APC MGETM GALAXYTM 6000 User Manual

MGETM GalaxyTM 6000
50, 60 Hz 250 - 600 kVA
Installation manual
Single-unit UPS
Modular UPS
Parallel UPS with SSC
Frequency converters
Static Switch Cubicle
6739381EN/
Page 2 - 6739381EN/JD
Contents
Characteristics
Characteristics common to all cubicles ..................................................................... 4
Rectifier-inverter cubicles .......................................................................................... 5
Static Switch cubicles ............................................................................................... 5
External maintenance bypass cubicles ..................................................................... 5
"Pack Advance" cubicles........................................................................................... 5
Electrical parameters for selecting protective devices .............................................. 6
Electrical parameters for determining cable cross-sections .................................... 7
Heat losses ............................................................................................................. 7
Installation
Handling .................................................................................................................. 10
Positioning the cubicles .......................................................................................... 10
Floor loads .............................................................................................................. 11
Cubicle layout ......................................................................................................... 11
Power circuit wiring diagrams ................................................................................. 12
Connection of power circuits ................................................................................... 16
Connection of "Media Contacts 9" standard auxiliary circuits ................................. 26
Connections between cubicles ............................................................................... 27
Connections between
cubicle ..................................................................................................................... 29
Connection of "Media Contacts 15" additional auxiliary circuits.............................. 30
Connection of the battery "Temperature Monitor" ................................................... 31
Connection of the LED remote indications unit ....................................................... 33
Connection of "Tele Monitor" remote control and indication unit ............................ 33
Link to an IBM AS/400
Final installation steps ............................................................................................. 34
rectifier-inverter cubicles and external maintenance bypass
®
computer .......................................................................... 33
Appendix
Mains 2 line protection ............................................................................................ 35
Cubicle mounting and connection for 600kVA UPSs .............................................. 36
Cubicle mounting and connection for 2000kVA Static Switch Cubicles .................. 40
Details of earthing connections in the various cubicles .......................................... 43
TM
All MGE
GalaxyTM 6000 products are protected by patents. They implement original APC by Schneider Electric technology
not available to other manufacturers.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric.
This document may be copied only with the written consent of APC by Schneider Electric. Authorized copies must be marked "APC by Schneider Electric MGE
® : IBM AS/400 is a registered trademark of the International Business Machines Corporation.
TM
GalaxyTM 6000 Installation Manual nr 6739381EN".
6739381EN/
Characteristics
Characteristics common to all cubicles
TM
location on their pallets,
TM
MGE
GalaxyTM 6000 cubicles can be
moved short distances using a forklift or pallet-mover when the front, rear and side base panels are not mounted. The forks can be inserted from all four sides into 100 mm +/– 10 mm high openings;
the unadjusted cubicle height (H) is
1900/2000 mm; after lifting the cubicle, the height can be adjusted +/– 10 mm by screwing in or out the four feet;
the bearing surface corresponds to
the area of the four cylindrical foot pads (60 mm diameter) positioned in each corner of the cubicle;
the cubicle depth (D) is 840 mm
(800 mm without doors and panels);
operating temperature range for
rectifier-inverter, frequency converter or Static Switch Cubicles: 0°C to 35°C at rated output (40°C for a maximum of 8 hours) and 30°C maximum for overload conditions. Operation outside the specified temperature range will reduce service life;
relative humidity: 95% maximum;maximum operating altitude without
derating: 1000 m;
connection via the bottom for
rectifier-inverter cubicles, or via the top with the addtion of an optional duct that can be installed on the right side of the cubicle. The auxiliary and Static Switch Cubicles are designed for connections via the top or bottom.
the connection cables may be run in
three ways:
in a trench running under the
cubicles,
under a false floor,on the floor under the cubicles, in the
free space equal to the height of the feet; in this case the cables should be run side by side to avoid blocking the flow of air for ventilation.
the intercubicle connection cables
are not supplied (except for the wires for auxiliary interconnections);
normally the cubicles do not have to
be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed for the fitting of M16 anchor bolts;
the cubicle doors are secured by
Ronis locks (key 405).
MGE
GalaxyTM 6000 UPS: example of a rectifier-inverter cubicleAfter moving them to their installation
A
V k 5
%
2
0
1
2
1 . n i
M
% 0
Y
X A L
A G
IQ
E L L
A S
e
m o H
s
rm la A
e
lin n O
d
n e r T
C l A a
rm
s
o ic t
N is t
a t S
r
ie if t
c e R
y r te
at B
r
e t r e
v
A
In
s as p y
B
s s a
p y B
t u tp
u O
p u
t e S
5
r u o
H 0
A V
k 0 0
4
0 0 0
6
k
c a B
d
e
l e t
b c
a
e
il
t
a
o
v r p
A d
a o
L
1Q Q
1 F Q
S
4
Q
C
P
B 3 Q
0
0
1 % 0 0
1
%
80
% 0 5
% 0
5
0 l e v
e
l d a
o L
0
e m i T
p u
5N
d
a
o
t
L
n
e m ip
u q e
5 0 0
/2
5 /0 0
3 2 3 :
4 2
: 5 1
Galaxy 6000
com ps. u
ge m
w. w w
H
L
P
Page 4 - 6739381EN/JD
Rectifier-inverter cubicles
Characteristics (cont.)
The parameters given in the table opposite can be used to determine the required rating of a single-unit or modular UPS, a frequency converter, or a parallel UPS with SSC.
Static Switch cubicles
Characteristics of rectifier-inverter cubicles
rated cubicle cubicle cubicle maximum inverter width W height H depth D weight output in mm (1) in mm in mm in kg in kVA
250 1600 1900 ± 10 840 1650 300 1600 1900 ± 10 840 1650 400 1600 1900 ± 10 840 2030 450 1600 2000 ± 10 840 2070 500 1600 2000 ± 10 840 2205 600 3600 1900 ± 10 840 3500
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
Characteristics of Static Switch Cubicles
rated cubicle cubicle cubicle maximum heat SSC width W height H depth D weight losses (2) output in mm (1) in mm in mm in kg in kVA in kW in cal./s
500 1000 1900 ± 10 840 350 2.9 696 800 1000 1900 ± 10 840 500 3.7 888 1200 1600 1900 ± 10 840 1000 < 0.5 < 120 2000 2450 1900 ± 10 840 1710 < 0.5 < 120
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
External maintenance bypass cubicles
Characteristics of external maintenance bypass cubicles
(Modular UPS with external maintenance bypass)
rated cubicle cubicle cubicle maximum bypass width W height H depth D weight in kVA in mm (1) in mm in mm in kg
1200 1200 1900 ± 10 840 450
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
"Pack Advance" cubicles
Characteristics of "Pack Advance"Cubicles
rated cubicle cubicle cubicle maximum heat SSC width W height H depth D weight losses (2) output in mm (1) in mm in mm in kg in kVA in kW in cal./s
300 400 1900 ± 10 840 335 2.9 696 400 400 1900 ± 10 840 440 3.7 888 450 400 1900 ± 10 840 440 < 0.5 < 120
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
6739381EN/
Characteristics (cont.)
Electrical parameters for selecting protective devices
The parameters given in the table opposite can be used to determine the required rating of the source side protective circuit breaker on Mains 1 of a single-unit or modular UPS, a frequency converter, or a parallel UPS with SSC.
Important:
It is essential to choose the type of circuit breaker according to its breaking capacity and the prospective short­circuit current at its place of installation.
Note:
For Mains 1 power supply voltages of 380, 400 and 415V, the Mains 1 current is the same because it is a function of the DC voltage.
The parameters given in the table opposite can be used to determine the required rating of the source side protective circuit breaker on the Mains 2 line for a single-unit or modular UPS.
Important:
It is essential to choose the type of
circuit breaker according to its breaking capacity and the prospective short­circuit current at its place of installation. This choice must also be made so as to protect the static switch semiconductors and ensure discrimination with respect to the UPS output fuses (refer to "appendix" chapter).
For an installation with a Static
Switch Cubicle, the Mains 2 currents indicated in the table must be multipled by the number of parallel-connected rectifier-inverter cubicles required to supply the load power (i.e. without taking redundant rectifier-inverter units into account).
Remark:
If the installation includes a transformer on the Mains 2 input, allow for the inrush current caused by magnetization of the transformer windings.
Electrical parameters for Mains 1
rated inverter output in kVA
250 447 407 509 611 300 537 490 612 734 400 727 654 818 981 450 775 735 919 1102 500 920 821 1026 1231 600 1089 981 1226 1472
(1) the rated Mains 1 currents (In) have been determined for a rated phase-to-phase voltage of 380V to 415V, a battery with a 15 minute backup time (206 cells at 2V per cell, i.e. 412V) and at the beginning of its recharge cycle, and full rated load with a power factor of 0.8.
(2) the rated Mains 1 currents (In) have been determined for a minimum float charging voltage of 423V and full rated load with a power factor of 0.8.
Mains 1 current rated current In for unit: with battery at start without battery (2)
of charge cycle (1)
(3) the Mains 1 currents given for an overload of
25% or 50% are maximum values. They have been determined for a battery drawing the minimum float charging voltage and a load power factor of 0.8. When choosing the circuit breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the values in the overload columns.
for 25% for 50% overload (3) overload (3)
Electrical parameters for Mains 2 (415V)
rated Mains 2 current (1) inverter output rated current for 25% for 50% in kVA In overload overload
250 347 433 519 300 416 519 624 400 556 695 834 450 649 811 973 500 722 902 1083 600 866 1082 1300
(1) the Mains 2 currents have been determined for a rated phase-to-phase voltage of 415V, a load power factor of 0.8 and for full rated load as well as overloads of 25% or 50%. When choosing the circuit breaker rating, use the "rated curent" column and check that the circuit breaker tripping curves are compatible with the data in the overload columns. For a Mains 2 voltage of 380V, multiply the currents indicated in this table by 1.09. For a Mains 2 voltage of 400V, use the table in another language version of this manual.
Page 6 - 6739381EN/JD
Electrical parameters for determining cable cross-sections
Characteristics (cont.)
this table has been drawn up for
rated phase-to-phase Mains and load voltages of 415V. For voltages of 380V, multiply the currents for Mains 2 and load by 1.09; for voltages of 400V, use the table in another language version of this manual;
the current values and cable cross-
sections for Mains 1 are given for full rated load with a power factor of 0.8 and a battery consuming its minimum
the battery current values and cable
cross-sections have been determined for a battery at the end of a charge cycle;
the current values and cable sections
for Mains 2 and load are given for full rated load with a power factor of 0.8.
For frequency converters, the parameters concerning Mains 2 are not applicable. The load parameters common to all the converters are given in the table below.
For a parallel UPS, the parameters for
Mains 2 and load are also provided in the table below.
For a modular UPS, the parameters for Mains 2 and load are also provided in the table below.
float charging voltage;
Parameters for single-unit UPS cables
rated inverter output in kVA
250 407 361 630 185 300 150 240 240 2 x 185 300 490 433 758 240 2 x 150 240 2 x 150 240 2 x 240 400 654 577 1013 2 X 185 2 x 300 2 x 150 2 x 240 2 x 185 3 x 185 450 735 649 1137 2 X 185 2 X 300 2 X 185 2 x 300 2 x 185 2 x 300 500 821 722 1252 2 x 240 4 x 185 2 X 185 2 x 300 3 x 150 3 x 240 600 981 866 1519 3 x 240 4 x 240 2 X 240 4 x 185 3 x 185 2 x 400
(1) the rated Mains 1 currents (In) have been determined for a minimum float charging voltage of 423V and full rated load with a power factor of 0.8.
line currents absorbed in Amps cross-sectional area of Cu cables in mm2 (2) Mains 1 415V battery Mains 1 415V battery with or without battery (1)
Mains 2 with or without battery Mains 2 and load and load Copper Aluminium Copper Aluminium Copper Aluminium
(2) the cable cross-sections are given for copper
conductors. They are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m (AC circuits) or 25 m (DC circuits if cables not provided). For greater lengths, the cross-sections should be chosen to limit voltage drops to 3% (AC) or 1% (DC).
NF C 15-100 authorizes a maximum of 4 cables per phase.
Heat losses
rectifier-inverter cubicles
rated heat inverter losses (1) output in kVA in kW in cal./s
250 13,5 3220 300 17,5 4170 400 23 5480 450 25 5960 500 30 7150 600 32,8 7830
(1) the indicated heat losses are those produced by the unit at full rated load and with the battery float charging. They must be taken into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation. The air enters via the doors and grids at the bottom and is discharged via the roof.
static switch cubicles
rated heat SSC losses (1) output in kVA in kW in cal./s
500 2,9 696 800 3,7 888 1200 < 0,5 < 120 2000 < 0,5 < 120
(1) the indicated heat losses are those produced by the unit at full rated load when operating on Mains 2. They are not to be taken into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation.
"Pack advance" cubicles
rated heat inverter losses (1) output in kVA in kW in cal./s
300 2,2 525 400 2,6 620 450 2,6 620
(1) the indicated heat losses are those produced by the unit at full rated load and with the battery float charging. They must be taken into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation. The air enters via the doors and grids at the bottom and is discharged via the roof.
6739381EN/
Characteristics (cont.)
The table opposite serves as an example for an installation comprising up to four frequency converters or four parallel UPSs with a centralised SSC.
for installations with redundant units,
take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected rectifier-inverter cubicles, one being redundant, only 2 rectifier-inverter cubicles are used to determine Mains 2 and load currents and cable cross-sections);
this table has been drawn up for
rated phase-to-phase Mains 2 and load voltages of 415V and full rated load with a power factor of 0.8. For voltages of 380 or 400V, multiply the indicated currents by 1.09 and 1.04 respectively, then modify the cable cross-sections accordingly if necessary. The cable cross-sections in this table are for the parts illustrated in bold on the following block diagrams (installation examples, figures 1 and 2).
Parameters for Mains 2 and load cables for an installation comprising frequency converters or parallel UPSs with a centralised SSC.
rated inverter number of total UPS Mains 2 or load cable cross-section (1) output parallel-connected rated output line current in mm in kVA inverters in kVA in Amps Copper Aluminium
250 2 500 722 2 x 185 2 x 300
300 2 600 866 2 x 240 4 x 185
400 2 800 1298 4 x 185 4 x 300
450 2 900 1154 4 x 240 4 x 400
500 2 1000 1444 4 x 240 4 x 400
600 2 1200 1731 Please consult us*
(1) cable cross-sections are given for copper conductors of the U1000 R02V type. They are calculated according to permissible temperature rise and allow for line voltage drops over a
3 750 1082 3 x 300 4 x 240 4 1000 1444 4 x 240 4 x 400
3 900 1299 4 x 240 4 x 400 4 1200 1732 Please consult us*
3 1200 1947 Please consult us* 4 1600 2596 Please consult us*
3 1350 1731 Please consult us* 4 1800 2308 Please consult us*
3 1500 2164 Please consult us* 4 2000 2888 Please consult us*
3 1800 2598 Please consult us* 4 2400 3462 Please consult us*
maximum length of 100 m. For greater lengths, the cross-sections should be chosen to limit voltage drops to 3%.
NF C 15-100 authorizes a maximum of 4 cables per phase.
2
Installation with parallel frequency converters
mains 1
mains 1
mains 1
inverter 1
inverter 2
inverter 3
Fig. 1
Installation with parallel UPSs with a centralised SSC
mains 2
mains 1
mains 1
mains 1
inverter 1
inverter 2
inverter 3
static switch cubicle
load
load
Page 8 - 6739381EN/JD
Fig. 2
Characteristics (cont.)
The table opposite serves as an example for an installation with up to four modular UPSs with an external maintenance bypass.
for installations with redundant units,
take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected rectifier-inverter cubicles, one being redundant, only 2 units are used to determine the currents on the maintenance bypass line and the load, and the cross­sectional areas of cables);
this table has been drawn up for
rated phase-to-phase Mains 2 and load voltages of 415V and full rated load with a power factor of 0.8. For voltages of 380 or 400V, multiply the indicated currents by 1.09 and 1.04 respectively, then modify the cable cross-sections accordingly if necessary. The cable cross-sections in this table are for the parts illustrated in bold on the following block diagrams (installation example, figure 3);
important. In an installation with an
external maintenance bypass, the power cables between each UPS and
the upstream protection devices
must be the same length. The same holds for the power cables between
each UPS cubicle and the external maintenance bypass.
Parameters for connection of the external maintenance bypass circuit and the load in an installation comprising modular UPSs
rated inverter number of total UPS Mains 2 or load cable cross-section output parallel-connected rated output line current (1) in mm in kVA inverters in kVA in Amps Copper Aluminium
250 2 500 722 2 x 185 2 x 300
300 2 600 866 2 x 240 4 x 185
400 2 800 1154 4 x 185 4 x 300
450 2 900 1299 4 X 240 4 x 400
500 2 1000 1444 4 X 240 4 x 400
(1) cable cross-sections are given for copper conductors of the U1000 R02V type. They are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 100 m. For greater lengths, the cross-sections should be chosen to limit voltage drops to 3%.
3 750 1082 3 x 300 4 x 240 4 1000 1444 4 x 240 4 x 400
3 900 1299 4 x 240 4 x 400 4 1200 1732 Please consult us*
3 1200 1731 Please consult us* 4 1600 2308 Please consult us*
3 1350 1948 Please consult us*
3 1500 2166 Please consult us*
NF C 15-100 authorizes a maximum of 4 cables per phase.
2
Installation comprising modular UPSs with an external maintenance bypass
maintenance Bypass cubicle
Fig. 3
mains 1
mains 2
mains 1
mains 2
mains 1
mains 2
inverter 1
inverter 2
inverter 3
load
6739381EN/
Installation
(to be carried out by qualified personnel only)
Handling
Unpacked cubicles may be moved using a forklift from the front or from the back. Distances must not exceed a few meters.
Positioning the cubicles
(for 600 kVA UPSs, see the appendix as well)
prior to moving the cubicles to their
final position, remove the packing material and withdraw the base panels from the space on the side created by the spacing uprights. The panels will be installed at the end of the installation procedure;
spacing uprights on the sides of the
cubicles create a 50 mm clearance when cubicles are positioned next to each other, enabling users to open the doors (see figure 4). If a cubicle is installed next to a wall, leave additional space so that the cubicle is 50 mm from the wall;
when the spacing uprights are not
required (cubicles are not positioned next to a wall or another cubicle), they may be removed:
loosen the four screws securing the
upright,
lift the upright and pull it free,replace the long gold-coloured
screws with the black screws supplied in a bag attached to the cable terminals in the cubicle;
adjust the height of the feet until the
first cubicle is perfectly vertical; adjust the feet of the subsequent cubicles so that the all the doors are perfectly aligned.
Side clearances provided by the spacing uprights
rear
50
cubicle 1
front
spacing uprights of cubicle 1
Fig. 4
50
cubicle 2
spacing uprights of cubicle 2
Page 10 - 6739381EN/JD
Floor loads (figure 5)
Installation (cont.)
the floor supports the weight of each
Cubicle footpads
cubicle via the four 60 mm diameter pads at the bottom of the feet screwed
rear
33 33
into the corners of the frame;
the exact locations of the footpads
33
are indicated in the figure;
normally the cubicles do not have to
be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed for the fitting of M16 anchor bolts;
to determine the stresses applied by
four 60 mm dia. footpads with 12 mm average depth holes for M16 anchor bolts
736
the cubicle feet on the floor, divide the cubicle weight (see the first 3 tables of this manual) by the total area of the 4 footpads (110 cm
2
).
front
Fig. 5
Cubicle layout on false floor or normal floor (figures 6, 7, 8)
the cubicles can be installed directly
up against the rear wall;
an overall clearance of 400 mm must
be left above the entire surface of the cubicles for ventilation;
a side clearance of 25 mm is
provided by the vertical bars on the sides of the cubicles to allow door opening. For cubicles mounted side by side, the two adjacent bars ensure an inter-cubicle clearance of 50 mm;
a minimum clearance of 1000 mm is
required in front of the cubicles to allow complete opening of the doors and easy access for maintenance work (replacement of subassemblies);
for extended battery backup times or
high output systems, the UPS may have several battery cubicles (see the table at the end of the previous chapter). If this is the case, install the battery cubicles on the left side of the rectifier-inverter cubicle with the cubicle containing the battery circuit breaker QF1 closest to the rectifier-inverter cubicle (figure 7);
when an auxiliary cubicle is included
in the UPS, it should be installed to the left of the battery cubicle(s);
connection via the bottom
The connection cables may be run in three ways:
in a cable trench running underneath
the front of the cubicles (see trench dimensions and layout in figure 6),
under a false floor.
A cutout must in this case be made in the floor for cable entry (see figure 6 for dimensions),
Layout for a single-unit UPS with one battery cubicle
rear
>25
80
cubicle width W (see table)
battery cubicle
front
cutouts necessary for cable entry from underneath a false floor: 200 mm x (W – 160 mm)
Fig. 6
Layout for a single-unit UPS with several battery cubicles
rear
battery cubicle 2
front
Fig. 7
50
cubicle width W (see table)
rectifier-inverter cubicle
spacing uprights
battery cubicle 1 containing battery circuit breaker QF1
cubicle width less 66 mm
> 1000
can equal 0
800
location of trench under cubicles (if applicable)
rectifier-inverter cubicle
33
3333
6739381EN/
Installation (cont.)
on the floor under the cubicles, in the
free space equal to the height of the feet. In this case the cables should be run side by side to avoid blocking the flow of air for ventilation. The cables exit from the rear or sides of the cubicles;
connection via the top
the Static Switch, filter and auxiliary
cubicles are designed for connection via the bottom or top,
for the rectifier-inverter cubicles, a
special 400 mm wide connection duct must be added to the right of the cubicle to allow connection via the top.
Power circuit wiring diagrams
The single-wire diagrams for typical UPS installations are given in figures 9 to 15. The heavy lines represent the cables that must be connected (see the table in the previous chapter for the required cross-sectional areas of the cables).
Note:
for frequency converters, the input
and output frequencies may be different (50 or 60Hz);
for frequency converters without
batteries, ignore the battery cubicles and the + and - cables shown in the diagram.
Special case:
The UPSs can be optionally supplied with the neutral conductor not interrupted by switches Q4S, Q3BP and Q5N.
Layout for an installation with two parallel UPSs and a centralised SSC
rear
front
auxiliaries cubicle 2 (if applicable)
battery cubicle(s) 2
rect./inv. cubicle 2
auxiliaries cubicle1 (if applicable)
battery cubicle(s) 1
rect./inv. cubicle 1
static switch cubicle
Fig. 8
Diagram for a single-unit or single modular UPS with separate Mains 1 and 2
rectifier-inverter cubicle
Q3BP
mains 2
mains 1
earth
Q4S
Q1 Q5N
rectifier charger
battery cubicle beside the rectifier-inverter cubicle
QF1
static switch
inverter
+
frames interconnections for earthing
-
+
-
other battery cubicles (if applicable)
earth
load
earth
Fig. 9
Page 12 - 6739381EN/JD
Diagram for a single-unit or single modular UPS with common Mains 1 and 2
rectifier-inverter cubicle
Q3BP
mains
earth
mains 2 input
mains 1 input
Q4S
Q1 Q5N
rectifier charger
battery cubicle beside the rectifier-inverter cubicle
QF1
static switch
inverter
+
frames interconnections for earthing
+
-
-
other battery cubicles (if applicable)
earth
load
earth
Fig. 10
Installation (cont.)
Diagram for a frequency converter with batteries
rectifier-inverter cubicle
mains 1
earth
Q1 Q5N
rectifier charger
battery cubicle beside the rectifier-inverter cubicle
QF1
inverter
+
frames interconnections for earthing
-
+
-
Fig. 11
Diagram for a frequency converter without batteries
rectifier-inverter cubicle
mains 1
Q1 Q5N
rectifier charger
inverter
Fig. 12
Example of a 2 parallel UPS rectifier-inverters with SSC
other battery cubicles (if applicable)
load
earth
earth
load
earth
Note:
Both the rectifier-inverter cubicles and the Static Switch Cubicle can be supplied from a common mains, in which case there is only one upstream circuit breaker (same as the case of a single-unit UPS with a common Mains 1 and 2).
mains 2
mains 1
earth
mains 1
earth
Static Switch Cubicle
Q3BP
Q4S
rectifier-inverter cubicle 1
Q1 Q5N
rectifier charger
battery cubicle beside rectifier­inverter cubicle 1
rectifier-inverter cubicle 2
Q1 Q5N
rectifier charger
battery cubicle beside rectifier­inverter cubicle 2
static switch
inverter 1
QF1
inverter 2
QF1
frames interconnection for earthing
frames interconnections for earthing
+
-
frames interconnections for earthing
frames interconnections for earting
+
-
+
+
Q5N
other battery
-
cubicles (if applicable)
other battery
-
cubicles (if applicable)
earth
load
inverter 1 output
inverter 2 output
earth
earth
earth
earth
Fig. 13
6739381EN/
Installation (cont.)
Example of 2 multi-bypass modular UPS cubicles for redundancy (from 250 to 500kVA)
modular UPS cubicle 1
Q3BP
earth
mains 2
mains 1
earth
mains 2
mains 1
Q4S
Q1 Q5N
rectifier charger
battery cubicle beside rectifier­inverter cubicle 1
modular UPS cubicle 2
Q4S
Q1 Q5N
rectifier charger
static switch
inverter 1
QF1
static switch
inverter 2
frames interconnection for earthing
+
-
Q3BP
+
frames interconnection for earthing
-
other battery cubicles (if applicable)
inverter 1 output
earth
earth
inverter 2 output
load
Fig. 14
earth
battery cubicle beside rectifier­inverter cubicle 2
QF1
frames interconnection for earthing
other battery
+
-
+
-
cubicles (if applicable)
earth
Page 14 - 6739381EN/JD
Loading...
+ 32 hidden pages