INTRODUCTION
The Network Management Teleservice Card (66124) is recommended for central UPSs protecting entire networks or for UPS units backing up critical loads. With the card installed, the UPS has its own IP address and uses the local computer capabilities to: supply web pages (http or https (SSL)) with information on status conditions and measurements/settings/alarms, integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli Netview and Computer Associates Unicenter, communicate with shutdown modules installed on the protected servers (Network Shutdown Module),
send e-mail and SMS messages, control the ON/OFF function of the UPS and the outlets, monitor the Environment Sensor, Access the Teleservice solution for remote monitoring and
maintenance services of your UPS.
The Network Management Teleservice Card must be installed and used in accordance with manufacturer instructions.
UNPACKING AND CHECKS
UPS Data CD
PHONE
ETHERNET
AC
T
RESET
000623001C07
100M
SENSOR/RS 485
( Settings)
66124
OVERVIEW
MAC adress
PHONE port:
Green LED : Phone communication with the UPS
Orange LED : Modem connection
ETHERNET port:
Green LED : Connection + activity
Orange LED : 10/100 M
Service port (Sensor/RS485):
Green LED : Communication with the UPS
Orange LED :RS232 activity
Catalogue number
INDICATIONS
One Network Management Teleservice Card (66124), One serial cable for configuration (3402226700), One phone cable for teleservice (3402226800), One installation manual (34022315EN), One Teleservice information form (3402228500),
Settings/Sensor
ETHERNET
Settings/Sensor
Settings/Sensor
Settings/Sensor
Settings/Sensor
100M
UPS data RS232
10M
66108
S e
ttin
g s
/S
en
so
r
E
TH
E
R N
E
T
S ettin
g s/S
en
so
r
S
ettin
g
s/S
e n
so
r
S e t t i n
g s / S e n
s o r
S e t t in g s /S
e n s o r
10 0 M
U
1
P
S d
ata
0
R
M
S 23
2
66124
Network Management Teleservice Card (66124)
Installation manual
PHONE port
LED Colour Status Description
UPS Data Green OFF
CD Orange
ETHERNET port
LED Colour Status Description
ACT Green OFF
100M Orange
Service port (Sensor/RS485)
LED Colour Status Description
Sensor Green OFF
RS485 Orange
ON
FlashingOFF
ONFlashing
ON
FlashingOFF
ON
ONFlashing
OFFFlashingFlashing
every seconds
Card not connected to phone
network
Card connected to phone
network, but no activity
Port is sending/receivingModem is not connected
Modem is connectedModem is connecting
Card not connected to networkCard connected to network, but
no activity
Port is sending/receivingPort operating at 10 Mbits/s
Port operating at 100 Mbits/s
Card startingCard readyCommunication with en vironment
Sensor is operational
Settings mode activatedPort is sending/receivingCommunication fault or
configuration errors
3402231500/AC
SWITCHES SETTING
Default settings, sensor configuration :
ON
SA1
1
3
3
8
ON
OFF
SA2
1
8
OFF
INSTALLATION
000623001C07
The Network Management Teleservice Card (66124) can be hot­plugged on MGE shutdown the UPS, disconnect the load or restart the UPS.
A. Remove the plastic cover of the Minislot.B. Note the MAC address of the card before inserting it. C. Connect the PHONE cable.D. Connect the ETHERNET cable (network already connected).E. Insert and secure the card with the screws.
A
000623001C07
Check the ETHERNET port indications. Wait until the UPS Data LED flashes regularly (approx. two minutes),
indicating that card start-up has terminated correctly.
TM
GalaxyTM 7000 UPSs. It is not necessary to
E
U
P S
D a
ta
C
D
E
T H
E R
N E
T S
E N
S O
R
/R S
4 8
5
P
H O
N E
A
C T
1 0 0 M
R
(
S
E
e t
S
t in
E
g
T
s )
6 6
1
24
UPS
DC
IP SETTINGS
Your network is not equipped with a BOOTP/DHCP server
Manual configuration is required. To set the network configuration(from the main configuration menu): ◗ Press the 2 key (Network configuration), then press the ↵ key.
Press the 2 key (Modify Network settings), then press the ↵ key.
Follow the instructions and enter the IP parameters:
1 : Read Network settings 2 : Modify Network settings 3 : Set ethernet speed
0 : Exit For each of the following questions, you can press "Return" to select the value shown in braces, or you can enter a new value Should this target obtain IP settings from the network?[N] N Static IP address [172.17.16.16]?172.16.1.82 Subnet mask IP address [255.255.0.0]? 255.255.255.0 Gateway address IP address [0.0.0.0]? 172.17.17.1 Done
Wait until "Done" is displayed, indicating that the IP parameters have been saved.
Press the 0 key (Exit), then press the ↵ key.
Press the 1 key (Reset), then press the ↵ key.
The card restarts with the new IP settings (after approx. two minutes).
ACCESS TO SUPERVISION
Once the card has started, proceed as indicated below.
Connect one end of the serial cable to the Service port.
Connect the other end of the cable to the COM (IOIOI) port of a PC.
Run a terminal emulator such as HyperTerminalTM with these settings
Bits per second Data bits Stop bits Flow control 38400 8 1 none
"Echo typed characters locally" option: disabled
Press the ↵ key.
press the 1 key (Network configuration menu)
Type MGEUPS (or mgeups), then press the ↵ key.
The main configuration menu is displayed
: APC by Schneider Electric
NETWORK MANAGEMENT CARD
1 : Reset 2 : Network configuration 3 : Set Login Password to Default 4 : Return to Default Configuration 0 : Exit
Your network is equipped with a BOOTP/DHCP server (default)
The card is configured by default with this service enabled. No manual configuration is required.The IP parameters are automatically collected by the card. To view the network configuration(from the main configuration menu):
Press the 2 key (Network configuration), then press the ↵ key.
Press the 1 key(Read Network settings)., then press the ↵ key.
The settings supplied by the server are displayed:
Network configuration :
MAC address : 00:06:23:00:1C:07 Mode : DHCP IP address : 172.17.23.18 Subnet mask : 255.255.248.0 Gateway : 172.17.17
Note the IP address.
Press the ↵ key
Press the 0 key (Exit), then press the ↵ key.
Press the 0 key (Exit), then press the ↵ key.
To check whether the
Network Management Teleservice Card
is
operational after installation and IP settings, proceed as follows.
Run a browser Enter in the address bar:
http://IP address/ (e.g. http://172.16.1.82/)
The home page is displayed:
Set the time by clicking the Time command.
Continue configuration via the sections in the Settings menu.
Teleservice procedure
Install the Network Management Teleservice Card kit using the
present manual.
Fill in the information form (3402228500).
Send the form to your Teleservice centre (by Fax or Internet).
Your centre will activate this service.
You receive an acknowledgement of receipt.
The information form must be sent back in order to trigger remote monitoring of your equipment.
USER MANUAL
The manual (34003991EN) provides all the information required to use, install and configure the
For more information on the supervision, control and configuration functions offered by the the user manual on the
Network Management Teleservice Card
Network Management Teleservice Card
www.apc.com
web site.
.
, see
3402231500/AC
SENSOR CONNECTION (option)
The Environment sensor is a Network Management Teleservice Card option.
The sensor remotely monitors the UPS environment by regularly measuring the temperature and humidity, and checking the states of two external contacts. It can also send alarms (e-mail, SNMP trap) tripped by pre-set thresholds. Connection is made via the Service port (Settings/Sensor) on the Network Management Teleservice Card. The sensor is detected automatically. Configuration and supervision use a menu that may be accessed directly from the home page. For more information, see the user manual of the Network Teleservice Management Card.
Settings/Sensor
ETHERNET
Settings/Sensor
U
PS
dat
a
R
S2
3
PHONE
ETHERNET
2
1 00
M
10
O
n =
L i
nk
B
lin
k =
A
c t
Settings/Sensor
M
U
PS
d
at
ETHERNET
a
R
S2
3 2
66102
Settings/Sensor
100
M
1
0M
UPS
TECHNICAL CHARACTERISTICS
Physical characteristics
Dimensions (W x D x H) 132 x 66 x 42 mm Weight 85 g RoHS 100% compatible
Storage
Storage temperature range
Ambient conditions
Operating temperature range
Relative humidity 90% RH max. without condensation
Card performance
Supply voltage 5V ±5% Supply current (all LEDs
ON and Environment Sensor connected)
Functions
Web supervision 5 browsers max. (http),
Languages English Alarms E-mail, SNMP TRAP, Web page Log 400 measurements or events Server protection Up to 35 servers protected Network Fast ETHERNET, 10/100 Mbits, auto-negotiation
Identification User name and password Security SSL 3.0, TLS 1.0 Browsers Microsoft Internet Explorer 6.x or higher NMS Enterprise Power Manager (EPM)
MIB MIB II standard - MGE V1.7 MIB
Settings (default values)
IP network BOOTP/DHCP enabled
Web-page access control User name: MGEUPS
Service-port menu access control
Date and time Synchronise with an NTP server (GMT) Service port 38400 bits/s, 8 bits, 1 bit stop, no parity
Standards
ITE (Information Technology Equipment) safety
R&TTE 99/05/EEC EMC EN 61000-6-2 (2005), EN 61000-6-3 (2006)
Low voltage 2006/95/EEC FCC (Federal
Communication Commission )
-10°C to 70°C
0°C to 40°C
500 mA max.
3 browsers max. (https)
HTTP 1.1, SNMP V1, NTP, TFTP, SMTP, BOOTP/DHCP
Management-Pac 2
IP address: 172.17.16.16 Subnet mask: 255.255.0.0 Gateway: 0.0.0.0 NTP server: pool.ntp.org
Password: MGEUPS Password: MGEUPS or mgeups
(not modifiable)
IEC/EN 60950-1 (2005)
2004/108/EEC
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
3402231500/AC