ANALOG DEVICES ADE7754 Service Manual

The World Leader in High Performance Signal Processing Solutions
Multi-functional Polyphase
Energy Metering IC with Serial
Port Interface
ADE7754
Energy Measurement Group
Precision Converters (PRC) Division

ADE7754: A programmable solution for Polyphase Energy measurementTransducers

2

ADE7754: Technology at a glance

3

ADE7754: Overview of Functionalities

Surpasses IEC1036 requirement. Less than 0.1% error
over wide dynamic range
Supplies the following information:
Active energySign of Reactive energyApparent energySimultaneous RMS calculation on the six analog inputsPeak Voltage and Current detectionSAG Line Voltage detectionLine PeriodTemperature
Digital calibration
4

ADE7754: Characteristics

24-pin SOIC package
5V Power Supply
[-40 C; +85 C] Temperature Operating range
500mV maximum analog input range with PGA of 1, 2 or 4
on all channels
External Clock frequency = 10MHz
5

ADE7754: Block Diagram

Analog Front end
Current sensor connection
Digital solution
Active Energy
Calibration Mode
RMS measurements
Apparent Energy
Reactive Energy
Power Line Quality
Temperature sensor
6

ADE7754: A validated Analog front end

Analog Front end
Current sensor connection
Digital solution
RMS measurements
Active Energy
Apparent Energy
Calibration Mode
Reactive Energy
Power Line Quality
Temperature sensor
16-bit accuracy from 2nd order ΣΔ ADCs
Linearity error < 0.1% over wide dynamic
range (int. reference)
Measurement Bandwidth 14 kHz
7

ADE7754: Easy use of Current sensors

Analog Front end
Current sensor connection
Digital solution
RMS measurements
Active Energy
Apparent Energy
Calibration Mode
Input Gain up to 4
Reactive Energy
Power Line Quality
Temperature sensor
8
Phase compensation for CT connection
~ +/-0.5°max in 0.02°increment @ 50Hz
Loading...