Isolated, Potentiometer Input
FEATURES
Amplifies, Protects, Filters, and Isolates a wide variety of
three-wire potentiometers and two-wire rheostats
(slidewires).
Generates a low-impedance output of 0 to +5V.
Module circuitry can withstand 240v rms at the input screw-
terminals.
All 5B36 series modules are mix-and-match and Hot
Swappable.
APPLICATIONS
Industrial signal conditioning
Industrial signal isolation
Industrial signal filtering
PRODUCT OVERVIEW
The 5B Series represents an innovative generation of low cost,
high performance plug-in signal conditioners. Designed for
industrial applications, these modules incorporate highly
reliable transformer-based isolation and automated surfacemount manufacturing technology. They are compact,
economical components whose performance exceeds that
available from more expensive devices. Combining 1500 V rms
continuous isolation, +0.05% calibrated accuracy, small size and
low cost, the 5B Series is an attractive alternative to expensive
signal conditioners and in-house designs
All modules are potted and identical in pin-out and size (2.27” x
2.32” x 0.595”). They can be mixed and matched, permitting
users to address their exact needs, and may be “hot swapped
without disturbing field wiring or power. The isolated input
modules provide 0 to +5V or +5V outputs and accept J, K, T, E,
R, S, N, or B type thermocouples.
These modules feature complete signal conditioning functions
including 240 V rms input protection, filtering, chopper
stabilized low drift +1 uV/oC amplification, 1500 V rms
isolation, and sensor excitation when required.
All modules feature excellent common mode rejection and
meet industrial transient surge withstand specifications.
5B36
FUNCTIONAL BLOCK DIAGRAM
Figure 1. 5B36 Functional Block Diagram
There are also a number of backplanes and mounting sockets
which provide a complete signal conditioning solution for end
users. Each backplane incorporates screw terminals for field
wiring inputs and outputs and cold junction sensors for
thermocouple applications.
These signal conditioners are designed to provide an easy and
convenient solution to signal conditioning problems of both
designers and end users in measurement and control
applications. Typical uses include microcomputer-based
measurement systems, standard data acquisition systems,
programmable controllers, analog recorders and dedicated
control systems. The 5 B series modules are ideally suited to
applications where monitoring and control of temperature,
pressure, f low, rotation and other analog signals are required.
The 5B Series modules and backplanes are approved by Factory
Mutual (FM) and the 5B Series modules are approved by the
Canadian Standards Association (CSA) for use in Class 1,
Division 2, Groups A, B, C, and D locations. These approvals
certify that the 5B Series is suitable for use in locations where a
hazardous concentration of flammable gas may exist only under
fault conditions of operation. Equipment of this category is
called “nonincendive” and they need no special enclosures or
other physical safeguards.
The 5B series modules and backplanes have been tested and
passed the stringent heavy industrial requirements of the
European Union’s electromagnetic compatibility (ENC)
directive – EN50082-1 and EN50081-2. When used according
to installation directions (refer to 5B series User Manual), any
errors caused by EMI/RFI interference will be less than 0.1% of
the full scale 5B measurement range for field strengths up to 10
V/M and frequencies up to 1 GHz.
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable.
However, no responsibility is assumed by Analog Devices for its use, nor for any
infringements of patents or other rights of third parties that may result from its use.
Specifications subject to change without notice. No license is granted by implication
or otherwise under any patent or patent rights of Analog Devices. Trademarks and
registered trademarks are the property of their respective companies.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
Tel: 781.329.4700
Fax: 781.326.8703 © 2004 Analog Devices, Inc. All rights reserved.
www.analog.com
GENERAL DESCRIPTION
The 5B36 is a single-channel signal conditioning module that
amplifies, isolates, filters, buffers a wide variety of three-wire
potentiometers and two-wire rheostats (slidewires). The module
provides an accurately scaled, low-noise low-impedance output
of 0 to +5V.
Accurate and Stable Performance – The 5B36 supplies
protected potentiometer / slidewire excitation from a pair of
closely matched precision current sources designed to cancel
errors due to lead resistances. A low-drift chopper-stabilized
differential amplifier allows use of a very low excitation current
to minimize error due to potentiometer self-heating. The
amplifiers low input offset drift (+
30 ppm/
range.
True Three-Port Isolation – The floating, differential input
circuit on the field side eliminates the need for any input
grounding. Signal and power isolation by transformer coupling
uses a proprietary modulation technique for linear, stable and
reliable performance. A demodulator on the computer side of
the signal transformer recovers the original signal, which is then
filtered and buffered to provide a low-noise, low-impedance
output signal. True three-port isolation (Input-Output-Power)
includes common-mode rating of : 1500V rms between input-
.
o
C assure accuracy over the full operating temperature
0.004 Ω /oC) and gain drift of
5B36
output and input-power; 250V rms between power and output
– no return path is required between the power and signal
output commons.
Filtering and Protection – An optimized five-pole Butterworth
filter (with a 4-Hz bandwidth) provides 116 dB of normal-mode
rejection (noise on signal) at 60 Hz and 108 dB at 50. Output
noise is an exceptionally low 0.3 mV pk-pk in a 100 kHz
bandwidth and 6 mV pk-pk in a 5 MHz bandwidth.
The 5B36 protects the computer side from damage due to fieldside over-voltage faults. The module withstands 240V rms at the
input terminals without damage, thereby shielding the internal
computer-side circuitry from field-side over-voltage conditions.
In addition, the 5B36 is mix-and-match and hot swappable with
all other 5B Series modules, so can be inserted or removed from
any socket in the same backplane without disrupting system
power.
A series output switch eliminates the need for external
multiplexing in many applications. The switch is turned on by
an active-low enable input. If the switch is to be on at all times,
the enable-input should be grounded to power common as it is
on the 5B01 and 5B08 backplanes..
.
Figure 2
Rev. 0 | Page 2 of 8
5B36 Models Available
Model Input Range Output Range
5B36-01
5B36-02
5B36-03
5B36-04
5B36-Custom * *
* Custom Input/Output ranges are available. Refer to configuration guide.
0 Ω to 100 Ω
0 Ω to 500 Ω
0 Ω to 1 kΩ
0 Ω to 10 kΩ
5B36 Specifications
(typical @ +25°C and Vs = +5 V dc)
Description Model 5B36
Input Ranges
Standard Ranges
Custom Ranges
Output Range (RL > 50 kΩ)
Accuracy1
Initial @ +25°C ±0.08% Span
Input Offset vs. Temperature
0 Ω to 10 kΩ (Refer to Model Table)
0 Ω to 10 kΩ (Refer to Ordering Section)
0 V to +5 V
0 V to +5 V
0 V to +5 V
0 V to +5 V
0 V to +5 V
5B36
100 Ω, 500 Ω, 1 kΩ Sensors ±0.004 Ω /°C
10 kΩ Sensor ±0.01 Ω /°C
Output Offset vs. Temperature ±20 µV/°C
Gain vs. Temperature ±0.003% of Reading/°C
Input Resistance
Power On
Power Off
Overload
Input, 0.1 Hz to 10 Hz Bandwidth 0.2 µV rms
Output, 100 kHz Bandwidth 100 µV rms (0.3 mV peak-peak)
Output, 1 MHz Bandwidth 1.5 mV peak-peak
Output, 5 MHz Bandwidth 6 mV peak-peak
Bandwidth, -3 dB 4 Hz
Output Rise Time, 10% to 90% Span 100 ms
Common-Mode Voltage (CMV)
Input-to-Output, Continuous 1500 V rms, maximum
> 1000 MΩ
200 kΩ
200 kΩ
Noise
Rev. 0 | Page 3 of 8