Analog Devices B30 31 0 (2) Datasheet

Millivolt and Voltage Input
FEATURES
Isolated Voltage Input. Amplifies, Protects, Filters, & Isolates Analog Input Voltages. Protect the computer side from damage due to field-side
overvoltage faults. A Series output switch eliminates the need for external
multiplexing in many applications. Module circuitry can withstand 240v rms at the input screw-
terminals. All 5B30 & 5B31 series modules are mix-and-match and Hot
Swappable.
APPLICATIONS
Industrial signal conditioning Industrial signal isolation Industrial signal filtering
PRODUCT OVERVIEW
The 5B Series represents an innovative generation of low cost, high performance plug-in signal conditioners. Designed for industrial applications, these modules incorporate highly reliable transformer-based isolation and automated surface­mount manufacturing technology. They are compact, economical components whose performance exceeds that available from more expensive devices. Combining 1500 V rms continuous isolation, +0.05% calibrated accuracy, small size and low cost, the 5B Series is an attractive alternative to expensive signal conditioners and in-house designs
All modules are potted and identical in pin-out and size (2.27” x
2.32” x 0.595”). They can be mixed and matched, permitting users to address their exact needs, and may be “hot swapped without disturbing field wiring or power. The isolated input modules provide 0 to +5V or +5V outputs and accept J, K, T, E, R, S, N, or B type thermocouples.
These modules feature complete signal conditioning functions including 240 V rms input protection, filtering, chopper stabilized low drift +1 uV/oC amplification, 1500 V rms isolation, and sensor excitation when required.
All modules feature excellent common mode rejection and meet industrial transient surge withstand specifications.
5B30/5B31
Figure 1. 5B30/5B31 Functional Block Diagram
There are also a number of backplanes and mounting sockets which provide a complete signal conditioning solution for end users. Each backplane incorporates screw terminals for field wiring inputs and outputs and cold junction sensors for thermocouple applications.
These signal conditioners are designed to provide an easy and convenient solution to signal conditioning problems of both designers and end users in measurement and control applications. Typical uses include microcomputer-based measurement systems, standard data acquisition systems, programmable controllers, analog recorders and dedicated control systems. The 5 B series modules are ideally suited to applications where monitoring and control of temperature, pressure, f low, rotation and other analog signals are required.
The 5B Series modules and backplanes are approved by Factory Mutual (FM) and the 5B Series modules are approved by the Canadian Standards Association (CSA) for use in Class 1, Division 2, Groups A, B, C, and D locations. These approvals certify that the 5B Series is suitable for use in locations where a hazardous concentration of flammable gas may exist only under fault conditions of operation. Equipment of this category is called “non-incendive” and they need no special enclosures or other physical safeguards.
The 5B series modules and backplanes have been tested and passed the stringent heavy industrial requirements of the European Union’s electromagnetic compatibility (ENC) directive – EN50082-1 and EN50081-2. When used according to installation directions (refer to 5B series User Manual), any errors caused by EMI/RFI interference will be less than 0.1% of the full scale 5B measurement range for field strengths up to 10 V/M and frequencies up to 1 GHz.
FUNCTIONAL BLOCK DIAGRAM
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties that may result from its use. Specifications subject to change without notice. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices. Trademarks and registered trademarks are the property of their respective companies.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700 Fax: 781.326.8703 © 2004 Analog Devices, Inc. All rights reserved.
www.analog.com
GENERAL DESCRIPTION
The 5B30 and 5B31 are single-channel signal conditioning modules that amplify, protect, filter and isolate analog input voltages.
The 5B30 and 5B31 protect the computer side from damage due to field-side over voltage faults. All models withstand 240V rms at their input terminals without damage thereby shielding computer side circuitry from field-side over voltage conditions. In addition, 5B30 and 5B31 Series modules are mix-and-match and hot swappable, so can be inserted or removed from any socket in the same backplane without disrupting system power.
A chopper-stabilized input amplifier provides low drift and stable gain. At the amplifier input, a stable, laser-trimmed zero­scale input voltage is subtracted from the input signal to set the zero scale value. For user convenience, the zero can be optionally factory-set to meet custom needs. This allows suppression of a zero-scale input value many times larger that the total span for precise expanded-scale measurements.
Internal multi-pole low-pass filtering with a four-Hz cutoff (­3dB) enhances normal-mode (noise on signal) and common-
5B30 / 5B31
mode (nosie on signal return) rejection at 50/60 Hz, enabling accurate measurement of small signals in high electrical noise.
Signal isolation by transformer coupling uses a proprietary modulation technique for linear, stable and reliable performance. The differential input circuit on the field side is fully floating, eliminating the need for any input grounding. A demodulator on the computer side of the signal transformer recovers the original signal, which is then filtered and buffered to provide a low-noise, low-impedance output signal. The output common must be kept within +
A series output switch eliminates the need for external multiplexing in many applications. The switch is turned on by an active-low enable input. If the switch is to be on at all times, the enable-input should be grounded to power common as it is on the 5B01 and 5B08 backplanes.
.
3 V of power common.
Figure2
Rev. 0 | Page 2 of 8
5B30 / 5B31—SPECIFICATIONS
5B30 and 5B31 Models Available
Model Input Range Output Range
5B30-01 -10 mV to +10 mV -5 V to +5 V 5B30-02 -50 mV to +50 mV -5 V to +5 V 5B30-03 -100 mV to +100 mV -5 V to +5 V 5B30-04 -10 mV to +10 mV 0 V to +5 V 5B30-05 -50 mV to +50 mV 0 V to +5 V 5B30-06 -100 mV to +100 mV 0 V to +5 V
5B30-Custom * *
Model Input Range Output Range
5B31-01 -1 V to +1 V -5 V to +5 V 5B31-02 -5 V to +5 V -5 V to +5 V 5B31-03 -10 V to +10 V -5 V to +5 V 5B31-04 -1 V to +1 V 0 V to +5 V 5B31-05 -5 V to +5 V 0 V to +5 V 5B31-06 -10 V to +10 V 0 V to +5 V 5B31-07 -20 V to +20 V -5 V to +5 V
5B31-Custom * *
*Custom Input/Output ranges are available. Refer to configuration guide.
5B30 and 5B31 Specifications
Description Model 5B30 Model 5B31
5B30 / 5B31
Input Ranges
Standard Ranges ±10 mV to ±100 mV ±1 V to ±20 V Custom Ranges ±5 mV to ±500 mV ±0.5 V to ±20 V Output Ranges (R
Initial @ +25°C ±0.05% Span ±10 µV RTI ±0.05% (Vz Nonlinearity ±0.02% Span * Input Offset vs. Temperature ±1 µV/°C ±20 µV/°C Output Offset vs. Temperature ±20 µV/°C * Gain vs. Temperature ±25 ppm of Reading/°C ±50 ppm of Reading/°C Input Bias Current ±3 nA ±0.2 nA
> 50 kΩ)4
L
-5 V to +5 V or 0 V to +5 V *
Accuracy
2
1
) ±0.05% Span ±0.2 mV RTI ±0.05% (Vz1)
Input Resistance
Power On Power Off
5 M 650 k 40 k 650 k
Rev. 0 | Page 3 of 8