Din Mounted Digital Display
Panel Meter
Series: DDD
®
The Series DDD Din Mounted Digital Display is a two-line, analog-input panel meter with multiple output and display
options. With two congurable, six-character lines and eight LED alarm indicators, the DDD ts a lot of information
in a compact area. The DDD is easily programmed with the four buttons on the face or through a USB connection to
a PC. Add an optional bright, sunlight-readable display, and the DDD has the versatility and functionality you need in
a panel meter.
Features
• 2-line, 6-character display
• Environmentally sealed face; NEMA 4X / IP65
• Easy 4-button programming
• Current Inputs: 4-20 or 0-20 mA
• Voltage Inputs: 0-5, 1-5, 0-10 VDC
• 1 Digital Input / Input Contact
• Current Output: Isolated 4-20 mA
Automation Products Group, Inc. | 888.525.7300 | sales@apgsensors.com | www.apgsensors.com
• Relay Outputs: 2 or 4 SPDT Relays
• Up to 200 mA for powering sensor
• Congurable High/Low alarms
• Alternating Pump Control (with output relays)
• Optional bright display (DBD model)
Rev. A, 01/23/2019
DDD Specications
Oponal Removable
Connectors
2.45”
62 mm
0.59”
15 mm
Micro USB
connecon
5.05”
128 mm
Performance
• Display:
2 lines, 6 characters each
Top line: 0.6” (15mm) characters
Bottom line: 0.46” (12mm) characters
• Optional Sunlight Readable Bright Display (model DBD)
• Display Update Speed:
200 ms (5 updates per second)
• Accuracy:
±0.03% of calibrated span
Connectivity
• Input Options:
0-20 mA, 4-20 mA
0-5 VDC, 1-5 VDC, 0-10 VDC, ±10 VDC
• Output Options:
2 or 4 SPDT Relays
Isolated 4-20 mA
• Sensor Power Supply
24/10/5 VDC selectable
200 mA for VAC models
100 mA for VDC models
• Analog Output Power Supply
40 mA @ 24 VDC
Environmental
• Front panel rating: NEMA 4X, IP65
• Storage Temp: -40º - 185ºF (-40º - 85ºC)
• Operating Temp: -40º - 149ºF (-40º - 65ºC)
Certication
• CE
• UL/C-UL Listed
1.76”
44.5 mm
Programming
• Programmable Features:
Min/Max, Tare, Hold
Multi-scale Input Display (e.g. Level & Volume)
Noise Filter
High/Low Alarms
Alternating Pump Control
Time Delay for Output Relays
• Methods:
4 Front-panel Push Buttons
MeterView Pro Software (with PC)
Electrical
• Supply Voltage:
VAC: 85 - 265
VDC: 12 - 24
• Input Impedence:
Voltage Inputs: > 500 kΩ
Current Inputs: 50 - 100 Ω
• SPDT Relays:
3 A @ 30 VDC / 125/250 VAC resistive loads
1/14 HP ( ≈ 50 W) @125/250 VAC inductive loads
• Input Contact/Digital Input
Contact Voltage: 3.3 VDC
Digital Input Logic High: 3 - 5 VDC
Digital Input Logic Low: 0 -1.25 VDC
Default Logic: Normally Open/Low
Physical
• Size:
4.68” x 2.45” x 5.64” (119 mm x 62 mm x 143 mm)
• Weight:
9.5 oz (269 g)
3.61”
91.5 mm
NO
NO
C
C
R
+
NC
-
NC
4.68”
119 mm
NO
NO
C
C
NC
NC
Automation Products Group, Inc. | 888.525.7300 | sales@apgsensors.com | www.apgsensors.com
®
2
Rev. A, 01/23/2019