A. O. Smith HWI-S 0648 10 User Manual

Page 1
Commercial Semi-Instantaneous Water Heaters
FEATURES
INSUL ATION AND JACKETING - T he HWI systems will be insulated with
fiberglas s to an R value of 12.5 and enclosed in a baked enamel ja cket.
CODE LISTING
ASME “U” code 3/4” diameter copper tube heat exchang er.
INTEGRAL PUMP
pump.
STEAM UNITS
auxiliary steam traps, inlet and auxiliar y strainers, steam pressure gauge with siphon , vacuum breaker and air vent.
BOILER UNITS
water temperature gauge.
CONTROL FEATURES
n
SINGLE POINT WIRING
Single 120V connection, controls including integral circulation
n
ON/OFF SWITCH
Allows local on/off for service
n
TEMPERATURE READOUT
LED readout of water temperature
n
PID TEMPERATURE CONTROL
Modulates electrical control valve
n
HIGH TEMPERATURE LIMIT
Closes main valve under over temperature condition
n
REMOTE TEMPERATURE SIGNAL
n
2-WIRE RS485 COMMUNICATION (MODBUS or ASCII)
- The system will employ an A SME”U” code shell. fitted with an
- The HWI system will employ an integral bronze circulator
- Steam trim consists of temperature control valve, inlet and
- Boiler water trim includes temperature control valve and boiler
HWI Models
LIMITED WARRANTY OUTLINES
If the shell should leak any time during the first five years, under the terms of the warranty A. O. Smith will repair or replace the shell. Installation, labor, handling and local delivery extra.
THE COIL HAS A ONE YEA R LIMITED WARRANTY.
NOTE: THIS OU TLINE IS NOT A WA RR ANTY. For complete information, consult the written warrant y or A. O. Smith.
U
Revised November 2012
Page 1 of 8
AOSCG40100
Page 2
Commercial Semi-Instantaneous Water Heaters
TO SPECIFY HWI SERIES PACKAGE WATER HEATER:
1. Determine what t ype of heating medium will be used; steam or b oiler water.
• If STEAM - Determine pressure in coil.
• If BOILER WATER - Determine available boiler water temperature.
2. From the recovery table, obtain the required GPH capa cit y and temperature rise. Selecting heating coil size.
3. Decide whether single or double wall coil is required.
SE LE CT YOUR M OD EL
ST YL E CO IL M OD EL TY PE
CAPACITY CHARTS:
Temp Range Heater Model
40°F
To
120°F
40°F
To
140°F
HWI-W 0848 HWI-W 1048 HWI-W 1248 HWI-W 1448 HWI-W 1648 HWI-W 1848
HWI-W 0848 HWI-W 1048 HWI-W 1248 HWI-W 1448 HWI-W 1648 HWI-W 1848
HWI
CHOS EN F ROM TABLE S TO DETE RMIN E CODE SI ZE
ST EA M = S WATE R = W
0 8 4 8S E15 D
Boiler Water 180°F - 160°F
DOM water
flow GPM
11 19 26 35 47 59
7 12 17 22 30 39
DOUB LE WALL = D SING LE WALL = S
ST EA M PRE SS UR E
WATER TEMPERATURE
Boiler Water
flow GPM
45
77 106 143 192 241
35
61
86 112 152 198
BTU/HR Passes
438,000
756,000 1,035,000 1,393,000 1,870,000 2,347,000
347,000
596,000
844,000 1,092,000 1,489,000 1,936,000
2 2 2 2 2 2
4 4 4 4 4 4
Boiler Water 190°F - 170°F
Temp Range Heater Model
HWI-W 0848
40°F
To
120°F
40°F
To
140°F
For Technical Information and Automated Fax Service, call 800-527-1953. A . O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised November 2012
HWI-W 1048 HWI-W 1248 HWI-W 1448 HWI-W 1648 HWI-W 1848
HWI-W 0848 HWI-W 1048 HWI-W 1248 HWI-W 1448 HWI-W 1648 HWI-W 1848
DOM water
flow GPM
13 22 31 41 55 68
8 14 19 26 35 44
Boiler Water
flow GPM
53
90 127 167 225 278
41
71
97 133 178 224
BTU/HR Passes
517,000
875,000 1,234,000 1,631,000 2,189,000 2,706,000
397,000
695,000
943,000 1,291,000 1,738,000 2,185,000
www.hotwater.com
2 2 2 2 2 2
2 2 2 2 2 2
Page 2 of 8
AOSCG40100
Page 3
CAPACITY CHARTS (Continued):
Commercial Semi-Instantaneous Water Heaters
Temp Range Heater Model
40°F
To
120°F
40°F
To
140°F
Steam pressure in lines/steam pressure in tubes.
*
Temp Range Heater Model
40°F
To
120°F
40°F
To
140°F
Steam pressure in lines/steam pressure in tubes.
*
HWI-S 0648 05 HWI-S 0848 05 HWI-S 1048 05 HWI-S 1248 05 HWI-S 1448 05 HWI-S 1648 05
HWI-S 0648 05 HWI-S 0848 05 HWI-S 1048 05 HWI-S 1248 05 HWI-S 1448 05 HWI-S 1648 05
HWI-S 0648 10 HWI-S 0848 10 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
HWI-S 0648 10 HWI-S 0848 10 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
10 10 10 10
10 10 10 10
Steam 5/2*
DOM water flow GPM Ibs /HR
11 20 33 47 61 82
7 14 23 34 43 58
Steam 10/5*
DOM water flow GPM Ibs /HR
11 21 35 51 66 87
8 15 25 36 48 63
617
778 1285 1848 2369 3185
363
686 1130 1648 2096 2821
459
846 1373 2030 2649 3472
410
755 1250 1807 2380 3119
Temp Range Heater Model
HWI-S 0648 15
40°F
To
120°F
40°F
To
140°F
Steam pressure in lines/steam pressure in tubes.
*
For Technical Information and Automated Fax Service, call 800-527-1953. A . O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised November 2012
HWI-S 0848 15 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
HWI-S 0648 15 HWI-S 0848 15 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
15 15 15 15
15 15 15 15
Steam 15/10*
DOM water flow GPM Ibs /HR
12 23 38 56 73 96
9 17 28 40 53 69
512
946 1546 2268 2968 3889
467
861 1420 2045 2691 3510
www.hotwater.com
Page 3 of 8
AOSCG40100
Page 4
CAPACITY CHARTS (Continued):
Commercial Semi-Instantaneous Water Heaters
Temp Range Heater Model
40°F
To
120°F
40°F
To
140°F
Steam pressure in lines/steam pressure in tubes.
*
Temp Range Heater Model
40°F
To
120°F
40°F
To
140°F
Steam pressure in lines/steam pressure in tubes.
*
HWI-S 0648 20 HWI-S 0848 20 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
HWI-S 0648 20 HWI-S 0848 20 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
HWI-S 0648 30 HWI-S 0848 30 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
HWI-S 0648 30 HWI-S 0848 30 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
20 20 20 20
20 20 20 20
30 30 30 30
30 30 30 30
Steam 20/15*
DOM water flow GPM Ibs /HR
13 25 41 60 76
103
10 18 30 44 57 75
Steam 30/20*
DOM water flow GPM Ibs /HR
14 26 44 63 83
109
10 19 32 46 61 80
558 1031 1699 2455 3130 4210
515
934 1546 2246 2844 3840
600 1097 1824 2619 3434 4498
544 1000 1664 2399 3157 4132
Temp Range Heater Model
HWI-S 0648 50
40°F
To
120°F
40°F
To
140°F
Steam pressure in lines/steam pressure in tubes.
*
For Technical Information and Automated Fax Service, call 800-527-1953. A . O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised November 2012
HWI-S 0848 50 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
HWI-S 0648 50 HWI-S 0848 50 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
50 50 50 50
50 50 50 50
Steam 50/30*
DOM water flow GPM Ibs /HR
16 29 48 69 91
119
11 21 35 51 67 88
676 1227 2024 2913 3818 5000
609 1124 1863 2696 3531 4625
www.hotwater.com
Page 4 of 8
AOSCG40100
Page 5
CAPACITY CHARTS (Continued):
Commercial Semi-Instantaneous Water Heaters
Temp Range Heater Model
40°F
To
120°F
40°F
To
140°F
Steam pressure in lines/steam pressure in tubes.
*
HWI-S 0648 75 HWI-S 0848 75 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
HWI-S 0648 75 HWI-S 0848 75 HWI-S 1048 HWI-S 1248 HWI-S 1448 HWI-S 1648
75 75 75 75
75 75 75 75
Steam 20/15*
DOM water flow GPM Ibs /HR
18 33 54
78 100 135
13
24
40
59
74 100
783 1425 2343 3372 4318 5793
723 1319 2182 3162 4121 5401
For Technical Information and Automated Fax Service, call 800-527-1953. A . O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised November 2012
www.hotwater.com
Page 5 of 8
AOSCG40100
Page 6
Commercial Semi-Instantaneous Water Heaters
MODEL
HWI10648 HWI10848 HWI41048
HWI1248 HWI1448 HWI1648
HWI1848
A B C D
110 36 24 38 110 36 26 38 110 36 28 38 110 36 30 38 110 36 32 38 110 36 34 38
110 36 36 38
A
D
PRIMARY
FUSES
1.5 A
AUTO HIGH LIMIT
HONEYWELL L6008A
120VAC
BLK
WHT
B
BLK
WHT
CONTROL BOX
X-FMR
24V SEC.
FUSE
24VAC
SEC
BLK
WHT
PILOT SWITCH
BLK
WHT
WEST
TEMP PROBE
PUMP SWITCH
CIRC. PUMP
EQUIP
GND
RED
RED
WHT
FIELD WIRE 120VAC
CONTROLLER
C
VALVE AC TUATOR
SIEMENS SKD62U
RED
BLU
For Technical Information and Automated Fax Service, call 800-527-1953. A . O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised November 2012
www.hotwater.com
Page 6 of 8
AOSCG40100
Page 7
Commercial Semi-Instantaneous Water Heaters
SPECIFIC ATIONS - STEAM TO WATER
The instantaneous hot water generator package shall be A .O. Smith model HWI , (EDS) or (ESS) with _ ______1 heating coil. The jacketed and insulated heater shall have a 316L stainless steel vessel constructed in accordance with ASME section VIII for a working pressure of 150psi. The heater shall be de signed to recover _ _ _ _ _gpm for a temperature rise of _ _ _ _ degrees F to _ _ _ _ _ degrees F when supplied with ____ psig s team to the control valve. T he heating coil shall be constructed in accordan ce with ASME section VIII code. Single wall heat exchanger s shall have 3 /4” O.D., 20GA deoxidize d drawn copper tube s. Double wall heat exchangers shall have 5 /8” I.D. deoxidized drawn copper tube within a tube. The external tube shall have radial fins for enhanced h eat transfer. Each coil shall have s tainless steel baffles and shell side tube she et.
The heater shall be fac tory assembled and piped including y -s trainer, electric actuate d control valve, main and auxiliar y s team traps, condensate strainer, bronze integral circulator piped and wired to circulate water across the coil, vacuum breaker, air vent, ASME temperature and pre ssure relief valve and incoming steam pressure gauge.
SPECIFIC ATIONS - WATER TO WATER
The instantaneous hot water generator package shall be A .O. Smith model HWI , (EDW )- (2) or (4), (ES W)-(2) or (4) with ______ _ _- _ _ _ __ pas s heating coil. The jacketed and insulated heater shall have a 316L stainless steel vessel constructed in accordan ce with ASME section VIII for a working pressure of I5Opsi.
The heater shall be designed to recover _____gpm for a temperature rise of — — — — degrees F to _ _ _ _ _ d egrees F whe n supplied with ____ gpm of — — —, degrees F boiler water to the control valve. The heating coil shall be construc ted in accordance with ASME section VIII code. Single wall heat exchangers shall have 3/4” O.D., 20GA deoxidized drawn copper tubes. Double wall heat exchangers shall have 5/8” I.D. deoxidized drawn copper tube within a tube. The external tube shall have radial fins for enhanced heat transfe r. Each coil shall have stainless steel baffles and shell side tube sheet. The heater shall be factor y assembled and piped inclu ding elec tric actuated __ _ _ _ 3-way or __ _ _ 2-way control valve, bronze integral circulator piped and wired to circulate water across the coil, ASME temperature and pressure relief valve and incoming boiler water temperature gauge.
TEMPERATURE CONTROL
The heater shall be supplied with a (PID) solid st ate temperature controller with dual LED display. The controller shall have remote temperature selection, a green temperature set ting display screen and high limit display screen, The controller shall be supplied with output contact to interface with building automation s ys tem for power on and high temp erature limit statu s. The controller shall allow the building automation sy stem to turn the unit on or off through a 24VAC relay. The controller shall have u ser-selectable communications interface of 2-wire RS485 (MODBUS or ASCII) or of f-line PC configuration.
For Technical Information and Automated Fax Service, call 800-527-1953. A . O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised November 2012
www.hotwater.com
Page 7 of 8
AOSCG40100
Page 8
Commercial Semi-Instantaneous Water Heaters
For Technical Information and Automated Fax Service, call 800-527-1953. A . O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Revised November 2012
www.hotwater.com
Page 8 of 8
AOSCG40100