APC BACK-UPS ES 700VA-BE700G-FR, BACK-UPS ES 400VA, BACK-UPS ES 550VA User Manual

1
Back-UPS
Connect Battery
For safety, the Back-UPS ES is shipped with one battery wire disconnected. The Back-UPS ES will not operate until the wire is connected to the touch safe battery terminal.
ES 400/550/700
User’s Guide
2
TURN the Back-UPS ES over and
12
slide the battery compartment cover off of the battery housing.
Connect Equipment
Battery Backup Surge Protection
These outlets are powered whenever the Back-UPS ES is switched ON. During a power outage or other utility problems (brownouts, over-voltages), these outlets will be powered for a limited time by the Back-UPS ES. Plug your computer, monitor, and two other data-sensitive devices (external disk or tape drive) into these outlets.
LIFT the battery out of the compartment and connect the black wire to the negative (-) battery terminal. Ensure the batteries are installed as shown below.
Place the Back-UPS ES to avoid:
- Direct sunlight
- Excessive heat
- Excessive humidity or contact with fluids
Plug the Back-UPS ES power cord directly into a wall outlet; not a surge protector or power strip. The wall outlet should be located near the equipment and be easily accessible.
Connect Modem / Phone / DSL / Fax / 10/100 Base- T/HPNA to Surge Protection.
The Back-UPS protects a single line (2-wire) phone (including Digital Subscriber line - DSL), Home Phoneline Networking Association (HPNA) type equipment, modem, 10/100. Base-T Ethernet, or fax machines from surges when connected through the UPS as shown in the drawing below.
Slide the battery compartment cover
3
back onto the battery housing.
AC LINE CORD
POWER ON/ REPLACE BATTERY INDICATOR
Surge Protection Only
These outlets provide full-time protection from surges even if the Back-UPS ES is switched OFF. Plug your printer, fax machine, scanner, or other peripherals that do not need battery power into these outlets.
Status Indicators
Note: Telephone Cable OR Network Cable should be connected to Surge Protection ports. Do not connect the UPS surge protection ports to both Telephone and Network System cables at the same time.
Connect Computer Cable (This is applicable for 550/700 only)
The supplied cable and software provide automatic file saving and shutdown of the operating system in the case of a sustained power outage.
Connect the cable to the Data Port of the Back-UPS ES. Connect the other end of the cable to the USB port on your computer. The software will automatically find the USB Port of your computer.
TO COMPUTER USB PORT (BACK-UPS ES 550 AND ES 700 ONLY)
FROM WALL JACK
DATALINE OUTPUT TO DSL MODEM,
PHONE, NETWORK
(10/100 Base-T)
CIRCUIT BREAKER PUSH TO RESET
Power On and
3
EN 990-2392A Copyright 2012 APC by Schneider Electric. 05/2012
Install Software
Press the ON/OFF switch to power the unit ON.
A single short beep and the green “Power On” indicator confirms that Back-UPS ES is on and ready to provide protection.
The Back-UPS ES should charge for at least 16 hours to ensure sufficient runtime. The unit is being charged whenever it is connected to utility power, whether the unit is turned ON or OFF.
Install the PowerChute Personal software (This is applicable for 550/700 only.)
Place the PowerChute Personal Edition CD­ROM into your computer and follow the installation instructions on the screen.
Edition
The Back-UPS ES indicates operating status using a combination of visual and audible indicators. Use the following table to identify the status of the Back-UPS ES.
Status Visual Indications
Power On - UPS is supplying conditioned
utility power to the load. On Battery - UPS is supplying battery
power to the load connected to the Battery outlets.
Low Battery Warning - UPS is supplying battery power to the load connected to the Battery outlets and the battery is near exhaustion.
Replace Battery - Battery is in need of charging or is at the end of its usual life and must be replaced.
Battery Disconnected - The battery is disconnected or bad battery.
Overload Shutdown - During On Battery operation a battery power supplied outlet overload was detected.
Sleep Mode - During On Battery operation the battery power has been completely exhausted and the UPS is waiting for utility power to return to normal.
See the Troubleshooting section for additional assistance.
(Power On - Green)
(Replace Battery - Red)
Power On LED - ON None Not applicable.
Power On LED - ON (off during beep)
Power On LED - flashing Rapid beeping (every
Power On and Replace Battery LEDs - Flashing (alternating)
Replace Battery LED ­flashing
None Constant tone UPS turned off with the
None Beeping once every 4
All trademarks are owned by Schneider Electric Industries S.A.S.,
Audible Indication Alarm Terminates
Beeping 4 times every 30 seconds
1/2 second)
Constant tone UPS turned off with the
Constant tone UPS turned off with the
seconds.
American Power Conversion, or their affiliated companies.
When
UPS transfers back to Power On operation, or when UPS is turned off.
UPS transfers back to normal operation, or when UPS is turned off.
power switch.
power switch.
power switch.
Utility power is restored, or if utility power is not restored within 32 seconds, or the UPS is turned off.
Troubleshooting
Use the table below to solve minor Back-UPS ES installation or operation problems. Consult APC Online Technical Support or call APC Technical Support for assistance with problems that cannot be resolved using the table below:
Problem Solution
Specifications
Warranty
Service
Input Voltage 230 Vrms Nominal
Frequency 50 - 60 Hz (auto sensing) Brownout Transfer 180 Vrms, typical Over-voltage Transfer 266 Vrms, typical
Output Voltage On Battery 230 Vac rms +/- 8%
Total Amperage (8 outlets) 10 Amps (including UPS output) UPS Capacity (4 outlets) 400VA/240W 550VA/330W 700VA/405W Frequency - On Battery 50/60 Hz +/-1 Hz Transfer Time 6 ms typical, 10 ms maximum
Protection and Filter AC Surge Protection Full time, 310 joules
Phone/fax/DSL Surge Protection
Single line (2-wire)
Network Surge Protection 10/100Base-T Ethernet EMI/RFI Filter Full time AC Input Resettable circuit breaker
Battery Type Sealed, maintenance-free lead acid
Average Life 3 - 5 years depending on the number of discharge
cycles and environmental temperature
Physical Net Weight 5.4kg 6.4kg 6.8kg
Dimensions (H x W x D) 285 x 230 x 86 mm
(11.18” x 9.05” x 3.3 in.)
Operating Temperature
0
o
C to 40 oC (32 oF to 104 oF)
Storage Temperature
-15
o
C to 45 oC (5 oF to 113 oF) Operating Relative Humidity 0 to 95% non-condensing Operating Elevation 0 to 3000 m (0 to 10,000 ft)
Safety/Regulatory Safety Approvals CE, NEMKO-GS, PCBC, GOST, IEC62040-1-1,
IEC60884, IEC61643-1
EMC Compliance EN50091-2, EN55022 Class B
The standard warranty is 2 years from the date of purchase. APC’s standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to assigned asset tags and set depreciation schedules must declare such a need at first contact with APC Technical Support. APC will ship the replacement unit once the defective unit is received by the repair department or cross-ship upon the provision of a valid credit card number. The customer pays for shipping to APC, and APC pays ground freight transportation costs back to the customer.
Please DO NOT RETURN Back-UPS ES to the place of purchase under any circumstances.
1. Consult the Troubleshooting section to eliminate common problems.
2. Verify the battery is connected (see Connect Battery) and that the Circuit Breaker is not tripped (see Troubleshooting section).
If you still have problems or questions, please contact APC via the internet or at one of the phone numbers listed below.
3. Before contacting APC, please be sure to record the date purchased, UPS model, and serial number (on bottom of unit).
4. Be prepared to troubleshoot the problem over the telephone with a Technical Support Representative. If this is not successful, the representative will issue a Return Material Authorization Number (RMA#) and a shipping address.
5. Pack the unit in its original packaging. If the original packaging is not available, ask APC Technical Support about obtaining a new set. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty (insuring the package for full value is recommended).
6. Write the RMA# on the outside of the package.
7. Return the unit by insured carrier to the address given to you by APC Technical Support.
Order Replacement Battery
Replace with an APC qualified battery. Replacement batteries can be ordered from www.apc.com (valid credit card required). For Back-UPS ES 400, order APCRBC106 as directed by APC Technical Support. For Back-UPS ES 550, order RBC2. For Back­UPS ES 700, order RBC17.
Item Specification BE400 BE550 BE700
The UPS can be mounted vertically or horizontally to a wall surface. Use the template below to position the mounting fasteners (not supplied). Wall mount the UPS as follows;
165 mm (6.50 in.)
Wall Mounting Template
Wall Mount of UPS
4. Mount the UPS by positioning the key-hole slots over the mounting fasteners heads. For vertical mounting, slide the UPS down into place. For horizontal mounting , Turn it slightly counterclockwise until it is securly in place.
3. Install the mounting fasteners at the marked locations. Leave the head of both fasteners 8 mm ( 5/16) out from the face of the wall. The fasteners must be able to support 6.8 Kg.
2. Use thumbtacks or tape to hold this page in place against the wall. Use a sharp nail or pin to puncture the center of each template circle to mark the wall.
1. Hold this page against the wall in the desired mounting location.
Problem
Solution
Battery is disconnected or utility power is not available at the wall outlet.
Surge Protection Only outlets have been overloaded.
Utility power not available at the wall outlet.
Equipment is connected to the Surge Protection Only outlets.
The Back-UPS ES is overloaded.
PowerChute Personal Edition software has performed a shutdown due to a power failure.
The Back-UPS ES has exhausted its available battery power.
Connected equipment does not accept the step­approximated sine waveform of the Back-UPS ES.
The Back-UPS ES may require service.
The Back-UPS ES is using battery.
Battery capacity is low (about 2 minutes of use remaining).
The battery is not fully charged. Battery is near the end of useful life.
Back-UPS ES will not turn on.
No power available at the Surge Protection Only outlets.
Connected equipment loses power.
The Power On indicator is lit and the Back­UPS ES is beeping four times every 30 seconds.
The Power On indicator flashes once per second and the Back-UPS ES beeps once per second at the same time.
Inadequate runtime.
Connect the battery (see Connect Battery) and ensure power is available at the wall outlet.
Reduce the amount of equipment plugged into Surge Protection Only outlets.
Ensure the fuse or circuit breaker for the outlet is not tripped, and that the wall switch controlling the outlet (if any) is in the ON position.
Ensure the equipment you want to stay powered during a power failure is plugged into the Battery Backup/Surge Protection outlets and NOT the Surge Protection Only outlets.
Make sure the equipment plugged into the Battery Backup/Surge Protection outlets of the unit are not overloading the capacity of the unit. Try removing some of the equipment and see if the problem continues.
The Back-UPS ES is operating normally.
The Back-UPS ES can only operate on battery power for a limited amount of time. The unit will eventually turn off when the available battery power has been used. Allow the unit to recharge for 16 hours before continuing use of the unit.
The output waveform is designed for computers and computer-related equipment. It is not designed for use with motor-type equipment.
Contact APC Technical Support for further troubleshooting.
The Back-UPS ES is operating normally and using battery power. Once On Battery, you should save your current work, power down your equipment, and turn the unit OFF . Once normal power is restored, you may turn the unit back ON and power your equipment.
The Back-UPS ES is about to shut off due to a low battery charge condition! When the unit beeps once every second, the battery has about 2 minutes of power remaining. Immediately power down your computer and turn the unit OFF. When normal power returns, the unit will recharge the battery.
Allow the unit to charge by leaving it plugged into the wall for at least 16 hours. As a battery ages, the amount of runtime available will decrease. You can replace
the battery by ordering one at www.apc.com. Batteries also age prematurely if the Back-UPS ES is placed near excessive heat.
Probable Cause
APC Contact Information
Technical Support http://support.apc.com Internet http://www.apc.com/ru Worldwide +1.800.555.2725 Russia 8 800 200-64-46 Ukraine 0 800 502-72-20