A.O. Smith DRE - 80, DRE - 120 User Manual

COMMERCIAL ELECTRIC
WATER HEATERS
DRE-52, 80, 120
Designed for use as a recovery heater having its own storage tank. Note: Not recommended for sanitizing water application.
FEATURES
ELEMENTS - Incoloy sheathing for longer life. Low watt density; means lower surface temperature to minimize scale buildup and more surface to heat water. Element sizes from 3 to 6 Kw. Use 3, 6 or 9 elements standard; total of 6 to 54 Kw input (see chart on back).
STANDARD VOLTAGES - 208, 240 and 480V single-phase and three-phase delta; 277V single-phase also available.
TERMINAL BLOCK - Factory installed. Just bring the service to the heater and connect to block.
CONTROLS - One temperature control adjustable through a range of 120° to 180°F (49° to 82°C) and manual reset high temperature cutoff per element. Thermostat step control may be achieved by varying settings on individual temperature controls. Located behind hinged control compartment door for quick, easy access.
Meets or exceeds the requirements of ASHRAE 90.1b­1992 Standard for energy efficiencies.
OTHER STANDARD FEATURES
• Simplified circuitry , color coded for ease of service • Two anode rods for maximum corrosion protection • Cabinet has bonderized undercoat with baked enamel finish • Bottom inlet and top outlet openings • Brass drain valve • C.G.A./ ASME temperature and pressure relief valve • Single panel control box.
OPTIONAL
FUSING - Protects all elements, thermostats, and internal wiring circuits against excess current flow. Meets Canadian Electric Code requirements.
Manifold kits with gate valves - available for multiple installation.
ASME 160 psi tank construction.
GOLDENROD ELEMENTS - All DRE models are available with the Goldenrod 24K gold plated elements (patent pending).
Goldenrod elements provide long life and 6 times the scaling resistance of standard incoloy elements. Goldenrod elements carry a three-year warranty against failure due to scale.
Revised June 2001
ASME
(OPTIONAL)
LIMITED WARRANTY OUTLINE
If the tank should leak any time during the first three years, under the terms of the warranty , A.O. Smith will furnish a replacement heater; installation, labor, handling and local delivery extra. THIS OUTLINE
IS NOT A WARRANTY.
For complete information, consult the written warranty or A. O. Smith Water Products Company .
A 211.0C
RECOVERY CAP ACITY IN GALLONS A T TEMPERA TURE RISE OF
Standard BTU/ 30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F 120°F 130°F 140°F kW Input Hour 17°C 22°C 28°C 33°C 39°C 45°C 50°C 56°C 61°C 67°C 72°C 78°C
6 20,478 82 62 49 41 35 31 27 25 22 21 19 18 9 30,717 123 92 74 62 53 46 41 37 34 31 28 26
12 40,956 164 123 98 82 70 61 55 49 45 41 38 35
13.5 46,075 184 138 111 92 79 69 62 55 50 46 43 40 15 51,195 205 154 123 102 88 77 68 61 56 51 47 44 18 61,434 246 184 148 123 105 92 82 74 67 62 57 53 24 81,912 328 246 197 164 140 123 109 98 90 82 76 70 27 92,151 369 276 221 185 158 138 123 111 101 92 85 79 30 102,390 410 307 246 205 176 154 137 123 112 102 95 88 36 122,868 492 369 295 246 21 1 184 164 148 134 123 113 105
40.5 138,226 554 418 332 277 237 208 185 166 151 138 128 119 45 153,585 615 461 369 307 263 230 205 184 168 154 142 132 54 184,302 738 554 443 359 316 277 246 221 201 185 170 158
Figured at 1 KW (3413 BTU) = 4.1 Gallons at 100°F temperature rise. NSF ratings may be obtained by multiplying the above figures by 0.98.
310 233 166 155 133 116 103 93 85 78 72 66 465 349 279 233 199 174 155 140 127 116 107 100 620 465 372 310 266 233 207 186 169 155 143 133 698 523 419 349 299 262 233 209 190 174 161 150 775 582 465 388 332 291 258 233 211 194 149 166
930 698 558 465 399 349 310 279 254 233 215 199 1241 930 744 620 532 465 414 372 338 310 286 266 1396 1047 938 609 509 523 465 410 391 340 322 299 1551 1163 930 775 665 582 517 465 423 388 358 332 1861 1396 1117 930 798 698 620 556 508 465 429 399 2094 1570 1256 1047 897 785 698 628 634 582 537 498 2326 1745 1398 1163 997 872 755 698 634 582 537 498 2791 2094 1675 1396 1196 1047 930 837 761 696 644 598
Model Capacity A B C Outlet (NPT) Wt. (Lbs.) Number gal. litre in. cm in. cm in. cm in. cm lb kg
DRE-52 50 189 55 1/4 140.3 21 3/4 55.2 27 1/4 69.2 1 1/4 3.2 265 120 DRE-80 80 300 59 1/2 151.1 25 1/4 64.1 31 1/4 79.4 1 1/4 3.2 280 127 DRE-120 119 450 62 1/4 158.1 29 1/2 75.0 35 3/4 90.8 1 1/4 3.2 390 177
Model Numbers Number Full Load Current In Amperes
KW Tank Capacity in Gallons Of Element Single Phase Three Phase
Input 50 80 119 Elements Wattage 208V 240V 277V 480V 208V 240V 480V
6 DRE-52-6 DRE-80-6 DRE-120-6 3 2,000 28.8 25.0 21.7 12.5 16.7 14.4 7.2 9 DRE-52-9 DRE-80-9 DRE-120-9 3 3,000 43.3 37.5 32.5 18.8 25.0 21.7 10.8
12 DRE-52-12 DRE-80-12 DRE-120-12 3 4,000 57.7 50.0 43.3 25.0 33.3 28.9 14.4
13.5 DRE-52-13.5 DRE-80-13.5 DRE-120-13.5 3 4,500 64.9 56.3 48.7 28.1 37.5 32.5 16.2 15 DRE-52-15 DRE-80-15 DRE-120-15 3 5,000 72.1 62.5 54.2 31.3 41.6 36.1 18.0 18 DRE-52-18 DRE-80-18 DRE-120-18 3* 6,000 86.5 75.0 65.0 37.5 50.0 43.3 21.7 24 DRE-52-24 DRE-80-24 DRE-120-24 6 4,000 115.4 100.0 86.6 50.0 66.6 57.7 28.9 27 DRE-52-27 DRE-80-27 DRE-120-27 6 4,500 129.8 112.5 97.5 56.3 74.9 65.0 32.5 30 DRE-52-30 DRE-80-30 DRE-120-30 6 5,000 144.2 125.0 108.3 62.5 83.3 72.2 36.1 36 DRE-52-36 DRE-80-36 DRE-120-36 6* 6,000 173.1 150.0 130.0 75.0 99.9 86.6 43.3
40.5 DRE-52-40.5 DRE-80-40.5 DRE-120-40.5 9 4,500 194.7 168.8 146.2 84.4 112.4 97.4 48.7 45 DRE-52-45 DRE-80-45 DRE-120-45 9 5,000 216.3 187.5 162.5 93.8 124.9 108.3 54.1 54 DRE-52-54 DRE-80-54 DRE-120-54 9 6,000 N/A 225.0 194.9 112.5 149.9 129.9 65.0
*208 volt models may contain three (3) additional elements.
Tank Dimensions Inlet/ Approx. Ship.
SUGGESTED SPECIFICA TIONS
The heater(s) shall be Dura-Power Commercial Electric Model Number _______________ as manufactured by A.O. Smith Water Products Company or equivalent. Heater(s) shall be rated at ______________ KW ________ V _____________ phase, 60 cycle AC listed by Canadian Standards Association. Tank(s) shall be ________ gallon (Liter) capacity. Heater(s) shall have 150 psi (1034 kPa) working pressure and be equipped with extruded high density anode. All internal surfaces of the heater(s) exposed to water shall be glass-lined with an alkaline borosilicate composition that has been fused to steel by firing at a temperature range of 1400°F to 1600°F (760° to 870°C). Electric heating elements shall be low watt density with incoloy sheath and 1" screw-in type. Each element shall be controlled by an individually mounted thermostat and high temperature cut-off switch. All internal circuits shall be fused (optional). The outer jacket shall be of baked enamel finish and shall be provided with full size control compartment for performance of service and maintenance through hinged front panel and shall enclose the tank with vermin proof foam insulation. Electrical junction box with heavy duty terminal block shall be provided. The drain valve shall be located in the front for ease of servicing. Heater tank shall have a three year limited warranty as outlined in the written warranty. Manufacturer shall supply ASME rated temperature and pressure relief valve. Fully illustrated instruction manual to be included.
A 212.0C
A.O. Smith Water Products Co., Inc. On Line
www.hotwater.com
For Technical Information
Phone: 800-265-8520
A. O. Smith Enterprises Ltd. A Division of A. O. Smith Corporation Stratford, Ontario
A. O. Smith Corporation reserves the right to make product changes or improvements at any time without notice.
© A. O. Smith Corp., 2001
McBee, South Carolina El Paso, Texas Seattle, Washington Veldhoven, The Netherlands
Printed in U.S.A.