APC PMP3XS-B, PMF3XS-B, PML3XS-B, PMJ3XS-B, PMH3XS-B User Manual

...
Page 1
Installation and
Operation Manual
APC Brick Panel Products
PMF3XS-B PMJ3XS-B
PMP3XS-B PMH3XS-B PMG3XS-B
PML3XS-B
Page 2
Compliant with UL1449 3rd Edition requirements dated September 29, 20 09.
Page 3
Table of Contents
Precautions ............................................................................................... 4
Introduction ............................................................................................... 6
Unpacking and Preliminary Inspection ................................................... 8
Storage ....................................................................................................... 8
Safety Labels ............................................................................................. 8
Identification Nameplate .......................................................................... 8
Installation Considerations ...................................................................... 8
Environment ................................................................................................8
Audible Noise ..............................................................................................8
Mounting ..................................................................................................... 8
Service Clearance .......................................................................................8
Equipment Performance .............................................................................8
Electrical .................................................................................................... 9
Voltage Rating ............................................................................................9
Terminals, Wire Size, and Installation Torque ..........................................10
Branch Circuit Overcurrent Protection and Disconnect Means .................10
Location of SPD .............................................................. ..........................11
Grounding ................................................................................................ 12
Installation ............................................................................................... 13
Conduit Location and Recommendations .................................................13
Special Enclosure Considerations ............................................................13
Removing and Reconnecting the RJ45 Patch Cables ........................ 13
NEMA 3R Applications ........................................................................13
Optional Flush Mounting .....................................................................13
Optional Integral Switch ......................................................................13
Wiring ....................................................................................................... 14
Wiring Diagrams without Integral Switch .................................................. 15
Operation ................................................................................................. 16
LED Status Indicators ............................................................................... 16
Audible Alarm ............................................................................................17
Surge Counter ...........................................................................................17
Dry Contacts ........................... ... ................................................... ... ......... 18
Maintenance and Troubleshooting ....................................................... 19
Preventive Maintenance ...........................................................................19
Troubleshooting ........................................................................................ 20
Replacement Parts ...................................................................................20
Customer Support................................ .. ................................................... .24
Installation and Operation Manual 3
Page 4
DANGER
Precautions
Precautions
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Turn off all power supplying this equipment before working on or inside equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this equipment.
• This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
Failure to follow these instructions will result in death or serious injury.
CAUTION
LOSS OF BRANCH CIRCUIT POWER/LOSS OF SURGE SUPPRESSION
• Ensure that the branch circuit breaker or fuse trip characteristic has been coordinated with the overcurrent components inside the SPD (See Table 1).
• Perform periodic inspection of the SPD status indicator lights as part of the preventative maintenance schedule.
• Promptly service the SPD when an alarm state exists.
• Use dry contacts to signal an alarm state to the central supervisory system for unmanned, inaccessible, or critical installations.
• Use multiple SPDs to achieve redundancy for critical applications.
Failure to follow these instructions can result in injury or equipment damage.
At end-of-life conditions, Surge Protective Devices (SPDs) can lose their ability to block power system voltage and attempt to draw excessive current from the line. This SPD is equipped with overcurrent and overtemperature components that will automatically disconnect the surge suppression elements from the mains should the surge suppression elements reach end of life. Tripping of the branch circuit breaker or fuse feeding the SPD can occur. Mitigate the tripping of the branch circuit breaker or fuse feeding the SPD by coordinating the surge suppression elements with the branch circuits.
For the purposes of coordination, the SPD is equipped with overcurrent components that will limit the per phase I listed in table 1 when connected to a power system with a short-circuit current rating not exceeding 200,000 A.
4
Installation and Operation Manual
2
t, I
, Ip, and Ith values to those
apparent
Page 5
CAUTION
Precautions
Table 1:
SPD Per Phase I2tI
PM_3XS-B 175 kA2 seconds 17,000 A RMS 40,000 A RMS 220 A
LOSS OF SURGE SUPPRESSION
• Do not energize the SPDs until the electrical system is completely installed, inspected, tested, and all conductors have been connected and functional, including the neutral.
• Verify the voltage rating of the device and system before energizing the SPD.
• Disconnect the SPD, including the neutral, from the power source before performing high-potential insulation testing or any tests where SPD components will be subjected to voltages higher than their rated turn-on voltage.
Failure to follow these instructions can result in injury or equipment damage.
apparent
I
p
I
th
Installation and Operation Manual 5
Page 6
Introduction
Introduction
Thank you for choosing the APC SurgeArrest® PM_3X Series “Brick” Surge Protective Device. The APC non-modular Surge Protective Device (SPD) is a high-quality, high-energy surge attenuation system that has been designed
to protect sensitive equipment from damaging transient voltage surges. Proper installation is imperative to maximize the surge suppressor’s effectiveness and performance.
This manual is to be used as a guide for installing the device. Read and understand all information contained in this manual prior to installation. The outlined procedures are not intended to supersede local or national electrical codes. Check all applicable electrical
codes to assure compliance. This device must be installed by qualified electrical personnel. The installer should follow the steps detailed in this manual to
ensure proper installation. A copy of the installer’s invoice, detailing the installation of this device, is required in order to take advantage of the unit’s product w arranty.
®
The SurgeArrest applications. These units provide replaceable “brick” (all included surge protections are encapsulated into a single “brick” module) surge protection and are available in 120 kA phase rating.
All APC products are extensively tested according to industry standards as set by IEEE C62.41 and C62.45 for Type 2 Applications. Type 2 applications are permanently connected to SPDs intended for installation on the load side of the service equipment overcurrent device; including SPDs at the branch panel.
Save this manual! It includes instructions regarding the product warranty and replacement parts. Testing
Any factory or on-site testing that exceeds the normal operating voltage, such as high-potential insulation testing or other tests where the suppression components will be subjected to voltages higher than their rated “turn on” voltage, must be run with the suppressor disconnected from the power source. For 4-wire devices, the neutral connection at the SPD must also be disconnected prior to performing high-potential testing and then reconnected upon completion of the test.
Failure to disconnect this surge suppression device and its associated suppression components during elevated voltage testing will result in damage to the suppression components and/or other electronic components.
PM_3X Series product lines specify a parallel SPD designed for service entrance and downstream panelboard
6
Installation and Operation Manual
Page 7
DANGER
Introduction
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Turn off all power supplying this equipment before working on or inside equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this equipment.
• This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
Failure to follow these instruct ions will result in death or serio us injury.
NOTE: T y pe 2 SPDs are designed for use on
the load side of the service entrance Overcurrent Protection Device (OCPD) only.
NOTE: F or troubleshooting, call APC Technical Support at 1-800-800-4272.
Proper installation is imperative to maximize the modular Surge Protective Device’s (SPD’s) effectiveness and performance. The installer should follow the steps outlined in this instruction bulletin to ensure proper installation. Read the entire instruction bulletin before beginning the installation. These instructions are not intended to replace national or local electrical codes. Check all applicable electrical codes to verify compliance. Installation of modular surge suppressors should only be performed by qualified electrical personnel.
Installation and Operation Manual 7
Page 8
PM_3XS-B
www.apc.com
1-800-800-4272
Inspection
Unpacking and Preliminary Inspection
Inspect the entire shipping container for damage or signs of mishandling before unpacking the device. Remove the packing material and further inspect the device for any obvious shipping damage. If any damage is found and is a result of shipping or handling, immediately file a claim with the shipping company.
Storage The device should be stored in a clean, dry environment. Storage temperature
is -40 °F to +149 °F (-40 °C to +65 °C). All of the packaging materials should be left intact until the device is ready for installation.
Safety Labels English, Spanish, and French versions of all safety labels (Danger, Warning,
Caution) are provided.
Identification Nameplate The identification nameplate is located on the inside of the door/cover.
Figure 1: SPD Nameplate Example
Installation Considerations
Environment The device is designed to operate in an ambient temperature range of
-4 °F to +149 °F (-20 °C to + 65 °C) with a relative humidity of 0 to 95% non­condensing. Refer to the product catalog for further details on enclosures. All SPDs operate normally without reduction in performance when subjected to shock and vibrations described in IEC 60721-3-3, Class 3M4.
Audible Noise The device background noise is negligible and does not restrict the location of
the installation.
Mounting The device is designed to be surface or flush mounted. Refer to the device
submittal drawings or the product catalog for typical mounting dimensions and weight.
Service Clearance The service clearance should meet all applicable code requirements. Equipment Performance To obtain the maximum system performance, locate the device as close to the
circuit being addressed as possible to minimize the interconnecting wiring length. For every foot of wire length, approximately 160 volts (6 kV / 3 kA, 8/20 microsecond) is added to the suppressed voltage. The Voltage Protection Rating (VPR) is located on the device nameplate and is measured 6 inches from the device terminals, according to UL 1449 Third Edition.
8
Installation and Operation Manual
Page 9
DANGER
Electrical
Electrical
Voltage Rating
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Confirm the SPD voltage rating on the module or nameplate label is the same as the operating voltage.
Failure to follow these instruct ions will result in death or serio us injury.
Prior to mounting the SPD, verify that the device has the same voltage rating as the power distribution system in which it is installed. Compare the nameplate voltage or model number on the SPD with the nameplate of the electrical distribution equipment.
The specifier or user of the device should be familiar with the configuration and arrangement of the power distribution system in which any SPD is to be installed. The system configuration of any power distribution system is based strictly on how the secondary windings of the transformer supplying the service entrance main or load are configured. This includes whether or not the transformer windings are referenced to earth via a grounding conductor. The system configuration is not based on how any specific load or equipment is connected to a particular power distribution system. See Table 2 for the service voltage of each SPD.
Table 2: Voltage Ratings
Service Voltage
120/240, 1 phase, 2-3 wire
120/208Y, 127/220Y 3 phase, 3-4 wire
240/120, 3 phase, 4 wire (high-leg delta)
277/480Y, 3 phase, 3-4 wire
220/380Y, 230/400Y, 240/415Y 3 phase, 3-4 wire
347/600Y, 3 phase, 3-4 wire
1
Enclosures are rated 3R
Peak Surge Current Rating Per Phase
120 kA PMP3X S-B
120 kA PMF3X S-B
120 kA PMJ3X S-B
120 kA PMG3X S-B
120 kA PMH3X S-B
120 kA PML3X S-B
Catalog Number
1
Installation and Operation Manual 9
Page 10
DANGER
Electrical
Terminals, Wire Size, and Installation Torque
Branch Circuit Overcurrent Protection and Disconnect Means
Terminals are provided for phase (line), neutral, and equipment ground connections. The SPD terminals accept a range of 12 AWG (3 mm2) to 2 AWG
2
(34 mm connections to the following values.
Table 3: Terminal Torque
Power Connection Torque
AØ, BØ, CØ and N Ground
A branch circuit Overcurrent Protection Device (OCPD) either in the form of a circuit breaker or fuse, must be provided for the SPD. The branch circuit OCPD should either provide or include a disconnecting means.
Since the current drawn by the SPD during standby operation is negligible, the SPD can be connected to a dedicated, separate branch circuit or connected to a suitable existing branch circuit.
) copper wire for phase, neutral, and ground connectors. Torque
35 lb-in. (4 N•m)
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Use conductors rated for the Overcurrent Protection Device (OCPD) per applicable codes.
• Use conductors rated for the application per applicable codes.
Failure to follow these instructions will result in death or serious injury.
When connected to a separate, dedicated branch circuit, the OCPD
setting must be selected to protect the conductors feeding the SPD.
When connected to an existing branch circuit, the conductors connected
to the SPD must have an ampacity not less than the setting of the existing OCPD. Refer to Terminals, Wire Size, and Installation Torque section above, for the maximum conductor cross-section that can be connected to the SPD.
During overvoltage surge diversion, current will flow through the SPD. The branch circuit OCPD must pass this current without tripping for the SPD to function properly.
For further information concerning coordination of the OCPD with the SPD, refer to the Caution statement “Loss of Branch Circuit Power/Loss of Surge Suppression” on page 4.
10
Installation and Operation Manual
Page 11
To load(s)
Phases
Neutral
Ground
Ground bus
Neutral bus
SPD
Phase A Phase B Phase C
Neutral
Ground
Panel
Interconnect wiring
– Minimize length – Avoid sharp bends
Location
Location of SPD Install Type 2 SPDs on the load side of the main Overcurrent Protection Device
(OCPD) to comply with NEC Article 285 for Type 2 SPDs. Locate the SPD as close as possible to the circuit being addressed to minimize
the wire length and optimize SPD performance. Avoid long wire runs so that the device will perform as intended. To reduce the impedance that the wire displays to surge currents, the phase, neutral, and ground conductors must be routed within the same conduit and tightly bundled or twisted together to optimize device performance. Avoid sharp bends in the conductors. See Figure 2.
Figure 2: SPD Wiring
Installation and Operation Manual 11
Page 12
WARNING
Grounding
Grounding
HAZARDOUS TOUCH VOLTAGE
• Connect the SPD ground terminal to the building grounding grid structure.
• Use an appropriately sized equipment grounding conductor.
• When using metallic raceway or conduit: — Do not use the SPD ground unless augmented with an insulated
equipment grounding conductor installed inside the metallic raceway or conduit.
— Do not use isolated bushings to interrupt the metallic raceway or
conduit.
— Maintain electrical continuity at all raceway and conduit connections
using appropriate bonding devices.
• Do not use a separate isolated ground for the SPD.
• Verify proper equipment connection to the grounding system.
• Verify ground grid continuity by performing regularly scheduled inspections and testing as part of a comprehensive electrical maintenance program.
Failure to follow these instructions can result in death or serious injury.
The SPD has leakage current to ground when energized and can present a hazardous touch voltage.
The device has SPD elements connected from phase to ground. To prevent hazardous touch voltage on the SPD enclosure during normal operation or during SPD end-of-life, it is critical that there be a robust and effective connection to the building grounding structure. The grounding connection must utilize an equipment grounding conductor run with the phase and neutral (if present) connection of the power system. The SPD should not be connected to a separate isolated ground.
When metallic raceway is used as the wiring method, an insulated grounding conductor should be run inside the raceway and sized in accordance with all applicable codes. Maintain electrical continuity at all raceway connections using appropriate bonding devices and do not install isolating bushings to interrupt a metallic raceway run.
For best overvoltage suppression by the SPD, use a single-point ground system where the service entrance grounding electrode system is connected to and bonded to all other available electrodes, building steel, metal water pipes, driven rods, etc. (for reference, see IEEE 142-2007). The ground impedance measurement of the electrical system should be as low as possible, and in compliance with all applicable codes.
SPDs rated for use on solidly-grounded power systems must not be connected to resistance-grounded (for example HRG) or ungrounded power systems. Such a connection can result in damage to the components within the SPD.
12
Installation and Operation Manual
Page 13
DANGER
Installation
Installation
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Turn off all power supplying this equipment before working on or inside equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this equipment.
• This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
Failure to follow these instruct ions will result in death or serio us injury.
Conduit Location and Recommendations
The recommended conduit entry is at the bottom of the device enclosure. Use a conduit seal that is appropriate for the enclosure rating.
Special Enclosure Considerations
Removing and Reconnecting the RJ45 Patch Cables
NEMA 3R Applications Remove screws from the bottom of the enclosure to create drain holes. Optional Flush Mounting The flush mount collar option provides a mechanical means to install the surge
Optional Integral Switch After making electrical cable connections to the SPD integral switch and prior to
The RJ45 patch cables are marked with matching phase connections. If any of the cables are removed, reconnect the cables as marked.
suppressor flush to the surface of sheetrock or firewall construction.
energizing the SPD, ensure that the line barrier is in place and intact.
Installation and Operation Manual 13
Page 14
DANGER
DANGER
Wiring
Wiring
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Turn off all power supplying this equipment before working on or inside equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this equipment.
• This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
Failure to follow these instructions will result in death or serious injury.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Confirm the SPD voltage rating on the module or nameplate label is the same as the operating voltage.
NOTE: The surge protective device must be installed in an accessible location as described in the NEC
NOTE: The neutral connection is not present on 3-wire, 3-phase wye ground or 2-wire single­phase mid-point ground power systems. For these systems, bond the neutral and ground lugs together in the SPD. For installing wiring see Figures 3 through 5.
NOTE: See “Terminals, Wire Size, and Installation Torque” section for the acceptable wire size and installation torque on page 10.
NOTE: Always install the SPD on the LOAD side of the main Overcurrent Protection Device (OCPD).
®
.
Failure to follow these instructions will result in death or serious in jury.
Follow the steps listed below when making wiring connections.
1. Turn off all power supplying this equipment before working on or inside any enclosure containing this equipment.
2. Confirm the SPD voltage rating and configuration is the same as the system voltage and power system configuration to which it will be connected.
3. Identify proper location for surge protective device. Locate as close as possible to the panel being addressed so the wires are as short as possible. Mount unit securely.
®
4. Install in accordance with National Electrical Code electrical codes for overcurrent protection recommendations and wire ampacity considerations.
5. Twist conductors 1/2 turn or more for every 12 inches of length. Do not loop or coil wires. Be sure to maintain adequate wire bending space per NEC.
6. If the remote signaling contacts of the diagnostic display panel are to be used, refer to the section, “Dry Contacts”, on page 18 for wiring instructions.
7. On a high-leg delta installation, note the high leg connection per wiring diagram. See Figure 5.
8. Replace all devices, doors, and covers, including the line barrier for the optional integral disconnect, before turning on power to the equipment. If the SPD is properly installed and functioning, the green LED indicators on the display will be lit.
If you have any questions pertaining to the installation of this device, contact the APC Technical Support at 1-800-800-4272.
(NEC®) and local
14
Installation and Operation Manual
Page 15
N
SPD
A
N
C
Made in USA / Hecho en E.U.A. / Fabriqué aux É.-U. 8222-0528A
Phase A
Phase C
GROUND
Neutral
Customer Connections
NOTE: The neutral conductor is not present on two-wire grounded power systems. For these systems, bond the neutral and ground lugs together inside the SPD.
Customer Connections
Phase A Phase B
Phase C
GROUND
Neutral
Phase A
GROUND
Neutral
Phase C
Phase B
(High-Leg)
Customer Connections
Wiring
Wiring Diagrams without Integral Switch
Figure 3: SIngle-Phase, Three-Wire, Grounded Installation
Figure 4: Three-Phase, Three- or Four-Wire, Grounded Wye Installation
A
B
SPD
N
C
Figure 5: Three-Phase, Three- or Four-Wire, High-Leg Delta Installation
B
SPD
C
A N
Installation and Operation Manual 15
Made in USA / Hecho en E.U.A. / Fabriqué aux É.-U. 8222-0528A
ØCØABØN
8222-0013-05
Made in USA / Hecho en E.U.A. / Fabriqué aux É.-U. 8222-0528A
8222-0013-06
Page 16
DANGER
GN N NGG
Left green LED lit: L-G suppression is operating
Left green LED not lit: Loss of surge suppression from L-G
Right green LED lit: L-N suppression is operating
Right green LED not lit: Loss of surge suppression from L-N
Operation
Operation
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Turn off all power supplying this equipment before working on or inside equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this equipment.
• This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
Failure to follow these instructions will result in death or serious injury.
LED Status Indicators The diagnostic display panel shows the status of the SPD module with
diagnostically controlled green/red LEDs. If a unit is operating correctly, all the phase LEDs will be illuminated green. To test the integrity of the diagnostics for each phase, push the button below the phase LEDs on the diagnostic display panel. The green LED will turn red and the alarm will sound, if the alarm is enabled. Releasing the test button will complete the test; the red LED will turn green and the alarm will shut off.
If an inoperable condition occurs on any phase, the audible alarm sounds and the corresponding phase LED on the diagnostic display panel is illuminated red. This indicates that the device needs service by qualified electrical personnel. The audible alarm can be silenced by pressing the alarm enable/disable button. The alarm will silence and the green alarm LED will not be lit. The red phase LED will continue to be illuminated until the inoperative condition had been cleared.
®
On an SurgeArrest indicates a loss of suppression from line-to-ground for that phase. If the right green LED is not lit, it indicates a loss of suppression from line-to-neutral for that phase. If the diagnostic display has power and both green LEDs are not lit the module should be replaced.
Figure 6: SurgeArrest® Module LEDs
module (see Figure 6), if the left green LED is not lit, it
16
Installation and Operation Manual
Page 17
NOTE: Phase B is not present on
single-phase applications
Alarm enable/disable
push button
Phase LEDs
On-Line diagnostics
push buttons
Surge counter
Surge counter reset switch or diagnostic circuit board
Description of phase LEDs
Alarm LED Enable alarm Disable alarm
Operation
When power is applied to the SPD and one or more of the diagnostic display panel LEDs are red, and one or more module LEDs are out, the module should be replaced. Refer to “Maintenance and Troubleshooting” on page 19 for proper troubleshooting procedures.
®
Table 4: SurgeArrest
Replacement Modules
System Voltage
120/240, 1-phase,
2-3 wire
120/208Y, 127/220Y
3-phase,
3-4 wire
240/120,
3-phase, 4-wire,
high-leg delta
277/480Y,
3-phase,
3-4 wire
220/380Y, 230/400Y, 240/415Y
3 phase,
3-4 wire
347/600Y,
3-phase,
3-4 wire
Peak Surge Current
Rating (kA)
120 BMP3-B
120 BMF3-B
120 BMJ3-B
120 BMG3-B
120 BMH3-B
120 BML3-B
Catalog Numbers
Audible Alarm Push the alarm enable/disable button to enable or disable the alarm (see
Figure 7). If the green alarm LED is lit the alarm is enabled. If the green alarm LED is not lit the alarm is disabled.
Surge Counter The surge counter displays the number of transient voltage surges since the
counter was last reset. The counter is battery powered to retain memory in the event of a power loss to the diagnostic display panel. To reset the surge counter remove all power and press the small switch located inside the unit on the underside of the diagnostic circuit board near the RJ45 connectors (also refer to Figure 8). This will reset the counter to zero.
Figure 7: Three-Phase Diagnostic Display Panel with Surge Counter
Installation and Operation Manual 17
Page 18
Dry contacts
RJ45
Connectors
Surge counter
reset switch
(white)
DANGER
Operation
Figure 8: Rear of Diagnostic Circuit Board
Dry Contacts The SurgeArrest
connection for the dry contacts is located on the back of the diagnostic display panel (lower right corner). The dry contacts are 3-position, Form “C” type with Normally Open, Normally Closed and Common connections. In the unpowered state the contact is closed between terminals NC and COM. This is also the alarm condition. The opposite state, closed between terminals NO and COM, indicates that power is on to the unit and that no alarm condition exists (See Table 5). These contacts can be used for remote indication of the SPD’s operating status to a computer interface board or emergency management system. Also, these contacts are designed to work with the SPD remote monitor option described below.
The dry contacts are designed for a maximum voltage of 24 Vdc / 24 Vac and a maximum current of 2 A. Higher energy applications may require additional relay implementation outside the SPD. Damage to the SPD’s relay caused by use with energy levels in excess of those discussed in this instruction bulletin are not covered by warranty. For application questions, contact APC Technical Support at 1-800-800-4272.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Use 600 Vac rated dry contact wiring.
• Dry contact wiring must have less than 1/16 in. (1.6 mm) exposed wire from the dry contact block.
• Maintain at least 1.0 in. (25 mm) separation between dry contact wiring and the power wiring in the enclosure.
®
series SPDs come standard with dry contacts. The
18
Failure to follow these instructions will result in death or serious injury.
Care must be taken in installing the dry contact wiring because the terminals are on a moving door. Avoid the door hinge, any switches, and the high voltage areas of the enclosure when routing the wiring. To avoid the door hinge, tie wrap any dry contact wiring to the existing cable harness which crosses the hinge. Once the dry contact wiring is secured on a non-moving point of the enclosure, it is the user’s responsibility to maintain at least 1.0 in. (25 mm) separation between 600 Vac rated dry contact wiring and the power wiring in the enclosure.
Table 5: Dry Contact Configuration
Alarm Contact Terminals Contact State with Power Removed
NC Normally closed COM Common NO Normally open
Installation and Operation Manual
Page 19
DANGER
Maintenance
Maintenance and Troubleshooting
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Turn off all power supplying this equipment before working on or inside equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this equipment.
• This equipment must be effectively grounded per all applicable codes. Use an equipment-grounding conductor to connect this equipment to the power system ground.
Failure to follow these instruct ions will result in death or serio us injury.
Preventive Maintenance Inspect the SPD periodically to maintain reliable system performance and
continued transient voltage surge suppression. Periodically check the state of the diagnostic display panel LED status indicators. Routinely use the built-in diagnostics to inspect for inoperative modules
Installation and Operation Manual 19
Page 20
START
Red phase
LED(s) lit.
Alarm on?
Is alarm
Enable/Disable
LED on?
Press alarm
Enable/Disable
switch. Is
alarm on?
Is alarm LED
on?
NO
NO
YES
YES
Check
patch cable
connections. Is
Red LED(s)
on?
Check the
voltage on
each phase. Is
the voltage
correct?
LEDs lit on all modules?
Possible diagnostic
display panel failure.
Contact APC
Technical Support at
1-800-800-4272 for
troubleshooting.
NO
YES
YES YES
NO
YES
YES
NO
Check the power
utility feed and
verify voltage levels.
NO
Replace module(s)
that do not have
LEDs lit.
Energize SPD and
verify proper
connection.
NO
Troubleshooting
Troubleshooting If a module shows two green indicator lights and the display panel shows a red
phase indicator light, follow the Troubleshooting Flow Chart in Figure 9 below.
Figure 9: Troubleshooting Flowchart
Replacement Parts The following replacement parts are available. For ordering information refer to
the product catalog.
SPD modules. Replacement instructions are included with the
replacement parts.
D iagnostic display panel assemblies. Replacement instructions are
included with the replacement parts.
20
Installation and Operation Manual
Page 21
Installation and Operation Manual 21
Page 22
22
Installation and Operation Manual
Page 23
Installation and Operation Manual 23
Page 24
APC Worldwide Customer Support
Customer support for this or other APC products is available at no charge in the following ways:
Visit the APC website to access documents in the APC Knowledge Base and to submit customer support requests. — www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer support information.
www.apc.com/support
Global support searching APC Knowledge Base and using e-support.
Contact the APC Customer Support Center by telephone or e-mail. — Local, country-specific centers: go to www.apc.com/support/contact for contact information.
For information on how to obtain local customer support, contact the APC representative or other distributors from whome you purchased your APC product.
© 2010 APC by Schneider Electric. APC, the APC logo, and APC SurgeArrest® are owned by Schneider
990-3424A (8251-0137C)
Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies.
All trademarks are property of their respe ctive owne rs.
10/2010
Loading...