A. O. Smith ET-5, PMET-2 Installation Manual

RESIDENTIAL & COMMERCIAL
HYDRONIC SPACE HEATING SYSTEM
EXPANSION TANK
INSTALLATION INSTRUCTIONS
SIZES 2 THROUGH 86 GALLON
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others
of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use or service this water heater.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
W ARNING
CAUTION
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and how to avoid the risk of injury.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage.
PRINTED 0210 205786-001
PURPOSE OF EXPANSION TANKS
When water is heated it expands. Provision must be made for this expansion in a closed hot water heating system. This precharged diaphragm tank stores the expanded hot water and returns Air Free water to the system when the temperature drops.
INSTALLATION
Install into a tee or tapping anywhere in the hot water heating system. A residential tank may be installed vertically or horizontally. The tank may also be installed remotely and piped to system. A commercial tank must be installed vertically only.
For best installation, install the tank into the airout with the float vent as shown below. The airout device will provide both a mounting tee and continuous automatic air removal from the system.
WARNING
This expansion tank is designed and intended for water storage at a maximum pressure of 100 psig and a maximum temperature of 240°F. Any use other than water or at a sustained or instantaneous pressure in excess of 100 p sig is UNSAFE. A pressure relief valve of adequate size must be incorporated in the system.
CAUTION
This expansion tank, as all expansion tanks, will eventually leak. Do not install without adequate drainage provisions where water flow will cause damage. The manufacturer of this tank does not accept any liability or other responsibility for personal injury or property damage resulting from improper use, installation or operation of this tank, or of the system of which it is a part.
RESIDENTIAL
Note: This tank was shipped with 12 psi air charge. NEVER LET AIR FROM TANK. Air charge
should always equal setting of reducing valve (12 pounds is standard.)
COMMERCIAL
Loading...
+ 2 hidden pages