- Hazardous electrically-charged parts inside the UPS are energized from the
battery supply even when the AC power is disconnected. Follow Total Power Off
procedure to completely de-energize the system.
- Remove all conductive jewel ry such as chains, wat ches, and rin gs befor e handling
the Battery Units.
- Battery Units do not contain serviceable parts. Do not open.
- Do not dispose of Battery Units in a fire, as they may explode. Do not mutilate
Battery Units, as released electrolyte is harmful to the skin and eyes and may be
toxic.
WARNING!
After the UPS has been electrically wired, do not start it up. Start-up is
commissioned to APC-authorized personnel only.
For configurations including customer-supplied external batteries, refer to
manufacturer’s battery installation and maintenance instructions.
Total Power OFF procedure
WARNING!
Before electrical installation begin s, verify that the UPS is in the Total Power Off
mode by following this procedure.
The PowerView is the user control interface to the UPS. It is used to configure and monitor the
system, set alarm thresholds, and provide audible and visual alarms.
Five navigation keys are used to
Four LED indicators
report the operational
status of the UPS.
Liquid crystal
display (LCD)
select and open menu items,
access information, change system
parameters, and launch contextsensitive help.
LOAD ON
Chrg 100%
ON BATT
Load 000%
120Vin 000Vout 60Hz
BYPASS
Runtime: 00hr 30m
FAULT
ESC
?
LOAD ON LED - When green, the Symmetra PX UPS is providing power to the load
equipment.
ON BATT LED - When yell ow, power is flowing from the batteries to the Power Modules.
BYPASS LED - When yellow, power to the load is being supplied through the Bypass Static
Switch.
FAULT LED - When red, a fault condition exists.
LCD - Display alarms, status data, instructional help, and configuration items.
UP and DOWN navigation keys - Selects menu items and accesses information.
ENTER key - Opens menu items and input changes to system parameters.
Do Self T estInitiate a system of self-tests and diagnostics
UPS LOAD IS OFF
Load Off Screen
UPS IS BYPASSED
Bypassed Screen
Simulate Power FailSimulate a power failure
Graceful RebootTurn off and start load equipment correctly
Graceful Turn Off Shut down load equipment correctly
Start Runtime CalBegin runtime calibration of the UPS
Control screen
From the Control screen, you can select the following items:
Statu
UPS into BypassPlace into or return from maintenance bypass operation
Do Self T estInitiate a system of self-tests and diagnostics.
Simulate Power FailSimulate a power failure
Graceful RebootTurn off and start load equipment in an ordinary manner.
Graceful Turn Off Shut down load equipment in an orderly manner.
Start Runtime CalBegin runtime calibration of the UPS.
Turn Load On/OffApply power to or shut down the UPS
Information on the last transfer to battery operation.
General UPS status.
Status of the main intelligence module.
Status of the redundant intelligence module.
Set-up functions
Display parameters are set to factory defaults.
Selector
Arrow
Control
Status
Setup
Accessories
Top-Level Menu
Logging
Display
Diags
Help
Changing factory default settings:
Control
Status
Setup
Accessories
Top-Level Menu
Logging
Display
Diags
Help
Set-up screens
From the Setup screen, you can select the following:
ShutdownConfigure the following system shutdown conditions:
Low Batt Dur: Low battery duration is the time from low battery signal to the
shutdown of the load. This signal is sent to the server using shutdown software
(PC + PCNS).
Shutdwn Dly: Shutdown delay is the time from when the UPS receives a
shutdown command (usually sent by a server) to the shutdown of UPS power to
the load equipment. This delay allows load equipment to finish shutdown
processes.
Return Dly: Return delay is the amount of time the UPS needs to turn on after a
power outage has ended.
Settings:
Shutdown
Defaults
Output Freq
Settings Menu
Alarms
Bypass
Copy
Other
Return Bat Cap: Return battery capacity is the minimum percentage of battery
capacity required for the UPS to turn the load on.
DefaultsReturn all UPS settings to their default values.
Output FrequencySet the desired output frequency
AlarmsRedundancy: The state of redundancy that will trigger an alarm. Choices are:
BypassSet the conditions in which the UPS will automatically go into bypass operation.
CopyCopy the UPS settings.
OtherSelf Test: Set the UPS to perform a self-test automatically at periodic intervals.
• N+0 – an alarm will occur only when there is more load than all functioning
power modules can support;
• N+1 – an alarm will occur when there are no spare power modules in good
condition;
• N+2 – an alarm will occur when there is only one functioning power module.
Load: When the load is greater than this threshold, an alarm will sound.
Runtime: When the UPS time duration for powering the load is les s th an this
threshold, an alarm will sound. This alarm is the result of an increase in load or a
decrease in battery capacity.
USP ID: Type in a unique name for the UPS.
Vout Reporting: Set the reporting to the number of the tap to which the most
significant load is wired on the output transformer.
Output: Set the UPS output voltage.
BatFrAmpHour: Set the Ampere-Hour rating of external battery enclosures that
are not APC Symmetra PX Battery Enclosures.
Accessories screen
Control
Status
Setup
Accessories
Top-Level Menu
Logging
Display
Diags
Help
From the Accessories screen, you can view the status of APC accessories connected to the UPS.
The Logging screen allows you to customize the UPS log. The following items are accessible from
this screen:
View LogPoint to an entry in the log and press the Enter key to view a description of the
event. The display logs the most recent 64 events.
View StatisticsView statistics of the events logged.
Configure LoggingSet the type of events that are recorded in the log. To log a type of event, choose
On.
List Event Groups• View the list of event types.
• Power Events
• UPS Control Events
• User Activities
• UPS Fault Events
• Measure UPS Events
For each group, press the Enter key to display the individual events listed under
the group.
Clear LogClear all events currently stored in the log.
Display screens
Control
Status
Setup
Accessories
Top-Level Menu
Logging
Display
Diags
Help
The Display screens allow you to customize the UPS display interface. The following items are
accessible from this screen:
DateSet the correct date (day:month:year) and time (hour:minute).
PasswordProtect the password against unauthorized configuration changes.
InformationView the model number , serial numb er , da te of manuf acture, and revisi on number
ConfigPersonalize the Top-Level Status screen. Choose each line you want displayed
Diag screens
from a list of options. To change a line, move the selection arrow to the line you
want to change and press the ENTER key. Scroll up or down the list to find the
data you want displayed an d press t he ENTER key to sav e your changes . Press the
ESC key to discard your changes.
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
Top-Level Menu
The Diagnostic screens provide information used in troubleshooting. The following items are
accessible from this screen:
Fault & DiagnosticsLists any failures found.
If any status except ON or OK is displayed, a module or card must be replaced.
The Faults and Diagnostics screen will describe the location of the failed module/
card. If you do not have a redundant intelligence module installed, you must place
the UPS in bypass operation before you remove an intelligence module.
Lists external device status.
If any status except ON or OK is displayed, a module, card or battery must be
replaced. If you do not have a redundant intelligence module installed, you must
place the UPS in bypass operation before you remove an intelligence module.
Help screens
To access the display interface context-sensitive Help screens, press the ? key.
Disregard the procedures in this section if you have an APC InfrastruXure Manager as
part of your system. See the InfraStruXure Manager’s documentation for more
information.
You must configure three TCP/IP settings before the Management Card can operate on a network:
If a Default Gateway is unavailable, use the IP address of a computer located on the same subnet
Management Card that is usually running. The Management Card uses the Default
as the
Gateway to test the network when traffic is very light. See “Watchdog Features” in the
“Introduction” of the Network Management Card User’s Guide CD (.\doc\usrguide.pdf) for
more information about the watchdog role of the Default Gateway. The Management Card
User’s Guide CD is located in the documentation storage tray.
Maintenance Bypass Operation for
Installations with Optional MBP
How to place the UPS in Maintenance Bypass operation
Before servicing the UPS, place the UPS in Maintenance Bypass operation. When the UPS is
operating in Maintenance Bypa ss opera tion, power flows dir ectl y from the util ity to th e Maintena nce
Bypass Panel and out of the load equipment.
1. Use the UPS display interface to place the UPS in Maintenance Bypass operation:
a. Press the Esc key on the Monitoring screen to open the Main menu.
b. Select Control on the Main menu and press the Enter key.
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
c. Select UPS into Bypass on the Control menu and press the Enter key.
d. Confirm the selection on the next screen: Select Yes, UPS into Bypass and press the Enter
key. The BYPASS LED will illuminate and the display will show the following two screens:
UPS has been
commanded to go
into Bypass...
UPS load is in Bypass
Press any key...
The H3 LED above the Q3 Breaker should then illuminate, indicating that it is safe to
operate the Q3 breaker.
Maintenance Bypass Operation for Installations with Optional MBP
2. Set the Symmetra PX UPS DC Disconnect Breaker and System Enable Switch to the ON
position.
As soon as the DC Disconnect Breaker and the System Enable Switch are set to the ON
position, the UPS transfers to Static Bypass Operation (with the load supported).
3. If applicable, set the XR Battery Enclosure DC Disconnect Breaker to ON.
The H2 LED above the Q2 Breaker should then illuminate, indicating that it is safe to
operate the Q2 Breaker.
WARNING!
Only trained persons familiar with the construction and operation of the
equipment, as well as the electrical and mechanical hazards involved, may install
and remove system components.
WARNING!
Before handling any modules in the UPS, ensure that the System Enable Switch is
in the Stand- By posit ion. See Total Power Off procedure.
How to replace Power Modules
5th
4th
3rd
2nd
1st
e
e
d
d
i
i
u
u
X
X
G
G
P
P
r
r
M
M
e
e
s
T
T
s
U
U
a
a
t
t
r
r
r
r
a
t
a
t
t
t
e
e
S
S
-
-
k
m
m
k
c
c
i
i
m
m
u
u
y
y
Q
Q
S
S
To de-activate the module, turn Locking Latch (with arrow pointing towards the module)
counter-clockwise until it points downwards.
Unscrew spring-activated knobs on both sides of the module until they pop out. Standing on
both sides of the UPS, 2 people can now pull the module almost free of the UPS (the lock
mechanism prevents the module from being pulled clear of the UPS). With the module still
resting in the UPS, rel ease t he lock by pu shing t he blac k plas tic t ab on ei ther s ide of t he modul e.
Pull out the module. Reverse procedure for installation of replacement module. Display shows
message saying it has registered the new module.
Power Module will not operate unless locking latch is engaged.
Holding the handle, gently push the Battery Unit upwards and pull it halfway out of the UPS. A
lock mechanism prevents it from being pulled all the way out.
To release from the lock mechanism, gently push the Battery upwards again and pull out while
supporting it with the other hand.
Reverse procedure for installation of replacement Unit. Display shows message saying it has
registered the new Unit.
How to replace Cards
Loosen the 2 Phillips screws on both sides of the Card.
Carefully pu ll out the Card.
Reverse procedures for installation of replacement Card. Display shows message saying it has
One Intelligence Module can be replaced without interrupting power to the co nnected equipment,
provided a second Intelligence Module is installed and operational.
INT
ELLI
GEN
CE MO
DULE
INTE
L
LIGENCE MO
DULE
Module and Card Replacement
INTELLIGENCE MODULE
INTELLIGENCE MODULE
Loosen the 2 Phillips screws on both sides of the module (top of module). As soon as the left
side screw is loose, the module will be deactivated. Display shows message saying the number
of Cards has been decreased.
Reverse procedures for installation of replacement module.
How to obtain replacement Modules
To obtain a replacement module, contact APC Customer Support.
1. In the event of a module failure , the displa y inte rface may di splay addi tional “f ault lis t” screen s.
Press any key to scroll through these fault lists, record the information, and relay it to the
customer support representative.
2. If possible, call APC Customer Support f rom a telepho ne that i s withi n reach of the UPS disp lay
interface so that you can gather and report additional information to the representative.
3. Be prepared to provide a detailed description of the problem. A representative will help you
solve the problem over the telephone, if possible, or will give you a return material
authorization (RMA) number. If a module is returned to APC, this RMA number must be
clearly printed on the outside of the package.
4. If the Symmetra PX UPS is within the warranty period, rep airs will be performed fr ee of charge .
If it is not within the warranty period, there will be a charge for repair. Review APC ‘s warranty
policy.
See section onWarranty for more information
5. If the UPS is covered by a n APC service c ontract , have th at informa tion avai lable and provide it
to the representative.
40kW Enclosure Only SYCF40KF
10kW Power ModuleSYPM10KF
Battery ModuleSYBT4
Battery UnitSYBTU1
Intelligence ModuleSYMIM4
Symmetra PX Static Switch ModuleSYSSW40KF
System Power Supply CardSYCSPS
Display and Computer Interface Card SYCDCI
Battery Monitoring CardSYCBTMON
Switch Gear Monitoring CardSYCSGMON
System ID CardSYCSYSID
XR Communication CardSYCXRCOM
Web Card, SNMPAP9606 Web/
Management Slot Card
Battery Enclosure onlySYCFXR8
WARNING!
Only trained persons familiar with the construction and operation of the
equipment, and the electrical and mechanical hazards involved, may install and
remove system components.
This section lists all of the alarm and status messages that might be displayed on the UPS display
interface. A suggested corrective action is listed with each message to help you troubleshoot
problems.
If a problem is reported, ensure that the system component in qu estion is correctly installed (ref er
to section on Module & Card Replacement).
General status
Display messageMeaningCorrective action
Input Freq outside
configured range
AC adequate for UPS but
not for bypass
Low/No AC input,
startup on battery
Main Intelligence
Module inserted
Main Intelligence
Module removed
The input frequency to the UPS is
outside the configured range. The
output frequency will not sy nchronize
with the input frequency.
Normal bypass is not available.
The UPS will function online with the
input voltage, but the input voltage is
not adequate to power the load in the
event of Bypass Operation.
Input voltage is not adequate to start
the UPS. If start-up proceeds, the
UPS will function in Battery
Operation.
An Intelligence Module has been
installed into the UPS.
An Intelligence Module has been
removed from the UPS.
Option 1: Improve the frequency of
the incoming voltage.
Option 2: Widen range of the
acceptable incoming frequency using
the display interface. Select Start-UP,
Setup, Output, Freq Select.
Option 3: Proceed with startup.
Normal bypass is not available.
Option 1: Improve the incoming
voltage.
Option 2: Proceed with startup.
Normal bypass is not available.
Option 1: Cancel start-up until
acceptable input voltage is present.
Option 2: Continue start-up and run
on battery.
No corrective action necessary.
If no Intelligence Modules has been
removed, check that the Intelligence
Modules are properly inserted and
that the fastening screws are tight.
An Intelligence Module has been
installed into the UPS.
An Intelligence Module has been
removed from the UPS.
At least one battery module has been
added or removed from the UPS si nce
the last time the Power ON command
was used.
No corrective action necessary.
If no Intelligence Modules has been
removed, check that the Intelligence
Modules are properly inserted and
that the fastening screws are tight.
No corrective action necessary.
Page 32
Troubleshooting
Display messageMeaningCorrective action
# Pwr modules changed
since last ON
Battery Module Quantity
increased
Battery Module Quantity
decreased
Power Module Quantity
increased
Power Module Quantity
decreased
Battery Cabinet Quantity
increased
Battery Cabinet Quantity
decreased
At least one power module has been
added or removed from the UPS si nce
the last time the Power ON command
was used.
At least one Battery Module has been
added to the system.
At least one Battery Module has been
removed from the system.
At least one Power Module has been
added to the system
At least one Power Module has been
removed from the system.
At least one external battery cabinet
has been connected to the UPS.
At least one external Battery
Enclosure has been disconnected
from the UPS.
Check that all power modules are
properly inserted, the two fastening
screws are tight, and the locking
latches are engaged.
No corrective action necessary.
If no Battery Modules has been
removed, ensure that all Battery Units
are properly inserted.
No corrective action necessary.
If no Power Modules has been
removed, check that all power
modules are properly inserted, the
two fastening screws are tight, and
the locking latch is engaged.
No corrective action necessary.
Ensure that all Battery Enclosure
communication cables are properly
connected and that the LEDs are
illuminated on the battery
communication cards.
Low-BatteryThe UPS is online and the battery
charge is low.
Battery DischargedThe UPS is in battery operation and
the battery charge is low.
Automatic Self Test
Started
Number of System
Power Supplies
The UPS has started pre-programmed
battery test.
One of the system power supp lies has
been removed.
Decreased
External switch gear
Q001 closed
External switch gear
Q001 opened
External switch gear
Q002 closed
The external switch gear Q001 is
closed.
The external switch gear Q001 is
open.
The external switch gear Q002 is
closed.
No corrective action necessary.
Note:If the input voltage fails,
runtime will be limited.
No corrective action necessary. Note:
Runtime is limited in duration. Shut
down the system and the load
equipment or restore incoming
voltage.
No corrective action necessary.
If no system power supplies has been
removed, check that they have been
properly inserted.
No corrective action necessary.
No corrective action necessary. The
UPS is disconnected from the input
power.
The Redundant Intelligence Module Has
Assumed Control
The Main Intelligence Module has
failed, and the Redundant Intelligence
Module is functioning as the primary
Intelligence Module.
On BatteryThe UPS has transferred to battery
operation as the input is not within the
acceptable range. The batteries continue to discharge until the input is
restored to an acceptable range.
Load Shutdown From
Bypass. Input Freq/Volts
Out Of Range
Internal Temperature
Exceeded Upper Limit
The UPS has transferred to battery
operation because the input is out of
acceptable range.
The temperature of one or more battery units has exceeded system specifications.
Shutdown D ue To Low
Battery
The UPS was in Battery Operation
and shut down the load when no more
battery power was available.
Refer to Module Replacement section
for procedures.
Replace the Main Intelligence
Module. Refer to Module Replacement secti on for proce dures.
No corrective action necessary.
Note: Runtime is limited in duration.
Prepare to shut down the UPS and the
load equipment or restore incoming
voltage.
Correct the input voltage problem.
Ensure that the ambient temperature
meets the specifications of the system.
If the ambient temperature is below
o
104
F (40oC), initiate a self test to
detect any bad battery units. Replace
any bad battery units.
No corrective action necessary.
No Batteries Are Connected
No battery power is available.Option 1: Check that batteries are
inserted properly.
Option 2: Check for DC breaker trip.
UPS Is OverloadedThe load exceeded the system power
capacity.
Option 1: Decrease the load.
Option 2: If possible, add a Power
Module to the system.
Internal Communications Failed
On of the buses used for the communication between the UPS Modules
Contact APC Customer Support. See
Customer Support section.
failed.
No W orking Power
Modules Found
No working Power Modules were
found.
Option 1: Check that all power modules are properly inserted, the two fastening screws are tight, and the
locking latches are engaged.
Option 2: Check for other alarm messages.
XR Frame FaultOne of the Battery Frames has failed.Contact APC Customer Support. See
System cannot synchronize to AC line
and bypass mode may not be available if required.
Option 1: Decrease the sensitivity to
input frequency (sel ect St artup, Setup,
Output Freq, and select value).
Option 2: Correct the input voltage to
provide acceptable voltage on frequency.
Battery Voltage Is Too
High
Site Wiring FaultWrong phase rotation on the input
Isolation Transformer
Over-temperature
External DC Disconnect
Switch Tripped
The battery voltage is too high and the
charger has been deactivated.
side.
The Isolation Transformer tempera-
ture is too high.
The external DC disconnect switch
tripped. Battery powe r is not availabl e
Contact APC Customer Support. See
Customer Support section.
An electrician should check that the
UPS has been wired properly.
Contact APC Customer Support. See
Customer Support section.
Activate the external DC Disconnect
Switch.
or the runtime is lower than expected.
Sys Power Sply FailA system power supply has failed.
One of the power supplies has to be
Contact APC Customer Support. See
Customer Support section.
changed.
Battmon Card FailedThe Battery Monitor Card has failed.Refer to Module Replacement section
for further details.
Battery Monitor Card
Removed
The Battery Monitor Card has been
removed.
If the battery monitor card has not
been removed, check that it has been
properly inserted.
SwGr Comm Card FailThe Switch Gear Communications
Card has failed.
Switch Gear Communication Card Removed
The Switch Gear Communcations
Card has been removed.
Refer to Module Replacement section
for further details.
If the Switch Gear Communication
card has not been removed, check that
it has been properly inserted.
Internal DC Disconnect
Switch Tripped
The internal DC Disconnect Switch
tripped and battery power is not avail-
Activate the internal DC Disconnect
Switch.
able.
Static Bypass Switch
Module Fault
System ID Card
Removed
The Static Bypass Switch module has
failed.
The System ID Card has been
removed.
Contact APC Customer Support. See
Customer Support section.
If the System ID card has not been
removed, check that it has been properly inserted.
System ID Card FailedThe System ID Card has failed.Refer to Module Replacement section
for further details.
System Start Up Configuration Failed
System configuration download
failed. Unable to determine system
voltage and/or frame size.
Check for other alarms and contact
APC customer support i f pro blem p ersists.
Battery Module FaultA Battery Module has failed and
Power Module FaultA Power Module has failed and
Intelligence Module
Fault
Redundant Intelligence
Module Fault
Threshold alarm
Display messageMeaningCorrective action
Redundancy Has Been
Lost
requires replacement.
requires replacement.
The Main Intelligence Module has
failed and requires replacement.
The Redundant Intelligence Module
has failed and requires replacement.
The UPS no longer detects redundant
power modules. One or more power
module(s) have fail ed, o r t he lo ad h as
increased.
Refer to Module Replacement Section for procedures.
Refer to Module Replacement Section for procedures.
Replace the Main Intelligence Module. Refer to Module Replacement
Section for procedures.
Replace the Redundant Intelligence
Module. Refer to Module Replacement Section for procedures.
Option 1: If possible, install
additional power modules.
Option 2: Replace failed modules.
Refer to Module Replacement Section
for procedures.
Option 3: Reduce the load.
Redundancy Is Below
Alarm Limit
Runtime Is Below Alarm
Threshold
Load Power Is Above
Alarm Limit
Load Is No Longer
Above Alarm Threshold
Actual Power Module redundancy has
fallen below user-specified
redundancy alarm threshold. At least
one Power Module has failed or the
load increased.
The predicted runtime is lower than
the user-specified minimum runtime
alarm threshold. Either the battery
capacity has decreased, or the load
has increased
The load has exceeded the userspecified load alarm threshold
The load exceeded the alarm
threshold and the situation has been
corrected either because the load
decreased or the threshold was
increased.
Option 1: If possible, install
additional Power Modules.
Option 2: Replace failed modules.
Refer to Module Replacement Section
for procedures.
Option 3: Reduce the load.
Option 4: Use display interface to
change alarm limit.
Option 1: Allow the battery modules
to recharge.
Option 2: If possible, increase the
number of battery modules.
Min Runtime RestoredThe system runtime dropped below
the configured minimum and has been
restored. Additional Battery Modules
were installed, the existing Battery
Modules were recharged, th e load was
reduced, or the threshold was
decreased.
No corrective action necessary
Bypass
Display messageMeaningCorrective action
Bypass Not Available
Input Freq/Volt Out Of
Range
UPS In Bypass Due To
Fault
UPS In Bypass Due To
Overload
The frequency or voltage is out of
acceptable range for bypass. This
message occurs when the UPS is
online, and indicates that the bypass
mode may not be available if
required.
The UPS has transferred to Bypass
Mode because a fault has occurred.
The load exceeded the system power
capacity. The UPS has switched to
Bypass Mode.
Correct the input voltage to provide
acceptable voltage or frequency.
Contact APC Customer Support
(see rear cover).
Option 1: Decrease the load.
Option 2: If possible, add a power
module to the system.
UPS In Maintenance
Bypass
UPS In Forced Bypass
State
Static Bypass Switch
Module Removed
The system is in maintenance bypass:
Q002 is open and Q003 is closed.
The system has been forced into
Maintenance Bypass Operation: Q003
is closed and/or Manual Bypass
Switch is activated.
The Static Bypass Switch has been
removed.
No corrective action necessary.
No corrective action necessary.
If a static Bypass Switch has not been
removed, check that it has been properly inserted.
If the system works in bypass, ensure the presence of AC mains supply input.
If a problem persists, note UPS model #, serial #, and date purchased before calling APC Customer
Support (see rear cover).
System start-up is includ ed with your system. If you have to move your system to a new locati on and
need a new start-up, remove all power modules and follow the Total Power Off procedure. Raise the
stabilizing feet.
Secure the UPS by setting the stabilizing feet
After the electrical wiring has been completed, secure the UPS in its final operating position. Use a
13/14-mm wrench (shipped with UPS) to adjust all 4 stabilizing feet until pads make solid contact
with the floor.
Level the UPS (recommended)
Adjust stabilizing feet to level from front to back and left to right.
13/14-mm wrench
CAUTION!
Do not move the UPS after the stabilizing feet have been lowered, or equipment
damage may occur.
WARNING!
Only APC-trained personnel familiar with the construction and operation of the
equipment, and the electrical and mechanical hazards involved, may install and
remove system components.
CAUTION!
Before installing any modules in the UPS, ensure that the System Enable Switch is left in
the STAND-BY position (if not, see Total Power OFF procedure).
At least 1 Battery Mo dul e (4 Batt ery Units) is required in t he Battery Enclosure and t he
DC Breaker must be on to start up the system. If using value-line battery cabinets, the
battery configuration will need to be entered manually through the display.
Battery Module installation
4th
3rd
2nd
1st
1st
2nd
3rd
4th
Install Bat tery Units in the lowest available bay, 4 across. Po sition the Battery Unit to s lide in
between the grooves. Push completely into the UPS to ensure connection.
Install Pow er Modules in the top 5 sh elves, starting from the lowest available bay. Push
completely into the UPS.
Fasten screws using a screwdriver.
Engage Locking Latch. Turn knob on right hand side of the UPS clockwise until arrow faces
module.
The Power Module will not start unless the Locking Latch is engaged.
After installation and securing of the Power Modules, make sure that the locking latch
on the Bypass Static Switch Module is engaged.
W ait approx imately 30 seconds for system to boot up. Displa y will show a fault if Power
Module Locking Latch is not engaged.
Press until you get to the Top-Level Status Screen, which provides you with basic
ESC
system stat us information.
LOAD ON
Chrg 100%
ON BATT
Load 000%
120Vin 000Vout 60Hz
BYPASS
Runtime: 00hr 0m
FAULT
Top-Level Status Screen
ESC
?
Press Enter to open the Top-Level Menu screen. This screen is the launching pad to
command, configure, and monitor the system.
Control
Status
Setup
Accessories
Top-Level Menu
Press the down key and then the enter key to select Status. Verify that all power,
Logging
Display
Diags
Help
battery and intelligence modules are detected by the system and are functioning correctly by
scrolling down and reviewing all status screens. Please note that the intelligence modules
are monitored under the “Miscellaneous” Status Screen (submenu under Status).
Bat Voltage: 215V
Bat Capacity 100.0%
Runtime: 01hr 30min
16 Batts, 00Bad
Typical Status Screen
If a problem is reported, ensure that the system component in question is correctly
installed. If the problem persists, refer to Basic Troubleshooting.
From the Control Menu, choose Turn Load On.
Turn Load On
Do Self Test
Simulate Power Fail
Graceful Reboot
Control Menu Scre e n
Load On LED should now be lit.
System Re-Start Procedure
LOAD ON
ON BATT
BYPASS
FAULT
UPS Load is ON.
Confirm Menu Screen
The UPS is now ready to support the load equipment.
If On Batt, Fault or Bypass LED is on, refer to Troubleshooting section.
American Power Conversion Corporation (APC) and its affiliates and subsidiaries worldwide do not
recommend the use of any of their products in life-support applications where failure or malfunction
of the APC product can be reasonably expected to cause failure of the life-support device or to
significantly affect its safety or effectiveness. APC does not permit the use of any of its products in
direct patient care. APC will not knowingly sell its products for use in such applications unless the
life-support system or direct patient care device is part of a whole facility/building in to which the
UPS is integ r ated, and unless APC rece ives, in writing, assurances satisfact ory to APC tha t:
a. The UPS system will be configured in a manner that will provide N+1 power redundancy to
the critical load,
b. The end-user customer assumes all risks and signs the APC System Configuration and Use
Form, and
c. The customer and operators of the APC UPS system agree to indemnify and hold APC and
its affiliates and subsidiaries harmless for any and all claims arising out of the systems use in
such applications.
Examples of life-support devices include, but are not limited to, neonatal oxygen analyzers, nerve
stimulators (whether used for anaesthesia, pain relief, or other purposes), auto-transfusion devices,
blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems,
peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants,
anaesthesia ventilators, infusion pumps, and any other device designated as “critical” by the
U.S.F.D.A.
Hospital-grade wiring devices and leakage current may be ordered as options on many APC UPS
systems. APC does not cl ai m that units with this modification are certifi ed or l is te d as hospital-grade
by APC or any other organization. Therefore, these units do not meet the requirements for use in
direct patient care.
The limited warranty provided by American Power Conversion Corporation (“APC”) in this
Statement of Limited Factory Warranty applies only t o Product s you pur chase fo r your c ommercia l or
industrial use in the ordinary course of your business.
APC product covered
Symmetra PX UPS
Terms of warranty
APC warrants that the Product shall be free from defects in materials and workmanship, for a period
of two (2) years from the date of start-up when APC authorized service personnel has performed the
start-up of the Product. In the event that the Product fails to meet the foregoing warranty, APC shall
repair or replace any defective parts. Any parts furnished under this warranty may be new or factory
remanufactured.
Warranty extends to first purchaser for use, non-transferable
This Warranty is extended to the first person, firm, association or corporation for whom the APC
Product specified herein (herein referred to as “You or Your”.) This Warranty is not transferable or
assignable without the prior written permission of APC.
Assignment of warranties
APC will assign to you any warranties which are made by manufacturers and suppliers of
components of the APC Product and which are assignable. Any such warranties are assigned “as is”
and APC makes no representations as to the effectiveness or extent of such warranties, assumes no responsibility for any matters which may be warranted by such manufacturers or suppliers and
extends no coverage under this Warranty to such components.
Drawings, descriptions
APC warrants for the Warranty Period and on the terms of the Warranty s et forth herein that the APC
Product will substantially conform to the descriptions contained in APC's Official Published
Specifications or any the drawings certified and agreed to by an authorized APC representative, if
applicable thereto (“Specifications”). It is understood that the Specifications are not warranties of performance and not warranties of fitness for a particular purpose.
APC SHALL NOT BE LIABLE UNDER THE WARRANTY IF ITS TESTING AND
EXAMINATION DISCLOSES THAT THE ALLEGED DEFECT IN THE PRODUCT DOES
NOT EXIST OR WAS CAUSED BY YOUR OR ANY THIRD PERSON’S M ISUSE,
NEGLIGENCE, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED
ATTEMPTS TO REPAIR OR MODIFY, OR ANY OTHER CAUSE BEYOND THE RANGE
OF THE INTENDED USE, OR BY ACCIDENT, FIRE, LIGHTNING OR OTHER HAZARD.
THERE ARE NO WARRANTIES, EXPRESSED OR IMPLIED, BY OPERATION OF LAW
OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS
AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED
WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A
PARTICULAR PURPOSE. APC’S EXPRESS WARRANTIES WILL NOT BE ENLARGED,
DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE
OUT OF, APC’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN
CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND
REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND
REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE APC’S SOLE
LIABILITY AND YOUR EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. APC’S WARRANTIES RUN ONLY TO YOU AND ARE NOT EXTENDED
TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR
EMPLOYEES BE LIABLE FOR ANY FORM OR INDIRECT, SPECIAL,
CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE
OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN
CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT
LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE
POSSIBILITY OF SUCH DAMAGE.
SOME COUNTRIES, TERRITORIES, LOCALITIES OR STATES, AS APPLICABLE, DO
NOT ALLOW LIMITATIONS ON HOW LONG A WARRANTY LASTS, IMPLIED
WARRANTIES, OR THE EXCLUSION OR LIMITATION OF INCIDENTAL OR
CONSEQUENTIAL DAMAGES, SO SUCH LIMITATIONS OR EXCLUSIONS MAY NOT
APPLY TO YOU. IT IS APC’S INTENT TO MAKE SUCH LIMITATIONS AND
EXCLUSIONS IN THESE TERMS AND CONDITIONS TO THE FULLEST EXTEND
ALLOWED UNDER ANY APPLCABLE LAW.
• APC warrants the par ts of their systems for 2 ye ars. This wa rranty only covers the cost of the
part and not the labor for installation.
• Calls for warranty parts requests ne ed to have specific unit information (serial number, model
number, job number) to allow proper identification and processing of the warranty part
transaction.
• A purchase order may be required to issue a warranty part(s). An invoice will be sent once the
part(s) are shipp ed to the f ie ld. You have 30 days to return t he part back to APC. After 30 days,
the warranty invoice will be outstanding and payment of the invoice will be expected in full.
• Return authorizatio n documen tation wi ll be s ent wit h the r eplace ment par t. This d ocumenta tion
must be sent back with the defective p art to APC for proper identification of t he warranty
return. Mark the warranty return number on the outside of the package.
• After the part has been received at APC, we will determine the status of the credit based on the
findings of the returned part. Parts that are damaged from: lack of maintenance, mis-application,
improper installation, shipping damage, and acts of man/nature will not be covered under the
parts warranty.
• Any warranty parts request received before 1:00 PM EST will be shipped same day standard
ground delivery. Any costs associated with Next Day or Airfreight will be the responsibility of
the party re questing the part.
• Return freight of warranty parts to APC is the responsibility of the party requesting the part.
To request warranty parts, please contact APC Customer Support.
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to find answers to frequently asked questions (FAQs), to access documents
in the APC Knowledge Base, and to submit customer support requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer
support information.
– www.apc.com/support/
Global support with FAQs, knowledge base, and e-support.
• Contact an APC Customer Support center by telephone or e-mail.
– Regional centers: