Automation Products Group, Inc.
®
ACF-10 Acoustical Flow Sensor for Solids
■
Operational Description
e ACF-10 is a self-contained
acoustical sensor that detects the
audible noise made by powders
or grains in a pipe or conveyor. It
may also be used to detect audible
noise on mechanical equipment for
preventive maintenance.
e solid state sensor detects
acoustical vibrations by means
of a sound pickup. If the audible
vibrations exceed a predetermined
limit, a relay output occurs. Because
sound is transmitted very effectively
by a metal or plastic pipe, this is
especially suitable for pneumatic
conveying. A lack of sound indicates
a plugged pipe.
ACF-10
Acoustical Flow Sensor for Solids
■
Acoustic noise sensor for
equipment maintenance
requirements and solid flow
sensing in pipes
■
Works in audible sound
frequencies of 8 to 16 kHz
■
Easy to install: strap or screw to
pipe or bearing
■
Self-contained with 24 to
240 VAC or VDC power and
1 SPST relay output
■
Offset, gain and time delay
adjustments with (4) LED
indicators
■
Applications
e ACF-10 works best in
granular and powdered materials
that are hard. e rattling of
conveyed material on the pipe wall
will convey audible noise through
the pipe wall to the transducer. e
ACF-10 can also be affixed to motor
or machine bearings and can be
adjusted to provide an alarm when
excessive noise from the bearing
occurs. Calibration will require an
audible noise source comparable to a
faulty bearing.
Automation Products Group, Inc.
1025 West 1700 North Tel. 1/888/525-7300
Logan, UT 84321 USA Fax 1/435/753-7490
1
w w w . a p g s e n s o r s . c o m
s a l e s @ a p g s e n s o r s . c o m
Automation Products Group, Inc.
4.21
107
1.97
50
1.65
42
0.02
0.5
3.15
80
1
Supply Voltage: 24-264V AC/DC
Relay Contact Output: 240V 2A AC
(resistive load)
2 3NO4
Line
®
ACF-10 Acoustical Flow Sensor for Solids
■
Specications
Performance
Operation Characteristics
Sensitivity Adjustment: By offset and gain
trim potentiometers
Operation Indication: (4) LEDs (Red detection of noise. Four red - relay will trip)
Alarm Output: Relay contact rating:
240 V 2 A AC; 30 V 2 A DC (resistive)
Electrical
Supply Voltage: 22 VDC to 264 VAC inclusive
(50/60 Hz AC) Withstand Voltage 1500 VAC
for 1 min. (between line and output) Insulation
Resistance 500 VDC, 100 m ohm (between
line and output)
Power Consumption: Approx. 2.5 VA
(at 100 VAC)
Physical
Material: ABS, Polycarbonate PC
Mounting: (2) straps or screws
Wiring: PF1/2 cable gland
Rating: IP54/NEMA 12
Environmental
Operating Temperature Range: 14 to 158°F
(-10 to 70°C)
Operational Humidity: 5 to 85% RH
Shock Resistance: 60 to 2000 Hz, 10 g
Specifications are subject to change without
notice.
■
Dimensions — in./mm
■
Wiring
Calibration
1
NON
DETECT
ZERO RY ON
DETECT
6
OFFON
DELAYDELAYGAINOFFSET
Automation Products Group, Inc.
1025 West 1700 North Tel. 1/888/525-7300
Logan, UT 84321 USA Fax 1/435/753-7490
5432
■
Ordering Information
ACF -
Configuration
10 Flow Sensor, Standard Duty
2
w w w . a p g s e n s o r s . c o m
s a l e s @ a p g s e n s o r s . c o m