6.4PARAMETER LOCATIONS, DESCRIPTIONS, AND DEFAULT VALUES.......................................................22
ivMX28B
Page 5
1. GENERAL INFORMATION
1.1 Introduction
DC Power Systems from APC have unique features that make them easy to install,
maintain, and upgrade. The rectifier units are modular and truly “hot-pluggable” into the
shelf assembly without any separate ac wiring.
All system settings are made from the system control unit that provides monitoring and
control functions for each component of the system as well as alarm listings for system
diagnosis and maintenance.
The APC international network of sales and service offices and qualified representatives
provides sales assistance for proposals, purchases, and after-sales support.
APC provides nationwide 24-hour, 7-day service response by dialing:
(800) 727-8695
This service will answer your call, gather specific service information, and have a qualified
APC service representative contact you as quickly as possible (refer to section on customer
service and support).
1.2 Precautions
It is extremely important to read, understand, and strictly follow the instructions in
sections on installation and setup. Also, please note the special SAFETY
PRECAUTIONS outlined in Section 5.1.4 before beginning actual installation of the
power system.
If any precautions are not clearly understood, or local conditions are not covered, contact
the nearest APC representative or APC at (214) 342-5000 for clarification.
Also, refer to all applicable federal, state, and local regulations, and industry guidelines for
correct installation of this power system.
1.3 Inspection upon Receipt of Goods
1.3.1 General
APC has taken precautions in packing the power equipment for shipment to ensure its safe
arrival; however, the entire shipment including any boxes or crates should be inspected
upon receipt for evidence of damage that may have occurred during transit.
1.3.2 Visible External Damage
It is the responsibility of the person receiving the shipment to inventory and inspect all
materials against the bill of lading or waybill provided IMMEDIATELY upon taking delivery
while the carrier representative is STILL ON SITE. Please be sure that all items are
accounted for, including the correct number of pallets and the quantity of accessory and/or
component boxes. Also, note any visible external damage that may have occurred during
transit.
MX28B1
Page 6
If damage has occurred or the quantity of items is not correct, then:
1) Make a descriptive notation on the delivery receipt before signing.
2) File a damage or shortage report with the carrier that delivered the shipment.
1.3.3 Concealed Damage
It is the customer’s responsibility to unpack the power system and equipment received from
APC and check for concealed damage. Within 15 days of receipt, check the materials
received against the detailed packing list to verify that the quantity and condition are
complete and satisfactory.
Again, note any damage to the internal packing material and/or material shortages. If
damage or shortage is noted, then:
1) Request an inspection by the carrier;
2) File a concealed damage claim; and/or
3) File a material shortage claim with your APC representative.
DELAY IN NOTIFYING THE CARRIER MAY RESULT IN LOSS OF RIGHT TO
REIMBURSEMENT FOR DAMAGES OR LOSS.
If you are unsure about the appearance of a part while conducting the materials inventory
and inspection, refer to the manual or contact the Customer Service Department of APC.
Should you have any questions concerning potential damages or should you
experience a lack of cooperation from your carrier, please contact your APC
representative, or call APC.
1.3.4 Return of Damaged Goods
Should equipment be damaged and require return to APC for repair, the APC service
representative will provide instructions along with a valid returned material authorization
(RMA) number to facilitate return of the damaged goods to the APC repair center.
It is important that the steps outlined in Section 1.3.2 and Section 1.3.3 above are followed
carefully. Your APC representative will assist you, if required, in obtaining proper
disposition of an initial delivery return issue; however, a valid RMA number must be
obtained before returning any equipment to APC.
2MX28B
Page 7
2. CUSTOMER SERVICE AND SUPPORT
APC manufactures a line power plants and provides customers with complete product and
systems support and service. APC has an international network of factory trained service
technicians. The service organization is on call 24 hours a day, 365 days a year.
If there is a problem with the power system, contact APC at
(800) 727-8695
Units returned for repair can be turned around within 24 to 48 hours of receipt at the
factory location. Shipment should be sent pre-paid. The unit will be returned prepaid provided it was received that way.
An RMA must be obtained for all equipment returned to APC. It is important that correct
procedures be followed in filing an RMA, including providing an accurate written description
of the problem. An accurate written problem description will help ensure that the unit will be
properly repaired.
If a unit is returned and a “No Fault Found” results, APC reserves the right to bill the
customer for labor and assess a service charge to cover extra costs incurred.
MX28B3
Page 8
3. WARRANTY PROVISIONS
3.1 General Provisions
APC warrants the power equipment and components it manufactures or sells against
defective materials and workmanship for a period of TWO (2) YEARS from the date of
shipment.
3.1.1 Warranty Returns
If initial physical inspection results in identification of a material or workmanship flaw(s) that
could impair product performance as defined by Advance Power’s electrical and physical
specification in effect at the time of shipment, and if this flaw(s) is not due to transportation
damage or installation abuse, contact Advance Power, Inc. or call the 24-hour emergency
number, (800) 727-8695, to request assistance.
You will be provided either a) an RMA number with instructions for return of the equipment
or component(s) to the Advance Power, Inc. factory service center, FOB destination, freight
pre-paid, for examination, or b) for non-returnable systems and equipment, notice to wait
until an Advance Power, Inc. authorized service representative arrives at the site to inspect
the equipment. Repaired or advance replacement modules or circuit components will
normally be available within 24 to 48 hours of receipt of equipment or RMA.
3.1.2 Warranty Repair or Replacement
If, during the warranty period, the supplied equipment is found to be physically or electrically
faulty due to defective materials or workmanship on the part of Advance Power, Inc., the
defective product(s) or component(s) will be repaired or replaced at the sole option of
Advance Power, Inc. without charge to the user for replacement materials or repair labor.
(The procedure outlined above for contacting Advance Power, Inc. must be followed.)
Costs incurred for replacement installation including, but not limited to, installation
equipment, travel expenses of an Advance Power, Inc. representative(s), and costs of
installation material transportation expenses are not the responsibility of Advance Power,
Inc. Any replacement product(s) or component(s) shall only complete the remaining unused
portion of the original warranty of the replaced product(s) or component(s).
3.2 Exclusions and Limitations
1. This warranty applies only to the original US domestic purchaser (user) and is not
transferable internationally, except with expressed written consent from Advance
Power, Inc. headquarters in Dallas, Texas.
2. Advance Power, Inc. reserves the right to void the warranty if identification marks or
serial numbers have been removed or tampered with, or the defect is determined to
have been caused by misuse, neglect, improper installation, environmental
conditions, non-authorized repair, alteration, or accident.
3. This warranty does not cover physical damage due to the acts of nature or man
that stress the equipment or component(s) beyond design limits and exert
undesirable influence aside from normal wear and tear.
4MX28B
Page 9
4. Advance Power, Inc. assumes no responsibility for any work accomplished or
expenses incurred except with expressed written consent from Advance Power,
Inc.
5. Advance Power, Inc. shall not be liable to the user (purchaser) or any third party for
indirect, incidental, or consequential damages such as, but not limited to, loss of
use, loss of profits, costs associated with removal/installation of a defective
product(s) or component(s) arising out of the sale or relating to the use of this
product, and the user (purchaser) assumes responsibility for all personal injury and
property damage resulting from the handling, possession, or use of the product. In
no event shall the liability of Advance Power, Inc. for any and all claims, including
claims of breach of warranty or negligence, exceed the purchase price of the
product that gave rise to the claim.
The above warranty is in lieu of all other remedies, including actions for contract or
negligence.
All other warranties, expressed or implied, including but not limited to the implied
warranties of merchantability and fitness for a particular purpose, are hereby
excluded.
MX28B5
Page 10
4. PRODUCT OVERVIEW AND TECHNICAL DESCRIPTION
4.1 Description
The Advance Power, Inc. Model MX28B is a modular stand-alone -48V dc power plant. It is
configurable in such a manner that it will support most typical applications within the
specified current ranges (either 200 or 400 amperes) without special application
engineering or assistance. Distribution is included for up to 24 plug-in circuit breakers.
These circuit breakers can be 1 to 100 amps, with 60-100 amp breakers requiring two
positions and a circuit breaker adapter kit. An optional low voltage disconnect (LVD) can be
provided on either the battery or the load side. A 400 amp MX28B is shown in Figure
4.1-1. A block diagram is shown in Figure 4.1–2.
Figure 4.1-1. 400 Amp MX28B
6MX28B
Page 11
Figure 4.1-2. MX28B BLOCK DIAGRAM
MX28B7
Page 12
4.2 Power Output Capacity
The power plant has two basic configurations:
The first supplies a maximum of 200 amps or 150 amps with N+1 redundancy. The housing
for this configuration provides space for one rectifier shelf that can hold up to four rectifiers,
a control unit, and one tier of up to 24 distribution circuit breakers.
The second supplies a maximum of 400 amps or 350 amps with N+1 redundancy. The
housing for this configuration provides space for two rectifier shelves that can hold up to
four rectifiers each, a control unit, and one tier of up to 24 distribution circuit breakers.
The difference between the 200 and 400 amp units are the side plates and an additional
rectifier shelf; all other parts are the same for both configurations.
4.3 Rectifiers
The rectifiers are Advance Power, Inc. Model MRF28H54BV with specifications as follows:
• Input Voltage:176-264V ac (230V ac nominal) @ 45-66 Hz
• Input Current per Rectifier:13.9 Amps @ 230V ac
• Apparent Power Factor:99% Typical, 98% Minimum
• Output Voltage:54.5V dc
• Overvoltage Protection:Set at 59.5V dc
• Output Current per Rectifier:50 Amps Minimum Continuous
• Power Output per Rectifier:2800W Continuous, Vin > 198V ac
• Efficiency:91% Typical
• Cooling:Fan cooled, front to rear airflow
• Ambient Temperature:-25°C to 65°C Operational
4.4 Control Unit
The microprocessor-based power system control unit is 1U high (1.75”) and provides
control and monitoring functions. Features implemented are:
• 32-character alphanumeric display
• LED alarm and status indicators
• Standard voltage and battery charging control
• Battery temperature compensation (optional)
• Monitoring of up to two shelves of four rectifiers each
• Individual alarm monitoring of 24 breakers
• Eight alarm / annunciation relays (Major, Minor, and six user defined) with form C
contact outputs
• Four external alarm inputs (either N.O. or N.C. contacts)
8MX28B
Page 13
• Control of either a battery or a load LVD
4.5 AC Input Power
Each rectifier requires 208/220/240V ac, single-phase, 50/60 Hz, supplied through an
external 20-amp two-pole breaker. A rear located enclosure, with two holes for customersupplied one-inch conduit entry, provides a terminal strip(s) for ac input power connection
and a separate “Earth Ground” bar for connection of the safety ground wire(s).
4.6 Battery connections
Top entry battery connections are made at the top rear of the unit (see Figure 4.6-1). The
-48V and return buses each provide two sets of threaded 3/8”-16 holes on one-inch centers
for connecting two-hole battery cable lugs.
A battery disconnect breaker is required external to this equipment. The power plant can
monitor auxiliary contacts from this breaker.
Battery temperature compensation is available. Advance Power’s standard temperature
monitor sensor and cable is used to implement this optional function.
Figure 4.6-1. Battery Cable Connection Locations
MX28B9
Page 14
4.7 DC Distribution
A standard 24-position plug-in circuit breaker tier provides -48V distribution. The breaker
tier is connected at its center to the -48V dc bus, and each side has an ampacity of 300A.
Connections for -48V dc loads, requiring standard #10-32 two-hole lugs on 5/8-inch centers,
are located directly above the corresponding breaker. The load returns connect to the
return bus, which accommodates 24 two-hole #10-32 lugs on 5/8-inch centers, and four
two-hole ¼”-20 lugs on ¾-inch centers. The return bus also provides a pair of threaded
3/8”-16 holes on 1-inch centers for connection of a cable to the master station ground.
Figure 4.7-1 shows the power plant’s dc distribution section with the front cover removed.
Eight GMT fused outputs are also available as an option. This option uses one of the 24
available circuit breaker positions.
Figure 4.7-1. DC Distribution (Front Cover Removed)
4.8 Mounting
Both front mounting on standard 2-inch rails and optional wall mounting are available.
4.9 Environmental
Ambient Temperature:-20°C to +65°C operating
-40°C to +85°C storage
Humidity:0% to 85% RH non-condensing operating
0% to 95% RH non-condensing storage
Altitude:Up to 3000m, operating
Up to 10,000m, storage
10MX28B
Page 15
4.10 Mechanical
Dimensions:15.75” high x 23” wide x 17.5” deep (200 amp unit)
Weight:Housing - 85 lbs. (200A); 110 lbs. (400A)
Color:Dawn Gray (fronts)
4.11 Compliance
UL 1950
FCC Part 15, Class A
22.75” high x 23” wide x 17.5” deep (400 amp unit)
Rectifier - 11 lbs.
MX28B11
Page 16
5. INSTALLATION PROCEDURES
5.1 Preparation
5.1.1 Recommended Tools
• Standard selection of insulated hand tools.
• Proper tools for crimping the selected cable lugs.
5.1.2 Recommended Test Equipment
• Digital Multimeter
5.1.3 Equipment Inspection
Remove equipment from packing material and inspect for shipping damage to verify the
safety and operational suitability for the installation site. [Refer to Section 1.3]
5.1.4 Safety Precautions
***** WARNING *****
The MX28B dc power plant is supplied from a nominal 220V ac, 60 Hz source. Keep
the ac input enclosure cover in place when the system is operational or energized.
***** WARNING *****
Hazardous energy levels are present on bare conductors in the -48V dc distribution
connection area of the plant. Accidental shorting of distribution conductors can
cause arcing and high currents that can cause serious burns or other physical harm.
It is recommended that:
• Any jewelry, rings or watches be removed while working on this equipment.
• Handles of all wrenches, screwdrivers, cutters and pliers be insulated.
• Shafts of screwdrivers be wrapped in electrical tape or otherwise insulated.
5.1.5 Room/Locations
NOTE: The Advance Power, Inc. Model MX28B dc power plant is to be installed in a
room, vault, or similar enclosure that is accessible only to qualified persons in
accordance with the NEC or the authority having jurisdiction.
Prior to installation, drawings, floor loading requirements, external alarm points, ac service
entrance, and grounding schemes should all be checked and confirmed. If batteries are to
be mounted in a room separate from the power plant, careful attention should be paid to
battery cable voltage drop effects. Environmental operating temperatures and
ventilation/cooling considerations should also be noted, not just for the power system but for
all other equipment that may reside in the power room area.
12MX28B
Page 17
5.1.6 Mounting
Both front mounting on standard 23-inch rails and optional wall mounting are available.
5.1.7 Ventilation
The rectifiers have fans that provide front to rear airflow for internal cooling. The MX28B
housing should mounted such that there is free airflow to the front, top, and bottom of the
unit. [Refer to Section 4.9 for environmental characteristics.]
5.2 AC Service and Ground Connections
***** WARNING *****
Ensure that all of the dc and external ac circuit breakers are in the OFF position prior
to connecting service to the power plant. Confirm that all voltages have been
removed including any battery sources before proceeding.
The MX28B dc power plant requires the supply of 208/220/240V ac, single-phase, 50/60 Hz
power through individual external 20-amp two-pole circuit breakers to the ac input terminal
block connections for each rectifier in the system. (The ac wiring, from the ac input terminal
block connections to the hot-pluggable ac input connector for each rectifier, is factory
installed.)
The ac input enclosure, located at the top right rear of the MX28B housing, is provided with
two one-inch conduit entry holes and an access cover. Inside, a terminal strip(s) for ac
input power connection and a separate “Earth Ground” bar for connection of the safety
ground wire(s) are provided. The terminal block(s) is labeled as Position 1 through Position
4 (Position 1 through Position 8 for the 400-amp unit) with each position having inputs
designated “L1” and “L2” for connection of the two ac wires. Positions 1-4 correspond to
the top rectifier shelf positions from left to right. Positions 5-8 are applicable to the 400-amp
unit only and correspond to the lower rectifier shelf positions from left to right.
The suggested wire size is #10 AWG rated at 90°C or higher; however, the ambient
temperature and number of wires in a conduit must also be considered in accordance with
NEC requirements. It is suggested that feeds for four rectifiers (8 wires) and one safety
ground wire be run in a one-inch conduit; however, be sure to follow any local electrical
wiring codes.
If the ac input power is provided from a three-phase distribution panel, the circuit breaker
positions should be selected such that the load is balanced as much as possible.
5.3 Battery Connections
5.3.1 Battery Disconnect
An external circuit breaker (not supplied) is required in the negative line (located at the
battery end) to protect the cables from the battery to the MX28B dc power plant. The power
plant can monitor auxiliary contacts from this breaker.
5.3.2 Cable Sizing Considerations
The battery cable(s) should be sized sufficiently large to limit the voltage drop from the
MX28B dc power plant to the battery during charging per system design requirements. The
MX28B13
Page 18
cable(s) must also carry the full load current during battery operation. If assistance is
required to determine the necessary cables for the application, contact your sales
representative or Advance Power, Inc.
5.3.3 Connecting the Cables
The battery cable connections are located at the top rear of the unit as shown in Figure
4.6-1. The battery positive (return bus) and battery negative (-48V bus) buses each provide
two sets of threaded 3/8”-16 holes on one-inch centers for connecting two-hole battery
cable lugs. Connect the battery cables as applicable using 3/8”-16 bolts (not provided) and
tighten them with a torque wrench to 200 in-lbs.
***** CAUTION *****
Make certain that the battery polarity is correct when making connections to the
Model MX28B dc power plant. Incorrect connection could cause severe equipment
damage.
5.4 DC SYSTEM GROUNDING
THE POSITIVE BATTERY CONNECTION (RETURN BUS) FOR THE POWER PLANT
MUST BE CONNECTED TO THE MASTER STATION GROUND. THE LEFT END OF
THE RETURN BUS PROVIDES A PAIR OF THREADED 3/8”-16 HOLES ON 1-INCH
CENTERS FOR CONNECTION OF A TWO-HOLE LUGGED CABLE TO THE MASTER
STATION GROUND. DETAILS FOR THIS CONNECTION SHOULD BE PROVIDED IN
THE SITE ELECTRICAL GROUNDING PLAN.
5.5 Rectifier Installation
The Advance Power, Inc. Model MRF28H54BV rectifiers are shipped in separate
containers. Follow the procedure below to install a rectifier.
1) Remove the rectifier from its shipping container.
2) Remove the rectifier retaining screw from the shelf position where the rectifier is to
be installed.
3) Slide the rectifier into the shelf between the guides until it is fully seated.
4) Fasten the rectifier in place with the rectifier retaining screw.
Since all adjustments are made from the system control unit, no rectifier adjustments are
necessary.
5.6 Alarm Connections
The alarm connections for all rectifiers, breakers, and fuses are factory pre-wired. The
MX28B dc power plant, however, permits the user to program the system alarms in various
ways.
5.6.1 External Alarm Inputs
Four external alarm inputs with assignable priority levels are available. These alarm inputs
respond to external dry contact closures between normally open (NO) and common (C) or
contact openings between normally closed (NC) and C (see Table 5.6-1).
14MX28B
Page 19
External Alarm Source
(non-alarm state)
Connect To Input
Alarm Terminals
OPEN
CLOSED
NO-C
NC-C
Table 5.6-1. External Alarm Input Definition
Table 5.6-2 shows the external alarm input connection designations. Connector J4 is
located on the interface card mounted in the top left side of the unit. Systems are shipped
with jumper wires connecting each NC and corresponding C contact. A jumper wire should
be removed only if the corresponding NC-C contacts are going to be used.
EXTERNAL
ALARM
INPUT
#1
#2
#3
#4
J4 TERMINAL
DESIGNATION
(NO-NC-C)
NO1-NC1-C1
NO2-NC2-C2
NO3-NC3-C3
NO4-NC4-C4
USER ALARM NOTES
__________________________
_
__________________________
_
__________________________
_
__________________________
_
Table 5.6-2. External Alarm Input Connections
5.6.2 Alarm Outputs
There are eight alarms available that provide outputs via Form “C” relay contacts. The last
two of these are preassigned as the Minor and Major alarm outputs. The Major relay is
energized (NO-C contacts closed) during normal (non-alarm) operating conditions; all the
other relays energize when an alarm condition occurs. The other six outputs are initially
designated as “Relay 1” through “Relay 6” (the user may assign more meaningful names if
desired). The various system alarm conditions can be assigned to any of the eight alarm
outputs.
Table 5.6-3 shows the alarm output connection designations. Connectors J1 and J2 are
located on the interface card mounted in the top left side of the unit. The relay contacts
should only be used to switch resistive loads of 0.5 amperes or less at 60 volts or less.
MX28B15
Page 20
ALARM
OUTPUT
TERMINAL
DESIGNATION
NO-NC-C
J1
USER ALARM NOTES
RELAY #1
RELAY #2
RELAY #3
RELAY #4
RELAY #5
RELAY #6
MINOR
MAJOR
Table 5.6-3. Alarm Output Connections
5.7 Connecting The Loads
NO1-NC1-C1
NO2-NC2-C2
NO3-NC3-C3
NO4-NC4-C4
J2
NO5-NC5-C5
NO6-NC6-C6
NO7-NC7-C7
NO8-NC8-C8
_______________________
_
_______________________
_
_______________________
_
_______________________
_
_______________________
_
_______________________
_
_______________________
_
_______________________
_
5.7.1 DC Circuit Breakers and Fuses
Both plug-in circuit breakers and GMT fuses can be installed in the MX28B power plant for
dc distribution circuit protection. Available plug-in circuit breakers are shown in Table 5.7-1.
Plug-in circuit breakers rated at 60A or more require two mounting positions and require a
breaker adapter kit, which is included (see kit selection information below the table). The
breaker adapter kit includes all necessary mounting hardware.
*-1: adapter has #10 studs on 5/8” centers for two-hole cable lug
-2: adapter has #10 studs on ¾” centers for two-hole cable lug
-3: adapter has ¼” studs on 1” centers for two-hole cable lug
Table 5.7-1. Plug-in Circuit Breakers
A list of GMT type fuses available from Advance Power, Inc. is provided in Table 5.7-2.
FUSE RATINGPART NUMBER
1/4 AFFA-0030
1/2 AFFA-0031
3/4 AFFA-0032
1 AFFA-0033
1¼ AFFA-0039
1½ AFFA-0035
3 AFFA-0036
5 AFFA-0037
10 AFFA-0038
Table 5.7-2. GMT Fuses
5.7.2 Installation of Circuit Breakers and Fuses
5.7.2.1 Plug-in Circuit Breakers
1) Remove the circuit breaker cover panel and the plastic cover(s) from the desired
location(s).
2) Install the circuit breaker(s) by snapping the top terminal onto the upper bus bar
and rotating the unit down until the second terminal snaps onto the breaker
termination post as shown in Figure 5.7-1. The breaker alarm terminals are
designed to make contact with the alarm terminal board as the breaker is snapped
into place.
MX28B17
Page 22
NOTE: Circuit breaker alarm contacts close when the circuit breaker is tripped
but not when it is turned OFF.
***** CAUTION *****
During circuit breaker installation, carefully align the breaker alarm terminals with the alarm
terminal board to avoid breaker terminal damage.
3) Reattach the circuit breaker cover panel.
Figure 5.7-1. Installation of Circuit Breakers
5.7.2.2 GMT Fuses
Fuseholders that accommodate GMT fuses are located on the interface card mounted in the
top left side of the unit. These fuseholders are only connected to -48V dc if the system has
been purchased with the GMT fuse option. This option supplies -48V dc to the fuseholders
through a 50 A. circuit breaker located in circuit breaker Position 1. The interface card
provides fuseholders for eight fuses, labeled “F1” through “F8”, which can be used for small
-48V dc loads. The maximum fuse size that should be used is 10A.
5.7.3 Load Connections
5.7.3.1 Circuit Breakers
Connections for -48V dc loads require standard two-hole lugs for #10 screws on 5/8”
centers and are located directly above the corresponding circuit breaker. The load returns
connect to the return bus located just above and rearward of the breaker connection points
18MX28B
Page 23
as seen in Figure 5.7-1. The return bus provides 24 sets of threaded #10-32 holes on 5/8”
centers and four sets of threaded ¼”-20 holes on ¾” centers for connection of two-hole lugs
on load return wires.
5.7.3.2 GMT Fuses
Connections to the GMT fuses are made at terminal block connectors labeled “F1” through
“F8” that are located on the interface card mounted in the top left side of the unit. Each
connector has two positions, labeled “-48V” and “RTN”, for connection of the -48V dc load
and load return wires.
5.8 Battery Temperature Probe Installation
The optional temperature probe is used to monitor the battery string temperature. To get
the most representative temperature measurement, the probe should be placed in contact
with a battery cell that is centrally located. The probe should be placed directly in contact
with the cell (not the frame surrounding the cell). Generally, the cell cover can be used; be
careful not to allow the probe body to touch the terminals.
1) Plug the connector end of the temperature probe into J5 the control unit backplane
card.
2) Route the cable as required to position the probe on the selected battery cell
3) Remove the adhesive protection strip from the probe body and press the adhesive
side of the probe on the battery cell cover.
5.9 Power-Up and Checkout
Before initiating power-up and checkout, ensure that the following conditions exist:
1) Make sure that the external circuit breaker protecting the cables from the battery to
the power plant is turned OFF (the battery cables should be connected to the
power plant, but the battery should not be connected).
2) Make sure that all load circuit breakers are turned OFF (including the one feeding
the GMT fuses if the unit has the GMT fuse option).
3) Verify that all rectifiers have been installed.
5.9.1 Apply AC Power
Turn on the circuit breakers that supply ac power to the rectifiers in the MX28B dc power
plant. The main screen should appear on the control unit display (see Figure 5.9-1). The
display on the control unit is a 2-lines by 16-characters display. The cursor cycles below
the characters of the active selection on the display. Information shown in the second line
of Figure 5.9-1 that extends beyond 16 characters (to the right of the “S” in “ALARMS”) can
viewed on the control unit display by using the scrolling controls (refer to Section 6 for
operation of the control unit).
NOTE: When ac power is initially applied, there is a 60-second period during which no
alarms are reported.
MX28B19
Page 24
MX28B +
STATUS ALARMS SYSTEM MODULES BATT PIN OEM
Figure 5.9-1
5.9.2 System Parameters Verification/Adjustment
The MX28B system control unit is delivered with pre-programmed parameter default
settings. A complete listing and description of all system configuration parameters as well
as displayable system status and information is provided in Section 6. Read Section 6 to
gain an understanding of and how to use the operational features provided by the MX28B
dc power plant. As a minimum, the following parameters should be verified and adjusted, if
required, before connecting batteries or loads to the power plant:
1) Battery Float Voltage - default = -54.00V dc (Check the manufacturer’s
recommendation for the batteries being used in the system.)
2) Battery Maximum Recharge Rate - default = 12A. (Bellcore specifications
recommend a maximum charging rate of capacity (in Ampere-hours) divided by 20
hours; check the manufacturer’s recommendation.)
3) System Voltage - measurement ≅ -54.00V dc (This is a measurement by the
system of the dc output bus voltage.)
4) LVD Option - default = “Enable” (If the MX28B does not have an LVD installed,
this should be changed to “Disable”.)
5) Rectifier Information - Check the rectifier information displays to verify that all
rectifiers installed can be viewed on the control unit display and that no rectifier
alarms are active.
Section 6 provides location information for these parameters and how to make changes if
required.
5.9.3 Full System Power Up
To complete a full system power up, perform the following steps
1) Turn OFF all the circuit breakers that supply ac power to the rectifiers in the MX28B
dc power plant.
2) Turn on the external circuit breaker from the battery to the power plant.
3) Turn on all the circuit breakers that supply ac power to the rectifiers in the MX28B
dc power plant.
4) Load circuit breakers may now be turned on as required.
20MX28B
Page 25
6. SETUP, ADJUSTMENTS, AND OPERATION
6.1 User Interface
The MX28B control unit provides a user interface designed with a hierarchical menu that
can be viewed on the 32-character display by “navigating” with the “ï” (left), “ð” (right), “ñ”
(up), and “ò” (down) arrow keys located on the front panel. The selected item on the
display is identified by the cursor cycling beneath its characters.
The “M” (modify) key and the arrow keys are used to set parameters and text to customize
the system operation for a specific application. Items that can be modified have "m+" in the
upper right corner of the display. (If a security level higher than the one presently set is
required to modify the parameter, "s+" is displayed instead of “m+”.) Status, alarms, and
information screens have "+" in the upper right corner of the display (or “#” in the case of
rectifier information screens) and can not be modified. When ac power is initially applied,
there is a 60-second period during which no alarms are reported.
Pressing the "M" key on the front panel will change the "m+" to "M+", indicating that the
parameter can now be changed using the arrow keys. Some parameters can be changed
to other predefined selections by pressing the up or down arrow keys to display an
alternative selection. These parameters can be recognized after the “M” key is pressed by
the cursor cycling beneath the characters of the selection. For other parameters, such as
text and most numeric values, after the “M” key is pressed the cursor will be displayed
under an individual character. The right or left arrow key is used to position the cursor
below the character to be changed and the up or down arrow key is used to "spin" the digit
or letter to the desired value. When the desired changes have been made to an individual
parameter screen, the “M” key is pressed again; the “M+” changes back to “m+” and the
new entry is stored in memory.
If the user plans to make any changes to system parameters, the first item that should be
verified or entered is the appropriate password for the security level required for the
parameters to be modified. Security level 2 enables modification of all variable system
parameters, level 1 permits modification of some parameters; no security is required for
viewing status items. The security level password is entered through the “PIN” screen. If
no front panel keys are pressed for 60 minutes, the active password reverts to “0000” and
“ADVANCE” begins to move about the display. Pressing any key returns the display to
normal; the password must be re-entered if system parameters require changes.
Eleven LEDs are provided on the front panel of the control unit to indicate system status.
Three LEDs grouped together vertically provide overall system status; they are “MAJOR”,
“MINOR”, and “NORMAL”, indicating the presence of a major alarm, a minor alarm, or
normal operation. The other eight LEDs correspond to the active state of each of the alarm
output relays and are labeled “ALM1”···“ALM6”, “MIN”, and “MAJ”.
6.2 External Alarm Inputs
The four external alarm inputs (also referred to as “Input Relay Alarms”) can be assigned a
priority and routed or “mapped” to alarm output relays. Available assignments are “Ignore”,
“Major”, “Minor”, and “Relay 1” ··· “Relay 6”. Screens for making the assignments are
located at [SYSTEM/IN-RLY/RLY-MAP]. A user defined name or “alias” may also be
assigned to each of these input alarms. Screens for making these assignments are located
at [SYSTEM/IN-RLY/ALIAS]. For information on wiring connections to these inputs refer to
Section 5.6.1.
MX28B21
Page 26
6.3 Alarm Output Relays
There are eight alarm output relays designated Relay 1 through Relay 6, Minor, and Major,
respectively. Various system parameters may be programmed to activate any of these
alarm relays when set thresholds are exceeded or specific conditions occur. The first six
relays can also be assigned a priority and routed or “mapped” to other output alarm relays.
Available assignments are “Ignore”, “Major”, “Minor”, and “Relay 1” ··· “Relay 6”. Screens
for making these assignments are located at [SYSTEM/OUT-RLY/RLY-MAP]. This feature
makes it possible for a single alarm condition to activate multiple alarm output relays
including the Minor or Major alarm relay. A user defined name or “alias” may also be
assigned to each of the eight output relay alarms. Screens for making these assignments
are located at [SYSTEM/OUT-RLY/ALIAS]. For information on making wiring connections
to the alarm output relays refer to Section 5.6.2.
6.4 Parameter Locations, Descriptions, and Default Values
The location, description, and factory programmed default value for each of the MX28B
system parameters is found in Table 6.4.1. The table also shows all of the status and
information screens with typical displays. The location of a parameter screen is shown in
brackets, for example: [SYSTEM/IN-RLY/RLY-MAP]. To find the parameters that can be
accessed in this category, starting from the main menu screen, do the following:
1) Use the right or left arrow keys to position the cycling cursor below “SYSTEM”.
2) Press the down arrow key once.
3) Use the right arrow key to position the cycling cursor below “IN-RLY”.
4) Press the down arrow key once; the cursor will be cycling below “RLY-MAP”.
5) Press the down arrow key (repeatedly if necessary) until the desired parameter
screen is displayed (there are eight parameter screens in this category).
6) After making any desired changes (refer to Section 6.1 for the procedure), to return
to the main menu press the up arrow key repeatedly.
If a parameter requires a level 1 or level 2 security access to permit changes to it, the
security level will be found in braces, i.e. {2}, in the “PARAMETER” column of Table 6.4.1.
The complete menu structure shown in the order in which it is accessed from the control
unit display is presented in outline form in Figure 6.4-1. Each indentation to the right
represents a menu level below the indicated title.
22MX28B
Page 27
Table 6.4-1. Parameter Locations, Descriptions, and Default Values
Voltage offset adjustment for factory calibration of
voltage readings/settings.
Voltage gain adjustment for factory calibration of
voltage readings/settings.
Current offset adjustment for factory calibration of
battery current readings/settings.
Current gain adjustment for factory calibration of
battery current readings/settings.
PIN m+
0000
PIN 1 m+
1111
PIN 2 m+
2222
OEM R Offset m+
0.000 V
OEM R Gain m+
1.000 V
OEM S Offset m+
0.0 A
OEM S Gain m+
1.000 A
Address 1 {1}
[SYSTEM/SETUP]
Address 2 {1}
[SYSTEM/SETUP]
Address 3 {1}
[SYSTEM/SETUP]
Control Unit Setup & Info.
Model Type {2}
[SYSTEM/SETUP]
Temperature Scale {1}
[SYSTEM/SETUP]
Control Unit Revision
[SYSTEM/SETUP]
Firmware Version
[SYSTEM/SETUP]
Power plant address or identification - first line.
Power plant address or identification - second line.
Power plant address or identification - third line.
Model type number for the MX28B dc power plant
NOTE: Changing the model number causes the
system to reinitialize.
Enables selection of Fahrenheit or Celsius temperature
scale (Fahrenheit “OFF” displays readings in °C).
Hardware revision level of the control unit.
Version number of the control unit firmware.
NOTE: Actual firmware version number displayed
is the current version as of the date of
manufacture.
Address 1 m+
Advance, Inc.
Address 2 m+
11035 Switzer Av
Address 3 m+
Dallas, TX.
Model m+
0001
Fahrenheit m+
OFF
Cntrl Rev +
000002
FW Version +
000131
MX28B23
Page 28
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETERDESCRIPTIONDISPLAY SCREENS /
DEFAULT SETTINGS
Display Type
[SYSTEM/SETUP]
Date/Time Setup
Type number for the control unit display.
Display Type +
000255
Date {1}
[SYSTEM/DATE]
Time {1}
[SYSTEM/DATE]
Alarm Threshold Setup
High Voltage Threshold {1}
[SYSTEM/SET-ALM]
Low Voltage Threshold {1}
[SYSTEM/SET-ALM]
High Temperature Threshold {1}
[SYSTEM/SET-ALM]
Low Temperature Threshold {1}
[SYSTEM/SET-ALM]
System Status
System Voltage
[STATUS]
System Current
[STATUS]
Internal system calendar date.
Internal system clock time (24-hour format).
System High voltage alarm threshold.
System Low voltage alarm threshold.
Over temperature alarm threshold.
Under temperature alarm threshold.
System output voltage measured between the MX28B
dc power plant -48V and return buses.
The total system output current (calculated as the sum
of the individual rectifier output currents).
Date m+
DEC 16 1999
Time m+
9:00:25
Sys HV Thr m+
-58.00 V
Sys LV Thr m+
-50.00 V
Sys HT Thr m+
70.0 C
Sys LT Thr m+
0.0 C
Sys Voltage +
-54.00 V
Sys Current +
145.8 A
System Temperature
[STATUS]
Battery Current
[STATUS]
Battery Temperature
[STATUS]
System Alarms
System High Voltage {1}
[SYSTEM/SET-ALM]
System Low Voltage {1}
[SYSTEM/SET-ALM]
System High Temperature {1}
[SYSTEM/SET-ALM]
System temperature measured within the control unit.
Battery current measured at the current shunt.
Battery temperature measured by the optional battery
temperature sensor probe.
System voltage is above the high voltage threshold.
System voltage is below the low-voltage threshold.
The control unit temperature is above the high
temperature threshold.
Sys Temp +
26.7 C
Batt Current +
-15.0 A
Batt Temp +
25.2 C
Sys HV Alm m+
Minor
Sys LV Alm m+
Minor
Sys HT Alm m+
Minor
24MX28B
Page 29
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETERDESCRIPTIONDISPLAY SCREENS /
DEFAULT SETTINGS
System Low Temperature {1}
[SYSTEM/SET-ALM]
The control unit temperature is below the low
temperature threshold.
Sys LT Alm m+
Minor
Rectifier Configuration {1}
[SYSTEM/SET-ALM]
Rectifier Fail 1-of-N {1}
[SYSTEM/SET-ALM]
Rectifier Fail 2-of-N {1}
[SYSTEM/SET-ALM]
Hardware System Voltage {2}
[SYSTEM/SET-ALM]
Hardware Battery Current {2}
[SYSTEM/SET-ALM]
Hardware Battery Temperature {2}
[SYSTEM/SET-ALM]
Hardware System Temperature
{2}
[SYSTEM/SET-ALM]
Hardware LVD {2}
[SYSTEM/SET-ALM]
SYSTEM ALARMS DISPLAY
Alarms Item 1
[ALARMS]
The rectifier configuration differs from its stored
configuration.
Rectifier Fail 1-of-N alarm - one rectifier has at least
one alarm condition.
Rectifier Fail 2-of-N alarm – two or more rectifiers have
at least one alarm condition each.
This alarm indicates there is a hardware failure in the
system voltage monitoring function.
This alarm indicates there is a hardware failure in the
battery current monitoring function.
This alarm indicates there is a hardware failure in the
battery temperature monitoring function.
This alarm indicates there is a hardware failure in the
system temperature monitoring function.
This alarm indicates there is a conflict between the
commanded and sensed positions of the LVD.
Display of up to 16 active alarms (a typical alarm
screen is shown).
Rect Cfg Alm m+
Minor
Rect 1ofN Alm m+
Minor
Rect 2ofN Alm m+
Major
Hw Sys V Alm m+
Minor
Hw Batt C Alm m+
Minor
Hw Batt T Alm m+
Minor
Hw Sys T Alm m+
Minor
Hw LVD Alm m+
Minor
Alarm Item 1 +
Batt LV Alm On m
•
•
•
Alarms Item 16
[ALARMS]
SYSTEM DIAGNOSTICS
Store Configuration {1}
[SYSTEM/DIAG]
Lamp Test {1}
[SYSTEM/DIAG]
Test Relay Enable {1}
[SYSTEM/DIAG]
Test Relay 1 {1}
[SYSTEM/DIAG]
Display of up to 16 active alarms (a typical alarm
screen is shown).
Setting this parameter to “Enable” will cause the current
rectifier configuration to be stored (the display toggles
back to “Disable” after entry).
Setting Lamp Test to “ON” will turn on the “MAJOR”,
“MINOR”, “NORMAL”, “MAJ”, and “MIN” LEDs on the
control unit front panel.
This parameter must be set to “Enable” to permit the
eight output relays to be manually tested; otherwise,
the state of the relays will be per system conditions.
Setting this parameter to “ON” energizes Relay 1 and
turns on the “ALM1” LED on the control unit front panel.
•
•
•
•
•
•
Alarm Item 16 +
Store Cfg m+
Disable
Lamp Test m+
OFF
Test Relay En m+
Disable
Test Relay 1 m+
OFF
MX28B25
Page 30
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETERDESCRIPTIONDISPLAY SCREENS /
DEFAULT SETTINGS
•
•
•
Test Relay 6 {1}
[SYSTEM/DIAG]
Test Minor Relay {1}
[SYSTEM/DIAG]
Test Major Relay {1}
[SYSTEM/DIAG]
BATTERY SETUP
Float Voltage {1}
[BATT/PARAM]
Maximum Recharge Current {1}
[BATT/PARAM]
Compensation Method {1}
[BATT/COMP]
Temperature Compensation {1}
[BATT/COMP]
Compensation High Knee {1}
[BATT/COMP]
Compensation Low Knee {1}
[BATT/COMP]
Discharge Threshold {1}
[BATT/SET-ALM]
High Voltage Threshold {1}
[BATT/SET-ALM]
Low Voltage Threshold {1}
[BATT/SET-ALM]
High Temperature Threshold {1}
[BATT/SET-ALM]
Low Temperature Threshold {1}
[BATT/SET-ALM]
Battery Alarms
•
•
•
Setting this parameter to “ON” energizes Relay 6 and
turns on the “ALM6” LED on the control unit front panel.
Setting this parameter to “ON” energizes the Minor
Relay and turns on the “MIN” LED on the control unit
front panel.
Setting this parameter to “ON” de-energizes the Major
Relay and turns on the “MAJ” LED on the control unit
front panel.
Float voltage at 25°C battery temperature.
Maximum battery recharge current (the system limits
the charging current to this programmable value).
Activate “000001” or de-activate “000000” battery
temperature compensation.
Temperature compensation between low knee and high
knee in mV/cell/°C. (Compensation equals zero at
25°C.)
The temperature compensation high knee is the point
above which there is no additional battery voltage
compensation for further increases in temperature.
The temperature compensation low knee is the point
below which there is no additional battery voltage
compensation for further decreases in temperature.
An alarm is generated if the battery discharge current
exceeds this value.
An alarm is generated if the magnitude of the battery
voltage rises above this value.
An alarm is generated if the magnitude of the battery
voltage drops below this value.
An alarm is generated if the battery temperature
exceeds this value.
An alarm is generated if the battery temperature drops
below this value.
•
•
•
Test Relay 6 m+
OFF
Test Min Rly m+
OFF
Test Maj Rly m+
OFF
Batt Float m+
-54.00 V
Batt Max Rech m+
12 A
Comp Method m+
000000
Comp TC m+
- 3.00mV
Comp Hknee m+
40.0 C
Comp Lknee m+
0.0 C
Batt Disc Thr m+
10 A
Batt HV Thr m+
-58.00 V
Batt LV Thr m+
-44.00 V
Batt HT Thr m+
70.0 C
Batt LT Thr m+
0.0 C
Discharge Alarm {1}
[BATT/SET-ALM]
An alarm that is generated if the battery discharge
current exceeds the programmed battery discharge
threshold.
Batt Disc Alm m+
Minor
26MX28B
Page 31
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETERDESCRIPTIONDISPLAY SCREENS /
DEFAULT SETTINGS
High Voltage Alarm {1}
[BATT/SET-ALM]
An alarm that is generated if the magnitude of the
battery voltage rises above the high voltage threshold.
Batt HV Alm m+
Minor
Low Voltage Alarm {1}
[BATT/SET-ALM]
High Temperature Alarm {1}
[BATT/SET-ALM]
Low Temperature Alarm {1}
[BATT/SET-ALM]
RECTIFIER SETUP
Fail Safe Voltage {1}
[MODULES/RECT/PARAM]
Communications Timeout {1}
[MODULES/RECT/PARAM]
Rectifier InformationNOTE: This information can be viewed for each
Rectifier Description
[MODULES/RECT/INFO]
Rectifier Current
[MODULES/RECT/INFO]
Current Limit Alarm
[MODULES/RECT/INFO]
An alarm that is generated if the magnitude of the
battery voltage drops below the low voltage threshold.
An alarm that is generated if the battery temperature
exceeds the high temperature threshold.
An alarm that is generated if the battery temperature
drops below the low temperature threshold.
Rectifier default output voltage if communication with
the control unit fails.
The maximum rectifier communications response time
allowed before a communications failure is declared.
rectifier installed by using the horizontal arrow
keys.
Displays the model number of the installed rectifier.
A display of the dc output current for the individual
rectifier.
The status will be “ON” if the rectifier has been forced
into its current limited mode.
Batt LV Alm m+
Minor
Batt HT Alm m+
Minor
Batt LT Alm m+
Minor
Rect Fail Safem+
-54.00 V
Rect Fail Commm+
1 min
Rect 1 Desc #
MRF28H54
Rect 1 Curr #
24.9 A
Rect 1 CL #
OFF
Standby Alarm
[MODULES/RECT/INFO]
Fan Fail Alarm
[MODULES/RECT/INFO]
Rectifier Fault Alarm (RFA)
[MODULES/RECT/INFO]
Rectifier Alarms
Current Limit Alarm {1}
[MODULES/RECT/SET-ALM]
Standby Alarm {1}
[MODULES/RECT/SET-ALM]
Fan Fail Alarm {1}
[MODULES/RECT/SET-ALM]
The status will be “ON” if the control unit is holding the
rectifier in the standby mode.
The status will be “ON” if the rectifier fan has failed.
The status will be on if the rectifier output has failed.
This alarm indicates that a rectifier has been forced into
the current limited mode.
This alarm indicates that the control unit is holding a
rectifier in the standby mode.
This alarm indicates that a rectifier fan has failed.
Rect 1 Stdby #
OFF
Rect 1 FF #
OFF
Rect 1 RFA #
OFF
Rect CL Alm m+
n of N
Rect Stdby Almm+
n of N
Rect FF Alm m+
n of N
MX28B27
Page 32
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETERDESCRIPTIONDISPLAY SCREENS /
RFA Alarm {1}
[MODULES/RECT/SET-ALM]
CIRCUIT BREAKER SETUP
This alarm indicates that a rectifier output has failed.
DEFAULT SETTINGS
Rect RFA Alm m+
n of N
Breaker 1 Alias {1}
[MODULES/CIRBKR/ALIAS]
•
•
•
Breaker 24 Alias {1}
[MODULES/CIRBKR/ALIAS]
Circuit Breaker Alarms
Breaker 1 Tripped {1}
[MODULES/CIRBKR/SET-ALM]
•
•
•
Breaker 24 Tripped {1}
[MODULES/CIRBKR/SET-ALM]
GMT FUSE SETUP
GMT 1 Alias {1}
[MODULES/GMT/ALIAS]
An alternate name (alias) that can be assigned to a
circuit breaker if desired.
•
•
•
An alternate name (alias) that can be assigned to a
circuit breaker if desired.
An alarm that indicates Circuit Breaker 1 is tripped.
•
•
•
An alarm that indicates Circuit Breaker 24 is tripped.
An alternate name (alias) that can be assigned to a
GMT Fuse 1 if desired.
Cir Bkr 1 m+
-48V
•
•
•
Cir Bkr 24 m+
-48V
Cir Bkr 1 Alm m+
Major
•
•
•
Cir Bkr 24 Almm+
Major
GMT 1 +
-48V
•
•
•
GMT 8 Alias {1}
[MODULES/GMT/ALIAS]
GMT Fuse Alarms
GMT 1 Blown {1}
[MODULES/GMT/SET-ALM]
An alternate name (alias) that can be assigned to a
GMT Fuse 8 if desired.
An alarm that indicates GMT Fuse 1 is blown.
•
•
•
GMT 8 Blown {1}
[MODULES/GMT/SET-ALM]
28MX28B
An alarm that indicates GMT Fuse 8 is blown.
•
•
•
•
•
•
GMT 8 +
-48V
GMT 1 Alm m+
Major
•
•
•
•
•
•
GMT 8 Alm m+
Major
Page 33
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETERDESCRIPTIONDISPLAY SCREENS /
INPUT RELAY SETUP
DEFAULT SETTINGS
Input Relay 1 Alias {1}
[SYSTEM/IN-RLY/ALIAS]
•
•
•
Input Relay 4 Alias {1}
[SYSTEM/IN-RLY/ALIAS]
Input Relay Alarms
Input Relay 1 {1}
[SYSTEM/IN-RLY/RLY-MAP]
•
•
•
Input Relay 4 {1}
[SYSTEM/IN-RLY/RLY-MAP]
OUTPUT RELAY SETUP
Output Relay 1 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the relay
if desired.
•
•
•
An alternate name (alias) can be assigned to the relay
if desired.
An alarm activated in response to an external contact
closure or opening at the Input Relay 1 connection.
•
•
•
An alarm activated in response to an external contact
closure or opening at the Input Relay 4 connection.
An alternate name (alias) can be assigned to the relay
if desired.
In-Rly 1 m+
Input Relay 1
•
•
•
In-Rly 4 m+
Input Relay 4
In-Rly 1 Alm m+
Ignore
•
•
•
In-Rly 4 Alm m+
Ignore
Out-Rly 1 m+
Relay 1
•
•
•
Output Relay 6 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
Output Relay Minor Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
Output Relay Major Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
Output Relay 1 Delay {1}
[SYSTEM/OUT-RLY/RLY-MAP]
•
•
•
Output Relay 6 Delay {1}
[SYSTEM/OUT-RLY/RLY-MAP]
•
•
•
An alternate name (alias) can be assigned to the relay
if desired.
An alternate name (alias) can be assigned to the relay
if desired.
An alternate name (alias) can be assigned to the relay
if desired.
Delay between sensing of the alarm condition and
activation of the alarm relay. An alarm condition must
exist for longer than the delay to be activated.
•
•
•
Delay between sensing of the alarm condition and
activation of the alarm relay. An alarm condition must
exist for longer than the delay to be activated.
•
•
•
Out-Rly 6 m+
Relay 6
Relay Minor m+
Minor
Relay Major m+
Major
Out-Rly 1 Dly m+
0 sec
•
•
•
Out-Rly 6 Dly m+
0 sec
MX28B29
Page 34
(Table 6.4-1. Parameter Locations, Descriptions, and Default Values)
PARAMETERDESCRIPTIONDISPLAY SCREENS /
DEFAULT SETTINGS
Output Relay Alarms
Output Relay 1 {1}
[SYSTEM/OUT-RLY/RLY-MAP]
•
•
•
Output Relay 6 {1}
[SYSTEM/OUT-RLY/RLY-MAP]
LVD SETUP
LVD Trip {1}
[MODULES/LVD/PARAM]
LVD Restore {1}
[MODULES/LVD/PARAM]
LVD Option {1}
[MODULES/LVD/SET-ALM]
LVD Alarm
LVD Alarm {1}
[MODULES/LVD/SET-ALM]
Output Relay 1 alarm can be “mapped” to activate
other output relays (“Ignore” activates no additional
relays).
•
•
•
Output Relay 6 alarm can be “mapped” to activate
other output relays (“Ignore” activates no additional
relays).