APC SRT5KTF Owners Manual

Page 1
Smart-UPS
On-Line Isolation and
Step-Down Transformer SRT5KTF

Safety Messages

Read the instruct ions carefully to become famil iar with the equipment before att empting to install, operate, service or maintain the transformer . The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to informati on that clarifies or simpl ifies a procedure.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safe ty messages that follow this symbol to avoid possible injury or death.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.

Safety Information

• Adhere to all nati onal and local electrical codes.
• All wiring must be performed by a quali fied electrician.
• Changes and modifications to this unit not exp r essly approved by APC could void the warra nty.
• This transformer is intended for indoor use only.
• Do not operate this transformer in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
• Be sure the air vents on the transformer are not blocked. Allow adequate space for proper ventilation.
• For a transformer with a factory installed power cord, conn ect the transformer power cabl e directly to an output receptacle of th e UPS. Do not us e surge protectors or extension cords.
• The equipment is heavy. Always practic e s afe lifting techniques adequa te for the weight of the equipment.
• For rack mount transform ers, al ways i nstall t he tra nsform er dire ctly a bove the UPS in r ack-mount c onfi gurati ons. The UPS mu s t be in s t al l e d be lo w th e tr a nsformer.
• Always install peripheral equipment above the UPS in rack-mount configurations.
• Additional safety information can be found in the Safety Guide supplied with this unit.
Page 2
Electrical safety
• For models with a hardwired input, the connection to the branc h circuit (mains) must be performed by a qualif ied electrician.
• 230 V model s only: In order to maintain compl iance with the EMC directive for products sold in Europe, output cords attached to the transformer must not exceed 10 meters in length.
• The protective earth conductor for the transformer carries the leakage current from the load devices (computer equipment) . An ins ulated ground conducto r is to be installed as part of the branch circuit that supplies the transformer. The conductor must have the same size and insulation material as the grounded and ungrounded branch circui t supply conductors. The conductor will typically be green and with or without a yellow stri pe.
• The UPS input ground conductor must be properly bonded to protective earth at the service pane l.
• If the UPS input power is supplied by a separately derived system, the ground conductor must be prope rly bonded at the supply transformer or motor generator set.
Hardwire safety
• Verify that all branch circuit (mains) and low volta ge (control) circuits are deenergized, and locked out before installing cables or making connections, whether in the juncti on box or to the transformer.
• Wiring by a qualified electrici an is required.
• Check national and local codes before wiring.
• All openings that allow access to transformer hardwire ter mi nals must be covered. Failure to do so may result in personal injury or equipment damage.
• Select wire size and con nectors according to national and local cod es.
General information
• The model and serial numbers are located on a small, rear panel label.
• Recycle the package materials or save them for reuse.
FCC Class A radio frequency warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are intended to provide reasonable protection against harmful interference when the equipment is operated in a commercial envir o nment. This equipmen t g enerates, uses, and can radiat e radio freq u ency energy and, if not in stalle d and used in acco rdance with the instruc tion manual , may cause harmful interfer ence to ra dio communication s. Operation of this equipment in a re sidential area is like ly to cause harmful interf erence in which case the user will b e required to correct the interfe r ence at his own expense.

Product Information

The Sma rt -U PS™ SRT tra nsformer i s int ended for use as a step-down t ransfor mer. This trans former can a lso fu nction as an isolation transf ormer.
The transformer can be installed in a standard 19-inch rack. The transformer can be installed as a tower or in a rack. For rack-mount configuration use only the APC by Schneider
Electric rack model SRTRK2.
Isolation and Step-Down Trans for me r SRT5KTF2
Page 3

Package Contents

Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
Use with all
models
Front bezel 1 tie bracket to secure the UPS to
SRT5K/6K/8K/10K UPS Use with SRT3000XLT UPS
the transformer
2 screws to secure tie bracket
2 tie bra ckets to sec u r e th e U PS to the transformer
Use with
1 tie bracket to secure the UPS to the transformer
1 pan head screw to secure tie bracket

Specifications

For additional speci f ications refer to the APC by Schneider Electric web site, www.apc.com.
Top and bottom tie brackets to secure the UPS with transformer
2 pan head screws to secure tie brackets
Environmental
Temperature
Maximum Elevation
Humidity Protection Class
Operating Storage Operating Storage
0% to 95% relative humidi ty, non condensing IP 20 rating
0º to 40º C (32º to 104º F)
-15º to 45º C (5º to 113º F) 0 - 3,000 m (0 - 10,000 ft) 0 - 15,000 m (50,000 ft)
Physical
Lifting guidelines 32 - 55 kg (70 - 120lb) > 55 kg (> 120lb)
Unit weight, without packaging 56.82 kg (125 lb) Unit weight, with packaging 63.64 kg (140 lb) Unit dimensions without packaging
Height x Width x Depth Unit dimensions with packaging
Height x Width x Depth
The model and serial numbe rs a r e on a small label located on the rear panel.
432 mm x 130 mm x 660 mm 17 in x 5 in x 26 in
347 mm x 603 mm x 980 mm
13. 68 in x 23.7 4 in x 38.6 in
Isolation and Step-Down Tra nsformer SRT5KTF 3
Page 4
Electrical
suo1007a
Utility Power
3 ft cable L6-30 plug
Power to Load Equipment
Transformer
UPS
P D U
P D U
Nominal Input Voltage (Vac) 208 V, 220 V, 240 V Input Voltage Range (Vac) 170 V - 280 V Input Service Maximum Current (Amps) 30 A Input Connection 3 ft cord with L6-30P Line Frequency (Hz) 50/60 Hz Nominal Output Voltage (Vac) 220 V / 240 V / 208 V / 110 V / 120 V Output Recepta cles (2) L6-20R
(1) L6-30R (1) L14-30R
(8) 5-20R (accepts both 5-20P and 5-15P) Maximum Output Power (VA) 4800 VA Maximum Output Power (Watt) 4800 W

Wiring Diagram

CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• Adhere to all national and local electrical codes.
• Wiring should be performed by a qualified electrician.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Typical system configuration
Utility voltage UPS output Input voltage selection
switch position
208 V 208 V 208 V 240 V / 208 V / 120 V 240 V 240 V 240 V 240 V / 208 V / 120 V 220 V 220 V 240 V 220 V / 110 V
Transformer output voltage
Isolation and Step-Down Trans for me r SRT5KTF4
Page 5

Tower Installation

CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• Always use the recommended number of screws to secure brackets to the UPS and transformer.
• Always install the transformer to the left of the UPS when facing the front of the units.
• Always install the optional bypass panel to the left of the transformer when facing the front of the units.
Failure to follow these instructions can result in equipment damage and minor or moderate injury
Note: The transformer must be installed to the left of the UPS wh en fa ci n g the front of the units. If the configuration includes the optional bypass panel, ensure that the bypass panel is installed to the left of the transformer when facing the front of the units. Refer to the bypas s panel manual for installation instructions .
To wer transformer
Your UPS model may differ in appearance from those depicted in these graphics . The installation process is identical for the following models:
• SRT5KXLT
• SRT6KXLT
• SRT8KXLT
• SRT10KXLT
Place the transformer to th e left side of the UPS at the installat ion location.
suo1001a
suo1000a
Isolation and Step-Down Tra nsformer SRT5KTF 5
Page 6
Remove two screws at the top and bottom of the UPS.
suo1006c
Remove two screws at the top and bottom of the
transformer.
suo1002b
Reuse the screws removed in and to secure tie
brackets at the top and bottom of the transformer an d UPS.
su0051b
Install the tie brackets to the transformer and UPS.
suo1003a
Isolation and Step-Down Trans for me r SRT5KTF6
Page 7
Inst al l th e fr o n t bezel on th e tr an s f o r mer.
suo1004a
To wer transformer SRT3000XLT model
Place the transformer to th e left side of the UPS at the installat ion location.
suo1001a
suo1000a
Isolation and Step-Down Tra nsformer SRT5KTF 7
Page 8
Remove two screws at the top and bottom of the UPS.
suo1105a
s
u
o
1
1
0
1
b
suo
1004b
Remove two screws at the top and bottom of the
transformer.
su0051b
Reuse one screw removed in and one new pan head screw to secure the tie brackets at the top and bottom of the
transformer and UPS. Note: Mount the pan head screws to the UPS.
Insta ll the tie brackets to the transformer and UPS.
suo1003c
Inst al l th e fr o n t bezel on th e tr an s f o r mer.
Isolation and Step-Down Trans for me r SRT5KTF8
Page 9

Connection and Startup Instructions

suo1005a
CAUTION
DAMAGE TO EQUIPM EN T OR PERSON N EL
• Disconnect the mains input circuit breaker before installing or servicing the UPS or transformer or connected equipment.
• Disconnect internal and external batteries before installing or servicing the UPS or connected equipment.
• The UPS contains internal and external batteries that may present a shock hazard even when disconnected from the mains.
• UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
• Disconnect equipment from the UPS before servicing any equipment.
• Do not use the UPS as a safety disconnect.
Failure to follow these instructions can result in equipment da mage and minor or mod erate inj ury
1. Ensu r e th at th e transformer input cord is unplugged.
2. Remove the voltage selectio n switch cover .
3. Set the input voltage selection s w itch to match the utility volt age of 208 or 240 VAC. “Typi cal system configuration” on page 4.
4. If 240 V utility is used, program the UPS output for 240 V. See the UPS user manual.
5. Install the voltag e se lection switch cover .
6. Plug applicable load equipment into the PDU receptacles  on the transformer.
7. Plug the transformer input cord 1 into the appropriate PDU receptacle on the rear of the UPS.
8. Ensure that the output circuit breakers are ON.
9. Ensure that the input circuit breaker is ON.
Isolation and Step-Down Tra nsformer SRT5KTF 9
Page 10

Tower to Rack-Mount Conver sion

CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• Always use the recommended number of screws to secure brackets to the UPS and transformer.
• Always install the transformer above the UPS in the rack.
• Always install the optional bypass panel above the transformer in the rack.
Failure to follow these instructions can res ul t in equipment damag e and mino r or mod erate injury
Note: The transformer must be installed directly above the UPS in the rack. If the configuration includes the optional bypass panel, ensu re tha t the bypass panel is instal led above the transformer in the rack. Refer to the bypass panel manual for installation instructions.
1. Install the transformer directly above the UPS in the rack. Refer to the Smart-UPS RT Tower to Rack-mount Conversion Guide and the optional rail kit.
2. See the “Connection and Startup Instructio ns” on page 9 to complete the installation.

Service

If the transformer requires service do not return it to the dealer. Instead, follow these steps:
1. Contac t APC by Schneider Electric Custom er S ervice through the APC by Schneider El ec tric web site, www.apc.com/support.
a. Note the model number of the transformer, the ser ial number , and the date purchased. If you call APC by
Schneider Elect ric Customer Ser vic e, a techni cian wil l ask you t o describe the prob lem and try to s olve it over the phone, if possible. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
b. If the transformer is under warranty, repairs are free. If not, there is a repair char ge.
2. Pack the trans former in its original packa ging. If the original packing is not available, refer to the APC by Schneider Electric web site, www.a pc.com/support, for information about obtaining a new set.
a. Pack the transformer prope rly to avoid damage in transit. Never use Styrofoam beads for packaging.
Damage sustained in tra ns it is not covered under warranty.
3. Mark the RMA# on the ou ts ide of the package.
4. Return the transformer by insured, prepaid carrier to the address given to you by Cus tomer Service.
Isolation and Step-Down Trans for me r SRT5KTF10
Page 11

Limited Warranty

Schneider Electri c IT Corporation (SEIT), warrants its products to be free from defects in material s and workmanship for a period of two (2) years from the date of purcha se. The SEIT obligation under this warra nty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacemen t of a defective product or parts thereof does not exte nd the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products ma y be re gistered online at warranty.apc.com.
SEIT shall not be liab le under the warranty if its testing and examination dis close that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation, tes ting, operation or use of the product contrary to SEIT recommendations or specifications. Further, SEIT sha ll not be liable for defects resulti ng from: 1 ) unau thorize d attemp ts to re pair or m odify the produc t, 2) inc orrect or inade quate ele ctric al voltage or connection, 3) inappropriate on site operation cond itions, 4) Acts of God, 5) exposure to th e el ements, or 6) theft. In no event shall SEIT have any liability under thi s war r anty for any product where the serial number has bee n altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WA RRANT IES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGE S ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRAN TY SHALL SEEK TO EXCLUDE OR LIMIT SEIT LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty clai ms issues may access the SEIT worldwide cust omer support network through the APC Web site: www.apc.com the top of the web page to obtain inform ation for customer support in your region. Products must be returned with transportation c harge s prepa id and must be accomp anied by a brie f desc ription of the pro blem encou ntered and proof of date and pl ac e o f pu r chase.
. Select your country fr om t he count ry select ion drop down menu. Ope n the S upport ta b at
Isolation and Step-Down Tra nsformer SRT5KTF 11
Page 12
APC by Schneider Electric
Worldwide Customer Support
Customer support for this or any othe r APC by Schneider Electric product is available at no charge in any of the following ways:
• Visit the APC by Schneider Elec tric web site, www.a pc.com to access documents in the APC Knowledge Base and to submit customer support requests.
www.apc.com (Corporate Headquarters)
Connect to localized APC by Schneider Electric web site for specific countries, each of which provides customer support inform ation.
www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail. – Local, country specific centers: go to www.apc.com/support/contact for contact information. – For information on how to obtain local customer support, contact the APC by Schneider Electric
representative or other distributor from whom you purchased your APC by Schneider Electric product.
© 2016 APC by Schneider Electric. APC, the APC logo, Smart- U PS and PowerChute are owned by Schnei der Elec tric Indus tr ies S.A.S. or their affiliated co m p an ies. All ot her trade m ar k s are prope rty of their respective owners.
EN 990-5431C