GalaxyTM 6000 products are protected by patents. They implement original APC by Schneider Electric technology
not available to other manufacturers.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning
technical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric.
This document may be copied only with the written consent of APC by Schneider Electric. Authorized copies must be marked
"APC by Schneider Electric MGE
TM
GalaxyTM 6000 User Manual N° 6739380EN.
System performance
TM
A MGE
uninterruptible power supply (UPS)
delivers 3-phase power with the
following characteristics:
◗ stable voltage (+/-0.5% under steady
state conditions and +/-5% under
transient conditions for load step
changes of 25 to 100% or of 100 to
25%);
◗ stable frequency (+/-0.05Hz without
Mains 2);
◗ or frequency synchronized with
Mains 2 to 50/60Hz +/-2Hz (value may
be configured in 0.25 HZ steps);
◗ free of micro-breaks and outages for
the duration of the battery time (10, 15
or 30 minutes);
◗ less than 4% distortion in all system
configurations with linear loads;
◗ less than 5% distortion for a 100%
non-linear load with a peak factor of up
to 3.5.
The acoustic noise level of a
MGE
70dBA.
GalaxyTM 6000
TM
GalaxyTM 6000 UPS is under
Single-line diagram of the MGE
B
mains 2
(bypass input)
mains 1
(normal input)
isolation
isolation
and
protection
A
TM
GalaxyTM 6000 system
maintenance
bypass
emergency
bypass
AC/DC
conversion
isolation and
protection
battery
DC/AC
conversion
Introduction
isolation
and
protection
load
System description
◗ a rectifier-charger (RC) module
converts 3-phase AC power from the
Mains 1 supply into DC power for the
normal inverter input and float charges
or recharges the batteries;
◗ a battery unit provides backup power
for the inverter in the event of a voltage
drop or a Mains 1 failure;
◗ an inverter module converts the DC
power supplied by the rectifier-charger
module or the battery unit into 3-phase
AC power for the load;
◗ an emergency bypass module
ensures the instantaneous transfer of
the load via the static switch to the
Mains 2 bypass line in the event of an
inverter shutdown (initiated by the user
or by a protective device) or a sudden
overload;
◗ a maintenance bypass which isolates
the UPS for maintenance and transfers
the load without interrupting the supply
of power. The maintenance bypass is
made up of three manual switches.
Note:
◗ the Mains 1 normal input and the
Mains 2 bypass input have different
functions and, depending on the
installation, may be protected
differently upstream and/or come from
different sources;
◗ frequency converters are available
without backup batteries;
◗ the emergency bypass line and the
maintenance bypass line do not exist in
installations where the load frequency
and the Mains 2 frequency are different
(for example in frequency converters);
◗ for reasons of redundancy and/or
increased power, the rectifier-charger,
inverter and battery modules (the UPS,
part A in the MGE
TM
GalaxyTM 6000
schematic diagram above) may be
arranged in parallel lines. In this case,
an isolation function is added to the
output of each UPS for maintenance
without disrupting the load.
In this type of system, the components
of part B in the diagram are located in a
separate cubicle referred to as the
"Static Switch Cubicle".
The system may also include:
◗ an isolating transformer on the
Mains 2 line;
◗ a harmonics filter on the Mains 1
input;
◗ different remote control, indication
and display systems;
◗ a double bridge rectifier-charger
module.
6739380EN/JC - Page 5
Introduction (cont.)
Different types of MGETMGalaxyTM 6000 systems
◗ Single-unit or modular UPS:
(figure 1)
mains 2
mains 1
Fig. 1
◗ Multi-bypass modular UPSs:
(figure 2)
Note:
2 modular UPSs (identical ratings) can
be parallel-connected in this way.
mains 2
mains 1
rectifiercharger
rectifiercharger
Q3BP
Q3BP
static switch
inverter
load
battery
static switch
inverter
◗ Modular UPSs with external
maintenance bypass: (figure 3)
Note:
Up to 4 UPS (identical ratings) can be
parallel-connected.
Fig. 2
mains 2
mains 1
mains 2
mains 1
mains 2
rectifiercharger
Q3BP
rectifiercharger
battery
battery
Q3BP
static switch
inverter
battery
static switch
static switch
inverter
load
load
Q5N
Page 6 - 6739380EN/JC
Fig. 3
mains 1
rectifiercharger
inverter
battery
Introduction (cont.)
◗ Frequency converter with battery
backup power: (figure 4)
◗ Frequency converter without backup
power: (figure 5)
◗ Frequency converters with backup
power: (figure 6)
Fig. 4
Fig. 5
mains 1
mains 1
mains 1
rectifiercharger
rectifiercharger
rectifiercharger
rectifiercharger
inverter
load
battery
inverter
load
inverter
battery
inverter
load
◗ Parallel UPSs with SSC: (figure 7)
Note:
Up to 6 UPS (identical ratings) can be
parallel-connected in this way.
Fig. 6
mains 2
mains 1
rectifiercharger
Q3BP
Static Switch Cubicle
rectifiercharger
rectifiercharger
battery
battery
battery
inverter
inverter
inverter
load
Fig. 7
battery
6739380EN/JC - Page 7
Introduction (cont.)
Isolation and protection devices
UPS or converter cubicles
(figure 8)
◗ Q1 (switch):
◗◗ isolation from Mains 1,
◗◗ RC start-up;
◗ QF1 (circuit breaker):
◗◗ battery protection and isolation;
◗ Q5N (switch):
◗◗ isolation of the inverter, frequency
converter or static switch module from
the load;
◗ Q4S (switch):
◗◗ isolation of the static switch from
Mains 2;
◗ Q3BP (switch):
◗◗ bypass switch for maintenance;
◗ FU1-2-3 (fuses):
◗◗ protection of the RC from Mains 1;
◗ FU5-6-7 (fuses):
◗◗ protection of the inverter from the
load.
Note:
◗◗ switches Q4S and Q3BP do not exist
on frequency converters,
◗◗ circuit breaker QF1 does not exist on
frequency converters without a battery.
Example of a single-unit UPS or single modular UPS
static switch
mains 2
mains 1
rectifier-
Q1
FU1-2-3FU5-6-7
charger
Q4S
inverter
QF1
battery
Fig. 8
Q3BP
Q5N
load
Static Switch Cubicle
(figure 9)
◗ Q4S (switch):
◗◗ isolation of the static switch (and
mechanical contactor K2S) from
Mains 2;
◗ Q3BP (switch):
◗◗ bypass switch for maintenance;
◗ Q5N (switch):
◗◗ isolation of the load from the parallel
UPSs;
◗ Q1 (fuse switch):
◗◗ protection of the cubicle control
electronics from the parallel-connected
inverter outputs;
◗ Q2 (fuse switch):
◗◗ protection of the cubicle control
electronics from Mains 2.
External maintenance bypass
cubicle (figure 10)
◗ Q3BP (switch):
◗◗ bypass switch for maintenance;
◗ Q5N (switch):
◗◗ isolation of the load from the parallel-
connected UPSs.
Fig. 9
mains 2
parallel
UPSs
maintenance
bypass line
parallel
modular UPSs
Q2
Q1
Q4S
Q3BP
Q5N
static switch
control
electronics
Q3BP
Q5N
load
load
Page 8 - 6739380EN/JC
Fig. 10
Main operating modes
Normal operation
Mains 1 power is available:
(see figure 11).
The green "load protected" light 5 on
the control panel is on.
!
+–
!
I
Introduction (cont.)
static switch
mains 2
rectifiercharger
O
mains 1
inverter
load
5
légend :
offon
The power necessary for the load is
provided by Mains 1 through the
rectifier-charger and the inverter.
The rectifier-charger also supplies the
power to float charge and recharge the
battery (1). The rectifier-charger output
voltage (DC) is regulated for the
different battery types and charging
modes:
◗ vented lead-acid or Ni/Cd batteries:
two different voltages, one for float
charging and one for recharging;
◗ sealed lead-acid batteries: a single
voltage for both charge functions.
Operation with Mains 1 down
(figure 12)
In the event of a Mains 1 failure or
Mains 1 voltage outside specified
tolerance of –10% in amplitude (–15%
optionally), the rectifier-charger stops
and the battery supplies the necessary
backup power to the load via the
inverter. The battery, float-connected
between the rectifier-charger and the
inverter, discharges during this
operating mode.
The green "load protected" light 5 on
the control panel is on.
The user is warned of battery operation
by a buzzer and the orange "load on
battery" light 4 on the control panel.
beep...beep...
!
+–
!
I
Fig. 11
The voltages depend on the number of
battery cells and the battery
manufacturer. They can be factory set
and are adjustable by the after-sales
support technicians.
An optional electronic board may be
used to continuously measure the
battery temperature and automatically
adjust the voltages.
mains 2
mains 1
Fig. 12
This information is also available via
volt-free changeover contacts for
remote control devices.
In this case, there is a 30 seconds
delay.
O
rectifiercharger
battery
Parallel UPS systems:
the power drawn by the load is equally
shared between the different UPSs.
(1) Except for frequency converters without a
battery
static switch
inverter
load
battery
Note:
In the event of a Mains 1 failure,
frequency converters without a battery
shut down and the load is no longer
supplied.
5
4
6739380EN/JC - Page 9
Introduction (cont.)
Battery time
The available battery time during a
Mains 1 outage depends on the:
◗ rated capacity of the battery;
◗ power consumed by the load;
◗ temperature of the battery;
◗ age of the battery.
The specified battery time corresponds
to a minimum duration at full rated load.
The actual backup time can therefore
be greater if the system operates below
its full rated load during the Mains 1
outage. Operation on battery power can
be extended beyond the specified time
by reducing the load power
consumption (by disconnecting noncritical loads).
A "low battery shutdown" warning
signal is sent via volt-free changeover
contacts for remote control devices
when the battery voltage reaches a
level slightly above the minimum level.
Operation with Mains 1 restored
(figure 13)
When Mains 1 power is restored or its
voltage returns to within specified
tolerances, the system automatically
returns to its normal operating mode
described above (on the condition it did
not reach the end of battery power).
If the end of battery power was reached
(with the resulting inverter shutdown),
the RC restarts automatically, but the
inverter must be restarted manually,
either locally or remotely in systems
equipped with a remote-control unit.
The rectifier-charger recharges the
battery which was discharged during
the Mains outage.
Note:
In frequency converters without battery
power, the return of Mains 1 power
results in the automatic restart of the
RC and the inverter.
The battery charge cycle takes place in
two steps (see figure 14):
◗ step 1: the battery is recharged at a
constant current limited to 0.1C10
(i.e. 1/10th of the battery capacity
specified for a 10 hour discharge).
The DC voltage increases with the
battery charge until the charge level is
reached;
◗ step 2: the battery is recharged at
constant voltage equal to the charge
level (maximum value 463V).
The charging current gradually
decreases until reaching a specified
low value (floating current).
For vented lead-acid batteries, the
rectifier-charger supplies the charging
voltage for 0 to 255 hours (parameter
defined by the after-sales support
department) and then the floating
voltage. For sealed lead-acid batteries,
This signal warns the user of the
imminent end of battery power. On the
device itself, the buzzer beeps
increasingly rapidly and loudly.
Battery power stops when the voltage
supplied by the battery reaches the
voltage minimum (340V). This results in
inverter shutdown and transfer of the
load without interruption to Mains 2.
The red "load not protected" light 2 on
the control panel is on.
beep...beep...
!
2
mains 2
mains 1
+–
!
rectifiercharger
I
O
Fig. 13
Battery charge cycle
U/I
current
limiting
0.1 C10
constant voltage
decreasing current
voltage
current
Fig. 14
the charging and floating voltages are
the same.
Note:
If the Mains 1 failure is shorter than 0 to
255 seconds (parameter defined by the
after-sales support department), the
If Mains 2 also fails, the load is no
longer supplied. Normally, the inverter
shuts down when the time on the
battery power exceeds three times the
specified backup time.
Note:
As an optional function (battery time
estimator), the "low battery shutdown"
warning signal can be sent with an
adjustable time delay prior to the
effective end of battery power.
static switch
inverter
load
battery
U charge/floating
(sealed batteries)
U "floating"
(vented batteries)
t
charger does not initiate a complete
charge cycle but automatically supplies
the floating voltage.
Page 10 - 6739380EN/JC
Introduction (cont.)
Installation with an engine
generator set
(figure 15)
If a stand-by generator is included in
the installation, it is generally started
automatically in the event of a
Mains failure and connected to the
main low voltage switchboard.
It is disconnected when Mains power is
restored.
With such a system, the required
battery time may be reduced to the
time necessary for starting and bringing
on line the stand-by generator.
The battery supplies power to the
inverter during the transfers:
Mains ➔ generator and
generator ➔ Mains.
The transfer sequences described:
Mains ➔ battery ➔ generator and
generator ➔ battery ➔ Mains are fully
automatic. They in no way affect the
load and require no manual operation
by the user.
UPS shutdown or overload
(systems with a static switch
module)
(figure 16)
Single-unit UPSs, modular UPSs or
UPSs with an SSC:
◗ in the event of a UPS shutdown
(initiated by the user or by an internal
protective device), the load is
automatically transferred to the Mains 2
bypass line. If transfer conditions are
correct, transfer takes place instantly,
without interruption to the load.
Note:
Transfer conditions are not correct
when Mains 2 characteristics are
outside tolerances (voltage: +/-10%;
frequency as per personalization;
phase sync with inverter +/-3°);
◗ in the event of a major transient
overload (greater than 160% of the full
load), immediate transfer takes place
as above, without interruption to the
load.
When the overload disappears, the
load is automatically returned to the
inverter depending on the configured
value of the re-transfer counter: no
return to inverter, or 1 to 255
(personalized value) overloads
accepted before the load is
permanently transferred to Mains 2.
This operating mode allows start-up of
load devices causing high inrush
currents.
Example of an installation with an engine generator set
Galaxy
HV
network
generator
G
main LV
switchboard
mains 2
mains 1
Fig. 15
Note:
To avoid load surges on the generator,
the rectifier/charger is started with a 10
second maximum current consumption
walk-in.
static switch
mains 2
mains 1
rectifiercharger
inverter
battery
Fig. 16
This system requires correct transfer
conditions. If the conditions are not
correct, the inverter will current limit to
160% of its rated current for 1 second
beep...beep...
!
!
before stopping;
◗ in the event of a small but extended
overload (i.e. a continuous level of
2
1
power exceeding the full rated load),
the inverter will continue to supply
power for a period depending on the
magnitude of the overload (10 minutes
for a 125% overload, 1 minute for a
150% overload). See figure 17
(Overload curve);
◗ in all three of the above cases, the
inverter shutsdown and supplies the
load via Mains 2 with the following
information on the control panel:
◗◗ green "load protected" light 5 off,
◗◗ buzzer 1 on,
◗◗ red "load not protected" light 2 on.
+–
load
I
O
6739380EN/JC - Page 11
Introduction (cont.)
Frequency converters without
redundancy
◗ in the event of a shutdown, the load
is no longer supplied with power;
◗ in the event of a major transient
overload (greater than 160% of the
rated load), the inverters will current
limit to 160% of their rated current for 1
second before stopping;
◗ in the event of a small but extended
overload (i.e. a continuous level of
power exceeding the full rated load),
the inverters will continue to supply
power for a period depending on the
magnitude of the overload (10 minutes
for a 125% overload, 1 minute for a
150% overload, see figure 17), and
then stop;
◗ in all three of the above cases,
inverter shutdown results in the
following on the control panel of the
concerned unit:
◗◗ green "load protected" light 5 off,
◗◗ buzzer 1 on,
◗◗ red "load not protected" light 2 on.
Frequency converters with
redundancy
◗ the shutdown of one unit is of no
consequence for the load. The other
lines each take up an equal amount of
load power and the load continues to
be supplied normally;
Inverter shutdown results in the
following on the control panel of the
concerned unit:
◗◗ green "load protected" light 5 off,
◗◗ buzzer 1 on,
◗◗ red "load not protected" light 2 on.
Overload curve
I
1,5 In
1,35 In
1,25 In
1,15 In
1,10 In
1,05 In
In
12345678910
◗ in the event of an overload, the
system only loses its redundancy as
long as the overload is less than the
total rated power of the functioning
units. If the overload is greater, the
operating mode is that previously
described for systems without
redundancy.
t
30120
(minutes)
Output voltage quality and
continuity
The output voltage is stable in
amplitude and frequency and is free of
interruptions or transients outside
specified tolerances, irrespective of
Mains 1 or load disturbances (outages,
load step changes, etc.).
Steady state voltage regulation:
For stable or slowly varying load
conditions, the inverter output voltage is
regulated to within +/-0.5% in
amplitude.
The frequency of the output voltage can
theoretically be regulated to within
0.1% of the rated value, however the
output frequency range may be
intentionally extended to a maximum of
+/-2Hz so that the inverter can remain
synchronized with Mains 2 and its
inherent frequency fluctuations, thus
enabling transfer of the load to the
bypass line at any time.
Fig. 17
Note:
The output frequency range can be
personalized and if necessary modified
on the customer site by a qualified
support technician from +/-0.25Hz
to +/-2Hz in 0.25Hz steps.
When the Mains 2 voltage moves
outside this frequency range, the
inverter is desynchronized and
operates in "free running" mode, with
the output frequency regulated to a
high level of accuracy by a quartz
oscillator.
When the Mains 2 frequency returns to
within the specified tolerances, the
inverter is gradually re-synchronized to
the bypass line at a rate of 0.5Hz to
2Hz/s (as per the value personalized by
the after-sales support department),
thus avoiding exposing the load to
sudden frequency variations.
Transient voltage regulation:
The inverter output voltage is not
notably affected by instantaneous
major variations in load characteristics.
This is due to the PWM (Pulse Width
Modulation) chopping technique and
the microprocessor-based regulation
system that instantly compensates for
any variation. In particular, the inverter
output voltage remains within +/-5% of
the rated voltage for load step changes
of 25 to 100% or of 100 to 25%.
Page 12 - 6739380EN/JC
Inverter cubicle
Description of MGETMGalaxyTM 6000 cubicles
The rated outputs for
TM
MGE
GalaxyTM 6000 UPS’s (without
parallel connection) or frequency
converters are 160, 200, 250, 300, 400,
500, 600 kVA.
Legend for figures 18 to 21:
1-rectifier-charger (RC) module
2-inverter stack modules
3-rack for electronic control boards
4-static switch module (Single-unit or
modular UPS)
4' - output static switch module
(modular UPS, frequency converter or
parallel UPS with SSC)
5-RC input fuses FU1-2-3
6-Mains 1 input switch Q1
7-protection fuses FU8 for the
Mains 2 resistance/capacitance voltage
surge protection network
8-Mains 2 input switch Q4S (Singleunit or modular UPS)
9-maintenance bypass switch Q3BP
(Single-unit or modular UPS)