APC MGE Galaxy 4075KVA208V, MGE Galaxy GLF50KF, MGE Galaxy 4000, MGE Galaxy 40004075KVA208Vi User Manual

MGEGalaxy4000
40–75kVA208V
Installation
TableofContents
Safety....................................................................................................................................1
SafetyInstructions......................................................................................................1
CerticationStandards—ThreePhaseUPS.............................................................1
SafetyofPersons......................................................................................................2
ProductSafety...........................................................................................................2
SpecialPrecautions...................................................................................................2
Specications...................................................................................................................3
EnvironmentalRecommendations..........................................................................3
ElectricalSpecications............................................................................................3
MechanicalAssembly..................................................................................................4
MajorComponents......................................................................................................5
SingleLineDiagram..................................................................................................5
StandardCabinets.......................................................................................................5
PreparationforOperation..........................................................................................6
CabinetPlacement.......................................................................................................6
HeatRejection...............................................................................................................7
CabinetClearances.....................................................................................................7
PreparationforStorage..............................................................................................7
PreparetheInstallation...............................................................................................8
ConduitPlateLocationsforBottomEntry............................................................8
ConduitPlateLocationsforTopEntry...................................................................9
ConnectACInputandPowerCables..................................................................10
InstallationSteps.........................................................................................................10
Firststepsbyanon-sitequaliedTechnicalEngineer..............................................10
ElectricalConnections...............................................................................................10
TypicalPowerConnections.......................................................................................11
UPSConnections.......................................................................................................12
MainACInputConnections.......................................................................................12
BypassACInputConnections(optional)...................................................................12
ConnectBatteryCables..............................................................................................13
990–3964–001
MGEGalaxy400040–75kV A208V
i
BatteryConnections...................................................................................................13
BatteryControlConnections....................................................................................13
ConnectACOutput.......................................................................................................14
ACOutputConnections.............................................................................................14
ExternalMaintenanceBypassControlConnections(optional)......................14
AccessoriesOutlets....................................................................................................14
ConnectRemoteEmergencyPowerOff............................................................15
RemoteEmergencyPowerOffConnections........................................................15
ConnectRelayCommunicationCard..................................................................16
RelayCommunicationCardContacts....................................................................16
RelayCommunicationCardConnections.............................................................18
CharacteristicsofOutputContacts........................................................................18
CharacteristicsofInputContacts............................................................................18
AppendixSingleLineDiagram...............................................................................19
ii
MGEGalaxy400040–75kV A208V
990–3964–001

Safety

SafetyInstructions

ThismanualcontainsimportantinstructionsforMGEGalaxy4000thatmustbefollowedduring operationandmaintenanceoftheequipment.
WARNING:Openingenclosuresexposehazardousvoltages.Alwaysreferserviceto qualiedpersonnelonly.
WARNING:Asstandards,specications,anddesignsaresubjecttochange,please askforconrmationoftheinformationgiveninthispublication.
Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClass
Adigitaldevice,pursuanttopart15oftheFCCrules.Theselimitsaredesignedto providereasonableprotectionagainstharmfulinterferencewhentheequipmentis operatedinacommercialenvironment.Thisequipmentgenerates,uses,andcanradiate radiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstruction manual,maycauseharmfulinterferencetoradiocommunications.Operationofthis equipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasethe userwillberequiredtocorrecttheinterferenceatuser'sownexpense.
WARNING:Toreducetheriskofreorelectricshock,installinacontrolledindoor environmentfreeofconductivecontaminants.Thisequipmentisintendedonlyfor installationsinaRESTRICTEDACCESSLOCATION.
WARNING:HIGHLEAKAGECURRENT.Earthconnectionessentialbefore connectingsupply .
CerticationStandards—ThreePhaseUPS
IEC1004/ANSIC62.41StandardsforSurgeWithstandAbility.
FCCPart15,SubpartJ,ClassA.
UL/CUL1778,StandardsforUninterruptiblePowerSupplyEquipment.
NEMAPE1-UninterruptiblePowerSystems.
NFPA70–NationalElectricalCode.
ISO9001.
990–3964–001
MGEGalaxy400040–75kV A208V
1

SafetyofPersons

TheUPShasitsowninternalpowersource(thebattery).Consequently,thepowerterminalsmay
beenergizedeveniftheUPSisdisconnectedfromtheACpowersource.
TheUPSmustbeproperlygrounded.
ThebatterysuppliedwiththeUPScontainssmallamountsoftoxicmaterials.Toavoidaccidents,
thedirectiveslistedbelowmustbeobserved: —Neverburnthebattery(riskofexplosion). —Donotattempttoopenthebattery(theelectrolyteisdangerousfortheeyesandskin. —Complywithallapplicableregulationsforthedisposalofthebattery. —Batteriesconstituteadanger(electricalshock,burns).Theshort-circuitcurrentmaybevery high. —Precautionsmustbetakenforallhandling:removewatches,rings,braceletsandanyothermetal objects,usetoolswithinsulatedhandles. —Donotlaytoolsormetalpartsontopofbatteries.

ProductSafety

Upstreamprotectionmustbeinstalledandbeeasilyaccessible.
TheUPScanbedisconnectedfromtheACpowersourcebyopeningtheinputprotectivedevices.
TheUPSmustbeconnectedtoanearbypowersourcethatiseasilyaccessible.
NeverblocktheventilationopeningsoftheUPS.
TheUPSmustbeinstalledinacontrolledenvironment.

SpecialPrecautions

TheUPSconnectioninstructionsandoperationdescribedinthemanualmustbefollowedinthe
indicatedorder.
CheckthattheindicationsontheratingnameplatecorrespondtoyourACpoweredsystemandto
theactualelectricalconsumptionofalltheequipmenttobeconnectedtotheUPS.
Beforeandaftertheinstallation,iftheUPSremainsde-energizedforalongperiod,theUPS
mustbeenergizedforaperiodof24hours,atleastonceevery3months(foranormalstorage temperaturelessthan25°C).Thischargesthebattery,thusavoidingpossibleirreversibledamage.

Environment

Thisproducthasbeendesignedtorespecttheenvironment;ItdoesnotcontainanyChlorouorocarbon (CFC)orHydrochlorouorocarbon(HCFC).
UPSrecyclingattheendofservicelife;APCundertakestorecycle,bycertiedcompaniesandin compliancewithallapplicableregulations,allUPSproductsrecoveredattheendoftheirservicelife (contactyourAPCcertiedservicepartner).
Packing;UPSpackingmaterialsmustberecycledincompliancewithallapplicableregulations.
WARNING:Thisproductcontainslead-acidbatteries.Leadisadangerous substancefortheenvironmentifitisnotproperlyrecycledbyspecializedcompanies.
2
MGEGalaxy400040–75kV A208V
990–3964–001
Specications

EnvironmentalRecommendations

RecommendedEnvironment20°to25°C(68°to77°F .);50%relativehumidity;computerroomorother
temperature,andhumidity-controlledenvironment
OperatingTemperature0°to30°C(32°to86°F)exceptbattery
Storage
HumidityUpto90%non-condensing(operating)
AltitudeSealevelto3,000feetwithoutderating
AcousticNoise69dBAatratedloadasmeasured3feetfromthefrontoftheUPScabinet.
ElectricalSpecications
-20°to40°C(-4°to113°F)exceptbattery
OutputPowerRating(0.8)PF
UPSV oltage(input/output)208/208208/208208/208208/208
Input/OutputRequirements& Frequency
InputPhaseRotationA,B,CClockwise
InputPowerFactor
InputCurrent102A127A166A191A
MaximumInputCurrent(atlowline —15%)
BypassCurrent111A139A180A208A
OutputCurrent111A139A180A208A
BatteryV oltage198VDCEndV oltage240VDCNominal282VDC
Max.BatteryCurrentatNominal BatteryV oltage(240VDCat100% load)
Max.BatteryCurrentatNominalEnd­V oltage(198VDCat100%load)
BatteryDisconnectCircuitBreaker Rating
Input,Bypass,andMaintenanceBypass (optional)SwitchRating
InputFuseRating
OutputIsolationCircuitBreakerRating
NOTE:InterruptedTransfertoBypassSource: Ifthebypasssourceisbeyondtheconditionsstatedbelow,theUPSwillmakeaninterruptedtransfer(notmore than100msec.induration).
1.Bypassvoltagegreaterthan+15%,—15%fromtheUPSratedoutputvoltage.
2.Bypassfrequencygreaterthan±2HzfromtheUPSratedoutputfrequency.
40kV A50kV A65kV A75kV A
Threephase,Threewire+N+G,60Hz
>.98
120A150A195A225A
Max.MaintenanceV oltage
157A196A255A294A
190A238A309A357A
250A400A
150A250A
200A300A
175A300A
990–3964–001
MGEGalaxy400040–75kV A208V
3

MechanicalAssembly

GeneralDescription
TheMGEGalaxy4000istheworld’srstdatacentergradeUninterruptiblePowerSupplysystem designedspecicallyformid-rangeenterpriselevelapplications.TheMGEGalaxy4000family consistsofunitsavailableinpowerratingsfrom40-75KV A,andareoptimizedforcompatibilitywith nonlinearcomputer-typeloads.
ByincorporatingtheUltraHighAvailabilityT opology(UHAT),theMGEGalaxy4000familyofUPS systemsaredesignedtoprovidetheoptimallevelofreliabilityandtoreacttoanypowerdisturbance inaninherentlysafewaytoprotectthecriticalload.TheMGEGalaxy4000all-in-onedesign incorporateseveryfeatureintoonecompactcabinet,includingagraphicaluserinterface,powerfactor correctedinput,andcommunicationcardsthatsupportnetworkbasedpowermanagement.
TheMGEGalaxy4000UPSanditsauxiliaryequipmentaredesignedforinstallationinaroomwhere humidityandtemperaturecanbecontrolled.
TheMGEGalaxy4000UPSandauxiliaryequipmentislistedforsafetybyUnderwritersLaboratories, Inc.(UL)underULStandard1778–UninterruptiblePowerSystems;andalsolistedbyUnderwriters Laboratories(CUL)underCanadianStandardsAssociation(CSA)standardC22.107.