American Power Conversion PX User Manual

Page 1
Symmetra PX UPS
10-40 kW
208 V
Operation and
Maintenance Guide
Page 2
Page 3
®
PX
10-40 kW 208V
Operation And Maintenance Guide
Sym
m
®
etra
Q
u
ic
PX
k
-S
ta
rt U
s
e
r G
u
id
e
Page 4
Page 5
Contents
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 1
SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Symbols used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
ON, OFF & STAND-BY switch positions . . . . . . . . . . . . . . . . . . . 1
Weight symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Operation safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Total Power OFF procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overview of System Components . . . . . . . . . . . . . . . . . . . . . . . 4
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Status functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Set-up functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Set-up screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessories screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Logging screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Display screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Diag screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Help screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Network connection/APC Web Management Card . . . . . . . . . . 14
Quick configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maintenance Bypass Operation for Installations with
Optional MBP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
How to place the UPS in Maintenance Bypass operation . . . . . 16
How to return to On-Line Operation from
Manual Bypass operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B i
Page 6
Module and Card Replacement . . . . . . . . . . . . . . . . . . . . . . . . 21
How to replace Power Modules . . . . . . . . . . . . . . . . . . . . . . . . 21
How to replace Battery Units . . . . . . . . . . . . . . . . . . . . . . . . . . 22
How to replace Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
How to replace Intelligence Modules . . . . . . . . . . . . . . . . . . . . 23
How to obtain replacement Modules . . . . . . . . . . . . . . . . . . . . 23
Replacement parts and numbers . . . . . . . . . . . . . . . . . . . . . . . 24
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Module failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Threshold alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
System Re-Start (if applicable) . . . . . . . . . . . . . . . . . . . . . . . . . 32
Secure the UPS by setting the stabilizing feet . . . . . . . . . . . . . . 32
Level the UPS (recommended) . . . . . . . . . . . . . . . . . . . . . . . . . 32
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Battery Module installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Power Module installation and securing . . . . . . . . . . . . . . . . . 34
Connecting communication cables . . . . . . . . . . . . . . . . . . . . . . 35
System Re-Start Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Life support policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Warranty Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
LIMITED PRODUCT WARRANTY FOR APC PRODUCTS . . . . . . . . 39
APC product covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Terms of warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Warranty extends to first purchaser for use, non-transferable . 39
Assignment of warranties . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Drawings, descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Exclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
ii Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 7

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This guide contains important instructions that should be followed when handling the UPS, Battery Enclosures, and Batteries.

Symbols used in this guide

WARNING! Risk of electric shock.
CAUTION!
Read this information.
Indicates important information.
Indicates a heavy load that should not be lifted without assistance.
Indicates that more information is available on this subject in a different section of this manual.
Indicates that more information is available on the same subject in a different manual.

ON, OFF & STAND-BY switch positions

Indicates that a switch or current protection device is in the ON position.
Indicates that a switch or a breakeris in the OFF position for.
Indicates that a switch is in the STAND-BY position.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 1
Page 8
IMPORTANT SAFETY INSTRUCTIONS

Weight symbols

<40 lb 40 - 70 lb. 70 - 120 lb >120 lb

Operation safety

WARNING!
- Hazardous electrically-charged parts inside the UPS are energized from the battery supply even when the AC power is disconnected. Follow Total Power Off procedure to completely de-energize the system.
- Remove all conductive jewel ry such as chains, wat ches, and rin gs befor e handling the Battery Units.
- Battery Units do not contain serviceable parts. Do not open.
- Do not dispose of Battery Units in a fire, as they may explode. Do not mutilate Battery Units, as released electrolyte is harmful to the skin and eyes and may be toxic.
WARNING! After the UPS has been electrically wired, do not start it up. Start-up is commissioned to APC-authorized personnel only.
For configurations including customer-supplied external batteries, refer to manufacturer’s battery installation and maintenance instructions.

Total Power OFF procedure

WARNING! Before electrical installation begin s, verify that the UPS is in the Total Power Off mode by following this procedure.
2 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 9
IMPORTANT SAFETY INSTRUCTIONS
B
A
T
T
E
R
Y
U
N
I
T
O
N
O
F
F
O
F
F
Set System Enable Switch to the STAND-BY position.
Set DC Disconnect to the OFF position.
Disconnect ALL Battery Units by removing or pulling out to Red Disconnect Line
CAUTION!
T o ensure solid stability, do not pull Battery Uni t s out b eyound the Red Disconnect Line unless completely removing them from the UPS.
Set utility power to the OFF or LOCKED OUT position.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 3
Page 10

Overview of System Components

Intelligence Modules (2)
Power Module Bays
Power Module
DC Disconnect Switch
E
S
C
?
PowerView Display
Battery Module Bays
System Power Supply Cards
System Enable Switch
Battery Unit
Input / Output Chassis
Display/Computer Interface Card
XR Communication Card
e
e
d
i
d
i
u
X
u
X
G
P
G
r
P
M
M
e
r
T
s
e
T
s
U
a
U
t
a
r
r
t
r
t
r
a
t
t
e
a
t
e
S
-
S
m
-
k
m
k
c
i
m
c
i
m
u
y
u
y
Q
S
Q
S
Battery Monitor Card
Documentation Storage Tray
Bypass Static Switch Module
Smart Slots (2)
Web Management Card
Switch Gear Monitor Card
System ID Card
4 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 11

Weights

Overview of System Components
UPS (empty) 600 lb. (275 kg)
Power Module 60 lb. (26 kg)
Battery Module 4 x 50 lb. (4 x 23 kg)
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 5
Page 12

Operation

The PowerView is the user control interface to the UPS. It is used to configure and monitor the system, set alarm thresholds, and provide audible and visual alarms.
Five navigation keys are used to
Four LED indicators report the operational status of the UPS.
Liquid crystal display (LCD)
select and open menu items, access information, change system parameters, and launch context­sensitive help.
LOAD ON
Chrg 100%
ON BATT
Load 000% 120Vin 000Vout 60Hz
BYPASS
Runtime: 00hr 30m
FAULT
ESC
?
 
LOAD ON LED - When green, the Symmetra PX UPS is providing power to the load
equipment. ON BATT LED - When yell ow, power is flowing from the batteries to the Power Modules.
BYPASS LED - When yellow, power to the load is being supplied through the Bypass Static
Switch. FAULT LED - When red, a fault condition exists.
LCD - Display alarms, status data, instructional help, and configuration items.
UP and DOWN navigation keys - Selects menu items and accesses information.
ENTER key - Opens menu items and input changes to system parameters.
HELP key - Launches context-sensitive help.
ESC key - Returns to previous screen displayed.
6 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 13
Operation
Press ESC until you get to the Top-Level Status Screen, which provides you with basic
ESC
system stat us information.
Chrg 100% Load 000% 120Vin 000Vout 60Hz Runtime: 0hr 0m
Top-Level Status Screen
(factory default)
Press Enter to open the Top-Level Menu screen. This screen is the launching pad to command, configure, and monitor the system.
Selector Arrow
Control Status Setup Accessories
Top-Level Menu
Logging Display Diags Help
Press Up and Down to navigate the selector arrow and view all sub-menu screens.
Bat Voltage: 215V Bat Capacity 100.0% Runtime: 01hr 30min 16 Batts, 00Bad
Battery Module Status Screen
Scroll arrows indicate ad ditional screens
Capacity: 40.0kVA Fault Tolerance: n+1 Total UPS Modules: 5 Bad UPS Modules: 00
Power Module Status Screen
Press Up, Down and Enter to move input arrow to select and enter information.
Low Batt Dur: 2min Shutdwn Dly: Return Dly: Return Bat Cap:
Shutdown Menu
20sec
0sec
Input arrows indicate cha ngeable options
0%
Low Batt Dur: 10min Shutdwn Dly: Return Dly: Return Bat Cap:
Shutdown Menu
20sec
0sec
0%
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 7
Page 14
Operation

Control functions

Selector Arrow
Control Status Setup Accessories
Top-Level Menu
Logging Display Diags Help
Turn load on/off:
Graceful Turn Off Start Runtime Cal Turn Load On
Control Sub-Menu
Turn into/ out of bypass:
UPS into Bypass

Do Self Test Simulate Power Fail Graceful Reboot
Control Menu
Additional control functions:
Do Self T est Initiate a system of self-tests and diagnostics
UPS LOAD IS OFF
Load Off Screen
UPS IS BYPASSED
Bypassed Screen
Simulate Power Fail Simulate a power failure Graceful Reboot Turn off and start load equipment correctly Graceful Turn Off Shut down load equipment correctly Start Runtime Cal Begin runtime calibration of the UPS

Control screen

From the Control screen, you can select the following items:
Statu
UPS into Bypass Place into or return from maintenance bypass operation Do Self T est Initiate a system of self-tests and diagnostics. Simulate Power Fail Simulate a power failure Graceful Reboot Turn off and start load equipment in an ordinary manner. Graceful Turn Off Shut down load equipment in an orderly manner. Start Runtime Cal Begin runtime calibration of the UPS. Turn Load On/Off Apply power to or shut down the UPS
8 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 15

Status functions

Operation
Selector Arrow
Verify general module status:
Control
Status Setup Accessories
Top-Level Menu Sub-Sub-Sub Status Screen
Verify voltage on all phases:
Control
Status Setup Accessories
Top-Level Menu
Control Status Setup Accessories
Logging Display Diags Help
Logging Display Diags Help
Logging Display Diags Help
Top-Level Menu
Capacity: 40.0kVA Fault Tolerance: n+1 Total Pwr Modules: 05 Bad Pwr Modules: 0
0 Vin Vbyp Vout 1 119.6 119.2 0.0 2 119.4 119.4 0.0 3 119.6 119.3 0.0
Status Screen
Verify battery voltage/capacity:
Control

Status Setup Accessories
Top-Level Menu
Logging Display Diags Help
Bat Voltage: 215V Bat Capacity: 10.0% Self Test: None
Sub-Sub Status Screen
Allow a 24-hour battery recharging period after system start-up/battery replacement for battery monitoring data to become fully reliable.

Status screens

The status screen display information regarding load, battery, power module voltage, and current.
Status screen 1.
Vin, Vout, Iout The input voltage (V), output voltage (V), and output current (A) for each phase
(1-3).
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 9
Page 16
Operation
Status screen 2.
%load assuming no redundancy
Percentage of the load in relation to the total capacity of all power modules.
Status screen 3.
%load allowing for n+ redundancy
Percentage of the load, allowing for the redundancy in your system.
Status Screen 4.
Frequencies The input and output frequency in hertz (Hz).
Status screen 5.
Batt Voltage
Batt Capacity
Runtime
#Batts
Actual voltage of the DC bus (volts).
Percentage of battery capacity available.
The available runtime for battery operation in hours and minutes.
The number of installed battery modules.
#Bad
Status screen 6.
Capacity: kVA
Fault Tolerance
Total Pwr Modules
Bad Pwr Modules
Status screen 7.
Alarm Thresholds
Fault Tolerance n+0
Runtime hr min
load: kVA
The number of failed battery modules.
The system load capacity.
The configured redundancy for your UPS (n+0, n+1, n+2...).
The number of power modules installed.
The number of failed power modules installed.
Settings configured for the thresholds that trigger alarms.
The alarm threshold for reduced redundancy.
The alarm threshold for reduced runtime.
Alarm indication of exceeded load.
Status screen 8.
10 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 17
Operation
Self Test
Lst Xfr
Status
IM
RIM
Status of the last self-test.
Information on the last transfer to battery operation.
General UPS status.
Status of the main intelligence module.
Status of the redundant intelligence module.

Set-up functions

Display parameters are set to factory defaults.
Selector Arrow
Control Status Setup Accessories
Top-Level Menu
Logging Display Diags Help
Changing factory default settings:
Control Status Setup Accessories
Top-Level Menu
Logging Display Diags Help

Set-up screens

From the Setup screen, you can select the following:
Shutdown Configure the following system shutdown conditions:
Low Batt Dur: Low battery duration is the time from low battery signal to the
shutdown of the load. This signal is sent to the server using shutdown software (PC + PCNS).
Shutdwn Dly: Shutdown delay is the time from when the UPS receives a shutdown command (usually sent by a server) to the shutdown of UPS power to the load equipment. This delay allows load equipment to finish shutdown processes.
Return Dly: Return delay is the amount of time the UPS needs to turn on after a power outage has ended.
Settings:
Shutdown Defaults Output Freq
Settings Menu
Alarms Bypass Copy Other
Return Bat Cap: Return battery capacity is the minimum percentage of battery capacity required for the UPS to turn the load on.
Defaults Return all UPS settings to their default values.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 11
Page 18
Operation
Output Frequency Set the desired output frequency Alarms Redundancy: The state of redundancy that will trigger an alarm. Choices are:
Bypass Set the conditions in which the UPS will automatically go into bypass operation. Copy Copy the UPS settings. Other Self Test: Set the UPS to perform a self-test automatically at periodic intervals.
• N+0 – an alarm will occur only when there is more load than all functioning power modules can support;
• N+1 – an alarm will occur when there are no spare power modules in good condition;
• N+2 – an alarm will occur when there is only one functioning power module.
Load: When the load is greater than this threshold, an alarm will sound.
Runtime: When the UPS time duration for powering the load is les s th an this
threshold, an alarm will sound. This alarm is the result of an increase in load or a decrease in battery capacity.
USP ID: Type in a unique name for the UPS.
Vout Reporting: Set the reporting to the number of the tap to which the most
significant load is wired on the output transformer.
Output: Set the UPS output voltage.
BatFrAmpHour: Set the Ampere-Hour rating of external battery enclosures that
are not APC Symmetra PX Battery Enclosures.

Accessories screen

Control Status Setup Accessories
Top-Level Menu
Logging Display Diags Help
From the Accessories screen, you can view the status of APC accessories connected to the UPS.
12 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 19

Logging screen

Operation
Control Status Setup Accessories
Top-Level Menu
Logging Display Diags Help
The Logging screen allows you to customize the UPS log. The following items are accessible from this screen:
View Log Point to an entry in the log and press the Enter key to view a description of the
event. The display logs the most recent 64 events.
View Statistics View statistics of the events logged. Configure Logging Set the type of events that are recorded in the log. To log a type of event, choose
On.
List Event Groups • View the list of event types.
• Power Events
• UPS Control Events
• User Activities
• UPS Fault Events
• Measure UPS Events For each group, press the Enter key to display the individual events listed under the group.
Clear Log Clear all events currently stored in the log.

Display screens

Control Status Setup Accessories
Top-Level Menu
Logging Display Diags Help
The Display screens allow you to customize the UPS display interface. The following items are accessible from this screen:
Date Set the correct date (day:month:year) and time (hour:minute). Password Protect the password against unauthorized configuration changes. Information View the model number , serial numb er , da te of manuf acture, and revisi on number
of the display interface.
Beeper Configure the audible alarm interface.:
At UPS At Disp Vol Click
Contrast Set the contrast on the LCD.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 13
Page 20
Operation
Config Personalize the Top-Level Status screen. Choose each line you want displayed

Diag screens

from a list of options. To change a line, move the selection arrow to the line you want to change and press the ENTER key. Scroll up or down the list to find the data you want displayed an d press t he ENTER key to sav e your changes . Press the ESC key to discard your changes.
Control Status Setup Accessories
Logging Display Diags Help
Top-Level Menu
The Diagnostic screens provide information used in troubleshooting. The following items are accessible from this screen:
Fault & Diagnostics Lists any failures found.
If any status except ON or OK is displayed, a module or card must be replaced. The Faults and Diagnostics screen will describe the location of the failed module/ card. If you do not have a redundant intelligence module installed, you must place the UPS in bypass operation before you remove an intelligence module.
Lists external device status.
If any status except ON or OK is displayed, a module, card or battery must be replaced. If you do not have a redundant intelligence module installed, you must place the UPS in bypass operation before you remove an intelligence module.

Help screens

To access the display interface context-sensitive Help screens, press the ? key.

Network connection/APC Web Management Card

C
o
m
p
u
t
e
I
n
serial port
14 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
r
t
e
r
f
a
c
e
R
e
s
e
t
L
i
n
k
-
R
X
/
T
X
1
A
P
9
6
0
6
L
i
n
k
-
R
1
0
B
S
0
P
a
t
B
a
t
a
s
o
w
X
s
u
s
e
-
T
e
r
N
e
t
N
e
t
w
o
r
k
A
d
a
p
t
e
r
/
T
X
S
S
t
t
a
a
t
t
u
u
s
e
-
T
s
Page 21
Network Cable not supplied with unit.

Quick configuration

Disregard the procedures in this section if you have an APC InfrastruXure Manager as part of your system. See the InfraStruXure Manager’s documentation for more information.
You must configure three TCP/IP settings before the Management Card can operate on a network:
• IP address
• Subnet mask
• Default Gateway
Operation
From the PowerView Display:
Control
Status Setup Accessories
Top-Level Menu
IP>>159.215.086.082 Mask>>255.255.255.000 Gway>>159.215.086.001
Network Set-up Screen
Logging Display Diags Help
Accept changes
If a Default Gateway is unavailable, use the IP address of a computer located on the same subnet
Management Card that is usually running. The Management Card uses the Default
as the Gateway to test the network when traffic is very light. See “Watchdog Features” in the “Introduction” of the Network Management Card User’s Guide CD (.\doc\usrguide.pdf) for more information about the watchdog role of the Default Gateway. The Management Card User’s Guide CD is located in the documentation storage tray.
Web/SNMP Mngmnt Card
Network Setup
View Network Setup
Accessories Menu
IP>>159.215.086 Mask>>255.255.255.000 Gway>>159.215.086.001
Accept changes
Network Set-up Screen
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 15
Page 22

Maintenance Bypass Operation for Installations with Optional MBP

How to place the UPS in Maintenance Bypass operation

Before servicing the UPS, place the UPS in Maintenance Bypass operation. When the UPS is operating in Maintenance Bypa ss opera tion, power flows dir ectl y from the util ity to th e Maintena nce Bypass Panel and out of the load equipment.
1. Use the UPS display interface to place the UPS in Maintenance Bypass operation: a. Press the Esc key on the Monitoring screen to open the Main menu. b. Select Control on the Main menu and press the Enter key.
Control Status Setup Accessories
Logging Display Diags Help
c. Select UPS into Bypass on the Control menu and press the Enter key. d. Confirm the selection on the next screen: Select Yes, UPS into Bypass and press the Enter
key. The BYPASS LED will illuminate and the display will show the following two screens:
UPS has been
commanded to go
into Bypass...
UPS load is in Bypass
Press any key...
The H3 LED above the Q3 Breaker should then illuminate, indicating that it is safe to operate the Q3 breaker.
16 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 23
Maintenance Bypass Operation for Installations with Optional MBP
2. Close (turn ON) the Q3 Breaker on the Maintenance Bypass Panel.
Maintenance
Bypass Switch
UPS
The H2 LED above the Q2 Breaker should then illuminate, indicating that it is safe to operate the Q2 breaker.
3. Open (turn OFF) the Q2 Breaker on the Maintenance Bypass Panel.
Maintenance
Bypass Switch
UPS
4. Set the Symmetra PX UPS System Enable Switch and DC Disconnect Breaker to the STAND­BY position.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 17
Page 24
Maintenance Bypass Operation for Installatio ns with Optional MBP
5. If applicable, set the XR Batter y Enclosur e DC Disconnect Bre aker to the STAND-BY position.
6. Open (turn OFF) the Q1 Breaker on the Maintenance Bypass Panel.
Maintenance
Bypass Switch
UPS
7. When steps 1 through 6 have been completed, the UPS will be in Maintenance Bypass operation.

How to return to On-Line Operation from Manual Bypass operation

1. Close (turn ON) the Q1 Breaker on the Maintenance Bypass Panel.
Maintenance
Bypass Switch
UPS
18 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 25
Maintenance Bypass Operation for Installations with Optional MBP
2. Set the Symmetra PX UPS DC Disconnect Breaker and System Enable Switch to the ON position.
As soon as the DC Disconnect Breaker and the System Enable Switch are set to the ON position, the UPS transfers to Static Bypass Operation (with the load supported).
3. If applicable, set the XR Battery Enclosure DC Disconnect Breaker to ON.
The H2 LED above the Q2 Breaker should then illuminate, indicating that it is safe to operate the Q2 Breaker.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 19
Page 26
Maintenance Bypass Operation for Installatio ns with Optional MBP
4. Close (turn ON) the Q2 Breaker on the Maintenance Bypass Panel.
Maintenance
Bypass Switch
UPS
The H3 LED above the Q3 Breaker should then illuminate, indicating that it is safe to operate the Q3 Breaker.
5. Open (turn OFF) the Q3 Breaker on the Maintenance Bypass Panel.
Maintenance
Bypass Switch
UPS
6. As soon as the Q3 Breaker is opened, the UPS will automatically return from Static Bypass operation to On-line operation.
20 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 27

Module and Card Replacement

WARNING! Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components.
WARNING! Before handling any modules in the UPS, ensure that the System Enable Switch is in the Stand- By posit ion. See Total Power Off procedure.

How to replace Power Modules

5th
4th 3rd 2nd
1st
e
e
d
d
i
i
u
u
X
X
G
G
P
P
r
r
M
M
e
e
s
T
T
s
U
U
a
a
t
t
r
r
r
r
a
t
a
t
t
t
e
e
S
S
-
-
k
m
m
k
c
c
i
i
m
m
u
u
y
y
Q
Q
S
S
To de-activate the module, turn Locking Latch (with arrow pointing towards the module)
counter-clockwise until it points downwards. Unscrew spring-activated knobs on both sides of the module until they pop out. Standing on
both sides of the UPS, 2 people can now pull the module almost free of the UPS (the lock mechanism prevents the module from being pulled clear of the UPS). With the module still resting in the UPS, rel ease t he lock by pu shing t he blac k plas tic t ab on ei ther s ide of t he modul e.
Pull out the module. Reverse procedure for installation of replacement module. Display shows
message saying it has registered the new module.
Power Module will not operate unless locking latch is engaged.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 21
Page 28
Module and Card Replacement

How to replace Battery Units

1st
2nd
3rd
4th
4th 3rd
2nd
1st
Holding the handle, gently push the Battery Unit upwards and pull it halfway out of the UPS. A
lock mechanism prevents it from being pulled all the way out. To release from the lock mechanism, gently push the Battery upwards again and pull out while
supporting it with the other hand. Reverse procedure for installation of replacement Unit. Display shows message saying it has
registered the new Unit.

How to replace Cards

Loosen the 2 Phillips screws on both sides of the Card.
Carefully pu ll out the Card.
Reverse procedures for installation of replacement Card. Display shows message saying it has
registered the new card.
22 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 29

How to replace Intelligence Modules

One Intelligence Module can be replaced without interrupting power to the co nnected equipment, provided a second Intelligence Module is installed and operational.
INT
E LLI
G EN
C E MO
D ULE
IN TE
L
LIGENCE MO
D ULE
Module and Card Replacement
INTELLIGENCE MODULE
INTELLIGENCE MODULE
Loosen the 2 Phillips screws on both sides of the module (top of module). As soon as the left
side screw is loose, the module will be deactivated. Display shows message saying the number of Cards has been decreased.
Reverse procedures for installation of replacement module.

How to obtain replacement Modules

To obtain a replacement module, contact APC Customer Support.
1. In the event of a module failure , the displa y inte rface may di splay addi tional “f ault lis t” screen s. Press any key to scroll through these fault lists, record the information, and relay it to the customer support representative.
2. If possible, call APC Customer Support f rom a telepho ne that i s withi n reach of the UPS disp lay interface so that you can gather and report additional information to the representative.
3. Be prepared to provide a detailed description of the problem. A representative will help you solve the problem over the telephone, if possible, or will give you a return material authorization (RMA) number. If a module is returned to APC, this RMA number must be clearly printed on the outside of the package.
4. If the Symmetra PX UPS is within the warranty period, rep airs will be performed fr ee of charge . If it is not within the warranty period, there will be a charge for repair. Review APC ‘s warranty policy.
See section on Warranty for more information
5. If the UPS is covered by a n APC service c ontract , have th at informa tion avai lable and provide it to the representative.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 23
Page 30
Module and Card Replacement

Replacement parts and numbers

Part No
40kW Enclosure Only SYCF40KF 10kW Power Module SYPM10KF Battery Module SYBT4 Battery Unit SYBTU1 Intelligence Module SYMIM4 Symmetra PX Static Switch Module SYSSW40KF System Power Supply Card SYCSPS Display and Computer Interface Card SYCDCI Battery Monitoring Card SYCBTMON Switch Gear Monitoring Card SYCSGMON System ID Card SYCSYSID XR Communication Card SYCXRCOM Web Card, SNMP AP9606 Web/
Management Slot Card
Battery Enclosure only SYCFXR8
WARNING! Only trained persons familiar with the construction and operation of the equipment, and the electrical and mechanical hazards involved, may install and remove system components.
24 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 31

Troubleshooting

This section lists all of the alarm and status messages that might be displayed on the UPS display interface. A suggested corrective action is listed with each message to help you troubleshoot problems.
If a problem is reported, ensure that the system component in qu estion is correctly installed (ref er to section on Module & Card Replacement).

General status

Display message Meaning Corrective action
Input Freq outside configured range
AC adequate for UPS but not for bypass
Low/No AC input, startup on battery
Main Intelligence Module inserted
Main Intelligence Module removed
The input frequency to the UPS is outside the configured range. The output frequency will not sy nchronize with the input frequency. Normal bypass is not available.
The UPS will function online with the input voltage, but the input voltage is not adequate to power the load in the event of Bypass Operation.
Input voltage is not adequate to start the UPS. If start-up proceeds, the UPS will function in Battery Operation.
An Intelligence Module has been installed into the UPS.
An Intelligence Module has been removed from the UPS.
Option 1: Improve the frequency of the incoming voltage. Option 2: Widen range of the acceptable incoming frequency using the display interface. Select Start-UP, Setup, Output, Freq Select. Option 3: Proceed with startup. Normal bypass is not available.
Option 1: Improve the incoming voltage. Option 2: Proceed with startup. Normal bypass is not available.
Option 1: Cancel start-up until acceptable input voltage is present. Option 2: Continue start-up and run on battery.
No corrective action necessary.
If no Intelligence Modules has been removed, check that the Intelligence Modules are properly inserted and that the fastening screws are tight.
Redundant Intelligence Module inserted
Redundant Intelligence Module removed
# Batteries changed since last ON
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 25
An Intelligence Module has been installed into the UPS.
An Intelligence Module has been removed from the UPS.
At least one battery module has been added or removed from the UPS si nce the last time the Power ON command was used.
No corrective action necessary.
If no Intelligence Modules has been removed, check that the Intelligence Modules are properly inserted and that the fastening screws are tight.
No corrective action necessary.
Page 32
Troubleshooting
Display message Meaning Corrective action
# Pwr modules changed since last ON
Battery Module Quantity increased
Battery Module Quantity decreased
Power Module Quantity increased
Power Module Quantity decreased
Battery Cabinet Quantity increased
Battery Cabinet Quantity decreased
At least one power module has been added or removed from the UPS si nce the last time the Power ON command was used.
At least one Battery Module has been added to the system.
At least one Battery Module has been removed from the system.
At least one Power Module has been added to the system
At least one Power Module has been removed from the system.
At least one external battery cabinet has been connected to the UPS.
At least one external Battery Enclosure has been disconnected from the UPS.
Check that all power modules are properly inserted, the two fastening screws are tight, and the locking latches are engaged.
No corrective action necessary.
If no Battery Modules has been removed, ensure that all Battery Units are properly inserted.
No corrective action necessary.
If no Power Modules has been removed, check that all power modules are properly inserted, the two fastening screws are tight, and the locking latch is engaged.
No corrective action necessary.
Ensure that all Battery Enclosure communication cables are properly connected and that the LEDs are illuminated on the battery communication cards.
Low-Battery The UPS is online and the battery
charge is low.
Battery Discharged The UPS is in battery operation and
the battery charge is low.
Automatic Self Test Started
Number of System Power Supplies
The UPS has started pre-programmed battery test.
One of the system power supp lies has been removed.
Decreased External switch gear
Q001 closed External switch gear
Q001 opened
External switch gear Q002 closed
The external switch gear Q001 is closed.
The external switch gear Q001 is open.
The external switch gear Q002 is closed.
No corrective action necessary. Note:If the input voltage fails, runtime will be limited.
No corrective action necessary. Note: Runtime is limited in duration. Shut down the system and the load equipment or restore incoming voltage.
No corrective action necessary.
If no system power supplies has been removed, check that they have been properly inserted.
No corrective action necessary.
No corrective action necessary. The UPS is disconnected from the input power.
No corrective action necessary.
26 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 33
Display message Meaning Corrective action
Troubleshooting
External switch gear Q002 opened
External switch gear Q003 closed
External switch gear Q003 opened
Graceful Shutdown Started
The external switch gear Q002 is open.
The external switch gear Q003 is closed.
The external switch gear Q003 is open.
A graceful shutdown or reboot has been initiated from the display interface or other accessory.
Redundancy OK A loss of Power Module redundancy
occurred and the redundancy has been restored. Either additional modules have been installed or the load has been reduced.
No corrective action necessary. The load is disconnected from the UPS output.
No corrective action necessary. The UPS is in maintenance bypass operation.
No corrective action necessary.
No corrective action necessary.
No corrective action necessary.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 27
Page 34
Troubleshooting

General fault

Display message Meaning Corrective action
Replace Batt(s) One or more Battery Units need
replacement
The Redundant Intelli­gence Module Has Assumed Control
The Main Intelligence Module has failed, and the Redundant Intelligence Module is functioning as the primary Intelligence Module.
On Battery The UPS has transferred to battery
operation as the input is not within the acceptable range. The batteries con­tinue to discharge until the input is restored to an acceptable range.
Load Shutdown From Bypass. Input Freq/Volts Out Of Range
Internal Temperature Exceeded Upper Limit
The UPS has transferred to battery operation because the input is out of acceptable range.
The temperature of one or more bat­tery units has exceeded system speci­fications.
Shutdown D ue To Low Battery
The UPS was in Battery Operation and shut down the load when no more battery power was available.
Refer to Module Replacement section for procedures.
Replace the Main Intelligence Module. Refer to Module Replace­ment secti on for proce dures.
No corrective action necessary. Note: Runtime is limited in duration. Prepare to shut down the UPS and the load equipment or restore incoming voltage.
Correct the input voltage problem.
Ensure that the ambient temperature meets the specifications of the system. If the ambient temperature is below
o
104
F (40oC), initiate a self test to detect any bad battery units. Replace any bad battery units.
No corrective action necessary.
No Batteries Are Con­nected
No battery power is available. Option 1: Check that batteries are
inserted properly. Option 2: Check for DC breaker trip.
UPS Is Overloaded The load exceeded the system power
capacity.
Option 1: Decrease the load. Option 2: If possible, add a Power
Module to the system.
Internal Communica­tions Failed
On of the buses used for the commu­nication between the UPS Modules
Contact APC Customer Support. See Customer Support section.
failed.
No W orking Power Modules Found
No working Power Modules were found.
Option 1: Check that all power mod­ules are properly inserted, the two fas­tening screws are tight, and the locking latches are engaged. Option 2: Check for other alarm mes­sages.
XR Frame Fault One of the Battery Frames has failed. Contact APC Customer Support. See
Customer Support section.
28 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 35
Display message Meaning Corrective action
Troubleshooting
System Not Synchro­nized to AC Line
System cannot synchronize to AC line and bypass mode may not be avail­able if required.
Option 1: Decrease the sensitivity to input frequency (sel ect St artup, Setup, Output Freq, and select value). Option 2: Correct the input voltage to provide acceptable voltage on fre­quency.
Battery Voltage Is Too High
Site Wiring Fault Wrong phase rotation on the input
Isolation Transformer Over-temperature
External DC Disconnect Switch Tripped
The battery voltage is too high and the charger has been deactivated.
side. The Isolation Transformer tempera-
ture is too high. The external DC disconnect switch
tripped. Battery powe r is not availabl e
Contact APC Customer Support. See Customer Support section.
An electrician should check that the UPS has been wired properly.
Contact APC Customer Support. See Customer Support section.
Activate the external DC Disconnect Switch.
or the runtime is lower than expected.
Sys Power Sply Fail A system power supply has failed.
One of the power supplies has to be
Contact APC Customer Support. See Customer Support section.
changed.
Battmon Card Failed The Battery Monitor Card has failed. Refer to Module Replacement section
for further details.
Battery Monitor Card Removed
The Battery Monitor Card has been removed.
If the battery monitor card has not been removed, check that it has been properly inserted.
SwGr Comm Card Fail The Switch Gear Communications
Card has failed.
Switch Gear Communi­cation Card Removed
The Switch Gear Communcations Card has been removed.
Refer to Module Replacement section for further details.
If the Switch Gear Communication card has not been removed, check that it has been properly inserted.
Internal DC Disconnect Switch Tripped
The internal DC Disconnect Switch tripped and battery power is not avail-
Activate the internal DC Disconnect Switch.
able.
Static Bypass Switch Module Fault
System ID Card Removed
The Static Bypass Switch module has failed.
The System ID Card has been removed.
Contact APC Customer Support. See Customer Support section.
If the System ID card has not been removed, check that it has been prop­erly inserted.
System ID Card Failed The System ID Card has failed. Refer to Module Replacement section
for further details.
System Start Up Config­uration Failed
System configuration download failed. Unable to determine system voltage and/or frame size.
Check for other alarms and contact APC customer support i f pro blem p er­sists.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 29
Page 36
Troubleshooting

Module failure

Display message Meaning Corrective action
Battery Module Fault A Battery Module has failed and
Power Module Fault A Power Module has failed and
Intelligence Module Fault
Redundant Intelligence Module Fault

Threshold alarm

Display message Meaning Corrective action
Redundancy Has Been Lost
requires replacement.
requires replacement. The Main Intelligence Module has
failed and requires replacement.
The Redundant Intelligence Module has failed and requires replacement.
The UPS no longer detects redundant power modules. One or more power module(s) have fail ed, o r t he lo ad h as increased.
Refer to Module Replacement Sec­tion for procedures.
Refer to Module Replacement Sec­tion for procedures.
Replace the Main Intelligence Mod­ule. Refer to Module Replacement Section for procedures.
Replace the Redundant Intelligence Module. Refer to Module Replace­ment Section for procedures.
Option 1: If possible, install additional power modules. Option 2: Replace failed modules. Refer to Module Replacement Section for procedures. Option 3: Reduce the load.
Redundancy Is Below Alarm Limit
Runtime Is Below Alarm Threshold
Load Power Is Above Alarm Limit
Load Is No Longer Above Alarm Threshold
Actual Power Module redundancy has fallen below user-specified redundancy alarm threshold. At least one Power Module has failed or the load increased.
The predicted runtime is lower than the user-specified minimum runtime alarm threshold. Either the battery capacity has decreased, or the load has increased
The load has exceeded the user­specified load alarm threshold
The load exceeded the alarm threshold and the situation has been corrected either because the load decreased or the threshold was increased.
Option 1: If possible, install additional Power Modules. Option 2: Replace failed modules. Refer to Module Replacement Section for procedures.
Option 3: Reduce the load. Option 4: Use display interface to
change alarm limit. Option 1: Allow the battery modules
to recharge. Option 2: If possible, increase the number of battery modules.
Option 3: Reduce load Option 4: Decrease alarm threshold.
Option 1: Use the display interface to
raise the alarm threshold. Option 2: Reduce the load.
No corrective action necessary
30 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 37
Display message Meaning Corrective action
Troubleshooting
Min Runtime Restored The system runtime dropped below
the configured minimum and has been restored. Additional Battery Modules were installed, the existing Battery Modules were recharged, th e load was reduced, or the threshold was decreased.
No corrective action necessary

Bypass

Display message Meaning Corrective action
Bypass Not Available Input Freq/Volt Out Of Range
UPS In Bypass Due To Fault
UPS In Bypass Due To Overload
The frequency or voltage is out of acceptable range for bypass. This message occurs when the UPS is online, and indicates that the bypass mode may not be available if required.
The UPS has transferred to Bypass Mode because a fault has occurred.
The load exceeded the system power capacity. The UPS has switched to Bypass Mode.
Correct the input voltage to provide acceptable voltage or frequency.
Contact APC Customer Support (see rear cover).
Option 1: Decrease the load. Option 2: If possible, add a power
module to the system.
UPS In Maintenance Bypass
UPS In Forced Bypass State
Static Bypass Switch Module Removed
The system is in maintenance bypass: Q002 is open and Q003 is closed.
The system has been forced into Maintenance Bypass Operation: Q003 is closed and/or Manual Bypass Switch is activated.
The Static Bypass Switch has been removed.
No corrective action necessary.
No corrective action necessary.
If a static Bypass Switch has not been removed, check that it has been prop­erly inserted.
If the system works in bypass, ensure the presence of AC mains supply input.
If a problem persists, note UPS model #, serial #, and date purchased before calling APC Customer Support (see rear cover).
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 31
Page 38

System Re-Start (if applicable)

System start-up is includ ed with your system. If you have to move your system to a new locati on and need a new start-up, remove all power modules and follow the Total Power Off procedure. Raise the stabilizing feet.

Secure the UPS by setting the stabilizing feet

After the electrical wiring has been completed, secure the UPS in its final operating position. Use a 13/14-mm wrench (shipped with UPS) to adjust all 4 stabilizing feet until pads make solid contact with the floor.

Level the UPS (recommended)

Adjust stabilizing feet to level from front to back and left to right.
13/14-mm wrench
CAUTION!
Do not move the UPS after the stabilizing feet have been lowered, or equipment damage may occur.
32 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 39

Module Installation

WARNING! Only APC-trained personnel familiar with the construction and operation of the equipment, and the electrical and mechanical hazards involved, may install and remove system components.
CAUTION!
Before installing any modules in the UPS, ensure that the System Enable Switch is left in the STAND-BY position (if not, see Total Power OFF procedure).
At least 1 Battery Mo dul e (4 Batt ery Units) is required in t he Battery Enclosure and t he DC Breaker must be on to start up the system. If using value-line battery cabinets, the battery configuration will need to be entered manually through the display.

Battery Module installation

4th 3rd
2nd
1st
1st
2nd
3rd
4th
Install Bat tery Units in the lowest available bay, 4 across. Po sition the Battery Unit to s lide in
between the grooves. Push completely into the UPS to ensure connection.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 33
Page 40
Module Installation

Power Module installation and securing

5th 4th
3rd
2nd
1st
e
e
d
d
i
i
u
X
u
X
G
P
G
P
r
M
r
M
e
T
e
s
T
s
U
a
U
a
t
r
t
r
r
t
r
a
t
a
t
e
t
e
S
S
-
-
m
k
m
k
c
c
i
m
i
m
u
u
y
y
Q
S
Q
S
Install Pow er Modules in the top 5 sh elves, starting from the lowest available bay. Push
completely into the UPS.
Fasten screws using a screwdriver.
Engage Locking Latch. Turn knob on right hand side of the UPS clockwise until arrow faces
module.
The Power Module will not start unless the Locking Latch is engaged. After installation and securing of the Power Modules, make sure that the locking latch on the Bypass Static Switch Module is engaged.
34 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 41

Connecting communication cables

Use standard Cat 5 data cable of required length (not supplied).
Module Installation
r
e
t
u
p
m
o
C
e
c
e
a
t
f
r
o
e
t
m
n
I
e
w
R
e
i
V
r
e
w
o
P
y
a
l
p
s
i
D
y
a
l
p
s
i
D
o
C
R
X
y
r
e
t
t
a
B
e
c
a
f
r
e
t
n
I
r
e
t
u
p
m
o
C
/
m
m
M
2
t
r
o
P
1
t
r
o
P
s
n
o
i
t
a
c
i
n
u
r
o
t
i
n
o
t
e
s
e
R
s
u
t
a
t
S
X
T
/
X
R
-
k
n
i
L
T
-
e
s
a
B
0
1
r
e
t
p
a
d
A
k
r
o
w
t
e
N
t
e
N
r
e
w
o
P
6
0
6
9
P
A
If your UPS has been installed between devices and side panels cannot be removed the Bypass Static Switch Module can be removed to gain access.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 35
Page 42

System Re-Start Procedure

Utility Power ON
ON
OFF
Battery Enclosure
Switch ON
System Enable
Switch ON
S
E
Y
N
S
A
T
B
E
L
M
E
W ait approx imately 30 seconds for system to boot up. Displa y will show a fault if Power Module Locking Latch is not engaged.
Press until you get to the Top-Level Status Screen, which provides you with basic
ESC
system stat us information.
LOAD ON
Chrg 100%
ON BATT
Load 000% 120Vin 000Vout 60Hz
BYPASS
Runtime: 00hr 0m
FAULT
Top-Level Status Screen
ESC
?
Press Enter to open the Top-Level Menu screen. This screen is the launching pad to
command, configure, and monitor the system.
Control Status Setup Accessories
Top-Level Menu
Press the down key and then the enter key to select Status. Verify that all power,
Logging Display Diags Help
battery and intelligence modules are detected by the system and are functioning correctly by scrolling down and reviewing all status screens. Please note that the intelligence modules are monitored under the “Miscellaneous” Status Screen (submenu under Status).
36 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 43
Bat Voltage: 215V Bat Capacity 100.0% Runtime: 01hr 30min 16 Batts, 00Bad
Typical Status Screen
If a problem is reported, ensure that the system component in question is correctly installed. If the problem persists, refer to Basic Troubleshooting.
From the Control Menu, choose Turn Load On.
Turn Load On Do Self Test Simulate Power Fail Graceful Reboot
Control Menu Scre e n
Load On LED should now be lit.
System Re-Start Procedure
LOAD ON ON BATT
BYPASS
FAULT
UPS Load is ON.
Confirm Menu Screen
The UPS is now ready to support the load equipment.
If On Batt, Fault or Bypass LED is on, refer to Troubleshooting section.
LOAD ON ON BATT
BYPASS
FAULT
Bad Battery Module
Fault Screen
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 37
Page 44

Life support policy

American Power Conversion Corporation (APC) and its affiliates and subsidiaries worldwide do not recommend the use of any of their products in life-support applications where failure or malfunction of the APC product can be reasonably expected to cause failure of the life-support device or to significantly affect its safety or effectiveness. APC does not permit the use of any of its products in direct patient care. APC will not knowingly sell its products for use in such applications unless the life-support system or direct patient care device is part of a whole facility/building in to which the UPS is integ r ated, and unless APC rece ives, in writing, assurances satisfact ory to APC tha t:
a. The UPS system will be configured in a manner that will provide N+1 power redundancy to
the critical load,
b. The end-user customer assumes all risks and signs the APC System Configuration and Use
Form, and
c. The customer and operators of the APC UPS system agree to indemnify and hold APC and
its affiliates and subsidiaries harmless for any and all claims arising out of the systems use in such applications.
Examples of life-support devices include, but are not limited to, neonatal oxygen analyzers, nerve stimulators (whether used for anaesthesia, pain relief, or other purposes), auto-transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anaesthesia ventilators, infusion pumps, and any other device designated as “critical” by the U.S.F.D.A.
Hospital-grade wiring devices and leakage current may be ordered as options on many APC UPS systems. APC does not cl ai m that units with this modification are certifi ed or l is te d as hospital-grade by APC or any other organization. Therefore, these units do not meet the requirements for use in direct patient care.
38 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 45

Warranty Statement

LIMITED PRODUCT WARRANTY FOR APC PRODUCTS

The limited warranty provided by American Power Conversion Corporation (“APC”) in this Statement of Limited Factory Warranty applies only t o Product s you pur chase fo r your c ommercia l or industrial use in the ordinary course of your business.

APC product covered

Symmetra PX UPS

Terms of warranty

APC warrants that the Product shall be free from defects in materials and workmanship, for a period of two (2) years from the date of start-up when APC authorized service personnel has performed the start-up of the Product. In the event that the Product fails to meet the foregoing warranty, APC shall repair or replace any defective parts. Any parts furnished under this warranty may be new or factory remanufactured.

Warranty extends to first purchaser for use, non-transferable

This Warranty is extended to the first person, firm, association or corporation for whom the APC Product specified herein (herein referred to as “You or Your”.) This Warranty is not transferable or assignable without the prior written permission of APC.

Assignment of warranties

APC will assign to you any warranties which are made by manufacturers and suppliers of components of the APC Product and which are assignable. Any such warranties are assigned “as is” and APC makes no representations as to the effectiveness or extent of such warranties, assumes no responsibility for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to such components.

Drawings, descriptions

APC warrants for the Warranty Period and on the terms of the Warranty s et forth herein that the APC Product will substantially conform to the descriptions contained in APC's Official Published Specifications or any the drawings certified and agreed to by an authorized APC representative, if applicable thereto (“Specifications”). It is understood that the Specifications are not warranties of performance and not warranties of fitness for a particular purpose.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 39
Page 46
Warranty Statement

EXCLUSIONS

APC SHALL NOT BE LIABLE UNDER THE WARRANTY IF ITS TESTING AND EXAMINATION DISCLOSES THAT THE ALLEGED DEFECT IN THE PRODUCT DOES NOT EXIST OR WAS CAUSED BY YOUR OR ANY THIRD PERSON’S M ISUSE, NEGLIGENCE, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED ATTEMPTS TO REPAIR OR MODIFY, OR ANY OTHER CAUSE BEYOND THE RANGE OF THE INTENDED USE, OR BY ACCIDENT, FIRE, LIGHTNING OR OTHER HAZARD.
THERE ARE NO WARRANTIES, EXPRESSED OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. APC’S EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, APC’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE APC’S SOLE LIABILITY AND YOUR EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC’S WARRANTIES RUN ONLY TO YOU AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OR INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGE.
SOME COUNTRIES, TERRITORIES, LOCALITIES OR STATES, AS APPLICABLE, DO NOT ALLOW LIMITATIONS ON HOW LONG A WARRANTY LASTS, IMPLIED WARRANTIES, OR THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO SUCH LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO YOU. IT IS APC’S INTENT TO MAKE SUCH LIMITATIONS AND EXCLUSIONS IN THESE TERMS AND CONDITIONS TO THE FULLEST EXTEND ALLOWED UNDER ANY APPLCABLE LAW.
40 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 47
Parts
Warranty Statement
• APC warrants the par ts of their systems for 2 ye ars. This wa rranty only covers the cost of the part and not the labor for installation.
• Calls for warranty parts requests ne ed to have specific unit information (serial number, model number, job number) to allow proper identification and processing of the warranty part transaction.
• A purchase order may be required to issue a warranty part(s). An invoice will be sent once the part(s) are shipp ed to the f ie ld. You have 30 days to return t he part back to APC. After 30 days, the warranty invoice will be outstanding and payment of the invoice will be expected in full.
• Return authorizatio n documen tation wi ll be s ent wit h the r eplace ment par t. This d ocumenta tion must be sent back with the defective p art to APC for proper identification of t he warranty return. Mark the warranty return number on the outside of the package.
• After the part has been received at APC, we will determine the status of the credit based on the findings of the returned part. Parts that are damaged from: lack of maintenance, mis-application, improper installation, shipping damage, and acts of man/nature will not be covered under the parts warranty.
• Any warranty parts request received before 1:00 PM EST will be shipped same day standard ground delivery. Any costs associated with Next Day or Airfreight will be the responsibility of the party re questing the part.
• Return freight of warranty parts to APC is the responsibility of the party requesting the part.
To request warranty parts, please contact APC Customer Support.
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B 41
Page 48
Warranty Statement
42 Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104B
Page 49
Page 50
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to find answers to frequently asked questions (FAQs), to access documents  in the APC Knowledge Base, and to submit customer support requests.  – www.apc.com (Corporate Headquarters)  Connect to localized APC Web sites for specific countries, each of which provides customer  support information.  – www.apc.com/support/ Global support with FAQs, knowledge base, and e-support.
• Contact an APC Customer Support center by telephone or e-mail.  – Regional centers:
APC headquarters U.S., Canada (1) (800) 800-4272 (toll free)
Latin America (1) (401) 789-5735 (USA)
Europe, Middle East, Africa (353) (91) 702020 (Ireland)
Japan (0) 3 5434-2021
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.
Entire contents copyright © 2003 American Power Conversion. All rights reserved.
Reproduction in whole or in part without permission is prohibited. APC, the APC logo, and
Symmetra are trademarks of American Power Conversion Corporation and may be registered
in some jurisdictions. All other trademarks, product names, and corporate names are the
property of their respective owners and are used for informational purposes only.
990-4104B  10/2003
Loading...