset
high & low
Press Enter to reset max &
min displays
Rst tr
Reset tare
Reset tare
Contrl
Control
Enter Control menu
Auto
Automatic
Press Enter to set meter for
automatic operation
nmAn
Manual
Press Enter to manually
control relays or analog
output operation
Display
Parameter
Action/Setting Description
pass
Password
Enter the Password menu
Pass 1
Password 1
Set or enter Password 1
Pass 2
Password 2
Set or enter Password 2
Pass 3
Password 3
Set or enter Password 3
unloc
Unlocked
Program password to lock
meter
locd
Locked
Enter password to unlock
meter
999999
-99999
Flashing
Over/under range condition
004.000
004.000
005.000
dis 1dis 1dis 1
Next
Setting
Select
Next
Digit
Increment
Digital
Value
Accept
Setting
Main Menu
The main menu consists of the most commonly
used functions: Setup, Reset, Control, and
Password.
•Press Menu button to enter Programming
Mode then press the Up-arrow button to scroll
main menu.
•Press Menu, at any time, to exit and return to
Run Mode. Changes made to settings prior to
pressing Enter are not saved.
•Changes to the settings are saved to memory
only after pressing Enter/F3.
•The display moves to the next menu every
time a setting is accepted by pressing
Enter/F3.
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit
and Up arrow to increment digit value. The digit being changed is displayed brighter than the rest. Press
and hold Up to auto-increment the display value. If negative numbers are allowed, the first digit position
will include a negative symbol (-) after the 9.
Press the Enter button, at any time, to accept a setting or Menu button to exit without saving changes.
19
Din Mounted Digital Display Instruction Manual
Note:
Scal 1 & Scal 2 are
displayed instead of
Scale if d-SCAL is
selected under the
Setup Input menu.
They correspond to
the PV1 & PV2
scales.
Enter custom
units here
Note:
Use the d-SCAL selection
to activate the dual-scale
level feature - PV1 & PV2
(see introduction on page 6).
Set d-SCAL to no if both
displays are to be used for
anything other than PV1 & PV2.
Setting Up the Meter (setup)
The Setup menu is used to select:
1. Input signal the meter will
accept
2. Dual-scale feature for
some level applications
3. Select the display
units/tags
4. Decimal point position
5. Programming Menu
6. Display parameter and
intensity
7. Relay operation
8. 4-20 mA analog output
scaling
Press the Enter button to access
any menu or press Up arrow
button to scroll through choices.
Press the Menu button to exit at
any time.
Setting the Input Signal (Input)
Enter the Input menu to set up the meter to display current (mA) or voltage (volt) inputs.
The current input is capable of accepting any signal from 0 to 20 mA. Select current input to accept 0-20
mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC. Select voltage input to accept 05, 1-5, 0-10, or 10 VDC signals.
After selecting mA or Volt input, d-SCAL is displayed; press Enter to select “Yes” or “No”. Selecting “Yes”
enables the dual-scale feature, which allows for the Scale (SCALE) and Units (units) menus to be used to
scale the same input in two different scales for PV1 & PV2.
Set d-SCAL to no if both displays are to be used for anything other than PV1 & PV2.
20
Din Mounted Digital Display Instruction Manual
Display
Character
Display
Character
Display
Character
Display
Character
0
0
C
C
k
K
v V 1
1
c
c
l
L
uw
w
2
2
d
d
n m
m
x X 3
3
e
E
n
n
y Y 4
4
f
F
O
O
z Z 5
5
g
G
o
o
- - 6
6
9
g
p
P
/
/
7
7
H
H
q
q
[
]
8
8
h
h
r
r
] [ 9
9
I
I
s
S
=
=
A
A
I
i
t
t
!
Degree(<)
b
b
j
J
u
u
Space
Setting the Input Units or Custom Tags (units)
Enter the input unit or custom tag that will be displayed if d unit is selected as the line 2 parameter. See
the flow chart on page 25 to access the display menu to show the unit or tag on display line 2. The
engineering units or custom legends can be set using the following 7-segment character set:
Notes:
Degree symbol represented by (<) if programming with MeterView® Pro.
The letters “m” and “w” use two 7-segment LEDs each; when selected the characters to the right are shifted
one position.
Press and hold up arrow to auto-scroll the characters in the display.
Setting the Decimal Point (dEc pt)
The decimal point may be set with up to five decimal places or with no decimal point at all.
Pressing the Right arrow moves the decimal point one place to the right until no decimal point is
displayed, and then it moves to the leftmost position. Pressing the Up arrow moves the decimal point one
place to the left.
If the dual-scale level feature is selected, the decimal point selections for PV1 & PV2 are enabled.
21
Din Mounted Digital Display Instruction Manual
Programming the Meter (prog)
It is very important to read the following information, before proceeding to program the meter:
•The meter is factory calibrated prior to shipment to read in milliamps and volts depending on the input
selection. The calibration equipment is certified to NIST standards.
•Use the Scale menu to scale the process input (e.g. 4-20 mA). A calibrated signal source is not
needed to scale the meter.
• Use the Calibrate menu to apply a signal from a calibrator or a flowmeter.
• The meter is a single input meter with dual-scale capability.
The Program menu contains the Scale and the Calibrate menus.
Note: The Scale and Calibrate functions are exclusive of each other. The meter uses the last function
programmed. Only one of these methods can be employed at a time. The Scale and Calibrate functions
can use up to 32 points (default is 2). The number of points should be set in the Advanced menu under
the Multi-Point Linearization (Linear) menu selection prior to scaling and calibration of the meter, see
page 41 for details.
If the dual-scale level feature is selected in the Setup menu, the Scale 1 and Scale 2 menus are enabled
for PV1 & PV2 respectively.
The process input may be calibrated or scaled to any display value within the range of the meter.
Program Menu for Single Scale Process
Program Menu for Dual-Scale Level Applications
Additional parameters, not needed for most applications, are programmed in the AdvancedFeatures
menu; see Advanced Features Menu, page 38.
Multi-Point Calibration & Scaling
The meter is set up at the factory for 2-point linear calibration. The number of points for multi-point
calibration/scaling is set up in the AdvancedFeatures menu. Up to 32 linearization points may be
selected for PV1 and up to 8 linearization points may be selected for PV2. See page 41 for details.
22
Din Mounted Digital Display Instruction Manual
Scaling the Input for PV1 (SCAL 1)
Scaling the Input for PV2 (SCAL 2)
For instructions on how to
program numeric values see
Setting Numeric Values, page 19.
Input Range
Input 1 & Input 2 Span
4-20 mA
0.15 mA
10 VDC
0.01 VDC
Scaling the Meter (SCALE)
The process input (4-20 mA, 10 VDC) can be scaled to display the process variable in engineering units.
A signal source is not needed to scale the meter; simply program the inputs and corresponding display
values.
Dual-Scale for Level Application
The analog input can be displayed in two different scales, by enabling the dual-scale feature (d-SCAL) in
the Setup-Input menu, see page 20.
To enable the dual-scale feature for some level applications you must select d-SCAL in the Input
selection menu.
Error Message (Error)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to the input prior to the failure during calibration or
scaling and to input 1 during internal calibration, allowing the appropriate input signal to be applied or
programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is connected backwards.
2. Wrong signal selection in Setup menu.
3. Minimum input span requirements not maintained.
4. Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum input span is the minimum difference between
input 1 and input 2 signals required to complete the calibration
or scaling of the meter.
23
Din Mounted Digital Display Instruction Manual
Note: To scale the meter without a signal source refer to
Scaling the Meter (SCALE), page 23.
Warm up the meter for at least 15 minutes before
performing calibration to ensure specified accuracy.
Calibrating the Meter with External Source (Cal)
The meter can be calibrated to display the process variable in engineering units by applying the
appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended to calibrate the meter.
24
Din Mounted Digital Display Instruction Manual
Setting the Display Parameter & Intensity (dsplay)
The main display (Line 1) can be programmed to
display:
1. Process value 1 (PV1)
2. Process value 2 (PV2)
3. Percent of PV1 (PCT)
4. Relay set points
5. Max & min values
6. Modbus input
7. Display reading and units
8. Display gross
9. Toggle net & gross
The secondary display (Line 2) can be programmed
to display:
1. Unit
2. Process value 1 (PV1)
3. Process value 2 (PV2)
4. Percent of PV1 (PCT)
5. Relay set points
6. Max & min values
7. Engineering units or custom legends
8. Modbus input
9. Off (no display)
10. Toggle reading and units
11. Display gross
12. Toggle net/gross
Display Intensity: The meter has eight display
intensity levels to give the best performance under
various lighting conditions. Select intensity 8 for
outdoor applications. The default intensity setting is 8.
After setting up the input and display, press the Menu button to exit programming and skip the rest of the
setup menu. Press the Menu button again and the Up arrow to reach the Program menu and complete
the scaling or calibration of the meter.
25
Din Mounted Digital Display Instruction Manual
Caution!
During setup, the relays do not follow the input and they will
remain in the state found prior to entering the Relay menu.
!
From
Relay 1
Menu
Latch
Act 1
S am pl
Act 1
Act 1
rly 1
A -m An
Act 1
Auto
Act 1
Lt-Clr
Act 1
Altern
Act 1
OFF
Act 1
set 1
rly 1
rst 1
rly 1
Program
Set Point
Program
Reset Point
Setting the Relay Operation (relay)
This menu is used to set up the operation of the relays.
1. Relay action
a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm condition has cleared)
e. Pump alternation control (automatic reset only)
f. Sampling (the relay
is activated for a
user-specified time)
g. Off (relay state
controlled by Interlock feature)
2. Set point
3. Reset point
4. Fail-safe operation
a. On (enabled)
b. Off (disabled)
5. Time delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
6. Relay action for loss (break) of 4-20
mA input (ignore, on, off)
Setting the Relay Action
Operation of the relays is programmed in the Action menu.
The relays may be set up for any of the following modes of
operation:
1. Automatic reset (non-latching)
2. Automatic + manual reset at any time (non-latching)
3. Latching (manual reset only, at any time)
4. Latching with Clear (manual reset only after alarm condition has cleared)
5. Pump alternation control (automatic reset only)
6. Sampling (the relay is activated for a user-specified time)
7. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-8 are set up in a similar fashion.
Programming Set and Reset Points
High alarm indication: program set point above reset point.
Low alarm indication: program set point below reset point.
The deadband is determined by the difference between set and reset points. Minimum deadband is
one display count. If the set and reset points are programmed with the same value, the relay will reset
one count below the set point.
Note: Changes are not saved until the reset point has been
accepted.
26
Din Mounted Digital Display Instruction Manual
High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime
to turn "off" relay. To detect a new alarm condition, the
signal must go below the set point, and then go above
it.
Low Alarm Operation (Set < Reset)
For Manual reset mode, ACK can be pressed anytime
to turn "off" relay. For relay to turn back “on”, signal
must go above set point and then go below it.
Setting Fail-Safe Operation
In fail-safe mode of operation, the relay coil is energized when the process variable is within safe limits
and the relay coil is de-energized when the alarm condition exists. The fail-safe operation is set
independently for each relay. Select on to enable or select off to disable fail-safe operation.
Programming Time Delay
The On and Off time delays may be programmed for each relay between 0 and 999.9 seconds. The
relays will transfer only after the condition has been maintained for the corresponding time delay.
The On time delay is associated with the set point.
The Off time delay is associated with the reset point.
Relay Action for Loss of 4-20 mA Input (Loop Break)
The loop break feature is associated with the 4-20 mA input. Each relay may be programmed to go to one
of the following conditions when the meter detects the loss of the input signal (i.e. < 0.005 mA):
1. Turn On (Go to alarm condition)
2. Turn Off (Go to non-alarm condition)
3. Ignore (Processed as a low signal condition)
Note: This is not a true loop break condition; if the signal drops below 0.005 mA, it is interpreted as a
“loop break” condition.
Relay and Alarm Operation Diagrams
The following graphs illustrate the operation of the relays, status LEDs, and ACK button.
27
Din Mounted Digital Display Instruction Manual
High Alarm with Fail-Safe
Operation (Set > Reset)
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will
go to alarm state.
Low Alarm with Fail-Safe Operation
(Set < Reset)
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will
go to alarm state.
28
Din Mounted Digital Display Instruction Manual
Set
Reset
Relay
LED
Input
Sample
Time
Sample
Time
Sample
Time
Pump Alternation Control Operation
Relay Sampling Operation
When the signal crosses the set point, the relay trips and the sample time starts. After the sample time
has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up for high
alarms and going down for low alarms.
The sample time can be programmed between 0.1 and 5999.9 seconds.
29
Din Mounted Digital Display Instruction Manual
Relay
LED
Input
Loop Break = Ignore
de-energizedenergized
offon
Relay
LED
Loop Break = Off
Relay
LED
Loop Break = On
Set
Reset
Signal Loss or Loop Break Relay Operation
The following graph shows the loop break relay operation for a high alarm relay.
When the meter detects a break in the 4-20 mA loop, the relay will go to one of the following selected
actions:
1. Turn On (Go to alarm condition)
2. Turn Off (Go to non-alarm condition)
3. Ignore (Processed as a low signal condition)
Time Delay Operation
The following graphs show the operation of the time delay function.
When the signal crosses the set point, the On time delay timer starts and the relay trips when the time
delay has elapsed. If the signal drops below the set point (high alarm) before the time delay has elapsed,
the On time delay timer resets and the relay does not change state. The same principle applies to the Off
time delay.
Note: If “Automatic or Manual (A-mAn)” resetmode is selected, the LED follows the reset point and not
the relay state when the relay is acknowledged.
30
Din Mounted Digital Display Instruction Manual
Alarm #
HI or LO
Alarm
Set
Point
Reset
Point
Power-Up
Reading
Relay &
LED
1
HI
1000
500
499
Off 2 LO
700
900
499
On
3
LO
250
400
499
Off
4
HI
450
200
499
On
Fail-Safe
Selection
Non-Alarm State
Alarm State
Power Failure
NO
NC
NO
NC
Off
Open
Closed
Closed
Open
Relays go to
non-alarm state
On
Closed
Open
Open
Closed
Relays go to
alarm state
LED
Status
LED
Status
1
Alarm 1
5 Alarm 5
2
Alarm 2
6 Alarm 6
3
Alarm 3
7 Alarm 7
4
Alarm 4
8 Alarm 8
Relay Operation Details
Overview
The relay capabilities of the meter expand its usefulness beyond simple indication to provide users with
alarm and control functions. These capabilities include front panel alarm status LEDs as well as either 2
or 4 optional internal relays and/or 4 external relays expansion module. Typical applications include high
or low temperature, level, pressure or flow alarms, control applications such as simple on/off pump
control, and pump alternation control for up to 8 pumps. There are four basic ways the relays can be
used:
1. High or Low Alarms with Latching or Non-Latching Relays
2. Simple On/Off Control with 100% Adjustable Deadband
3. Sampling (Based on Time)
4. Pump Alternation Control for up to 8 Pumps
Relays Auto Initialization
When power is applied to the
meter, the front panel LEDs and
alarm relays will reflect the state
of the input to the meter. The
following table indicates how the
alarm LEDs and relays will react
on power-up based on the set
and reset points:
Fail-Safe Operation
The following table indicates
how the relays behave based
on the fail-safe selection for
each relay:
Note: NO = Normally Open,
NC = Normally Closed.
This refers to the
condition of the relay
contacts when the power to the meter is off.
Front Panel LEDs
The LEDs on the front panel provide status indication for the
following:
The meter is supplied with four alarm points that include front
panel LEDs to indicate alarm conditions. This standard feature
is particularly useful for alarm applications that require visualonly indication. The LEDs are controlled by the set and reset
points programmed by the user. When the display reaches a set point for a high or low alarm, the
corresponding alarm LED will turn on. When the display returns to the reset point the LED will go off. The
front panel LEDs respond differently for latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition and always on during alarm
condition, regardless of the state of the relay (e.g. Relay acknowledged after alarm condition).
For latching relays, the alarm LEDs reflect the status of the relays, regardless of the alarm condition. The
following tables illustrate how the alarm LEDs function in relation to the relays and the acknowledge
button (Default: F3 key assigned to ACK).
31
Din Mounted Digital Display Instruction Manual
Warning!
In latching relay mode, latched relays will
reset (unlatch) when power is cycled.
Relay terminology for following tables
Terminology
Relay Condition
On
Alarm (Tripped)
Off
Normal (Reset)
Ack
Acknowledged
Automatic reset only
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack (No effect)
On
On
Normal
Off
Off
Automatic + manual reset at any time
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Normal
Off
Off
Next Alarm
On
On
Ack
On
Off
Normal
Off
Off
Manual reset any time
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack
Off
Off
Manual reset only after alarm
condition has cleared
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack (No effect)
On
On
Normal
On
On
Ack
Off
Off
Latching and Non-Latching Relay Operation
The relays can be set up for latching (manual reset) or
non-latching (automatic reset) operation.
The On and Off terminology does not refer to the status of
the relay’s coil, which depends on the fail-safe mode
selected.
Non-Latching Relay (Auto)
In this application, the meter is set up for automatic reset
(non-latching relay). Acknowledging the alarm while it is still
present has no effect on either the LED or the relay. When
the alarm finally goes away the relay automatically resets
and the LED also goes off.
Non-Latching Relay (A-man)
In this application, the meter is set up for automatic and
manual reset at any time (non-latching relay). The LED and
the relay automatically reset when the meter returns to the
normal condition.
The next time an alarm occurs, the operator acknowledges
the alarm manually while the alarm condition still exists.
This causes the relay to reset, but the LED stays on until
the meter returns to the normal condition.
Latching Relay (LatcH)
In this application, the meter is set up for manual reset at any
time. Acknowledging the alarm even if the alarm condition is
still present resets the relay and turns off the LED.
Latching Relay (Lt-Clr)
In this application, the meter is set up for manual reset only
after the signal passes the reset point (alarm condition has
cleared). Acknowledging the alarm while it is still present has
no effect on either the LED or the relay. When the alarm is
acknowledged after it returns to the normal state, the LED
and the relay go off. Notice that the LED remains on, even
after the meter returns to the normal condition. This is
because, for latching relays, the alarm LED reflects the
status of the relay, regardless of the alarm condition.
32
Din Mounted Digital Display Instruction Manual
Set and Reset Point Programming
Relay
Set Point
Reset Point
Function
1
30.000
10.000
Controls pump #1
2
35.000
5.000
Controls pump #2
3
4.000
9.000
Controls low alarm
4
40.000
29.000
Controls high alarm
+5I1I2I3 I4O1 O2 O3 O4G
DO 1-4
GND
ACK
PDA1044 Digital I/O Module
12345678910
DI 1-4
Acknowledging Relays
There are two ways to acknowledge relays programmed for manual reset:
1. Via the programmable front panel function keys F1-F3 (Default:
F3 assigned to ACK).
2. Remotely via a normally open pushbutton wired across one of the digital inputs and the +5 V
terminals on the digital I/O modules, or using the F4 digital input, which is triggered with a contact
closure to COM, or with an active low signal (see page 14).
When the ACK button or the assigned digital input is closed, all relays programmed for manual reset are
acknowledged.
Figure 20. Acknowledge Relays w/Function Key or Digital Input
Pump Alternation Control Applications (Altern)
For pump control applications where two or more similar pumps are used to control the level of a tank or a
well, it is desirable to have all the pumps operate alternately. This prevents excessive wear and
overheating of one pump over the lack of use of the other pumps.
Up to 8 relays can be set up to alternate every time an on/off pump cycle is completed. The set points
and reset points can be programmed, so that the first pump on is the first pump off.
Application #1: Pump Alternation Using Relays 1 & 2
1. Relays 1 and 2 are set up for pump alternation.
2. Relays 3 and 4 are set up for low and high alarm indication.
Pump Alternation Operation
1. Pump #1 turns on when level reaches 30.000, when level drops below 10.000, pump #1 turns off.
2. The next time level reaches 30.000, pump #2 turns on, when level drops below 10.000, pump #2
turns off.
3. If the level doesn’t reach 35.000, pump #1 and pump #2 will be operating alternately.
4. If pump #1 cannot keep the level below 35.000, pump #2 will turn on at 35.000, then as the level
drops to10.000, pump #1 turns off, pump #2 is still running and shuts off below 5.000.
5. Notice that with the set and reset points of pump #2 outside the range of pump #1, the first pump on
is the first pump to go off. This is true for up to 8 alternating pumps, if setup accordingly.
6. Relay #3 will go into alarm if the level drops below 4.000 and relay #4 will go into alarm if the level
exceeds 40.000.
7. Adding the 4 external relays, expansion module allows using the 4 SPDT internal relays for pump
alternation and the 4 SPST external relays for high, high-high, low, and low-low alarm indication.
33
Din Mounted Digital Display Instruction Manual
Set and Reset Point Programming
Relay
Set Point
Reset Point
Function
1
495
750
Controls low alarm
2
7500
6900
Controls high alarm
3
7000
900
Controls backup pump
4
6000
1000
Controls main pump
Application #2: Pump Alternation Using Relays 3 & 4
1. Relays 1 and 2 are set up for low and high alarm indication.
2. Relays 3 and 4 are set up for pump alternation.
The following graphics provide a visual representation of a typical pump alternation application with high
and low alarm monitoring:
1. Relay #4 turns the main pump on at 6000
gallons and turns it off at 1000 gallons.
2. With the Pump Alternation feature
activated, the next time the level reaches
6000 gallons, relay #3 transfers and starts
the backup pump.
3. If the backup pump is not able to keep up,
and the level reaches 7000 gallons, relay
#4 transfers and starts the main pump as
well.
4. Relay #2 trips the High Level Alarm at
7500 gallons and resets at 6900 gallons.
5. Relay #1 trips the Low Level Alarm at 495
gallons and resets at 750 gallons.
34
Din Mounted Digital Display Instruction Manual
For instructions on how to program
numeric values see Setting Numeric
Values, page 19.
12345
6
+5
I1
I2
I3
I4
O1
7
8
O2
O3
9
10
O4
G
DI 1-4
DO 1-4
5 VDC
GND
SW2
SW1
Setting Up the Interlock Relay (Force On) Feature
Relays 1-4 can be set up as interlock relays. To set up the relays for the interlock feature:
1. Access the Setup – Relay – Action menu and set the action to off.
2. In the Advanced features – User menu program any of the digital inputs to Force On any of the
internal relays (1-4).
3. Connect a switch or dry contact between the +5V terminal and the corresponding digital input (dI-1 to
dI-4) terminal.
Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front panel LEDs are off) when SW1 & SW2 switches
(above) are closed. If the contacts to these digital inputs are opened, the corresponding front panel LEDs
flash indicating this condition. The processes being controlled by the interlock relay will stop, and will restart only after the interlock relay is re-activated by the digital inputs (switches).
Note: If multiple digital inputs are assigned to the same relay, then the corresponding logic is (AND) –
i.e. both switches must be closed to trip the relay.
Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal for any display range selected.
No equipment is needed to scale the analog output; simply program the display values to the
corresponding mA output signal.
The Analog Output menu is used to program the 4-20 mA output based on display values.
35
Din Mounted Digital Display Instruction Manual
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
Reset Menu (reset)
The Reset menu is used to reset the maximum or minimum reading (peak or valley) reached by the
process; both may be reset at the same time by selecting “reset high & low” (rst HL). The tare value
used to zero the display may be reset by selecting “reset tare” (rst tr).
Control Menu (Contrl)
The Control menu is used to control the 4-20 mA analog output and the relays manually, ignoring the
input. Each relay and analog output can be programmed independently for manual control. Selecting
automatic control sets all relays and analog output for automatic operation.
Setting Up the Password (pass)
The Password menu is used for programming three levels of security to prevent unauthorized changes to
the programmed parameter settings.
Protecting or Locking the Meter
Enter the Password menu and program a six-digit password.
For instructions on how to program numeric values see Setting Numeric Values, page 19.
36
Din Mounted Digital Display Instruction Manual
Did you forget the password?
The password may be disabled by entering a master
password once. If you are authorized to make changes,
enter the master password 508655 to unlock the meter.
Making Changes to a Password Protected Meter
If the meter is password protected, the meter will display the message Locd (Locked) when the Menu
button is pressed. Press the Enter button while the message is being displayed and enter the correct
password to gain access to the menu. After exiting the programming mode, the meter returns to its
password protected condition.
Disabling Password Protection
To disable the password protection, access the Password menu and enter the correct password twice, as
shown below. The meter is now unprotected until a new password is entered.
If the correct six-digit password is entered, the meter displays the message unLoc (unlocked) and the
protection is disabled until a new password is programmed.
If the password entered is incorrect, the meter displays the message Locd (Locked) for about two
seconds, and then it returns to Run Mode. To try again, press Enter while the Locked message is
displayed.
37
Din Mounted Digital Display Instruction Manual
Display
Parameter
Action/Setting
filtEr
Filter
Set noise filter value
bypASs
Bypass
Set filter bypass value
Round
Round
Set the rounding value for
display variables
seriAl
Serial
Set serial communication
parameters
SlaveId
Slave ID
Set slave ID or meter
address
baud
Baud rate
Select baud rate
Tr dLY
Transmit delay
Set transmit delay for serial
communication
Parity
Parity
Select parity
Even, Odd, or None with 1
or 2 stop bits
t-byt
Time byte
Set byte-to-byte timeout
SelEct
Select
Enter the Select menu
(function, cutoff, out)
Functn
Signal input
conditioning
Select linear, square root,
programmable exponent,
or round horizontal tank
function
Linear
Linear
Set meter for linear
function and select number
of linearization points
Pv 1
PV1
Select PV1 number of
linearization points
Pv 2
PV2
Select PV2 number of
linearization points
No PtS
Number of
points
Set PV1 for 2 to 32-point
linearization
Set PV2 for 2 to 8-point
linearization
Square
Square root
Set meter for square root
extraction
Display
Parameter
Action/Setting
Prog E
Programmable
exponent
Set meter for
programmable exponent
and enter exponent value
rht
Round
horizontal tank
Set meter for round
horizontal tank volume
calculation
Inch
Dimension
Calculate volume in
gallons
cnm
Dimension
Calculate volume in liters
dianmr
Diameter
Enter the tank’s diameter
in inches
Length
Length
Enter the tank’s length in
inches
CutofF
Cutoff
Set low-flow cutoff
AoutPr
Analog output
programming
Program analog output
parameters
Source
Source
Select source for the 4-20
mA output
O-rang
Overrange
Program mA output for
display overrange
u-rang
Underrange
Program mA output for
display underrange
break
Break
Set input break condition
operation
nmAx
Maximum
Program maximum mA
output allowed
nmin
Minimum
Program minimum mA
output allowed
Calib
Calibrate
Calibrate 4-20 mA output
(internal reference source
used for scaling the output)
4 nmA
4 mA output
Enter mA output value
read by milliamp meter
with at least 0.001 mA
resolution
Advanced Features Menu
To simplify the setup process, functions not needed for most applications are located in the Advanced
Features menu.
Press and hold the Menu button for three seconds to access the advanced features of the meter.
Advanced Features Menu & Display Messages
The following table shows the functions and messages of the Advanced Features menu in the order they appear in
the menu.
38
Din Mounted Digital Display Instruction Manual
Display
Parameter
Action/Setting
20 nmA
20 mA output
Enter mA output value
read by milliamp meter
with at least 0.001 mA
resolution
user
User I/O
Assign function keys and
digital I/O
F1
F1 function key
Assign F1 function key
F2
F2 function key
Assign F2 function key
F3
F3 function key
Assign F3 function key
F4
F4 function
Assign F4 function (digital
input)
dI I
Digital input 1
Assign digital input 1 – 8, if
expansion modules are
connected
dO 1
Digital output 1
Assign digital output 1 – 8,
if expansion modules are
connected
ICal
Internal source
calibration
Enter internal source
calibration (used for
scaling the meter without a
signal source)
Display
Parameter
Action/Setting
C CAL
Current
calibration
Calibrate 4-20 mA current
input (internal reference
source used for scaling the
input)
C lo
Current low
Calibrate low current input
(e.g. 4 mA)
C Hi
Current high
Calibrate high current input
(e.g. 20 mA)
v CAL
Voltage
calibration
Calibrate voltage input
v Lo
Voltage low
Calibrate low voltage input
(e.g. 0 V)
v Hi
Voltage high
Calibrate high voltage input
(e.g. 10 V)
Diag
Diagnostics
Display parameter settings
LED t
LED test
Test all LEDs
Info
Information
Display software and S/N
information
Erase
Erase
Erase MeterView Pro
software stored in meter’s
memory
Rounding
Selection
Actual
Value
Display
Value
Actual
Value
Display
Value
1
12.022
12.022
12.023
12.023
5
12.022
12.020
12.023
12.025
10
12.024
12.020
12.025
12.030
Noise Filter (filter)
The noise filter is available for unusually noisy signals that cause an unstable process variable display.
The noise filter averages the input signal over a certain period. The filter level determines the length of
time over which the signal is averaged. The filter level can be set between 2 and 199. The higher the filter
level, the longer the averaging time and so the longer it takes the display to settle to its final value. Setting
the filter level to zero disables the filter function.
Noise Filter Bypass (bypass)
The noise filter bypass changes the behavior of the meter so that small variations in the signal are filtered
out but large abrupt changes in the input signal are displayed immediately. The bypass value determines
the minimum amount of signal change to be displayed immediately. All signal changes smaller than the
bypass value are filtered or averaged by the meter. The noise filter bypass may be set between 0.1 and
99.9% of full scale.
Rounding Feature (round)
The rounding feature is used to give the user a steadier display with fluctuating signals. Rounding is used
in addition to the filter function.
Rounding causes the display to round to the nearest value according the rounding selected. See
examples below:
39
Din Mounted Digital Display Instruction Manual
Warning!
Do not connect any equipment other than Automation Products Group’s
expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise
damage will occur to the equipment and the meter.
Modbus RTU Serial Communications (serial)
The meter is equipped with serial communications capability as a standard feature using Modbus RTU
Serial Communication Protocol.
The meter may be connected to a PC for initial configuration via the onboard micro USB connection. For
ongoing digital communications with a computer or other data terminal equipment, an RS-232, or RS-485
option is required; see Ordering Information on page 5 for details.
Note: More detailed instructions are provided with each optional serial communications adapter.
Note: Refer to the Modbus Register Tables located at www.apgsensors.com for details.
When using more than one meter in a multi-drop mode, each meter must be provided with its own unique
address. The meter address (Slave ID) may be programmed between 1 and 247. The transmit delay may
be set between 0 and 199 ms. The parity can be set to even, odd, or none with 1 or 2 stop bits.
Select Menu (SElect)
The Select menu is used to select the signal input conditioner applied
to the input (linear, square root, programmable exponent, or round horizontal tank), low-flow cutoff, and analog output
programming. The multi-point linearization is part of the linear function selection.
40
Din Mounted Digital Display Instruction Manual
rht
rhtrht
Signal Input Conditioning (Functn)
The Function menu is used to select the signal input conditioner applied to the input: linear, square root,
programmable exponent, or round horizontal tank volume calculation. The multi-point linearization is part
of the linear function selection.
Meters are set up at the factory for linear function with 2-point linearization. The linear function provides a
display that is linear with respect to the input signal.
Square Root Linearization (Square)
The square root function can be used to linearize the signal from a differential pressure transmitter and
display flow rate in engineering units.
Programmable Exponent Linearization (Prog E)
The programmable exponent can be used to linearize the signal from level transmitters in open-channel
flow applications using weirs and flumes.
Multi-Point Linearization (Linear)
Meters are set up at the factory for linear function with 2-point linearization. Up to 32 linearization points
can be selected for PV1 under the linear function. The multi-point linearization can be used to linearize
the display for non-linear signals such as those from level transmitters used to measure volume in oddshaped tanks or to convert level to flow using weirs and flumes with complex exponent.
If the dual-scale level feature has been selected, the menus for PV1 & PV2 are enabled. PV2 can be
programmed with up to 8 linearization points.
Round Horizontal Tank Linearization (rHt)
This function automatically calculates the volume in a round horizontal tank with flat ends.
Set the display for the desired decimal point and engineering units before entering the round horizontal
tank function. Select units, inches or cm for the tank dimensions. Enter the diameter and the length in
inches and the results are calculated automatically in US gallons.
The meter can be scaled to display the volume in any engineering unit.
Note: After Scale is displayed continue pressing the Enter button until the meter completes the scaling of
the input and display values.
41
Din Mounted Digital Display Instruction Manual
*If installed
Changing the Volume from Gallons to Liters
In the above graphic, entering the 48" for the diameter and 120" for the length of the round horizontal
tank, the meter automatically calculates that the volume of the tank is 940.02 gallons.
1. Convert gallons to liters
1 US gallon = 3.7854 L
940.02 gal = 3558.4 L
2. Go to the Setup menu and change the decimal point to 1 decimal.
3. Go to the Program – Scale menu and press Enter until dis 2 is shown on the main display.
4. Press Enter and change the display 2 value to 3558.4.
5. The meter is now displaying the volume in liters.
Note: The display can be scaled to display the volume in any engineering units.
Low-Flow Cutoff (CutofF)
The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady output from a
differential pressure transmitter, at low flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will display zero below the cutoff
value. Programming the cutoff value to zero disables the cutoff feature.
Analog Output Programming (AoutPr)
The Analog Output Programming menu is used to program the behavior of the 4-20 mA output. The
following parameters and functions are programmed in this menu:
1. Source: Source for generating the 4-20 mA output (e.g. PV)
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to scale the 4-20 mA output
Analog Output Source
The source for generating the 4-20 mA
output may be assigned to the process
variable, maximum or minimum value
reached by the process, one of the set
points, or the Modbus PV input.
Analog Output Calibration
To perform the analog output calibration, it is recommended to use a milliamp meter with a resolution of
at least 0.1 µA to measure the output current. The values saved internally during this procedure are used
for scaling the 4-20 mA output in the Setup menu.
Programmable Function Keys User Menu (user)
The User menu allows the user to assign the front panel function keys F1, F2, and F3, the digital input F4
(a digital input located on the signal input connector), and up to eight additional digital inputs to access
most of the menus or to activate certain functions immediately (e.g. reset max & min, hold relay states,
etc.). This allows the meter to be greatly customized for use in specialized applications.
Up to eight digital outputs can be assigned to a number of actions and functions executed by the meter
(i.e. alarms, relay acknowledgement, reset max, min, or max & min, tare, and reset tare). The digital
outputs can be used to trigger external alarms or lights to indicate these specific events.
42
Din Mounted Digital Display Instruction Manual
Display
Description
Rst Hi
Reset the stored maximum display
value
Rst Lo
Reset the stored minimum display
value
Rst HL
Reset the stored maximum &
minimum display values
tare
Capture tare and zero the display
Rst tr
Reset captured tare and resume
normal operation
relay
Directly access the relay menu
Set 1*
Directly access the set point menu
for relay 1 (*through 8)
Rly d
Disable all relays until a button
assigned to enable relays (Rly E)
is pressed
Rly E
Enable all relays to function as they
have been programmed
O Hold
Hold current relay states and
analog output as they are until a
button assigned to enable relays
(Rly E) is pressed
d Hold
Hold the current display value, relay
states, and analog output
momentarily while the function key
or digital input is active. The
process value will continue to be
calculated in the background.
Ln1 Hi
Display maximum display value on
line 1
Ln1 Lo
Display minimum display value on
line 1
Display
Description
Ln1 HL
Display maximum & minimum
display values on line 1
Ln2 Hi
Display maximum display value on
line 2
Ln2 Lo
Display minimum display value on
line 2
Ln2 HL
Display maximum & minimum
display values on line 2
F On 1*
Force relay 1 (*through 4) into the
on state. This function is used in
conjunction with a digital input
expansion module to achieve
interlock functionality. See page 35
for details about interlock relays.
Contrl
Directly access the control menu
disabl
Disable the selected function key or
digital I/O
AcH
Acknowledge all active relays that
are in a manual operation mode
such as auto-manual or latching
Reset
Directly access the reset menu
nmenu
Mimic the menu button functionality
(digital inputs only)
rigHt
Mimic the right arrow/F1 button
functionality (digital inputs only)
up
Mimic the up arrow/F2 button
functionality (digital inputs only)
Enter
Mimic the enter/F3 button
functionality (digital inputs only)
Alnm 1*
Provide indication when alarm 1
(*through 8) has been triggered
(digital outputs only)
0.0
lbs
0.2
lbs
0.2
lbs
Before tare
After capture tare
After reset tare
Function Keys & Digital I/O Available Settings
Refer to the following table for descriptions of each available function key or digital I/O setting.
Tare (tare)
The tare function zero’s out the display. In the case of scale weight, tare is used to eliminate container
weight and provide net weight readings. There are two tare functions; Capture Tare and Reset Tare.
When the capture tare function is used, the display reading is offset by the displayed amount to make the
displayed value zero. This modified display value is the net value. The originally displayed value without
the tare offset is the gross value. Both may be chosen as a display option.
Reset tare removes the display offset of the net value, and the gross and net values become the same
until a new capture tare is entered.
43
Din Mounted Digital Display Instruction Manual
The meter is factory calibrated prior to shipment to read in
milliamps and volts depending on the input selection. The
calibration equipment is certified to NIST standards.
Notes:
1. If meter is in operation and it is intended to accept only one input type
(e.g. 4-20 mA), recalibration of other input is not necessary.
2. Allow the meter to warm up for at least 15 minutes before performing
the internal source calibration procedure.
Input Range
Input 1 & Input 2 Span
4-20 mA
0.15 mA
10 VDC
0.01 VDC
Internal Source Calibration (ICAL)
The use of calibrated signal sources is necessary to calibrate the internal source of the meter. The
meter’s internal source is what allows the user to scale the meter without applying a signal.
Check calibration of the meter at least every 12 months. Each input must be recalibrated separately.
The Internalcalibration menu is part of the AdvancedFeatures menu.
1. Press and hold the Menu button for three seconds to access the advanced features of the meter.
2. Press the Up arrow button to scroll to the Internal calibration menu (ICAL) and press Enter.
3. The meter displays either current calibration (C CAL) or voltage calibration (v CAL), according to the
input setup. Press Enter to start the calibration process.
Example of Internal Calibration for current input:
4. The meter displays low input current message (C lo). Apply the low input signal and press Enter. The
display flashes for a moment while the meter is accepting the low input signal.
5. After the display stops flashing, a number is displayed with the leftmost digit brighter than the rest.
The bright digit is the active digit that can be changed by pressing the Up arrow button. Press the
Right arrow button to move to the
next digit.
6. Set the display value to correspond
to the input signal being calibrated,
typically 4.000 mA.
7. The display moves to the high input
calibration (C Hi). Apply the high
input signal and press Enter.
8. Set the display for the high input
calibration, in the same way as it
was set for the low input calibration,
typically 20.000 mA.
The graphic above shows the calibration of the current input. The voltage input is calibrated in a similar way.
Tips:
• Low and high input signals can be any valid values within the range of the meter.
• Observe minimum input span requirements between input 1 and input 2.
• Low input should be less than high input signal.
Error Message (Error)
An error message indicates that the calibration or scaling process was not successful.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals, or it is connected backwards.
2. Wrong signal selection in Setup menu.
3. Minimum input span requirements not maintained.
Minimum Input Span
The minimum input span is the minimum difference between
input 1 and input 2 signals required to complete the calibration
or scaling of the meter.
44
Din Mounted Digital Display Instruction Manual
Button Symbol
Description
Press to enter or exit Programming Mode, view
settings, or exit max/min readings
Press to reset max/min readings or other
parameter/function assigned through the User menu
Press to display max/min readings or other
parameter/function assigned through the User menu
Press to acknowledge relays or other
parameters/function assigned through the User menu
Meter Operation
The meter is capable of accepting current (0-20 mA, 4-20 mA) and voltage signals (0-5 V, 1-5 V, 0-10 V,
10 V) and displaying these signals in engineering units from -99999 to 999999 (e.g. a 4-20 mA signal could
be displayed as -50.000 to 50.000).
The dual-line display can be customized by the user to operate in such a way as to satisfy a specific
application. Typically, the main display is used for the process variable; while the second display is used
for engineering units, custom legend, or set point indication.
The analog input can be scaled to display the process in two different scales; for example: with d-SCAL
enabled, the main display could indicate level in feet and the second display could indicate the volume in
gallons.
Additionally, the meter can be set up to display the analog input on the main display and the Modbus input
on the second display. The relays and analog output can be programmed to operate from the Modbus PV
input.
Front Panel Buttons Operation
Function Keys Operation
During operation, the programmable function keys operate according to the way they have been
programmed in the Advanced Features – User menu.
The table above shows the factory default settings for F1, F2, and F3.
F4 Operation
A digital input, F4, is standard on the meter. This digital input is programmed identically to function keys
F1, F2, and F3. The input is triggered with a contact closure to COM, or with an active low signal. During
operation, F4 operates according to the way it has been programmed in the Advanced Features – User
menu.
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by the process can be displayed either continuously or
momentary:
1. Display briefly by assigning to the F1-F3 function keys or to the digital inputs in the User menu.
2. Display continuously by assigning either display to max/min through the Display menu.
Any of the F1-F3 function keys (buttons) and the digital inputs can be programmed to reset the max & min
readings. The meters are set at the factory to display the max reading by pressing the Up arrow/F2 button
and to use the Right arrow/F1 button to access the Reset menu.
To display max reading using function key with factory defaults:
1. Press Up arrow/F2 button to display maximum reading since the last reset/power-up.
2. To reset max/min press Right arrow/F1
button to access the Reset menu. The
max & min displays are reset to actual
values.
3. Press Menu to exit max/min display reading.
To display max/min readings continuously:
Assign either display to Max (d Hi), Min (d Lo), or toggle
between Max and Min (d HL) every 10 seconds.
45
Din Mounted Digital Display Instruction Manual
Troubleshooting
The rugged design and the user-friendly interface of the meter should make it unusual for the installer or
operator to refer to this section of the manual. However, due to the many features and functions of the
meter, it’s possible that the setup of the meter does not agree with what an operator expects to see.
If the meter is not working as expected, refer to the Diagnostics menu and recommendations below.
Diagnostics Menu (diag)
The Diagnostics menu is located in the Advanced Features menu, to access Diagnostics menu see
Advanced Features Menu, page 38.
This menu allows the user to test the functionality of all the meter LEDs, check the meter’s software and
version information, and erase the MeterView Pro software installation files from the meter. Press the
Enter button to view the settings and the Menu button to exit at any time.
For a description of the diagnostic messages, see Advanced Features Menu & Display Messages, page
38.
Determining Software Version
To determine the software version of a meter:
1. Go to the Diagnostics menu (diAG) and press Enter button.
2. Press Up arrow button and scroll to Information menu (Info).
3. Press Enter to access the software number (SFT) and version (UER) information. Write down the
information as it is displayed. Continue pressing Enter until all the information is displayed.
4. The meter returns to Run Mode after displaying all the settings.
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to determine what’s happening, it might
be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the AdvancedFeatures menu. See Advanced Features Menu, page 38.
2. Press Up arrow to go to Diagnostics menu
3. Press and hold Right arrow for three seconds, press
Enter when display flashes reset.
Note: If Enter is not pressed within three seconds, the display returns to the Diagnostics menu.
4. The meter goes through an initialization sequence (similar as on power-up), and loads the factory
default settings.
Note: The dual-scale selection for some level applications (d-SCAL) is not reset to the single scale factory
default. This can be changed using the Setup – Input menu.
46
Din Mounted Digital Display Instruction Manual
Parameter
Display
Default Setting
Input type
Input
4-20 mA
Dual-scale feature
d-SCAL
No (Single scale)
Filter
filter
70
Bypass
bypass
0.2
Function
Functn
Linear
Number of points
No Pts
2
Programming
prog
Scale
Input 1
InP 1
4.000 mA
Display 1
Dis 1
4.000
Input 2
InP 2
20.000 mA
Display 2
Dis 2
20.000
Decimal point
dd.ddd
3 places
Cutoff value
CutofF
0.000 (disabled)
Display assignment
Dsplay
Display Line 1
Line 1
PV: Process variable
Display Line 2
Line 2
Eng unit default= mA
Display intensity
d-Inty
8
Relay 1 action
Act 1
Automatic
Relay 1 set point
Set 1
1.000
Relay 1 reset point
RSt 1
0.500
Relay 2 action
Act 2
Automatic
Relay 2 set point
Set 2
2.000
Relay 2 reset point
RSt 2
1.500
Relay 3 action
Act 3
Automatic
Relay 3 set point
Set 3
3.000
Relay 3 reset point
RSt 3
2.500
Relay 4 action
Act 4
Automatic
Relay 4 set point
Set 4
4.000
Relay 4 reset point
RSt 4
3.500
Fail-safe relay 1
Fls 1
Off
Fail-safe relay 2
Fls 2
Off
Fail-safe relay 3
Fls 3
Off
Fail-safe relay 4
Fls 4
Off
On delay relay 1
On 1
0.0 sec
Off delay relay 1
Off 1
0.0 sec
On delay relay 2
On 2
0.0 sec
Off delay relay 2
Off 2
0.0 sec
On delay relay 3
On 3
0.0 sec
Parameter
Display
Default Setting
Off delay relay 3
Off 3
0.0 sec
On delay relay 4
On 4
0.0 sec
Off delay relay 4
Off 4
0.0 sec
Loop break relay 1
ignore
Ignore
Loop break relay 2
ignore
Ignore
Loop break relay 3
ignore
Ignore
Loop break relay 4
ignore
Ignore
Display 1 analog out
Dis 1
4.000
Output 1 value
Out 1
4.000 mA
Display 2 analog out
Dis 2
20.000
Output 2 value
Out 2
20.000 mA
Source analog output
Source
Process Variable
Overrange output
O-rang
21.000 mA
Underrange output
u-rang
3.000 mA
Loop break output
break
1.000 mA
Maximum output
mAx
23.000 mA
Minimum output
min
1.000 mA
Slave ID (Address)
SlavId
247
Baud rate
baud
9600
Transmit delay
Tr dly
50 ms
Parity
Parity
Even
Byte-to-byte timeout
t-byt
010 (0.1 sec)
F1 function key
F1
Reset max & min
F2 function key
F2
Line 1: Max (Hi)
F3 function key
F3
Acknowledge relays
F4 function
F4
Acknowledge relays
Digital input 1
dI 1
Menu
Digital input 2
dI 2
Right arrow
Digital input 3
dI 3
Up arrow
Digital input 4
dI 4
Enter
Digital output 1
dO 1
Alarm 1
Digital output 2
dO 2
Alarm 2
Digital output 3
dO 3
Alarm 3
Digital output 4
dO 4
Alarm 4
Password 1
Pass 1
000000 (unlocked)
Password 2
Pass 2
000000 (unlocked)
Password 3
Pass 3
000000 (unlocked)
Factory Defaults & User Settings
The following table shows the factory setting for most of the programmable parameters on the meter.
47
Din Mounted Digital Display Instruction Manual
Symptom
Check/Action
No display at all
Check power at power connector
Not able to change setup or
programming, Locd is displayed
Meter is password-protected, enter correct six-digit
password to unlock
Meter displays error message during
calibration (Error)
Check:
1. Signal connections
2. Input selected in Setup menu
3. Minimum input span requirements
Meter displays
1. 999999
2. -99999
Check:
1. Input selected in Setup menu
2. Corresponding signal at Signal connector
Display is unstable
Check:
1. Input signal stability and value
2. Display scaling vs. input signal
3. Filter and bypass values (increase)
Display response is too slow
Check filter and bypass values
Display reading is not accurate
Check:
1. Signal input conditioner selected: Linear, square
root, etc.
2. Scaling or calibration
Display does not respond to input
changes, reading a fixed number
Check:
1. Display assignment, it might be displaying max,
min, or set point.
Display alternates between
1. Hi and a number
2. Lo and a number
Press Menu to exit max/min display readings.
Relay operation is reversed
Check:
1. Fail-safe in Setup menu
2. Wiring of relay contacts
Relay and status LED do not
respond to signal
Check:
1. Relay action in Setup menu
2. Set and reset points
Flashing relay status LEDs
Relays in manual control mode or relay interlock
switches opened.
Meter not communicating with application
programs
Check:
1. Serial adapter and cable
2. Serial settings
3. Meter address and baud rate
If the display locks up or the meter does
not respond at all
Cycle the power to reboot the microprocessor.
Other symptoms not described above
Call Technical Support for assistance.
Troubleshooting Tips
Note: Certain sequences of events can cause unexpected results. To solve these issues, it is best to start
fresh from factory defaults and map changes ahead of time, rather than at random.
48
EU Declaration of Conformity
Issued in accordance with ISO/IEC 17050-1:2004.
We,
Precision Digital Corporation
233 South Street
Hopkinton, MA 01748 USA
as the manufacturer, declare under our sole responsibility that the product(s),
APG Model DDD & DBD Series Digital Process Meters
to which this declaration relates, is in conformity with the European Union Directives
shown below:
2014/35/EU Low Voltage Directive
2014/30/EU EMC Directive
2011/65/EU RoHS Directive
This conformity is based on compliance with the application of harmonized or applicable
technical standards and, when applicable or required, a European Union notified body
certification.
Standards:
EN 55022:2003
EN 61000-6-2:2001
EN 61010-1:2001
EN 61326:2006
The standards EN 55022:2003, EN 61000-6-2:2001, EN 61010-1:2001, and EN
61326:2006 are no longer harmonized. The requirements of these standards have
been checked against the harmonized standards EN 55022:2010, EN 61000-62:2005, EN 61010-1:2010, and EN 61326:2013 and there were no major technical
changes affecting the latest technical knowledge for the products listed above.
Product Markings:
Signed for and on behalf of Precision Digital Corporation:
Name: Jeffrey Peters
Company: Precision Digital Corporation
Title: President
Date: 04/20/2016
Document No: DoC PD6000AP {042016}
Din Mounted Digital Display Instruction Manual
®
Automation Products Group
1025 W 1700 N • Logan UT 84321 USA
Tel (435) 753-7300 • Fax (435) 753-7490
www. apgsensors.com
Doc #9005525
Part #200223
Rev A., 01/19
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.