A.O. Smith BTL-120, BTL-154, BTL-180, BTL-198, BTL-199 Installation Manual

...
Page 1
Instruction Manual
COMMERCIAL GAS WATER HEATERS
MODELS
BTL 120, 154, 180, 198, 199,
500 Tennessee Waltz Parkway
Ashland City, TN 37015
INSTALLATION - OPERATION - SERVICE
- MAINTENANCE - LIMITED WARRANTY
Complies with SCAQMD Low NOx Rule 1146.2
Ultra Low NOx SERIES 200
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier,
call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Thank you for buying this energy efcient water heater. We appreciate your condence in our products.
Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater.
Failure to follow these instructions and safety messages could result in death or serious injury.
This manual must remain with the water heater.
PLACE THESE INSTRUCTIONS ADJACENT TO HEATER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.
PRINTED 0914 327502-005
Page 2
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE.............................3
APPROVALS ............................................................................. 3
GENERAL SAFETY INFORMATION ......................................... 4
Precautions .......................................................................... 5
Grounding Instructions ......................................................... 5
Hydrogen Gas Flammable ................................................... 5
INTRODUCTION ....................................................................... 6
Abbreviations Used .............................................................. 6
Qualications........................................................................ 6
Preparing for the Installation ................................................ 6
FEATURES AND COMPONENTS ............................................6
Controls ................................................................................ 6
The Eliminator (self-cleaning system) .................................. 6
High Limit Switch.................................................................. 7
Electronic Ignition Control .................................................... 7
Blower/Burner Assembly ...................................................... 7
INSTALLATION CONSIDERATIONS ........................................ 8
Rough In Dimensions ........................................................... 8
Locating the Water Heater ................................................... 9
Clearances ........................................................................... 9
NSF Leg Kit ........................................................................ 10
Insulation Blanket ............................................................... 10
Hard Water ......................................................................... 10
Circulation Pumps .............................................................. 10
High Altitude Installations ................................................... 11
INSTALLATION REQUIREMENTS ......................................... 12
Gas Supply Systems .......................................................... 12
Gas Pressure Requirements .............................................. 12
Supply Gas Regulator ........................................................ 12
Power Supply ..................................................................... 12
Water Temperature Control and Mixing Valves .................. 12
Dishwashing Machines ......................................................13
Closed Water Systems ....................................................... 13
Thermal Expansion ............................................................ 13
Temperature-Pressure Relief Valve ...................................13
Combustible Material Storage ............................................ 14
Contaminated Air................................................................14
Air Requirements ...............................................................15
Unconned Space .............................................................. 15
Conned Space.................................................................. 15
Fresh Air Openings for Conned Spaces ........................... 16
Outdoor Air Through Two Openings ................................... 16
Outdoor Air Through One Opening .................................... 16
Outdoor Air Through Two Horizontal Ducts ........................ 16
Outdoor Air Through Two Vertical Ducts ............................ 17
Air From Other Indoor Spaces ........................................... 17
VENTING INSTALLATION ...................................................... 18
Venting ............................................................................... 18
Multiple Heater Manifold ....................................................18
WATER HEATER INSTALLATION ...........................................21
Water Line Connections ..................................................... 21
T&P Valve Discharge Pipe ................................................. 21
Installation Diagrams - Top Inlet/Outlet Usage ................... 22
Heater Wiring ..................................................................... 23
Gas Piping.......................................................................... 24
Gas Line Leak Testing ........................................................ 24
Purging ............................................................................... 24
START UP ............................................................................... 25
Prior to Start Up .................................................................25
Initial Start Up..................................................................... 25
Checking Venting ............................................................... 26
Checking the Input ............................................................. 26
Water Temperature Adjustment .......................................... 26
SEQUENCE OF OPERATION ................................................ 27
Lighting & Operating Label................................................. 27
Sequence of Operation Flow Chart .................................... 28
MAINTENANCE .....................................................................29
Venting System .................................................................. 29
Intake Air Screen ................................................................ 29
Temperature-Pressure Relief Valve Test ............................ 29
Anode Rod Inspection ........................................................ 29
Draining and Flushing ........................................................ 30
Periodic Removal of Lime Deposits from Tank Type Commercial
Water Heaters .................................................................... 30
Deliming Solvents ..............................................................30
Tank Cleanout Procedure................................................... 31
Deliming Using Flo-Jug Method ......................................... 31
SERVICE ................................................................................. 32
Ignition Control System ...................................................... 32
System Diagnostics............................................................ 32
Electrical Servicing ............................................................. 32
FOR YOUR INFORMATION .................................................... 33
Start Up Conditions ............................................................ 33
Operational Conditions....................................................... 33
TROUBLESHOOTING ............................................................34
WATER PIPING DIAGRAMS ................................................... 35
NOTES .................................................................................... 50
LIMITED WARRANTY ............................................................. 51
2
Page 3
SAFE INSTALLATION, USE AND SERVICE
The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use, or service this water heater.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently
DANGER
WARNING
CAUTION
hazardous situation which, if not avoided, will result in injury or death.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury.
CAUTION used without the safety alert
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances.
WARNING: This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This appliance can cause low level exposure to some of the substances listed in the Act.
symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage.
APPROVALS
3
Page 4
GENERAL SAFETY INFORMATION
CAUTION
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell gas.
Do not expose water heater controls to excessive gas pressure.
Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended periods of non-use.
Read instruction manual before
installing, using or servicing
water heater.
Fire Hazard
For continued protection against risk of fire:
Do not install water heater on carpeted floor.
Do not operate water heater if exposed to flooding or water damage.
Fire and Explosion Hazard
Use joint compound or Teflon tape compatible with propane gas.
Leak test before placing the water heater in operation.
Disconnect gas piping and main gas shutoff valve before leak testing.
Install sediment trap in accordance with NFPA 54.
Property Damage Hazard
All water heaters eventually leak.
Do not install without adequate drainage.
Electrical Shock Hazard
Turn off power to the water heater
before performing any service.
Label all wires prior to disconnecting
when performing service. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
Failure to follow these instructions can
result in personal injury or death.
Fire and Explosion Hazard
Do not use water heater with any gas other than the gas shown on the rating label.
Excessive gas pressure to gas valve can cause serious injury or death.
Turn off gas lines during installation. Contact a qualified installer or service
technician for installation and service.
Jumping out control circuits or components can
result in property damage, personal injury or death.
Service should only be performed by a qualified service
technician using proper test equipment.
Altering the water heater controls and/or wiring in any way
could result in permanent damage to the controls or water heater and is not covered under the limited warranty.
Any bypass or alteration of the water
heater controls and/or wiring will result
in voiding the water heater warranty.
4
Page 5
GENERAL SAFETY INFORMATION
Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater.
Failure to follow these instructions and safety messages could result in death or serious injury.
This manual must remain with the water heater.
Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.
Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures.
Explosion Hazard
Overheated water can cause water tank explosion.
Properly sized temperature and pressure relief valve must be installed in the opening provided.
CAUTION
Improper installation, use and service may result
in property damage.
Do not operate water heater if exposed to flooding or
water damage.
Inspect anode rods regularly, replace if damaged.
Install in location with drainage.
Fill tank with water before operation.
Properly sized thermal expansion tanks are required on all
closed water systems.
Refer to this manual for installation and service.
Verify the power to the water heater is turned off before performing any service procedures.
GENERAL SAFETY INFORMATION
PRECAUTIONS
DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN EXPOSED TO FLOODING OR WATER DAMAGE. Immediately call a qualied service technician to inspect the water heater and to make a determination on what steps should be taken next.
If the unit is exposed to the following, do not operate heater until all corrective steps have been made by a qualified service technician.
1. External re.
2. Damage.
3. Firing without water.
GROUNDING INSTRUCTIONS
This water heater must be grounded in accordance with the National Electrical Code and/or local codes. These must be followed in all cases.
This water heater must be connected to a grounded permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater, see Figure 20.
HYDROGEN GAS FLAMMABLE
Explosion Hazard
Flammable hydrogen gases may be present.
Keep all ignition sources away from faucet when turning on hot water.
Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely ammable. To reduce the risk of injury under these conditions, it is recommended that a hot water faucet served by this water heater be opened for several minutes before using any electrical appliance connected to the hot water system. If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to ow. THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN.
5
Page 6
INTRODUCTION
Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service.
ABBREVIATIONS USED
Abbreviations found in this Instruction Manual include :
ANSI - American National Standards Institute
ASME - American Society of Mechanical Engineers
AHRI - Air-Conditioning, Heating, and Refrigeration Institute
NEC - National Electrical Code
NFPA - National Fire Protection Association
UL - Underwriters Laboratory
CSA - Canadian Standards Association
QUALIFICATIONS
Qualied Installer or Service Agency
Installation and service of this water heater requires ability equivalent to that of a Qualied Agency (as dened by ANSI below) in the eld involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service.
ANSI Z223.1 2012 Sec. 3.3.85: “Qualied Agency” - “Any individual, rm, corporation or company that either in person or through a representative is engaged in and is responsible for (1) the installation, testing or replacement of gas piping or (2) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction.”
If you are not qualied (as dened by ANSI above) and licensed or certied as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual.
PREPARING FOR THE INSTALLATION
1. Read the "General Safety Information" section, pages 4-5 of this manual rst and then the entire manual carefully. If you don’t follow the safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE.
This manual contains instructions for the installation, operation, and maintenance of the gas-red water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and all instructions are essential to the proper operation of the water heater and your safety. Since we cannot put everything on the rst few pages, RE AD THE ENTIRE MANUAL BE FORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER.
2. The installation must conform with these instructions and the local code authority having jurisdiction. In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or CAN/ CSA-B149.1 the Natural Gas and Propane Installation Code. All documents are available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH
44131. NFPA documents are also available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
3. If after reading this manual you have any questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate.
4. Carefully plan the place where you are going to put the water heater. Correct combustion, vent action, and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and res.
Examine the location to ensure the water heater complies with the “Locating the Water Heater” section in this manual.
5. For California installation this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Ofce of the State Architect, 400 P Street, Sacramento, CA 95814.
CONTROLS
FEATURES AND COMPONENTS
FIGURE 1.
THE ELIMINATOR (SELF-CLEANING SYSTEM)
These units include The Eliminator (Self-Cleaning System) installed in the front water inlet, see Figure 2. The Eliminator inlet tube can only be used in the front water inlet connection. Do not install the Eliminator inlet tube in either the top or back inlet water connection. The Eliminator must be oriented correctly for proper function. There is a marked range on the pipe nipple portion of the Eliminator, that must be aligned with the top of the inlet spud. A label above the jacket hole has an arrow that will point to the marked portion of the pipe nipple if the orientation is correct. If the arrow does not point within the marked range on the pipe nipple, adjust the pipe nipple to correct. A pipe union is supplied with the Eliminator to reduce the probability of misaligning the Eliminator accidentally while tightening the connection to the inlet water supply line. Improper orientation of the Eliminator can cause poor performance of the heater and can significantly reduce outlet water temperatures during heavy draws.
6
Page 7
Note: The Eliminator may have 1, 3 or 7 cross tubes.
ON
LIGHTS
FIGURE 2.
HIGH LIMIT SWITCH
The digital thermostat (Figure 3) contains the high limit (energy cutout) switch. The high limit switch interrupts burner gas ow should the water temperature reach 203°F (95°C).
In the event of high limit switch operation, the water heater cannot be restarted unless the water temperature is reduced to approximately 120°F (49°C). The high limit reset button on the front of the control then needs to be depressed.
Continued manual resetting of high limit control, preceded by higher than usual water temperature is evidence of high limit switch operation.
Contact your dealer or service agent if continued high limit switch operation occurs.
130
140
RESET
BUTT
BLOWER/BURNER ASSEMBLY
The fan-assisted combustion system includes a spark-to-pilot igniter, 100% premix stainless steel burners, and prejets for input rate and precision air/gas ratio control.
2-BURNER / BLOWER ASSEMBLY
(for Input of 199KBtu/H or Less)
LED
FUSE
DIGITAL THERMOSTAT
FIGURE 3.
ELECTRONIC IGNITION CONTROL
Each heater is equipped with an ignition control. The solid state ignition control (Figure 4), ignites the burner by utilizing an intermittent spark-to-pilot igniter. Spark and pilot gas ON until lightoff or trial for ignition ends. If pilot fails to light, pilot gas and spark OFF (100% shutoff). After 5 minutes delay, a new trial for ignition is initiated. This sequence continues until lightoff or "Call for Heat" is removed.
3-BURNER / BLOWER ASSEMBLY
(for Input of 250KBtu/H or Higher)
FIGURE 5.
The intake air screen is attached to the inlet of the combustion blower. Inspect the intake air screen every six months. The intake air screen should be cleaned of any buildup of debris or foreign material.
IGNITION CONTROL
FIGURE 4.
7
Page 8
INSTALLATION CONSIDERATIONS
ROUGH IN DIMENSIONS
FIGURE 6.
TABLE 1. ROUGH-IN-DIMENSIONS
MODEL DIM.
A 633/4 161.93 713/4 182.25 713/4 182.25 B 37 93.98 37 93.98 37 93.98 C 65 165.1 73 18542 73 18542 D 523/4 133.99 603/4 154.31 603/4 154.31 E 203/4 52.71 201/2 52.07 201/2 52.07 F 21 53.34 21 53.34 21 53.34 G 3/4 NPT 3/4 NPT 3/4 NPT H 53 134.62 61 154.94 61 154.94
I 6 15.24 6 15.24 6 15.24
J 273/4 70.49 273/4 70.49 273/4 70.49 K 1 1/2 NPT 1 1/2 NPT 1 1/2 NPT
L
M - - 8 20.3 8 20.3
Approx. Shipping Weight STD 650 295 750 341 810 367
Approx. Shipping Weight ASME N/A N/A 800 363 860 390
BTL-120, 154, 180, 198 BTL-199, 250(A), 275(A) BTL-310(A), 366(A), 400(A)
inches cm inches cm inches cm
1 1/2 NPT 1 1/2 NPT 1 1/2 NPT
TABLE 2. RECOVERY CAPACITIES, BASED ON 80% THERMAL EFFICIENCY
Model
BTL-120
BTL-154
BTL-180
BTL-198
BTL-199
BTL-250(A)
BTL-275(A)
BTL-310(A)
BTL-366(A)
BTL-400(A)
Input
Input KwU.S.
Kbtuh
120 81 80 GPH 320 288 230 213 192 165 160 144 128 115 107 105 96 91 89 82
35 307 LPH
154 81 80 GPH 411 370 296 274 246 211 205 185 164 148 137 134 123 117 114 106
45 307 LPH
180 81 80 GPH 480 432 346 320 288 247 240 216 192 173 160 157 144 137 133 123
53 307 LPH
199 81 80 GPH 531 478 382 354 319 273 265 239 212 191 177 174 159 152 147 137
58 307 LPH
199 100 80 GPH 531 478 382 354 319 273 265 239 212 191 177 174 159 152 147 137
58 378 LPH
250 100 80 GPH 667 600 480 445 400 343 333 300 267 240 222 218 200 191 185 171
73 378 LPH
275 100 80 GPH 734 660 528 489 440 377 367 330 293 264 245 240 220 210 203 189
81 378 LPH
310 86 80 GPH 827 744 595 551 496 425 413 372 331 298 276 271 248 236 229 213
91 325 LPH
366 86 80 GPH 976 879 703 651 586 502 488 439 391 352 325 320 293 279 270 251
107 325 LPH
390 86 80 GPH
114 325 LPH
Gal.
Liters
°F 36 40 50 54 60 70 72 80 90 100 108 110 120 126 130 140
Eff. %
°C 20 22 28 30 33 39 40 44 50 56 60 61 67 70 72 78
1212 1091
1555 1399 1120 1037
1818 1636 1309 1212 1091
2009 1808 1447 1340 1206 1033 1005
2009 1808
2524 2272 1818 1683 1515 1298 1262 1136 1010
2777 2499 1999 1851 1666 1428 1388 1250 1111 1000
3130 2817 2254 2087 1878 1610 1565 1409 1252 1127 1043 1024
3696 3326 2661 2464 2217 1901 1848 1663 1478 1330 1232 1209 1109 1056 1023 1040 3938 3544 2835 2625 2363 2025 1969 1772 1575 1418 1313 1289 1181 1125 1091 1013
U.S. Gallons/hr and Liters/hr at Temperature Rise Indicated
872 808 727 623 606 545 485 436 404 397 364 346 336 312
933 800 777 700 622 560 518 509 466 444 431 400
935 909 818 727 654 606 595 545 519 503 467
904 804 723 670 658 603 574 556 517
1447
1340 1206 1033 1005
936 749 694 624 535 520 468 416 375 347 340 312 297 288 268
904 804 723 670 658 603 574 556 517
909 841 826 757 721 699 649
926 909 833 793 769 714
939 894 867 805
TABLE 3. GAS AND ELECTRICAL CHARACTERISTICS
Model Gas Type
120 THRU 275(A) Natural 3.5" W.C. (0.87 kPa) 14" W.C. (3.48 kPa) 120/60 <5
310(A) THRU 400(A) Natural 4.5" WC (1.12 KPA) 14" W.C. (3.48 kPa) 120/60 <5
Gas Supply Pressure
Minimum Maximum
8
Volts / Hz Amperes
950
Page 9
LOCATING THE WATER HEATER
CAUTION
Property Damage Hazard
All water heaters eventually leak.
Do not install without adequate drainage.
When installing the heater, consideration must be given to proper location. Location selected should be as close to the stack or chimney as practicable, with adequate air supply and as centralized with the piping system as possible.
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell gas.
Do not expose water heater controls to excessive gas pressure.
Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended periods of non-use.
Read instruction manual before
installing, using or servicing
water heater.
There is a risk in using fuel burning appliances such as gas water heaters in rooms, garages or other areas where gasoline, other ammable liquids or engine driven equipment or vehicles are stored, operated or repaired. Flammable vapors are heavy and travel along the oor and may be ignited by the heater's igniter or main burner ames causing re or explosion. Some local codes permit operation of gas appliances in such areas if they are installed 18" or more above the oor. This may reduce the risk if location in such an area cannot be avoided.
Do not install this water heater directly on a carpeted oor. A re hazard may result. Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches in any direction. If the
heater is installed in a carpeted alcove, the entire oor shall be covered by the panel.
The heater shall be located or protected so it is not subject to physical damage by a moving vehicle.
Flammable items, pressurized containers or any other potential fire hazardous articles must never be placed on or adjacent to the heater. Open containers or flammable material should not be stored or used in the same room with the heater.
The heater must not be located in an area where it will be subject to freezing.
Locate it near a floor drain. The heater should be located in an area where leakage from heater or connections will not result in damage to adjacent area or to the lower floors of the structure.
When such locations cannot be avoided, a suitable drain pan should be installed under heater. Such pans should be fabricated with sides at least 2” deep, with length and width at least 2” greater than diameter of heater and must be piped to an adequate drain. Pan must not restrict combustion air ow.
CLEARANCES
This water heater is approved for installation on combustible ooring in an alcove with minimum clearance from combustion construction as indicated in Figure 7 and Table 4.
In all installations the minimum combustible clearances from vent piping shall be 6” (15.2 cm). Vent piping passing through a combustible wall or ceiling must be a continuous run (no joints) and retain 6” (15.2 cm) clearance unless an approved reducing thimble is used.
When the water heater is installed directly on carpeting, the water heater shall be installed on a metal or wood panel extending beyond the full width and depth of the water heater by at least 3 in (76.2 mm) in any direction or, if the water heater is installed in an alcove or closet, the entire oor shall be covered by the panel. The panel must be strong enough to carry the weight of the heater when full of water.
A service clearance of at least 24” (61 cm) should be maintained from serviceable parts.
TABLE 4. MINIMUM CLEARANCES TO COMBUSTIBLE OR NON-COMBUSTIBLE CONSTRUCTION
Model "A" Right Side "B" Left Side "C" Back "D" Ceiling
0" 0" 0" 12"
All
0 cm 0 cm 0 cm 30.5 cm
9
Page 10
death. Always read and understand instruction manual.
NSF LEG KIT
FIGURE 7.
INSULATION BLANKET
Breathing Hazard - Carbon Monoxide Gas
Do not obstruct water heater air intake with insulating blanket.
Gas and carbon monoxide detectors are available.
Install water heater in accordance with the instruction manual.
Breathing carbon monoxide can cause brain damage or
Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. The water heaters covered by this manual meet or exceed the Energy Policy Act standards with respect to insulation and standby heat loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you should follow these instructions. See the Features and Components section of this manual for identication of components mentioned below. Failure to follow these instructions can restrict the air ow required for proper combustion, potentially resulting in re, asphyxiation, serious personal injury or death.
DO NOT apply insulation to the front of the combustion
chamber ange plate to insure that the spark igniter, ame sensor, and sightglass remain uncovered.
DO NOT cover the gas control valve or the Temperature-
Pressure Relief Valve.
DO NOT apply insulation within 5” (13 cm) of the blower, to
insure the safe operation of the blower assembly.
DO NOT apply insulation on the control box that encloses
the thermostat, ignition control, and variable frequency drive.
DO NOT cover the instruction manual. Keep it on the side of
the water heater or nearby for future reference.
DO obtain new warning and instruction labels from the
manufacturer for placement on the blanket directly over the existing labels.
DO inspect the insulation blanket frequently to make certain
it does not sag, thereby obstructing combustion air ow.
FIGURE 8.
The NSF Leg Kit (part number 9008883005) is needed only for applications that must conform to NSF/ANSI Standard 5. The installed height of the water heater will increase by 4" (10.2 cm) when the leg kit is installed. Follow these steps to install the Leg Kit. Use caution to prevent damage to the unit when installing the Leg Kit
1. Lift, tilt or lay the unit on its side to access the bottom of the legs.
2. Position the extension under leg aligning the holes in the leg extension with the holes in the leg. Assemble the bolt, bevel washers, at washers, and nut through the aligned holes in the leg and leg extension as shown in Figure 8.
3. Once in place, tighten the nut and bolt assembly. Torque to 70 ft.lbs (9.67 kgf-m).
4. Insure that all four nut and bolt assemblies are torqued to the specied value before placing the unit on the oor.
HARD WATER
Where hard water conditions exist, water softening or the threshold type of water treatment is recommended. This will protect the dishwashers, coffee urns, water heaters, water piping and other equipment.
See the Maintenance Section in this manual for sediment and lime scale removal procedures.
CIRCULATION PUMPS
A circulating pump is used when a system requires a circulating loop or there is a storage tank used in conjunction with the water heater. See Water Piping Diagrams in this manual for installation location of circulating pumps.
See the Circulation Pump Wiring Diagrams (Figure 9.) in this manual for electrical hookup information. Install in accordance with the current edition of the National Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1.
Stainless steel circulating pumps are recommended for use with commercial water heaters.
10
Page 11
Some circulating pumps are manufactured with sealed
CIRCULATING PUMP WIRING DIAGRAM
CIRCULATING PUMP WIRING DIAGRAM
DISHWASHER LOOP WITH TOGGLE SWITCH
FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE
DISHWASHER TOGGLE SWITCH
CIRC
PUMP
MOTOR
L1 HOT
120 VAC POWER
NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION.
CIRCULATING PUMP WIRING DIAGRAM
bearings and do not require further lubrication. Some circulating pumps must be periodically oiled. Refer to the pump manufacturer’s instructions for lubrication requirements.
HIGH ALTITUDE INSTALLATIONS
Fire and Explosion Hazard
STORAGE TANK OR BUILDING RECIRCULATION
FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE STORAGE TANK
NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION.
L1 HOT
120 VAC POWER
L2 NEUTRAL
OR CIRCULATING LOOP RETURN LINE
DISHWASHER LOOP WITH TOGGLE SWITCH
DISHWASHER TOGGLE SWITCH
NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT. DO NOT SHARE POWER WITH WATER HEATER AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION.
L1 HOT
120 VAC POWER
L2 NEUTRAL
FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE CIRCULATING LOOP RETURN LINE
FIGURE 9.
CIRC
PUMP
MOTOR
CIRC
PUMP
MOTOR
Under no circumstances should the input exceed the rate shown on the water heater’s rating label.
Overfiring could result in fire or explosion.
Gas and carbon monoxide detectors are available.
Breathing Hazard - Carbon Monoxide Gas
Under no circumstances should the input exceed the rate shown on the water heater’s rating label.
Special consideration must be taken with installations above 10,100’ (3078m) for standard models.
Overfiring could result in damage to the water heater and sooting.
Gas and carbon monoxide detectors are available.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
The water heaters covered by this manual are certied for use without modication for an altitude of 10,100 feet (3,078 m). Consult the factory for installation at altitudes over 10,100 feet (3,078 m).
Some gas utility companies derate their gas for altitude, making it unnecessary to install high altitude orices. Call the local gas or utility company to verify BTU content.
Due to the input rate reduction at high altitudes, the output rating of the water heater is also reduced and should be compensated for in the sizing of the equipment for applications.
11
Page 12
INSTALLATION REQUIREMENTS
GAS SUPPLY SYSTEMS
Low pressure building gas supply systems are dened as those systems that cannot under any circumstances exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge). These systems do not require pressure regulation. Measurements should be taken to insure that gas pressures are stable and fall within the requirements stated on the water heater rating plate. Readings should be taken with all gas burning equipment off (static pressure) and with all gas burning equipment running at maximum rate (dynamic pressure). The gas supply pressure must be stable within 1.5” W.C. (0.37 kPa) from static to dynamic pressure to provide good performance. Pressure drops that exceed 1.5” W.C. (0.37 kPa) may cause rough starting, noisy combustion or nuisance outages. Increases or spikes in static pressure during off cycles may cause failure to ignite or in severe cases damage to appliance gas valves. If your low pressure system does NOT meet these requirements, the installer is responsible for the corrections.
High Pressure building supply systems use pressures that exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge). These systems must use eld supplied regulators to lower the gas pressure to less than 14” W.C. (3.49 kPa) (1/2 PSI Gauge). Appliances require gas regulators that are properly sized for the water heater input and deliver the rating plate specied pressures. Gas supply systems where pressure exceeds 5 PSI (34.5 kPa) often require multiple regulators to achieve desired pressures. Systems in excess of 5 PSI building pressure should be designed by gas delivery professionals for best performance. Water heaters connected to gas supply systems that exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge) at any time must be equipped with a gas supply regulator.
GAS PRESSURE REQUIREMENTS
All models require a minimum gas supply pressure as shown in Table 3 on page 8. The minimum supply pressure is measured while gas is owing (dynamic pressure). The supply pressure (dynamic) should never fall below that indicated in Table 3 page
8. The supply pressure should be measured with all gas red
appliances connected to the common main ring at full capacity. If the supply pressure drops more than 1.5” W.C. (0.37 kPa) as gas begins to ow to the water heater then the supply gas system including the gas line and/or the gas regulator may be restricted or undersized. See Supply Gas Regulator section and Gas Piping section of this manual.
The gas control valve on all models has a maximum gas supply pressure limit of 14" W.C. (3.48 kPa). The maximum supply pressure is measured while gas is not owing (static pressure).
SUPPLY GAS REGULATOR
The maximum allowable gas supply pressure for this water heater is 14 inches W.C. (3.48 kPa). Install a positive lock-up gas pressure regulator in the gas supply line if inlet gas pressure can exceed 14 inches W.C. (3.48 kPa) at any time. Regulators must be sized/used according to manufacturer's specications.
If a positive lock-up regulator is required follow these instructions:
1. Positive lock-up gas pressure regulators must be rated at or above the input Btu/hr rating of the water heater they supply.
2. Supply gas regulators shall have inlet and outlet connections not less than the minimum supply gas line size for the water heater they supply. See Table 7 on page 24.
3. Positive lock-up gas pressure regulator(s) should be installed no closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters) of equivalent length from the water heater’s inlet gas connection.
4. After installing the positive lock-up gas pressure regulator(s) an initial nominal supply pressure setting of 7.0” W.C. (1.74 kPa) while the water heater is operating is recommended and will generally provide good water heater operation.
Some addition adjustment maybe required later to maintain a steady gas supply pressure.
5. When installing multiple water heaters in the same gas supply system it is recommended that individual positive lock-up gas pressure regulators be installed at each unit.
POWER SUPPLY
The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/ NFPA 70 or the Canadian Electrical Code, CSA C22.1.
WATER TEMPERATURE CONTROL AND MIXING VALVES
Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.
Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures.
Water heated to a temperature which will satisfy clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the water heater’s temperature setting by up to 20°F (11°C).
Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the inrm and the physically/mentally disabled. Table 5 shows the approximate time-to-burn relationship for normal adult skin. If anyone using hot water provided by the water heater being installed ts into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken.
In addition to using the lowest possible temperature setting that satises the demand of the application a Mixing Valve should be installed at the water heater (see Figure 10) or at the hot water taps to further reduce system water temperature.
Mixing valves are available at plumbing supply stores. Consult a Qualied Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves.
TABLE 5.
Water Temperature
(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)
12
°F (°C)
110 (43) (normal shower temp.)
116 (47) (pain threshold)
116 (47) 35 minutes 45 minutes
122 (50) 1 minute 5 minutes
131 (55) 5 seconds 25 seconds
140 (60) 2 seconds 5 seconds
149 (65) 1 second 2 seconds
154 (68) instantaneous 1 second
Time for 1st Degree Burn
(Less Severe Burns)
Time for Permanent Burns
2nd & 3rd Degree
(Most Severe Burns)
Page 13
HOT WATER
OUTLET
TEMPERED WATER
OUTLET
12” TO 15” (30-38 cm)
expansion. Contact a local plumbing service agency to have a thermal expansion tank installed.
See Water Line Connections on page 21 and Water Piping Diagrams starting on page 35.
TEMPERATURE-PRESSURE RELIEF VALVE
COLD
WATER
INLET
CHECK
VALV E
TO TANK
INLET
CHECK
VALV E
MIXING
VALV E
FIGURE 10.
DISHWASHING MACHINES
All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 kPa and 173 kPa). Flow pressures above 25 pounds per square inch (173 kPa), or below 15 pounds per square inch (103 kPa), will result in improperly sanitized dishes. Where pressures are high, a water pressure reducing or flow regulating control valve should be used in the 180°F (82°C) line to the dishwashing machine and should be adjusted to deliver water pressure between these limits.
The National Sanitation Foundation also recommends circulation of 180°F (82°C) water. The circulation should be just enough to provide 180°F (82°C) water at the point of take-off to the dishwashing machine.
Adjust ow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle ow on the suction side of a pump. See Water Piping Diagrams in this manual.
CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed devices such as pressure reducing valves, check valves, and back ow preventers. Devices such as these cause the water system to be a closed system.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume of water grows there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent Temperature-Pressure Relief Valve operation: water discharged from the valve due to excessive pressure build up. This condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal
Explosion Hazard
Temperature-Pressure Relief Valve must comply with ANSI Z21.22­CSA 4.4 and ASME code.
Properly sized temperature­pressure relief valve must be installed in opening provided.
Can result in overheating and excessive tank pressure.
Can cause serious injury or death.
This water heater is provided with a properly rated/sized and certied combination Temperature-Pressure Relief Valve (T&P valve) by the manufacturer. The valve is certied by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of ASME.
If replaced, the new T&P valve must meet the requirements of local codes, but not less than a combination Temperature­Pressure Relief Valve rated/sized and certied as indicated in the above paragraph. The new valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035 kPa) and a discharge capacity not less than the water heater Btu/hr or kW input rate as shown on the water heater’s model rating label.
NOTE: In addition to the factory installed Temperature-Pressure Relief Valve on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature­Pressure Relief Valve installed. Call the toll free technical support phone number listed on the back cover of this manual for technical assistance in sizing a Temperature-Pressure Relief Valve for remote storage tanks.
For safe operation of the water heater, the Temperature-Pressure Relief Valve must not be removed from its designated opening nor plugged. The Temperature-Pressure Relief Valve must be installed directly into the tting of the water heater designed for the relief valve. Install discharge piping so that any discharge will exit the pipe within 6 inches (15.2 cm) above an adequate oor drain, or external to the building. In cold climates it is recommended that it be terminated at an adequate drain inside the building. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.
13
Page 14
No valve or other obstruction is to be placed between the
CAUTION
Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water ow may cause property damage.
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
T&P Valve Discharge Pipe Requirements:
• Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
Shall not be plugged or blocked.
Shall not be exposed to freezing temperatures.
Shall be of material listed for hot water distribution.
Shall be installed so as to allow complete drainage of both
the Temperature-Pressure Relief Valve and the discharge pipe.
Must terminate a maximum of six inches above a oor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.
Shall not have any valve or other obstruction between the relief valve and the drain.
see Closed Water Systems and Thermal Expansion on page 13.
If you do not understand these instructions or have any questions regarding the Temperature-Pressure Relief Valve call the toll free number listed on the back cover of this manual for technical assistance.
COMBUSTIBLE MATERIAL STORAGE
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell gas.
Do not expose water heater controls to excessive gas pressure.
Use only the gas shown on the water heater rating label. Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended periods of non-use.
Read instruction manual before
installing, using or servicing
water heater.
Keep water heater area clear and free of combustible materials, gasoline and other ammable vapors and liquids.
CONTAMINATED AIR
Burn hazard.
Hot water discharge.
Keep clear of Temperature­Pressure Relief Valve discharge outlet.
The Temperature-Pressure Relief Valve must be manually
operated at least twice a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot. If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions in this manual, and replace the Temperature-Pressure Relief Valve with a properly rated/sized new one.
NOTE: The purpose of a Temperature-Pressure Relief Valve is
to prevent excessive temperatures and pressures in the storage tank. The T&P valve is not intended for the constant relief of thermal expansion. A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion,
Breathing Hazard - Carbon Monoxide Gas
Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1.
To avoid injury, combustion and ventilation air must be taken from outdoors.
Do not place chemical vapor emitting products near water heater.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
Corrosion of the ue ways and vent system may occur if air for combustion contains certain chemical vapors. Such corrosion may result in failure and risk of asphyxiation.
Combustion air that is contaminated can greatly diminish the life span of the water heater and water heater components such as igniters and burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning processes that are present in the combustion, ventilation or ambient air can cause such damage.
Do not store products of this sort near the water heater. Air which is brought in contact with the water heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outdoor sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions).
14
Page 15
AIR REQUIREMENTS
Breathing Hazard - Carbon Monoxide Gas
Install water heater in accordance with the Instruction Manual and NFPA 54 or CAN/CSA-B149.1.
To avoid injury, combustion and ventilation air must be taken from outdoors.
Do not place chemical vapor emitting products near water heater.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided.
An insufcient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life. Such a condition often will result in a yellow, luminous burner ame, causing sooting of the combustion chamber, burners and ue tubes and creates a risk of asphyxiation.
Do not install the water heater in a conned space unless an adequate supply of air for combustion and ventilation is brought in to that space using the methods described in the Conned Space section that follows.
Never obstruct the ow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a re or explosion and cause property damage, serious bodily injury or death.
UNCONFINED SPACE
An Unconned Space is one whose volume IS NOT LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconned space.
Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and replaces shall also be considered in determining the adequacy of a space to
provide combustion, ventilation and dilution air.
Unusually Tight Construction
In unconned spaces in buildings, inltration may be adequate to provide air for combustion, ventilation and dilution of ue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Conned Space section that follows.
CONFINED SPACE
A Conned Space is one whose volume IS LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion, ventilation and dilution in conned spaces. The required size for the openings is dependent on the method used to provide fresh air to the conned space AND the total Btu/hr input rating of all appliances installed in the space.
Exhaust Fans
Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a water heater, sufcient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan. Undersized openings will cause air to be drawn into the room through the water heater’s vent system causing poor combustion. Sooting, serious damage to the water heater and the risk of re or explosion may result. It can also create a risk of asphyxiation.
Louvers and Grilles
The free areas of the fresh air openings in the instructions that follow do not take in to account the presence of louvers, grilles or screens in the openings.
The required size of openings for combustion, ventilation and dilution air shall be based on the “net free area” of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size of opening required to provide the free area specied. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25% free area and metal louvers and grilles will have 75% free area. Non motorized louvers and grilles shall be xed in the open position.
15
Page 16
FRESH AIR OPENINGS FOR CONFINED SPACES
The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in conned spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into conned spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on page 18 for complete venting installation instructions.
OUTDOOR AIR THROUGH TWO OPENINGS
Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 14. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (l50 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
1. 1 square inch per 3000 Btu/hr (733 mm
2
per kW) of the total input rating
of all appliances located in the enclosure, and
2. Not less than the sum of the areas of all vent connectors in the space.
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS
FIGURE 14.
The conned space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings shall communicate directly with the outdoors. See Figure 14.
Each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).
OUTDOOR AIR THROUGH ONE OPENING
FIGURE 16.
The conned space shall be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The horizontal ducts shall communicate directly with the outdoors. See Figure 16.
Each duct opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches (7.6 cm).
FIGURE 15.
16
Page 17
OUTDOOR AIR THROUGH TWO VERTICAL DUCTS
The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into conned spaces only.
DO NOT refer to these illustrations for the purpose of vent
installation. See Venting Installation on page 18 for complete venting installation instructions.
FIGURE 17.
The conned space shall be provided with two permanent vertical ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The vertical ducts shall communicate directly with the outdoors. See Figure 17.
Each duct opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm rating of all appliances installed in the enclosure.
2
per kW) of the aggregate input
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.
AIR FROM OTHER INDOOR SPACES
FIGURE 18.
The conned space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 18.
Each opening shall communicate directly with an additional room(s) of sufcient volume so that the combined volume of all spaces meets the criteria for an Unconned Space.
Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (2200 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).
17
Page 18
VENTING INSTALLATION
VENTING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
This heater is not approved for direct vent installation.
Heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will retard a free draft.
Type B venting is required with these heaters. For typical venting application see TECHNICAL DATA VENTING on pages 19 and 20.
This water heater must be vented in compliance with all local codes, the current revision of the National Fuel Gas Code (ANSI-Z223.1) and with the Category I Venting Tables.
If any part of the vent system is exposed to ambient temperatures below 40°F (4.4°C) it must be insulated to prevent condensation.
Do not connect the heater to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by many local building codes as is the practice of venting gas red equipment to the duct work of ventilation systems.
Where a separate vent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace, the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe.
MULTIPLE HEATER MANIFOLD
Figure 13 and tables on pages 19 and 20 should be used for horizontally manifolding two or more heaters.
FIGURE 13.
FIGURE 11. FIGURE 12.
18
Page 19
TABLE 6. TECHNICAL DATA VENTING
TYPE B GAS VENT Multiple Gas Fired Tank-Type Heaters
When venting multiple tank type heaters using Type B vent
pipe, follow the installation diagram (gure 13) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. 2006.
Model BTL-120 Input: 120,000 Btu/hr Total Vent Height (Feet) Vent connector size: 6 inches 6 8 10 15 20 30 50 100
Number of 120 Heaters
2 240,000 7 7 6 6 6 6 6 6 3 360,000 8 8 7 7 7 6 6 6 4 480,000 9 9 9 8 8 7 7 6
Model BTL-154 Input: 154,000 Btu/hr Total Vent Height (Feet) Vent connector size: 6 inches 6 8 10 15 20 30 50 100
Number of 154 Heaters
2 308,000 7 7 6 6 6 6 6 6 3 462,000 8 8 7 7 7 6 6 6 4 616,000 9 9 9 8 8 7 7 6
Model BTL-180, 198 &199 Input: 180,000 and 199,000 Btu/hr Total Vent Height (Feet) Vent connector size: 6 inches 6 8 10 15 20 30 50 100
Number of Heaters
2
3
4
Model BTL-250(A) Input: 250,000 Btu/hr Total Vent Height (Feet) Vent connector size: 6 inches 6 8 10 15 20 30 50 100
Number of 250 Heaters
2 500,000 9 9 9 8 8 7 7 7 3 750,000 12 12 10 10 10 9 8 8 4 1,000,000 14 14 12 12 10 10 9 9
Input Btu/hr Rise Vent Connector Diameter (Inches)
120,000 1 ft. 6 6 5 5 5 5 5 5 120,000 2ft. 5 5 5 5 5 5 5 5 120,000 3ft. 5 5 5 5 5 5 5 5
Combined Input in
Thousands of Btu/hr
Input Btu/hr Rise Vent Connector Diameter (Inches)
154,000 1 ft. 6 6 6 6 6 6 6 6 154,000 2ft. 6 6 6 6 6 6 6 6 154,000 3ft. 6 6 6 6 6 6 6 6
Combined Input in
Thousands of Btu/hr
Input Btu/hr Rise Vent Connector Diameter (Inches)
180,000 1 ft. 7 7 6 6 6 6 6 6 199,000 1 ft. 7 7 7 6 6 6 6 6 180,000 2ft. 6 6 6 6 6 6 6 6 199,000 2ft. 7 7 6 6 6 6 6 6 180,000 3ft. 6 6 6 6 6 6 6 6 199,000 3ft. 6 6 6 6 6 6 6 6
Combined Input in
Thousands of Btu/hr
360,000 8 8 8 7 7 7 6 6 398,000 8 8 8 7 7 7 6 6 540,000 10 9 9 9 8 8 7 7 597,000 10 9 9 9 8 8 7 7 720,000 12 12 10 10 9 9 8 8 796,000 12 12 10 10 9 9 8 8
Input Btu/hr Rise Vent Connector Diameter (Inches)
250,000 1 ft. 8 8 7 7 7 6 6 6 250,000 2ft. 7 7 7 7 6 6 6 6 250,000 3ft. 7 7 7 7 6 6 6 6
Combined Input in
Thousands of Btu/hr
Manifold and Common Vent Diameter (Inches)
Manifold and Common Vent Diameter (Inches)
Manifold and Common Vent Diameter (Inches)
Manifold and Common Vent Diameter (Inches)
19
Page 20
TABLE 6. TECHNICAL DATA VENTING (Continued)
Model 275 Input: 275,000 btu/hr Total Vent Height (Feet) Vent connector size: 6 inches 6 8 10 15 20 30 50 100
Number of Heaters Combined Input (Btu/hr) Manifold and Common Vent Diameter (Inches)
2 550,000 10 10 9 9 8 8 7 7 3 825,000 14 12 12 10 10 9 9 8 4 1,100,000 14 14 14 12 12 12 10 9
Model 310 Input: 310,000 btu/hr Total Vent Height (Feet) Vent connector size: 6 inches 6 8 10 15 20 30 50 100
Number of Heaters Combined Input (Btu/hr)
2 620,000 12 10 10 9 9 8 8 7 3 930,000 14 14 12 12 10 10 9 9 4 1,240,000 16 14 14 14 12 12 10 9
Model 366 Input: 366,000 btu/hr Total Vent Height (Feet) Vent connector size: 6 inches 6 8 10 15 20 30 50 100
Number of Heaters Combined Input (Btu/hr)
2 732,000 12 12 12 10 9 9 8 8 3 1,098,000 14 14 14 12 12 12 10 9 4 1,464,000 16 16 16 14 14 12 12 10
Input Btu/hr Rise Vent Connector Diameter (Inches)
275,000 1 ft. 8 8 8 7 7 6 6 6 275,000 2 ft. 8 8 7 7 7 6 6 6 275,000 3 ft. 7 7 7 7 7 6 6 6
Input Btu/hr Rise Vent Connector Diameter (Inches)
310,000 1 ft. - 8 8 8 7 7 6 6 310,000 2 ft. 8 8 8 7 7 7 6 6 310,000 3 ft. 8 8 8 7 7 7 6 6
Input Btu/hr Rise Vent Connector Diameter (Inches)
366,000 1 ft. - - - 8 8 7 7 6 366,000 2 ft. - - 8 8 8 7 7 6 366,000 3 ft. - 8 8 8 7 7 6 6
Model 400 Input: 390,000 btu/hr Total Vent Height (Feet) Vent connector size: 6 inches 6 8 10 15 20 30 50 100
Number of Heaters Combined Input (Btu/hr)
2 780,000 12 12 12 10 10 9 9 8 3 1,170,000 16 14 14 14 12 12 10 9 4 1,560,000 16 16 16 14 14 14 12 10
Input Btu/hr Rise Vent Connector Diameter (Inches)
390,000 1 ft. - - - - 8 7 7 6 390,000 2 ft. - - - 8 8 7 7 6 390,000 3 ft. - - 8 8 8 7 7 6
20
Page 21
WATER HEATER INSTALLATION
WATER LINE CONNECTIONS
The water piping installation must conform to these instructions and to all local code authority having jurisdiction. Good practice requires that all heavy piping be supported.
Read and observe all requirements in the following sections before installation of the water piping begins:
1. Water Temperature Control and Mixing Valves on page 12.
2. Dishwashing Machines on page 13.
3. Temperature-Pressure Relief Valve on page 13.
4. Closed Systems and Thermal Expansion on page 13.
5. For multiple water heater installations see Water Piping Diagrams beginning on page 35.
Water (potable) Heating And Space Heating
1. All piping components connected to this unit for space heating applications shall be suitable for use with potable water.
2. Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.
3. This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.
4. When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please
refer to Water Piping Diagrams beginning on page 35 of
this manual for suggested piping arrangements.
5. These water heaters cannot be used in space heating applications only
T&P VALVE DISCHARGE PIPE
Explosion Hazard
Temperature-Pressure Relief Valve must comply with ANSI Z21.22­CSA 4.4 and ASME code.
Properly sized temperature­pressure relief valve must be installed in opening provided.
Can result in overheating and excessive tank pressure.
Can cause serious injury or death.
This water heater is provided with a properly rated/sized and certied combination temperature - pressure (T&P) relief valve by the manufacturer. See Temperature-Pressure Relief Valve on pages 13-14 for information on replacement and other requirements.
CAUTION
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
Thermometers (not Supplied)
Thermometers should be obtained and eld installed as shown in the installation diagrams.
Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply.
Water Piping Diagrams
This manual provides detailed water piping diagrams for typical methods of application for the water heaters, see Water Piping Diagrams beginning on page 35.
The water heater may be installed by itself, or with a separate storage tank. When used with a separate storage tank, the circulation may be either by gravity or by means of circulating pump. Adjust ow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle ow on the suction side of a pump. See the Water Piping Diagrams beginning on page 35.
NOTE: In addition to the factory installed Temperature-Pressure Relief Valve (T&P valve) on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature-Pressure Relief Valve installed.
Call the toll free technical support phone number listed on the back cover of this manual for further assistance in sizing a T&P valve for remote storage tanks.
Install a discharge pipe between the T&P valve discharge opening and a suitable oor drain. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water ow may cause property damage.
T&P Valve Discharge Pipe Requirements:
• Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
Shall not be plugged or blocked.
Shall not be exposed to freezing temperatures.
Shall be of material listed for hot water distribution.
Shall be installed so as to allow complete drainage of both
the Temperature-Pressure Relief Valve and the discharge pipe.
Must terminate a maximum of six inches above a oor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.
Shall not have any valve or other obstruction between the relief valve and the drain.
21
Page 22
INSTALLATION DIAGRAMS - TOP INLET/OUTLET USAGE
Use of the top inlet water connection requires an inlet dip tube (refer to gure 19). The tube is supplied in the heater. Follow caution labels if applying heat to this tting. Do not allow pipe dope to contact the plastic tube during installation.
TUBE INLET INSTALLATION
FIGURE 19.
22
Page 23
HEATER WIRING
ELECTRICAL WIRING
All electrical work must be installed in accordance with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1 and local requirements. When installed, the water heater must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1. If any of the original wire as supplied with the water heater must be replaced, it must be replaced with 105°C rated wiring or its equivalent, except in the burner housing. In this case 200°C rated wire must be used.
The controls of this water heater are polarity sensitive. Be certain to properly wire the hot and neutral connections.
UPPER
PROBE
R R
BK BK
R
4
2
LOW GAS PRESSURE
SWITCH
(SELECT MODELS)
LOWER
PROBE
RR
THERMOSTAT
BLOWER
PRESSURE
SWITCH
WIRING DIAGRAM
BLK
R
R
W
POWER RELAY
BLOWER
W
BLK
1a1b1
120 VAC HOT 120 VAC NUETRAL
EARTH GROUND
IGNITION MODULE
SPARK
PV
MV
Y
BLUE
M
(GND)
24V
24V
GND
MV/PV
W
BLK
P
GAS VALVE
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED MUST BE REPLACED US ONLY 18 AWG
105
C 600V UL AWM STYLE #1015 WIRE EXCEPT GAS VALVE CABLE WHICH MUST USE
2 CONDUCTOR 18 AWG 80
C 300V UL CATEGORY QPTZ POWER LIMITED CIRCUIT CABLE
FIGURE 20.
23
PILOT
LEGEND: R= RED
W= WHITE
BLK= BLACK
Y= YELLOW
FACTORY INSTALLED
BY INSTALLER
327382-000 REV. 00
Page 24
GAS PIPING
Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area.
Size the main gas line in accordance with Table 7. The gures shown are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is considered normal for low pressure systems. Note: Fittings such as elbows, tees and line regulators will add to the pipe pressure drop. Also refer to the current edition of the National Fuel Gas Code.
Schedule 40 Steel or Wrought Iron Pipe is the preferred material for the gas line of this water heater. It is imperative to follow the sizing recommendations in the current edition of the National Fuel Gas Code if Corrugated Stainless Steel Tubing (CSST) is used as the gas line for this water heater.
The heater is not intended for operation at higher than 14.0" W.C.­natural gas, (1/2 pound per square inch gage) supply gas pressure. Exposure to higher supply pressure may cause damage to the gas control valve which could result in re or explosion. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system, the gas control valve must be checked for safe operation. Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system, not the heater. Vent blockage may occur during ice storms.
TABLE 7 - GAS SUPPLY PIPE LENGTHS (IN FEET) Maximum Equivalent Pipe Length - Natural Gas Only
Input rate
(BTU/HR)
120,000 20 70 200 200 200 154,000 10 40 150 200 200 180,000 - 30 100 200 200 199,000 - 30 90 200 200 250,000 - 20 60 200 200 275,000 - 10 50 200 200 310,000 - 10 40 150 200 366,000 - - 30 100 200 390,000 - - 20 100 200
Fitting Type* Equivalent length in feet
45°Ell 0.7 1.0 1.2 1.6 1.9 90°Ell 1.6 2.1 2.6 3.5 4.0
Tee 3.1 4.1 5.2 6.9 8.0
*Screwed Fittings
Natural Gas 0.60 Specic Gravity, 0.50" W.C. Pressure Drop
It is important to guard against gas control valve fouling from contaminants in the gas ways. Such fouling may cause improper operation, re or explosion.
If copper supply lines are used they must be internally tinned and certied for gas service. Before attaching the gas line, be sure that all gas pipe is clean on the inside.
To trap any dirt or foreign material in the gas supply line, a sediment trap must be incorporated in the piping (see Figure 21). The sediment trap must be readily accessible and not subject to freezing conditions. Install in accordance with recommendations of serving gas suppliers. Refer to the current edition of the National Fuel Gas Code.
To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas control valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compounds to the rst two threads. Use compounds resistant to the action of liqueed petroleum gases.
Schedule 40 Steel or Wrought Iron Pipe
1/2" 3/4" 1" 1 1/4" 1 1/2"
Gas Meter Size – Natural Gases Only
Be sure the gas meter has sufcient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas red equipment supplied by the meter. If gas meter is too small, ask the gas company to install a larger meter having adequate capacity.
GAS PIPING AND SEDIMENT TRAP INSTALLATION
FIGURE 21.
GAS LINE LEAK TESTING
Fire and Explosion Hazard
Use joint compound or Teflon tape compatible with propane gas.
Leak test before placing the water heater in operation.
Disconnect gas piping and main gas shutoff valve before leak testing.
Install sediment trap in accordance with NFPA 54.
Any time work is done on the gas supply system perform a leak test to avoid the possibility of re or explosion.
1. For test pressures exceeding 1/2 psi (3.45 kPa) disconnect the water heater and its Main Gas Shutoff Valve from the gas supply piping system during testing, see Figure 21. The gas supply line must be capped when disconnected from the water heater.
2. For test pressures of 1/2 psi (3.45 kpa) or less, the water heater need not be disconnected, but must be isolated from the supply gas line by closing the Main Gas Shutoff Valve during testing.
3. Coat all supply gas line joints and connections upstream of the water heater with a non-corrosive soap and water solution to test for leaks. Bubbles indicate a gas leak. Do not use matches, candles, ame or other sources of ignition for this purpose.
4. Repair any leaks before placing the water heater in operation.
PURGING
Gas line purging is required with new piping or systems in which air has entered.
Purging should be performed per the current edition of NFPA 54 the National Fuel Gas Code.
24
Page 25
START UP
PRIOR TO START UP
Installation and start up of this water heater requires abilities and skills equivalent to that of a licensed tradesman in the eld involved, see Qualications on page 6.
Do not place the water heater in operation if any part has been under water. Immediately call a qualied service technician to inspect the water heater and to replace any part of the control system and any gas control which has been under water.
Light the water heater in accordance with the Lighting and Operation Instruction label on the water heater and in this manual on page 27.
The water heaters covered by this manual are equipped with an electronic control system that automatically sequences the Blower, the Igniter, the 24 VAC Gas Valve, Burner ignition, and ame sensing. The control system will lock out after three unsuccessful ignition attempts.
Before attempting start up, thoroughly study and familiarize yourself with the exact Sequence Of Operation, see the written Sequence Of Operation on page 27 and the Sequence Of Operation Flow Chart on page 28.
Be certain that the water heater is full of water, that air is purged from the gas and water lines and that there are no leaks in the gas and water lines. Ensure all inlet water valves are open.
Filling The Water Heater
Follow these steps to ll the water heater prior to start up.
1. Close the heater drain valve.
2. Open a nearby hot water faucet to permit the air in the system to escape.
3. Fully open the cold water inlet valve allowing the piping and water heater to ll with water.
4. Close the hot water faucet opened in Step 2 as water starts to ow.
Supply Gas Line Purging
Fire or Explosion Hazard
Gas line purging is required with new piping or systems in which air has entered.
To avoid risk of fire or explosion purge discharge must not enter into confined areas or spaces where ignition can occur.
The area must be well ventilated and all sources of ignition must be deactivated or removed.
Use only the gas shown on the water heater rating label. Keep ignition sources away from faucets after extended
periods of non-use.
INITIAL START UP
Required Test Equipment
U-tube manometer, pressure gauge, or digital manometer. Recommended range: 20” W.C. (5 kPa).
NOTE: All test equipment must be acclimated to ambient temperature before calibration and use.
Preparation
1. Adjust the thermostat to the lowest temperature setting.
2. Turn the water heater’s on/off switch to the “off” position.
3. Close the Main Gas Shut Off Valve, see Figure 21 on page 24.
4. Wait ve (5) minutes for any residual gas to clear.
5. Open the Supply Gas Pressure Port on the gas control valve by turning the center screw counter-clockwise. Connect the manometer to the supply gas pressure test port, see Figure 22.
6. Open the Main Gas Shutoff Valve.
7. Measure and record the supply gas pressure, this is a “static” supply gas pressure reading; while the water heater is not ring.
FIGURE 22. – TOP VIEW
Lighting The Water Heater
1. Turn the water heater’s on/off switch to the “on” position.
2. Adjust the thermostat to the desired water temperature.
3. Record the supply gas pressure when the 24 VAC Gas Valve is energized and the Burner is operating. This is a “dynamic” gas pressure reading; while the water heater is ring.
4. Compare the actual supply gas pressure reading recorded above to the required minimum/maximum values given in Table 3 on page 8. Adjust supply gas pressure as necessary, see the instructions that follow.
5. After the supply gas pressure adjustments are complete, turn off the water heater and close the Main Gas Supply Shut Off Valve. Disconnect the manometer from the Supply Gas Pressure Port and turn the center screw clockwise until the port is closed.
Supply Gas Pressure Adjustment
Read instruction manual before
installing, using or servicing
water heater.
1. Close the Main Gas Shutoff Valve, see Figure 21 on page 24.
2. Purge all air from the supply gas line up to the water heater’s Main Gas Shutoff Valve.
3. When all air has been purged from the supply gas line, tighten all supply gas line connections.
4. Check for gas leaks, see Gas Line Leak Testing on page 24 and repair any leaks found.
Fire and Explosion Hazard
Do not use water heater with any gas other than the gas shown on the rating label.
Excessive gas pressure to gas valve can cause serious injury or death.
Turn off gas lines during installation. Contact a qualified installer or service
technician for installation and service.
25
Page 26
Supply gas pressure shall be measured while the water heater is not ring (static pressure) and while the water heater is ring at full capacity (dynamic pressure).
If the supply gas pressure to the water heater is not between the required minimum and maximum values given in Table 3 on page 8 adjust the supply gas regulator as necessary. Adjust the supply gas regulator(s) per the regulator manufacturer’s instructions to achieve the required “static” and “dynamic” supply gas pressure.
Multiple Water Heater Installations:
In multiple water heater installations or in installations where the installed water heater(s) share a common gas supply main with other gas red appliances; the supply gas pressures shall be measured at each water heater with all gas red appliances connected to a common main ring at full capacity.
On multiple water heater installations the supply gas line regulators shall be adjusted to provide gas pressure to each water heater within the minimum and maximum supply pressure requirements listed in Table 3 on page 8 with all gas red appliances connected to a common gas main ring at full capacity.
NOTE: A pressure drop of more than 1.5” W. C. (0.37 kPa) when the Main Burner ignites is an indication of an inadequate supply of gas and can lead to ignition failure, rough starts and/ or rough operation. If a drop of more than 1.5” W. C. (0.37 kPa) in supply gas pressure occurs when the Main Burner ignites, ensure the supply gas lines and regulator(s) are properly sized and installed. See the requirements for Supply Gas Regulator on page 12 and Gas Piping on page 24. Ensure all requirements and installation instructions are maintained.
CHECKING VENTING
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1or the CAN/ CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deciencies which could cause an unsafe condition.
3. So far as is practical, close all building doors and windows and all doors between the space in which the water heater(s) connected to the venting system are located and other spaces of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Close replace dampers.
4. Follow the lighting instruction. Place the water heater being inspected in operation. Adjust thermostat so water heater shall operate continuously.
5. Inspect vent system for leakage after 5 minutes of main burner operation.
6. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, replace dampers and any other gas burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests, the venting system must be corrected.
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS.
If the back draft cannot be corrected by the normal method or if a suitable draft cannot be obtained, a blower type ue gas exhauster must be employed to assure proper venting and correct combustion.
CHECKING THE INPUT
Follow these instructions to determine the ring rate of the water heater.
1. Follow the procedure described in the "Initial Start Up" section on page 25 to measure the static and dynamic supply gas pressures. Verify that the static and dynamic supply gas pressures conform to the values listed in Table 3 on page 8.
2. Use this formula to “clock” the meter. Be sure that other gas consuming appliances are not operating during this interval.
(3600/T) x H = Btuh
T = Time in seconds to burn one cubic foot of gas.
H = Btu’s per cubic foot of gas.
Btuh = Actual heater input.
Example: (BTL-199)
T = 18.1 seconds
H = 1000 BTU/Cu.Ft.
Btuh = (3,600/18.1) x 1,000 = 199,000
(Compare with BTL-199 model and rating.)
UNDER NO CIRCUMSTANCES SHOULD THE GAS INPUT EXCEED THE INPUT SHOWN ON THE HEATER'S RATING PLATE.
WATER TEMPERATURE ADJUSTMENT
Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.
Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures.
The water temperature is controlled by a thermostat, Fig. 3, which has two sensing elements. One sensor is located near the top of the tank and the other is near the center. The thermostat is set in the lowest position before the heater leaves the factory.
The thermostat temperature dial, Fig. 3, is accessible by removing the control cover. The dial is adjustable and may be set for 120°F (49°C) to 180°F (82°C) water temperature, but 120°F (49°C) is the recommended starting point. It is suggested the dial be placed on the lowest setting which produces an acceptable hot water supply. This will always give the most energy efcient operation. The temperature control has a 4°F xed differential.
26
Page 27
SEQUENCE OF OPERATION
The following information will describe the Sequence of Operation for this water heater.
1. Switch power on to unit.
2. Thermostat calls for heat.
3. Blower power relay is energized to start the blower.
4. The blower pressure switch is closed, 24VAC power is applied to the Ignition Control Module.
5. The Ignition Control performs diagnostic self check on system components.
6. After 30 seconds delay, the Ignition Control begins the trial for ignition by turning on the Spark Igniter and the Pilot Gas Valve.
7. The Ignition Control monitors the Flame Sensor during the ignition trial period.
LIGHTING & OPERATING LABEL
8. If the Ignition Control does not sense the pilot ame during the ignition trial period, the Ignition Control shuts the Pilot Gas Valve and turns off the Spark Igniter. After 5 minute delay, a new trial for ignition is initiated. This sequence continues until the unit lights or “Call for Heat” is removed.
9. If the pilot ame is proved during the ignition trial period, the Ignition Control will energize the main gas control valve to start the heating cycle. If the ame signal is lost during the heating cycle, the Ignition Control closes the gas control valve and re­starts the ignition process at step 5.
10. Once the unit is satised, the Thermostat will turn off the 24vac power to the blower relay and the Ignition Control, and the unit will be in standby mode until another call for heat is initiated by the thermostat.
See the ow chart on page 28 for more detailed information.
FIGURE 23.
27
Page 28
SEQUENCE OF OPERATION FLOW CHART
Description of this ow chart can be found in the “SEQUENCE OF OPERATION” section found on page 27.
Switch power on to unit
Thermostat calls for heat
Blower power relay is energized to
start blower
Blower engages Prover Switch
24VAC power to the Ignion
Control and self check
30 Seconds Prepurge
Trial for ignion
Ignion Control provides power to Spark
Igniter and Pilot Gas Valve and monitors
Flame Sensor to determine if Burner is lit
Flame Proved?
NO
Close pilot gas
valve and Spark off
5 minutes retry
delay
YES
Spark Off and Open main Gas Valve
Ignition Control monitors
flame signal
YES
Loss of flame signal?
NO
Thermostat is satisfied
Blower – off; Blower Prover – opens
Ignition Control – off; Gas Valve – closes
MAINTENANCE
Close Main valve
and Pilot valve
FIGURE 24.
28
Page 29
VENTING SYSTEM
Examine the venting system every six months for obstructions and/or deterioration of the vent piping. Check all vent system
connections for leakage and repair or reseal as necessary. Remove all soot or other obstructions from chimney which will
retard free draft.
INTAKE AIR SCREEN
The intake air screen is attached to the inlet end of the combustion blower. Inspect the intake air screen every six months. The intake air screen should be cleaned of any buildup of debris or foreign material.
TEMPERATURE-PRESSURE RELIEF VALVE TEST
• Burn hazard.
• Hot water discharge.
• Keep clear of Temperature­Pressure Relief Valve discharge outlet.
It is recommended that the Temperature-Pressure Relief Valve should be checked to ensure that it is in operating condition every 6 months.
When checking the Temperature-Pressure Relief Valve operation, make sure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot. Use care when operating valve as the valve may be hot.
To check the relief valve, lift the lever at the end of the valve several times, see Figure 25. The valve should seat properly and operate freely.
If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater and drain the water heater, see Draining and Flushing on page 30. Replace the Temperature­Pressure Relief Valve with a properly rated/sized new one,
see Temperature-Pressure Relief Valve on pages 13-14 for
instructions on replacement.
FIGURE 25.
If the Temperature-Pressure Relief Valve on the water heater weeps or discharges periodically, this may be due to thermal expansion.
NOTE: Excessive water pressure is the most common cause of Temperature-Pressure Relief Valve leakage. Excessive water system pressure is most often caused by "thermal expansion" in a "closed system." See Closed Water Systems and Thermal Expansion on page 13. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion.
Temperature-Pressure Relief Valve leakage due to pressure build
up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty. Thermal expansion tanks must be installed on all closed water systems.
DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE, SERIOUS INJURY OR DEATH.
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22­CSA 4.4 and ASME code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and excessive tank pressure.
Can cause serious injury or death.
ANODE ROD INSPECTION
The anode rod is used to protect the tank from corrosion. Most hot water tanks are equipped with an anode rod. The submerged rod sacrices itself to protect the tank. Instead of corroding tank, water ions attack and eat away the anode rod. This does not affect water’s taste or color. The rod must be maintained to keep tank in operating condition.
Anode deterioration depends on water conductivity, not necessarily water condition. A corroded or pitted anode rod indicates high water conductivity and should be checked and/or replaced more often than an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualied technician, and at a minimum should be checked annually after the warranty period.
Articially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions.
The use of a water softener may decrease the life of the water heater tank.
The anode rod should be inspected after a maximum of three years and annually thereafter until the condition of the anode rod dictates its replacement. Anode rod replacement is not covered by warranty.
NOTE: Articially softened water requires the anode rod to be inspected annually.
DRAINING AND FLUSHING
29
Page 30
TANK TYPE COMMERCIAL WATER HEATERS
Burn harzard.
Hot water discharge.
Keep hands clear of drain valve discharge.
It is recommended that the water heater storage tank be drained and ushed every 6 months to reduce sediment buildup. The water heater should be drained if being shut down during freezing temperatures.
To Drain the Water Heater Storage Tank:
1. Turn off the electrical supply to the water heater.
2. Turn off the gas supply at the Main Gas Shutoff Valve if the water heater is going to be shut down for an extended period.
3. Ensure the cold water inlet valve is open.
4. Open a nearby hot water faucet and let the water run until the water is no longer hot.
5. Close the cold water inlet valve to the water heater.
6. Connect a hose to the water heater drain valve and terminate it to an adequate drain.
7. Open the water heater drain valve and allow all the water to drain from the storage tank.
8. Close the water heater drain valve when all water in the storage tank has drained.
9. Close the hot water faucet opened in Step 4.
10. If the water heater is going to be shut down for an extended period, the drain valve should be left open.
The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils.
Lime accumulation may affect the life of equipment, the efciency of the heater, and fuel consumption characteristics. The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the hardness (lime). For this reason it is recommended that a regular schedule for deliming be maintained.
The time between cleaning will vary from weeks to years depending upon water conditions and usage.
The depth of lime buildup should be measured periodically. Heaters equipped with cleanouts will have about 2" of lime buildup when the level of lime has reached the bottom of the cleanout opening. A schedule for deliming should then be set up based on the amount of time it would take for a 1" buildup of lime. It is recommended that the water heater initially be inspected after 6 months.
Example 1:
Initial inspection after 6 months shows 1/2" of lime accumulation. Therefore, the heater should be delimed once a year.
Example 2:
Initial inspection after 6 months shows 2" of lime accumulation. Therefore, the heater should be delimed every 3 months.
To Flush the Water Heater Storage Tank:
1. Turn off the electrical supply to the water heater.
2. Ensure the cold water inlet valve is open.
3. Open a nearby hot water faucet and let the water run until the water is no longer hot. Then close the hot water faucet.
4. Connect a hose to the drain valve and terminate it to an adequate drain.
5. Ensure the drain hose is secured before and during the entire ushing procedure. Flushing is performed with system water pressure applied to the water heater.
6. Open the water heater drain valve to ush the storage tank.
7. Flush the water heater storage tank to remove sediment and allow the water to ow until it runs clean.
8. Close the water heater drain valve when ushing is completed.
9. Remove the drain hose.
10. Fill the water heater - see Filling The Water Heater in this manual.
11. Turn on the electrical supply to place the water heater back in operation.
12. Turn on the gas supply to the water heater at the Main Gas Shutoff Valve.
13. Allow the water heater to complete several heating cycles to ensure it is operating properly.
PERIODIC REMOVAL OF LIME DEPOSITS FROM
FIGURE 26.
DELIMING SOLVENTS
UN•LIME is recommended for deliming. UN•LIME is a patented food grade acid which is safe to handle and does not create the harmful fumes which are associated with other products.
UN•LIME may be obtained from your dealer, distributor or water heater manufacturer. Order Part Number 9005416105, 1 gallon, packed 4 gallons per case or Part Number 9005417105, 5 gallon container.
NOTE: Un•Lime is not available for use in Canada.
30
Page 31
Hydrochloric base acids are not recommended for use on glass lined tanks.
Observe handling instructions on label of product being used.
TANK CLEANOUT PROCEDURE
The following practices will ensure longer life and enable the unit to operate at its designed efciency:
1. Once a month the heater should be ushed. Open the drain
valve and allow two gallons of water to drain from the heater. Inlet water valve should remain open to maintain pressure in tank.
2. A cleanout opening is provided for periodic cleaning of
the tank. Gas must be shut off and heater drained before opening cleanout.
To clean heater through cleanout opening, proceed as follows:
3. Drain heater.
4. Remove outer cover plate from lower side of heater jacket.
5. Remove six (6) hex head screws securing tank cleanout
plate and remove plate.
6. Remove lime, scale, or sediment using care not to damage
the glass lining.
7. Inspect cleanout plate gasket, if new gasket is required,
replace with part no. 9004099215.
8. Install cleanout plate. Be sure to draw plate up tight by
tightening screws securely.
9. Replace outer jacket cover plate.
In some water areas the sediment might not be removed by this method and may result in the water heater making rumbling or boiling noises. To dissolve and remove these more stubborn mineral deposits, UN•LIME Professional Delimer should be used.
DELIMING USING FLO-JUG METHOD
UN•LIME in the 5 gallon size is recommended for deliming of all models. Contact your local dealer, distributor or water heater manufacturer.
Prepare the Water Heater
To delime the water heater using the Flo-Jug method, rst prepare the heater for deliming.
Explosion Hazard
Flammable hydrogen gases may be present.
Keep all ignition sources away from faucet when turning on hot water.
Do not smoke or have open ame or sparks in vicinity of heater. Do not mix UN•LIME with other chemicals. Do not allow contact with magnesium, aluminum or galvanized metals.
Chemical Hazard
• Product contains phosphoric acid.
• Keep out of reach of children.
• Use rubber or neoprene gloves.
UN•LIME contains phosphoric acid. In case of external contact, ush with cool water. If irritation persists, get medical attention. If swallowed, give 1 or 2 glasses of water or milk and call physician.
Get immediate medical attention for eyes. Keep out of reach of children.
NOTE: THE USE OF RUBBER OR NEOPRENE GLOVES IS RECOMMENDED, ESPECIALLY IF YOU HAVE ANY OPEN SORES OR CUTS TO AVOID UNNECESSARY IRRITATION OR DISCOMFORT.
1. Turn off fuel and/or power supply to heater. Also, turn off power to any electrical device or equipment, which is attached, or part of the system.
2. Open hot water side of faucet closest to heater and allow water to run until it is cool enough to handle safely.
3. Close cold water inlet valve to heater.
4. Connect hose to drain valve at bottom of heater and start draining heater into suitable oor drain area.
5. Remove relief valve while heater is draining. NOTE: Do not replace relief valve until deliming is completed. Relief valve opening will also act as a vent in case of possible contact between the delimer and the anode rod(s), which may produce ammable hydrogen-air mixtures.
6. If relief valve appears to be limed-up, place it in a clean glass or plastic container adequate in size so that you can pour enough UN•LIME® into the container to cover the valve and allow space for foaming. When foaming stops, run fresh cool water into the container and rinse the relief valve for a few minutes.
7. If heater does not drain completely after a reasonable length of time, turn off the main water supply valve to stop water from entering the tank due to a by-pass problem or defective cold water inlet valve. Also, check for clogged drain valve opening. Heater must be completely drained before introducing UN•LIME.
8. Remove the cleanout cover and place a clean plastic bucket next to the cleanout opening.
Partially open the cold water inlet valve to allow time to accomplish the following and then close the valve.
While the water is being run through the tank, insert a stiff wire, copper tube attened at one end or an opened wire coat hanger through the cleanout opening and scrape out any loose deposits of scale or sediment. This is an economical way to avoid unnecessary usage of the deliming solution.
Repeat the opening and closing of the cold water inlet valve as necessary but be sure the heater is completely drained when ready to introduce the UN•LIME.
Upon completion, reinstall the cleanout cover and use a new cleanout cover gasket (part number 9004099215).
Remove the drain valve.
31
Page 32
9. Install the long plastic male adapter insert tting into the drain valve opening of heater after applying Teon tape or paste to threads. Tighten rmly by hand and use wrench or adjustable pliers to check for secure connection. Do not over tighten to avoid damage to threads and ttings.
Prepare the Up-N-Down Transfer Kit
The next step is the preparation on the Up-N-Down Transfer Kit, if you have not already done so:
1. With the 5 gallon Up-N-Down container in the vertical position, unscrew the plastic vent cap in the handle and pierce the plastic membrane over the vent boss under the cap to allow the container to vent.
Note: If your container does not have the vent cap and vent boss, drill a 3/16” hole in the handle. When you have nished deliming you will be able to plug this drilled vent with the stainless steel screw that is supplied with the kit.
2. Remove the container’s cap and cut the plastic membrane located in the 3/4” IPT opening in the cap. Take care to not damage the threads.
3. Find the 3/4” male adapter, apply teon tape to the threaded end and screw it into the 3/4” IPT opening in the cap.
4. Put cap with male adapter back on the container and slide 3/4” hose over end of male adapter and fasten in place using hose clamp provided.
Delime using Flo-Jug Method
5. Slide the hose clamp over end of hose and slide hose over the male adapter in the water heater drain opening and secure in place using hose clamp.
6. Lift container to the “Pour” Position, see Figure 27, being careful to keep the vent in the handle above the liquid level
and pour the UN•LIME into the heater.
7. Lower container, you may have to place the container on its empty carton to prevent the UN•LIME from owing back into the container.
8. Let UN•LIME remain in the heater for 5 minutes and then lower the container to the “Drain” Position, see Figure 27.
9. Deliming activity is indicated by foaming on the surface of the UN•LIME. If there is deliming activity, repeat steps 6 thru 8.
Normally, lime removal will be completed within one hour. Severe build-up of lime may take longer than an hour to complete descaling.
Note: To check UN•LIME for continued use, place some scale or white chalk in a glass with a small amount of UN•LIME. If the material is vigorously dissolved by the UN•LIME, it can be reused; if not, the UN•LIME should be replaced.
FIGURE 27.
SERVICE
The installer may be able to observe and correct certain problems which may arise when the unit is put into operation. HOWEVER, it is recommended that only a qualied service agency, using appropriate test equipment, be allowed to service the heater.
As preliminary step, check wiring against diagram, check for grounded, broken or loose wires. Check all wire ends to be sure that they are making good contact.
IGNITION CONTROL SYSTEM
Before calling your qualied service agency, the following checklist should be examined to eliminate obvious problems from those requiring replacement or servicing.
Check that “main gas shutoff valve” is fully open and that gas service has not been interrupted.
Check electrical supply to the water heater for possible blown (or tripped) fusing or power interruption. Also check the 3 amp fuse on the front of the digital thermostat (Fig. 2).
Is the water temperature in tank below the thermostat dial setting on the water heater thermostat (calling for heat)?
It is possible that the high limit (E.C.O.) has functioned to shut off the water heater. See page 7 - High Limit Switch for reset procedure. Contact your service agent if limit continues to function to shut off water heater.
SYSTEM DIAGNOSTICS
Your water heater is equipped with an ignition control that incorporates a diagnostic system to assist in troubleshooting the water heater. The green LED codes on the ignition module are as follows:
TABLE 9.
2 FLASHES 5 Minutes Retry Delay
3 FLASHES Recycle - ame failed during run
4 FLASHES Flame sensed out of sequence
6 FLASHES Control Internal Error
7 FLASHES Flame rod shorted to ground
8 FLASHES Low secondary voltage supply
If an internal control failure is indicated, replace the ignition control.
Use this diagnostic system in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERATION” to troubleshoot the water heater.
ELECTRICAL SERVICING
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
32
Page 33
FOR YOUR INFORMATION
START UP CONDITIONS
Smoke/Odor
It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while.
Strange Sounds
Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not necessarily represent harmful or dangerous conditions.
Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal.
OPERATIONAL CONDITIONS
Hot Water Odor
In each water heater there is installed at least one anode rod for corrosion protection of the tank. Certain water conditions will cause a reaction between this rod and the water. The most common complaint associated with the anode rod is one of a “rotten egg smell” in the hot water. The smell is a result of four factors which must all be present for the odor to develop:
a. A concentration of sulfate in the supply water.
b. Little or no dissolved oxygen in the water.
c. A sulfate reducing bacteria which has accumulated within the
water heater (this harmless bacteria is nontoxic to humans).
d. An excess of active hydrogen in the tank. This is caused by
the corrosion protective action of the anode.
Hot water odor may be eliminated or reduced in some water heater models by replacing the anode(s) with one of less active material, and then chlorinating the water heater tank and all water lines.
Contact the local water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment.
If hot water odor persists after anode replacement and chlorination treatment, we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem.
Do not remove the anode rod leaving the tank unprotected. By doing so, all warranty on the water heater tank is voided.
“AIR” IN HOT WATER FAUCETS
HYDROGEN GAS: Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely ammable and explosive. To prevent the possibility of injury under these conditions, we recommend that the hot water faucet located farthest away from the water heater be opened for several minutes before any electrical appliances which are connected to the hot water system are used (such as a dishwasher or washing machine). If hydrogen gas is present, there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened. There must be no smoking or open ame near the faucet at the time it is open.
HIGH WATER TEMPERATURE SHUT OFF SYSTEM
This water heater is equipped with a manual reset type high limit (Energy Cutout) switch. The high limit switch interrupts the main burner gas ow should water temperature reach 203°F (95°C).
In the event of high limit switch operation, the water heater cannot be restarted unless the water temperature is reduced to approximately 120°F (49°C). The high limit reset button on the front of the thermostat then needs to be depressed. See Figure 2 for the location of the reset button.
33
Page 34
TROUBLESHOOTING
COMPLAINT CAUSE
*Water not hot enough Thermostat set too low. Set thermostat dial to a higher
Upper and/or lower temperature probe out of calibration.
*Insufcient hot water
*See WATER TEMPERATURE CONTROL WARNING (on page
12).
Water temperature too hot. Thermostat set too high. Set thermostat to a lower setting.
Rumbling. Sediment accumulation on
Ticking or metallic sounds. Expansion and contraction -
Pounding or water hammer. Air chambers in piping have
Water leaks. Drain valve not closed tightly. If drain valve cannot be closed
Gas odors. Possible gas leaks. Shut off gas supply to heater
Thermostat set too low. Set thermostat dial to a higher
Upper and/or lower temperature probe out of calibration.
Main manual gas shutoff valve
partially closed.
Heater too small for demand. Space usage to give heater time
Heater recovery is slower. Call qualied service agency Check gas input. If incorrect, check
bottom of tank.
normal.
become waterlogged. Thermal expansion tank damaged, improperly charged, or improperly sized.
If leakage source cannot be corrected or identied, call qualied service agency.
temperature
Call qualied service agency Check continuity and resistance (Ohms)
temperature
Call qualied service agency Check continuity and resistance (Ohms)
Open main manual gas shutoff
valve to fullest extent.
to restore water temperature.
Drain a quantity of water through drain valve. If rumbling persists, call a qualied service agency.
Drain piping system and rell. Heater must be off while this is being done. Check thermal expansion tank charge pressure when the water system pressure is zero.
tightly, replace.
Shut off gas supply to heater
and close cold water inlet valve to heater.
and call gas company at once
USER QUALIFIED SERVICE AGENCY
REMEDY
of upper and lower temperature probes. Replace probes if out of specication.
of upper and lower temperature probes. Replace probes if out of specication.
for inlet air blockage and/or ue gas exhaust blockage.
Delime heater.
Follow the manufacturer's instructions for proper charging of the thermal expansion tank.
Repair or in case of suspected tank leakage, be certain to conrm before replacing heater.
34
Page 35
FINISHED
FLOOR
HOT WATER
TO FIXTURES
COLD WATER
SUPPLY
EXPANSION
TANK
ALT. COLD WATER
CONNECTION
HOT WATER RETURN
FROM FIXTURES
PIPE T&P TO
OPEN DRAIN
WATER PIPING DIAGRAMS
FULL PORT BALL VALVE
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
MULTI FLUE - (1 UNIT) WITH VERTICAL STORAGE TANK
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
35
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
Page 36
FULL PORT BALL VALV
E
FINISHED
FLOOR
HOT WATER TO FIXTURES
COLD WATER
SUPPLY
HOT WATER
RETURN FROM
FIXTURES
ALTERNATE
LOCATION
CIRCULATING PUMP
EXPANSION
TANK
PIPE T&P TO
OPEN DRAIN
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
MULTI FLUE - (1 UNIT) WITH HORIZONTAL STORAGE TANK
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
36
Page 37
FULL PORT BALL VALVE
TEMPERED
WATER
RETURN
TEMPERED
WATER
OUTLET
HOT
WATER
OUTLET
HOT
WATER
RETURN
COLD WATER
SUPPLY
COLD
HOT
EXPANSION
TANK
PIPE T&P TO
OPEN DRAIN
CHECK VALVE
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
MULTI FLUE - (1 UNIT) WITH MIXING VALVE TWO TEMPERATURE
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
37
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
Page 38
FULL PORT BALL VALV
E
HOT WATER
TO FIXTURES
COLD WATER
SUPPLY
HOT WATER
RETURN
EXPANSION
TANK
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
CHECK VALVE
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
WARNING: THIS DRAWING SHOWS SUGGESTED
MULTI FLUE - (2 UNITS)
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
38
Page 39
FULL PORT BALL VALV
E
FINISHED
FLOOR
COLD WATER
SUPPLY
HOT WATER
TO FIXTURES
ALTERNATE
COLD WATER
CONNECTION
HOT WATER
RETURN
EXPANSION
TANK
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
CHECK VALVE
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
TEMPERATURE GAGE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
WATER FLOW SWITCH
DRAIN
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
MULTI FLUE - (2 UNITS) WITH VERTICAL STORAGE TANK
FOR ADDITIONAL REQUIREMENTS.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
39
Page 40
FULL PORT BALL VALV
E
FINISHED
FLOOR
COLD WATER
SUPPLY
HOT WATER
TO FIXTURES
ALTERNATE
COLD WATER
CONNECTION
HOT WATER
RETURN
EXPANSION
TANK
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
CHECK VALVE
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
MULTI FLUE - (2 UNITS) WITH VERTICAL STORAGE TANK
FOR ADDITIONAL REQUIREMENTS.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
40
Page 41
FULL PORT BALL VALV
E
FINISHED
FLOOR
HOT WATER TO FIXTURES
COLD WATER
SUPPLY
HOT WATER
RETURN FROM
FIXTURES
ALTERNATE
LOCATION
EXPANSION
TANK
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
MULTI FLUE - (2 UNITS) WITH HORIZONTAL STORAGE TANK
FOR ADDITIONAL REQUIREMENTS.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
41
Page 42
FULL PORT BALL VALV
E
N
BOOSTER WATER
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
LEGEND
BOOSTER WATER RETUR
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
HEATER
BOOSTER
TO FIXTURES
PRE-HEATED
WATER TO
BOOSTER
COLD WATER
SUPPLY
HOT WATER
HOT WATER
TO FIXTURES
RETURN
EXPANSION TANK
1st HEATER
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
MULTI FLUE (2 UNITS) TWO TEMPERATURE
FOR ADDITIONAL REQUIREMENTS.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
42
Page 43
FULL PORT BALL VALV
E
FINISHED FLOOR
HOT OUTLET
R
LEGEND
TEMPERATURE & PRESSURE
TEMPERATURE GAGE
CHECK VALVE
RELIEF VALVE
PRESSURE RELIEF VALVE
WATER FLOW SWITCH
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
AT STORED
TEMPERATURE
HOT WATE
RETURN
BOOSTER RETURN
(IF USED)
BOOSTED
WATER
OUTLET
COLD WATER
SUPPLY
TYPICAL
BOOSTER
EXPANSION
TANK
HEATER
PIPE T&P TO
OPEN DRAIN
PRE-HEATER
PIPE T&P TO
OPEN DRAIN
PRE-HEATER
MUST BE IDENTICAL HEATERS
MULTI FLUE (2 UNITS) WITH BOOSTER TWO TEMPERATURE
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
43
PIPE T&P TO
OPEN DRAIN
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
Page 44
FULL PORT BALL VALV
E
HOT WATER
R
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
HOT WATE
RETURN
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
PIPE T&P TO
OPEN DRAIN
COLD WATER
SUPPLY
EXPANSION
TANK
PIPE T&P TO
OPEN DRAIN
TO FIXTURES
PIPE T&P TO
OPEN DRAIN
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
MULTI-FLUE (3 UNITS)
FOR ADDITIONAL REQUIREMENTS.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
44
Page 45
E
TO FIXTURES
HOT WATE
R
HOT WATER
FINISHED FLOOR
RETURN
FULL PORT BALL VALV
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
COLD WATER
SUPPLY
EXPANSION TANK
LEGEND
ALT. COLD WATER
CONNECTION
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
AOS
STORAGE TANK
PIPE T&P TO
OPEN DRAIN
HEATERHEATERHEATER
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
MULTI-FLUE (3 UNITS) WITH VERTICAL STORAGE TANK
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
45
PIPE T&P TO
OPEN DRAIN
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
Page 46
E
HOT WATER
FINISHED FLOOR
EXPANSION TANK
FULL PORT BALL VALV
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
RETURN
COLD WATER
SUPPLY
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
PIPE T&P TO
HOT WATER TO FIXTURES
OPEN DRAIN
ALTERNATE
LOCATION
AOS
STORAGE TANK
HEATERHEATERHEATER
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
MULTI-FLUE (3 UNITS) WITH HORIZONTAL STORAGE TANK
FOR ADDITIONAL REQUIREMENTS.
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
46
Page 47
E
HOT WATER
HOT WATE
R
FULL PORT BALL VALV
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
RETURN
COLD WATER
SUPPLY
EXPANSION
TANK
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
TO FIXTURES
MULTI FLUE FLUE (4 UNITS)
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
47
Page 48
FULL PORT BALL VALV
E
HOT WATER
CHECK VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
HOT WATER
RETURN
COLD WATER
SUPPLY
EXPANSION
TANK
LEGEND
ALT. COLD
WATER
CONNECTION
TO FIXTURES
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
AOS
STORAGE TANK
PIPE T&P TO
OPEN DRAIN
HEATERHEATERHEATERHEATER
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
MULTI-FLUE (4 UNITS) WITH VERTICAL STORAGE TANK
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
48
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
Page 49
FULL PORT BALL VALV
E
EXPANSION TANK
CHECK VALVE
LEGEND
TEMPERATURE & PRESSURE
RELIEF VALVE
PRESSURE RELIEF VALVE
TEMPERATURE GAGE
WATER FLOW SWITCH
CIRCULATING PUMP
TANK TEMPERATURE CONTROL
DRAIN
HOT WATER
RETURN
PIPE T&P TO
OPEN DRAIN
COLD WATER
ALTERNATE
LOCATION
AOS
SUPPLY
HOT WATER
TO FIXTURES
HEATERHEATERHEATERHEATER
PIPE T&P TO
OPEN DRAIN
PIPE T&P TO
OPEN DRAIN
STORAGE TANK
MULTI-FLUE (4 UNITS) WITH HORIZONTAL STORAGE TANK
WARNING: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND OTHER DEVICES;
CHECK WITH LOCAL CODES AND ORDINANCES
FOR ADDITIONAL REQUIREMENTS.
PIPE T&P TO
OPEN DRAIN
49
PIPE T&P TO
OPEN DRAIN
NOTES:
1. Preferred piping diagram.
2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system.
3. Service valves are shown for servicing unit. However, local codes shall govern their usage.
4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
Page 50
NOTES
50
Page 51
COMMERCIAL
WATER HEATER
LIMITED WARRANTY
EFFECTIVE
For 3 Years, in the event of a tank leak, we will repair or, at our
discretion, replace the defective water heater.
For 1 Year, in the event of part failure, we will repair or, at our
discretion, replace the defective part.
We warrant this product against defects in materials or workmanship as described in this document if installed within the United States or Canada and provided the product remains at its original place of installation.
Warranty coverage begins the date of installation OR the date of manufacture if installation cannot be veried.
WHAT'S COVERED
Subject to these terms, in the event of defect in materials and/ or workmanship resulting in a tank leak during the rst three years, we will:
Replace the water heater should the tank leak.
Subject to these terms, in the event of a defect in materials and/or workmanship appearing during the rst year, we will:
Repair or, at our discretion, replace any part of the water
heater covered under this limited warranty excluding parts subject to normal maintenance (Example: non-electronic anode rod, lter, etc)
Service/labor, shipping, delivery, installation, handling or any other costs are not covered at any time under this warranty.
Any replacement part or product will be warranted only for the unexpired portion of the original water heater’s limited warranty period.
If an identical model is no longer available due to a change in law, regulation, or standard, we will replace the product with one having comparable capacity and input. In these instances, the owner will have the option of paying the difference between what was paid for the original model and the new model with the additional features, or receiving a refund of the portion of the purchase price, on a pro-rata basis allocable to the unexpired portion of the warranty.
WHAT'S NOT COVERED
• Problems caused by improper: gas supply line sizing, gas type, venting, connections, combustion air, voltage, wiring, or fusing
• Failure to follow applicable codes
• Failure to follow printed instructions
• Abuse, misuse, accident, re, ood, Acts of God
• Improper installation, sizing, delivery, or maintenance
• Claims related to rust, noise, smell, or taste of water
• Failure to conduct authorized factory start up if required
• Alterations to the water heater
• Non-outdoor heaters installed outdoors
• Damages due to a failure to allow for thermal expansion
• Heat exchanger failure due to lack of adequate / proper supply of water
• Heaters moved from their original location
• Service trips to explain proper installation, use, or maintenance of the product/unit or to describe compliance requirements under applicable codes and regulations
• Charges related to accessing your heater including but not limited to door/wall removal, equipment rental, etc.
• Replacement parts after expiration of this warranty
LIMITATIONS
NOTWITHSTANDING ANYTHING ELSE TO THE CONTRARY, THIS IS YOUR SOLE AND EXCLUSIVE WARRANTY. ALL OTHER WARRANTIES INCLUDING A WARRANTY OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE ARE EXPRESSLY DISCLAIMED. SELLER SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, SPECIAL, PUNITIVE OR OTHER INDIRECT DAMAGES. TOTAL LIABILITY ARISING AT ANY TIME SHALL NOT EXCEED THE PURCHASE PRICE PAID WHETHER BASED ON CONTRACT, TORT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY.
SERVICE INQUIRIES:
For service inquiries call the telephone number listed below. Be prepared to provide the following information:
name, address, and telephone number; the model and serial number of the water heater; proof of installation; and a clear description of the problem.
For your records, fill in the product:
Serial: ___________________ Model: ___________________ U.S. Customers: Canadian Customers:
A. O. Smith Corporation P. O. Box 310 – 768 Erie Street
500 Tennessee Waltz Parkway Stratford (Ontario) N5A 6T3 Ashland City, Tennessee 37015 800-265-8520
800-527-1953 www.hotwater.com
51
Page 52
500 Tennessee Waltz Parkway, Ashland City, TN 37015
Tech Support: 800-527-1953
Parts: 800-433-2545
www.hotwater.com