7.DO NOT block any ventilation openings. Install in accordance with the manufacturer's instructions.
8.DO NOT install near any heat sources such as radiators, heat registers, stoves, or other apparatus (including amplifiers) that
produce heat.
9.DO NOT defeat the safety purpose of the polarized or grounding type plug. A polarized plug has two blades with one wider than the
other. A grounding type plug has two blades and a third grounding prong. The wider blade or the third prong are provided for your
safety. If the provided plug does not f it into your outlet, consult an electrician for replacement of the obsolete outlet.
10. PROTECT the power cord from being walked on or pinched, particularly at plugs, convenience receptacles, and the point where
they exit from the apparatus.
11. ONLY USE attachments/accessories specified by the manufacturer.
12. USE ONLY with a cart, stand, tripod, bracket, or table specified by the manufacturer, or sold with the apparatus. When a cart is
used, use caution when moving the cart/apparatus combination to avoid injury from tip-over.
13. UNPLUG this apparatus during lightning storms or when unused for long periods of time.
14. REFER all servicing to qualified service personnel. Servicing is required when the apparatus has been damaged in any way, such as
power-supply cord or plug is damaged, liquid has been spilled or objects have fallen into the apparatus, the apparatus has been
exposed to rain or moisture, does not operate normally, or has been dropped.
15. DO NOT expose this apparatus to dripping or splashing and ensure that no objects filled with liquids, such as vases, are placed on
the apparatus.
16. To completely disconnect this apparatus from the AC Mains, disconnect the power supply cord plug from the AC receptacle.
17. Where th e mains plug or an appli anc e coupler is used as the disconnec t device, the disconne ct de vic e shall remain readily operable.
18. DO NOT overload wall outlets or extension cords beyond their rated capacity as this can cause electric shock or fire.
The exclamation point, within an equilateral triangle, is intended to alert the user to the presence of important operating and maintenance
(servicing) instructions in the literature accompanying the product.
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of uninsulated "dangerous
voltage" within the product's enclosure that may be of suff icient magnitude to constitute a risk of electrical shock to persons.
ESD Warning: The icon to the left indicates text regarding potential danger associated with the discharge of static electricity from an outside
source (such as human hands) into an integrated circuit, often resulting in damage to the circuit.
WARNING: To reduce the risk of fire or electrical shock, do not expose this apparatus to rain or moisture.
WARNING: No naked flame sources - such as candles - should be placed on the product.
WARNING: Equipment shall be connected to a MAINS socket outlet with a protective earthing connection.
WARNING: To reduce the risk of electric shock, grounding of the center pin of this plug must be maintained.
No patent liability is assumed with respect to the use of information contained herein. While every precaution has been taken in the preparation of this
publication, AMX assumes no responsibility for error or omissions. No liability is assumed for damages resulting from the use of the information
contained herein. Further, this publication and features described herein are subject to change without notice.
AMX WARRANTY AND RETURN POLICY
The AMX Warranty and Return Policy and related documents can be viewed/downloaded at www.amx.com.
WARNING: This product is intended to be operated ONLY from the voltages listed on the back panel or the recommended, or
included, power supply of the product. Operation from other voltages other than those indicated may cause irreversible damage to
the product and void the products warranty. The use of AC Plug Adapters is cautioned because it can allow the product to be
plugged into voltages in which the product was not designed to operate. If the product is equipped with a detachable power cord,
use only the type provided with your product or by your local distributor and/or retailer. If you are unsure of the correct operational
voltage, please contact your local distributor and/or retailer.
EU COMPLIANCE INFORMATION:
Eligible to bear the CE mark; Conforms to European Union Low Voltage Directive 2006/95/EC; European Union EMC Directive
2004/108/EC; European Union Restriction of Hazardous Substances Recast (RoHS2) Directive 2011/65/EU; European Union
WEEE (recast) Directive 2012/19/EU; European Union Eco-Design Directive 2009/125/EC; European Union Registration,
Evaluation, Authorization and Restriction of Chemicals (REACH) Directive 2006/121/EC.
You may obtain a free copy of the Declaration of Conformity by visiting http://www.amx.com/techcenter/certifications.asp.
WEEE NOTICE:
This appliance is labeled in accordance with European Directive 2012/19/EU concerning waste of electrical and electronic equipment
(WEEE). This label indicates that this product should not be disposed of with household waste. It should be deposited at an appropriate
facility to enable recovery and recycling.
US FCC COMPLIANCE NOTICE – CLASS A
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency energy, and if it is not installed and used in
accordance with the instruction manual, it may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own
expense.
US FCC AND CANADA EMC COMPLIANCE INFORMATION:
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
CANADA ICES INFORMATION
ICES (Interference-Causing Equipment Standard): CAN ICES-3 (A)/NMB-3(A)
LICENSE NOTICES AND TRADEMARK ACKNOWLEDGMENTS
Windows® and Internet Explorer® are registered trademarks of Microsoft Corporation in the United States and other countries.
®
and the UL logo are trademarks of UL LLC.
UL
Ethernet
ENERGY STAR
Other products mentioned herein may be the trademarks of their respective owners.
®
is a registered trademark of the Xerox Corporation.
®
is a registered trademark of the U.S. Department of Energy and the U.S. Environmental Protection Agency.
The information in this manual applies to the DXLink Multi-Format Transmitter Module, the DXLink HDMI Transmitter Module, the
DXLink Multi-Format Wallplate Transmitter, the DXLink Multi-Format Decor Style Wallplate Transmitter (US), and the DXLink HDMI
Receiver Module listed in the table below. In this manual, these products will be referred to as the DX-TX, HDMI TX, Wallplate TX,
Decor Wallplate TX, and the DX-RX. When referring to all four of the transmitter units, the term Transmitters will be used.
* The DXLink HDMI TX Module has been discontinued. This manual contains information on it for support. All of the features
previously available in this product are currently available in the DX-TX Module.
COMPATIBILITY NOTE: The Transmitters and the Receiver listed above are compatible with a number of other DXLink products (see
the section “Product Compatibility Tables” on page 8). All of the Transmitters are compatible with the Receiver. The Wallplate TX and
Decor Wallplate TX must use DXLink power injectors when connecting directly to a DX-RX; others may cause damage. Also note that
TX and RX compatibility with Enova DGX DXLink boards applies when the boards are used in Enova DGX 8/16/32/64 enclosures and in
Enova DGX 100 Series enclosures.
DXLink Multi-Format Decor Style Wallplate
Tra n smi t te r (US)
(BLACK or WHITE)
DX-TX-DWP, DXLINK MULTI-FORMAT DECOR STYLE
WALLPLATE TX (BLACK or WHITE)
Product Overview and Specifications
Product Notes
The Transmitters and Receiver are designed for transmission of an HDMI signal over twisted pair cable (or a DVI signal via a
DVI-to-HDMI cable adapter) up to 328 feet (100 m). Functionality is briefly described below.
DX-TX – The DX-TX receives an HDMI signal or analog video signal (composite, Y/C, Y/Pb/Pr, RGB, RGBS, or RGBHV) and an audio
sig nal fro m a source device. The audio can b e either digital a udio embedded wi th the HDMI signal, di gital audio over S/PDIF, or
analog stereo audio.
Either analog or digital video is transmitted out of the DXLink output. The active video selection is made using one of two methods:
1) Aut omatic, which se lects digital video as the prio rity video input or analog video when no dig ital video is present. 2) Active ICSP
command video input selection from a bound NetLinx Central Controller.
Both the video and audio are transported over twisted pair cable to an Enova DGX Digital Media Switcher, an applicable Enova DVX
Solution (to a DX-RX), or directly to a DX-RX.
The 232 port (RS-232) on the DX-TX supports bidirectional serial data via the twisted pair cable to/from the 232 port on a DX-RX.
The DX-TX also has IR ports.
HDMI TX – The HDMI TX receives an HDMI signal and an audio signal from a source device. The audio can be either digital audio
emb edded with th e HDMI, digital audio over S/PDI F, or analo g stereo au dio. Bo th the video an d audio are transported over twisted
pair cable to an Enova DGX Digital Media Switcher, an applicable Enova DVX Solution (to an DX-RX), or directly to a DX-RX. The 232
port (RS-232) on the HDMI TX supports bidirectional serial data via the twisted pair cable to/from the 232 port on a DX-RX. The
HDMI TX also has IR ports.
Wallplate TX and Decor Wallplate TX – These wallplates receive an HDMI signal or analog video signal (composite, Y/C, Y/Pb/Pr,
RGB , RGBS, or RGB HV) and an audio signal f rom a sourc e dev ice. The audio can be eit her digital au dio embedded with the HD MI
signal or analog stereo audio.
Either analog or digital video is transmitted out of the DXLink output. The active video selection is made using one of two methods:
1) Aut omatic, which se lects digital video as the prio rity video input or analog video when no dig ital video is present. 2) Active ICSP
command video input selection from a bound NetLinx Central Controller.
Both the video and audio are transported over twisted pair cable to an Enova DGX Digital Media Switcher, an applicable Enova DVX
Solution, or directly to an DX-RX. Direct connection requires either PDXL-2 (FG1090-170) or PS-POE-AT-TC (FG423-84).
DX-RX – The DX-RX receives an HDMI signal with embedded audio over twisted pair cable from a DXLink compatible device
(or from a DXLink Transmitter) and sends the signal on to the destination. Audio received on the DX-RX can also be output on the
Stereo Audio Out port if it originated as a 2 channel audio signal. The 232 port (RS-232) on the DX-RX supports bidirectional serial
data via the twisted pair cable to/from the 232 port on the DX-TX or HDMI TX. The DX-RX features SmartScale® Technology
(integrated EDID output scaling) to ensure an appropriate ou tput resolu tio n, plus it supports a Manual (override) option for setting
up custom resolutions and a Bypass option. The DX-RX also has IR ports.
NOTE: If a DVI-D signal is used (via a DVI-to-HDMI cable adapter), the advanced audio support from HDMI will not be available.
NOTE: These DXLink products support several different modes which are available for system setup and use. Brief explanations of the
modes are provided in the section “Quick Reference Tables for Modes” on page 20 along with page references to complete
information.
Product Compatibility Tables
The Transmitters and the Receiver are compatible with the DXLink products listed in the three tables following.
Enova DGX Solutions and DXLink Functions
The following table shows which Enova DVX products support specific DXLink functions.
* Inputs and outputs up to 8, 16, 32, or 64 depending on the system (in increments of 4 inputs or outputs per board).
** For power budget information for system planning when using DXLink Transmitters and Receivers with an Enova DGX Digital
Media Switcher, see page 31.
Enova DVX Solutions and DXLink Functions
The following table shows which Enova DVX products support specific DXLink functions.
DXLink Functions in Enova DVX Solutions***
DVX-3156HDDVX-3155HD DVX-2155HD DVX-2150HD
DXLink Inputs4220
Power on DXLink Inpu tsYesYesYesNA
DXLink Outputs2211
Power on DXLink Ou tputsNoNoYesYes
*** Does not apply to the DVX-2100HD.
Solecis Solutions and DXLink Functions
The following table shows which Solecis products support specific DXLink functions.
NOTE: The Wallplate TX and Decor Wallplate TX have a limited set of features (i.e., no S/PDIF, IR, or serial ports).
Incorporates HDMI® technology
HDCP 1.3 compatible
Supports computer video up to 1920x1200, HDTV up to 1080p, as well as 3D support (3D and Deep Color)
Supports HDMI passthrough with embedded digital audio and single link DVI (DVI-to-HDMI cable adapter required)
DX-TX, Wallplate TX, and Decor Wallplate TX support analog video: composite, Y/C, Y/Pb/Pr, RGB, RGBS, or RGBHV
Reads the do wnstream EDID fro m the switcher (Endpoint Mode) o r the sink (Ex ten der Mode )
Transports video signals over distances up to 328 feet (100 m) via the DXLink connection
Interruption free content when used in conjunction with a switcher, AMX’s exclusive InstaGate Pro
audio and video to be switched quickly and easily to every connected display without the difficulties typically associated
with HDCP.
AutoDetect on the TXs and SmartScale
®
on the DX-RX work to automatically recognize any device’s supported resolutions
and signal type parameters, allowing switching out source and destination devices without manual setup. Also included is
the ability to control detailed timing parameters for customized video output formats. (SmartScale is the ability to
configure the scaling output by automatically selecting destination defined resolutions.)
Supports HDMI em bedded dig ital audio, digital audio over S/ PDIF, and analog stereo audio
Standard twisted pair cable saves time and installation effort
The USB port on the DX-RX passes keyboard and mouse USB signals to control a remote computer. The Transmitter’s USB
port connects to a Host PC and will forward HID keyboard and mouse data received from a directed Receiver’s USB port.
(For USB port information, see page 18.)
The 232 port (RS-232 ser ial ) supports bidirectional transfer of serial data between Master and TX or R X (Endpoint Mo de) or
between TX and RX (Extender Mode)
The IR port supports bidirectional transfer of IR data between Master and TX or RX (Endpoint Mode) or between TX and RX
(Ex ten der Mode)
Power over DXLink (twisted pair cable) support when used with a switcher or with an approved AMX Power over DXLink
device (for power budget information when used with an Enova DGX Digital Media Switcher, see page 31)
A desktop power supply (ENERGY STAR
®
qualified) is provided per module. The Wallplate TX and Decor Wallplate TX receive
power from the switcher or can be used with a DXLink power injector (for power budget information, see page 31).
The modules are compatible with all V Style, versatile mounting options including rack, surface, and pole. The Wallplate TX
includes a mounting bracket, and the Decor Wallplate TX mounts in a standard US double-gang box.
Backed by AMX’s 3 year warranty (see www.amx.com)
24-hour technical support
NOTE: Features and specifications described in this document are subject to change without notice.
®
Technology a llows
Common Applications
DXLink Transmitters and Receivers are designed to send audio, video, and control to a remote display across the room, on the o ther
side of the house, or to a classroom down the hall. The installation’s requirements dictate the system setup which generally takes
one of the following three forms.
Endpoint Mode (Switcher) – One or more Transmitters and/or Receivers are connected to a switcher* containing an
integrated Master (see page 28).
Endpoint Mode (Standalone) – A standalone DXLink TX/RX pair** are connected directly to each other but, in addition,
either the TX or RX is connected to a NetLinx Central Controller via a LAN or directly to the Controller (see page 30).
Extender Mode (Standalone) – A standalone DXLink TX/RX pair** are connected directly to each other as a simple extender
solution (see page 31).
* The switcher can be either an Enova DGX Switcher or an applicable Enova DVX Solution (see page 8).
** A wallplate in a standalone configuration requires power via a DXLink power injector.
PowerGreenPower is applied to the Transmitter Module
Digital VideoGreenA digital video signal is present through the Transmitter Module
AudioGreenEmbedded audio signal is present through the Transmitter Module
Analog Video
(DX-TX only)
IR TXRedIR TX active communication
IR RXYellowIR RX active communication
232 (Serial) TXRedSerial TX active communication
232 (Serial) RXYellowSerial RX active communication
NetLinx Link/Act GreenActive LAN connection to an AMX Network (Blinking = #3 Toggle OFF)
NetLinx StatusGreenLAN connection is active
NOTE: For detailed behavior of the NetLinx Link/Act and Status LEDs on the module’s front, see page 50. For detailed behavior of the
RJ-45 connector LEDs on the module’s rear, see page 40.
One of the 3 LEDs
will be Green
The type of analog video present through the DX-TX:
• C (composite) or Y/C (two component)
• Y/PB/PR or RGB (three component)
• RGBHV (five component) or RGBS (four component)
DXLink Multi-Format Wallplate TX (DX-TX-WP) Front View
FIG. 3 Multi-Format Wallplate TX front view, plus left edge and bottom edge views
Components located on front of Wallplate TX:
HDMI In – HD MI connec tor (with locking center sc rew) for dig ital video and embedded digital au dio (suppo rts a DVI-D
signal with use of DVI-to-HDMI cable adapter). When more than one audio signal is present, HDMI embedded audio takes
precedence over analog audio.
Digital Video LED – Indic ates the unit i s co nf i gured to pass HDMI with embedded audio (default)
Video In – An HD-15 connector for analog video: C (composite), Y/C, Y/Pb/Pr, RGB, RGBHV, or RGBS. Pinouts for analog
video are on page 104
Analog Video LEDs – Illuminates when the Wallplate TX is configured to pass analog video: composite or Y/C; Y/Pb/Pr or
RGB; RGBHV or RGBS
Audio In Stereo – Audio connector is a 3.5 mm stereo jack. An analog audio signal is only available when HDMI embedded
digital audio is not present (or conf igured for analog audio).
Audio LED – Indicates the unit is configured to pass analog audio (coupled with dig ital or an alog vi deo path)
USB Host port – Mini-B USB connector (supports USB host) for receiving keyboard / mouse commands from a specific RX.
(For USB port information, see page 18.)
Power LED –Indicates when the Wallplate TX is powered on
Components located on left and bottom edges of Wallplate TX:
Reset button (left) – Resets the Wallplate TX’s CPU (acts like a power cycle soft reboot)
Program port (left) – This port (USB mini-B connector) supports DGX Conf iguration Software for programming a customer
VGA EDID
ID Pushbutton (left) – Places the Wallplate TX in ID Mode for setting the NetLinx ID (device only) and provides additional
functionality, such as placing the device in Static IP Mode or DHCP Mode
NetLinx LEDs (bottom) – Left green LED (L = Link/Act) indicates network communication activity; right green LED
(S = Status) indicates unit status
DXLink LEDs (bottom) – Left yellow LED indicates HDCP status; right green LED indicates that a valid DXLink connection has
been established
DXLink Decor Wallplate TX (DX-TX-DWP) Front View
Decor Wallplate TX front view (before customer provided standard decor style front cover plate is attached)
FIG. 4
IMPORTANT: Be sure to measure the back box and any other components used to mount the Decor Wallplate TX prior to installation/
construction to ensure the unit fits (e.g., some mud rings do not work unless their corners are modified).
Components located on left and right front sections of Decor Wallplate TX:
USB Host port – Mini-AB USB connector (supports USB host) for receiving keyboard / mouse commands from a specif ic
RX. (For USB port information, see page 18.)
Audio In Stereo – Audio connector is a 3.5 mm stereo jack. An analog audio signal is only available when HDMI embedded
digital audio is not present (or conf igured for analog audio).
Video In – An HD-15 connector for analog video: C (composite), Y/C, Y/Pb/Pr, RGB, RGBHV, or RGBS. Pinouts for analog
video are on page 104
HDMI In – HD MI connec tor (with locking center sc rew) for dig ital video and embedded digital au dio (suppo rts a DVI-D
signal with use of DVI-to-HDMI cable adapter). When more than one audio signal is present, HDMI embedded audio takes
precedence over analog audio.
Power LED –Indicates when the Decor Wallplate TX is powered on
Audio LED – Indicates the unit is configured to pass analog audio (coupled with dig ital or an alog vi deo path)
Analog Video LEDs – Illuminates when the Decor Wallplate TX is configured to pass analog video: composite or
Y/C; Y/Pb/Pr or RGB; RGBHV or RGBS
Digital Video LED – Illuminates when the Decor Wallplate TX is configured to pass HDMI with embedded audio (default)
The Decor Wallplate TX has a number of front panel components, some can been seen when a standard decor style front cover plate
is attached and some are hidden by the plate (FIG. 4 shows all of them). The cover plate is customer provided to allow matching the
individu al decor o f an env ironment or matching othe r st andard decor covers in a roo m/area.
Components located on center front section of Decor Wallplate TX:
USB Program port – This port (USB mini-B connector) supports DGX Conf iguration Software for programming a customer
VGA EDID
Reset button – Resets Decor Wallplate TX’s CPU (acts like power cycle soft reboot)
Dip switch – A four-toggle DIP switch is used for enabling/disabling special functionality (see page 34)
ID Pushbutton – Places the Decor Wallplate TX in ID Mode for setting the NetLinx ID (device only) and provides additional
functionality, such as placing the device in Static IP Mode or DHCP Mode
DXLink LEDs –HDCP LED indicates HDCP status; DXLink LED indicates that a valid DXLink connection has been established
NetLinx LEDs – Status LED indicates unit status; Link/Act LED indicates network communication activity
Wallplate TX and Decor Wallplate TX Indicator LEDs
LEDsNormal DisplayIndicates
Digital Video (default) GreenThe Wallplate TX and Decor Wallplate TX have been configured* to pass HDMI (for
Analog VideoOne of the 3 LEDs
will be Green
AudioGreenThe Wallplate TX and Decor Wallplate TX have been configured* to pass analog audio as the
PowerGreenPower (from switcher) is applied to the unit
LEDs (bottom edge of Wallplate TX)
NetLinx - L (Link)GreenActive LAN connection to an AMX Network (Blinking = #3 Toggle OFF)
NetLinx - S (Status) Green
Off
DX Li nk Ye llowYel lo w
Flashing
Off
DXLink Green GreenDXLink connection is established
LEDs (under customer provided front cover plate on Decor Wallplate TX)
HDCP (DXLink)Yellow
Flashing
Off
DXLink GreenDXLink connection is established
Status (NetLinx) Green
Off
Link/Act (NetLinx) GreenActive LAN connection to an AMX Network (Blinking = #3 Toggle OFF)
SEND_COMMAND information, see page 68)
The Wallplate TX and Decor Wallplate TX have been configured* to pass one of the following
types of analog video (for SEND_COMMAND information, see page 68):
• C (composite) or Y/C (two component)
• Y/PB/PR or RGB (three component)
• RGBHV (five component) or RGBS (four component)
audio source being embedded on the DXLink output connection (coupled with either the
analog or digital video input path); for SEND_COMMAND information, see page 72
• Speed status is 100 Mbps
• Speed status is 10 Mbps
• Authenticated HDCP (handshaking has occurred successfully)
• Video is active; no HDCP
•No Video
• Authenticated HDCP (handshaking has occurred successfully)
• Video is active; no HDCP
•No Video
• Speed status is 100 Mbps
• Speed status is 10 Mbps
* The LEDs for Digital Video, Analog Video, and Audio each indicate the configured state of the connectors, not necessarily the
presence of signals through the Wallplate TX and Decor Wallplate TX.
NOTE: Detailed behavior for the NetLinx-L and NetLinx-S LEDs on the Wallplate TX or Link/Act and Status LEDs on the Decor Wallplate
TX are on page 50, and basic information for the LEDs on the RJ-45 connector on the rear of the Wallplate TX and Decor Wallplate TX
is on page 40.
TIP: If the Wallplate TX is installed in a location where it is diff icult to check the LEDs on the bottom edge, slide a white piece of paper
or a small mirror under the edge to view LED status.
NOTE: The DX-TX and HDMI TX each have a DIP switch on the bottom (see page 17).
The following components are located on the rear of DX-TX and HDMI TX Modules (from left to right):
Video In Connector (DX-TX only) – The Video In connector on the DX-TX is an HD-15 connector for analog video
(composite, Y/C, Y/Pb/Pr, RGB, RGBHV, or RGBS). Pinouts for analog video are on page 104.
NOTE: When an analog video source cable is plugged into the DX-TX, the Video LEDs on the front and on the Receiver turn green
to show that video is present through the system. In addition, one of the Analog Video LEDs on the front of the DX-TX and the DXRX turns green to show the type of video that is present through the system.
HDMI In Connector – The HDMI In connector is for digital vide o and embedded dig ital audio. When more than on e audio
signal is present and the default “auto” mode is enabled, HDMI embedded audio takes precedence over S/PDIF and analog
audio.
When a NetLinx Central Controller is connected, an audio format SEND_COMMAND is available (the Transmitter must be set
for network connectivity via #3 Toggle) to select the desi red audio source (see page 72).
The HDMI connector has a center screw for locking capability. The HDMI connector also supports a DVI-D signal with the
use o f a DVI-to-HDMI cable adapter.
NOTE: When a digital video source cable is plugged into the HDMI connector, the Video LEDs on the front of the DX-TX or
HDMI TX and Receiver turn green to show that video is present through the system.
Stereo Audio In Jack – The Stereo Audio In jack is a 3.5 mm stereo jack. By default, the stereo audio jack will be third in
pri ority behind the embedded au dio o n the HDMI input and digital audio on the RCA connecto r.
When a NetLinx Central Controller is connected, an audio format SEND_COMMAND is available (the Transmitter must be set
for network connectivity via #3 Toggle) to select the desi red audio source (see page 72).
Digital Audio In Jack– The Digital Audio In jack is an RCA jack for an S/PDIF audio signal. When more than one audio signal
is p resent and the defa ult “au to” mode is e nabled, HDM I embedded audio takes precedence over S/PDIF, which takes
precedence over analog audio.
When a NetLinx Central Controller is connected, an audio format SEND_COMMAND is available (the Transmitter must be set
for network connectivity via #3 Toggle) to select the desired audio source (see page 72 ).
ICS LAN 10/100 Connector – The ICS LAN 10/100 (RJ-45) connector provides for Ethernet 10/100 connectivity (e.g.,
receiving SEND_COMMANDs and downloading firmware update files). For pinout and LED information, see page 39.
RS-232 (Serial) Port – The RS-232 port (serial data interface) is a 3-position screw terminal block which accepts data from
the source device and transfers it via the twisted pair cable to the DX-RX, which in turn transfers the data to the destination
devi ce. The transf er of data can also be made from th e destination to the source. I n additio n to being directly connected to
a device, this port can be connected as an independent native NetLinx control port from a networked NetLinx Central
Controller.
IR RX Port – The IR RX port is used for IR control (see page 19). This port is a 3.5 mm stereo jack. In addition to being
directly connected to a device, this port can be connected as an independent native NetLinx control port from a networked
NetLinx Central Controller.
IR TX Port– The IR TX port is used for IR control (see page 19). This port is a 2-way mini-Phoenix connector. In addition to
being directly connected to a device, this port can be connected as an independent native NetLinx control port from a
networked NetLinx Central Controller.
USB Port – The USB-B port on the rear of the DX-TX and HDMI TX is connected to a PC and supports a USB device. This is
the Host port that is used in conjunction with the USB-A port on the rear of the DX-RX for sending keyboard / mouse
commands to a connected PC at the Transmitter. (For USB port information, see page 18.)
DXLink Output Connector – T he DXLink (RJ-45) connecto rs transpo rt digital vide o, embedded audio, Ethernet, and
bidirectional control over twisted pair cable to DXLink devices or boards (or an DX-RX), including digitally transcoded
analog video signals. The DXLink path supports HDCP. The DXLink line also supports power from an Enova DGX Switcher
and from some Enova DVX Solutions to power the module. For pinout and LED information, see page 39.
Ground Screw – The ground screw is used for creating a technical ground for the ungrounded sources/destinations with
respect to the DXLink Transmitters/Receivers and switcher (see page 37).
Power Jack – The power receptacle is a 2.1 mm DC jack for connecting power. Power can come from a locally connected DC
supply of 12 V. The automatically adjusting universal 110/220 IEC power supply is provided. The power supply is ENERGY
®
STAR
qualified to ensure maximum eff iciency and savings.
IMPORTANT: If desktop power is used to power the Transmitter, only the provided desktop power supply should be used and it
must not be altered in any way. Remote power can also be provided via a switcher, PDXL-2 (FG1090-170), or PS-POE-AT-TC
(FG423-84).
NOTE: Transmitter Modules can also be powered via the DXLink connector when attached to a DXLink Input Board in an Enova
DGX Switcher. We recommend calculating the power budget for the switcher to maintain the redundancy of its power supplies
(see page 31).
Wallplate TX and Decor Wallplate TX Rear View
Located on the rear of the Wallplate TX are a DXLink (RJ-45) connector and a DIP switch.
The Decor Wallplate TX also has its DXLink connector on the rear, but its DIP switch is on the front (see page 17). The front can be
covered with a customer provided standard decor style front cover plate.
DXLink Output Connector – T he DXLink (RJ-45) connecto rs transpo rt digital vide o, embedded audio, bi directional cont rol ,
and Ethernet (SEND_COMMANDs only) over twisted pair cable to DXLink devices or boards, including digitally transcoded
analog video signals. The DXLink path supports HDCP. In addition, the Wallplate TX and Decor Wallplate TX receive power
over the DXLink line from an Enova DGX Switcher, some Enova DVX Solutions, or PDXL-2 (FG1090-170) or PS-POE-AT-TC
(FG423-84). For pinout and LEDinformation, see page 40.
DIP Switch – The DIP switch is on the rear of the Wallplate TX. It is on the front of the Decor Wallplate TX and can be
covered with a customer provided standard decor style front cover plate. For information on the DIP switch, see page 17.
Ground Screw – The ground screw is used for creating a technical ground for the ungrounded sources/destinations with
respect to the DXLink Transmitters/Receivers and switcher (see page 37).
Receiver
NOTE: If a DVI-D signal is used (via a DVI-to-HDMI cable adapter), the advanced audio support from HDMI will not be available.
DXLink HDMI Receiver (DX-RX) Front View
FIG. 8 DX-RX front view
NOTE: The DX-RX has a DIP switch on the bottom; for details, see page 17.
The following components are located on the front of the DX-RX (left to right):
Power LED – Indicates when the DX-RX is powered on.
Video and Audio LEDs – Indic ate the presenc e o f video and embedded audio signals through the DX-RX.
Scaling button and LEDs – Use the Scaling button to select one of the 3 scaling options: Bypass, Auto (default), or Manual.
For information on using the Scaling button and options for persisting the Scaling Mode, see page 49.
Program port – This port is a USB mini-B connector.
IR LEDs – TX and RX LEDs indicate active IR communication.
232 (RS-232) LEDs – TX and RX LEDs indicate active serial communication.
NetLinx LEDs – Link/Act LED indicates network communication activity. The Status LED indicates unit status.
CEC LED – CEC is not currently supported.
USB LED – When illuminated, the LED indicates that the USB port connection has been established (for details, see
page 19).
ID Pushbutton – Places the DX-RX in ID Mode for setting the NetLinx ID (device only) and provides additional functionality,
such as placing the device in Static IP Mode or DHCP Mode.
Receiver Module LEDs
HDMI RX Indicator LEDs
LEDNormal DisplayIndicates
PowerGreenPower is applied to the Receiver
VideoGreenA video signal is present through the Receiver
AudioGreenAn embedded audio signal is present through the Receiver
Scaling:
– Bypass
– Auto
– Manual
IR TXRedIR TX active communication
IR RXYellowIR RX active communication
Serial TXRedSerial TX active communication
Serial RXYellowSerial RX active communication
NetLinx Link/Act GreenActive LAN connection to an AMX Network (Blinking = #3 Toggle OFF)
One LED is green
The other two are off
The Receiver is in one of the three modes for scaling
• At initial power up, the Receiver defaults to the Auto scaling option*
• Pressing the Scaling button cycles the module through the options: Bypass, Auto, and
Manual
• If Bypass is solid and Auto is flashing, then the RX is trying to read EDID from the sink
* When the output cable is disconnected from the DX-RX or if no EDID can be found on the destination device, the last used Scaling
Mode LED will be ON. In either case, the DX-RX will continue to hold its output resolution to the last known preferred resolution
until a power cycle or reconnection of a sink with a valid EDID. On power up without a valid EDID, the default preferred output
resolution presented will be 1280x1024,60Hz until a different EDID is detected.
NOTE: For detailed behavior of the NetLinx Link/Act and Status LEDs on the module’s front, see page 50. For detailed behavior of the
RJ-45 connectors’ LEDs on the module’s rear, see page 40.
Receiver Rear View
FIG. 9 DX-RX rear view
The following components are located on the rear of the DX-RX (left to right):
Power Jack – The power receptacle is a 2.1 mm DC jack for connecting power. Power can come from a locally connected DC
supply of 12 V. An automatically adjusting universal 110/220 IEC power supply is provided. The power supply is ENERGY
STAR
IMPORTANT: If desktop power is used to power the Receiver, only the provided desktop power supply should be used and it
must not
(FG423-84).
®
qualified to ensure maximum eff iciency and savings.
be altered in any way. Remote power can also be provided via a switcher, PDXL-2 (FG1090-170), or PS-POE-AT-TC
NOTE: The DX-RX can also be powered through the DXLink connector when it is attached to a DXLink Output Board in an Enova
DGX Switcher. We recommend calculating the power budget for the switcher to maintain the redundancy of its power supplies
(see page 31).
Ground Screw – The ground screw is for creating a technical ground for the ungrounded sources/destinations with respect
to the DXLink Transmitters/Receivers and switcher (see page 37).
DXLink Input Connector – The DXLink (RJ -45) conn ectors transp ort digital video, embedded audio, Ethernet, and
bidirectional control over twisted pair cable to DXLink devices or boards, including digitally transcoded analog video signals.
The DXLink path supports HDCP and also supports power over the same path from an Enova DGX Switcher and from some
Enova DVX Solutions to power the module. For pinout and LED information, see page 39.
ICS LAN 10/100 Connector – The ICS LAN 10/100 (RJ-45) connector is for Ethernet 10/100 connectivity (e.g., receiving
SEND_COMMAND commands and downloading firmware update files). For pinout and LED information, see page 39.
RS-232 Port – The RS-232 (serial data interface) port is a 3-position screw block which accepts data from the source
device and transfers it via the twisted pair cable to the DX-RX, which in turn transfers the data to the destination device or
the transfer o f data can also be made from th e destination to the source. In additio n to being directly connected to a device,
this port can be connected as an independent native NetLinx control port from a networked NetLinx Central Controller.
IR RX Port – The IR RX port is used for IR control (see page 19). This port is a 3.5 mm stereo jack. In addition to being
directly connected to a device, this port can be connected as an independent native NetLinx control port from a networked
NetLinx Central Controller.
IR TX Port – The IR TX port is used for IR control (see page 19). This port is a 2-way mini-Phoenix connector. In addition to
being directly connected to a device, this port can be connected as an independent native NetLinx control port from a
networked NetLinx Central Controller.
USB Port – The USB-A port o n the RX supports keyboard/mouse. This port is used in conjunction with the USB-B Host port
on the HDMI TX which supports a USB device and connects to the PC. (For USB port information, see page 18.)
HDMI Out Connector – The HDMI Out connector is for digital video and embedded audio. The HDMI connector has a center
screw for locking capability. The HDMI connector also supports a DVI-D signal (a DVI-to-HDMI cable adapter is required).
Stereo Audio Out Connector – The Stereo Audio Out connector is a 3.5 mm stereo jack. This connector has an analog audio
signal available for output whether the embedded audio over the DXLink cable originated as 2 channel digital or analog
stereo. If enco ded digital audio (e.g., Dolby or DTS) or multi-channel audio paths (>2 CH L-PCM) are e mbedded o n the
HDMI path, then this local analog port out will not be available.
Common Features/Functionality
This section covers the DIP switches, the USB port, HDCP compliance, and IR functionality.
DIP Switches
TIP: For easiest access to the DIP switch toggles, we recommend setting them before installation.
A four-toggle DIP switch is on the bottom of the DXLink Modules, on the rear of the Wallplate TX, and on the front of the Decor
Wallplate TX (the front can be covered with a customer provided standard decor style front cover plate).
#1 Toggle is used for enabling/disablin g the physical ICS LAN 10/100 port (see page 34).
#2 Toggle is used for setting the DXLink Modules to either automatically or manually determine the DXLink Mode (see
page 35).
#3 Toggle is used for enabling/disabling network connectivity of the DXLink Transmitter or Receiver to a connected NetLinx
Central Controller (used for IR ports, serial ports, and commands to the DXLink unit); see page 35.
#4 Toggle is not functional.
FIG. 10
NOTE: The mounting bracket on the Wallplate TX must be removed (unscrew the four screws from the bracket and set it aside) before
For complete information on setting DIP switches (including settings for common scenarios), see the section starting on page 34.
DIP switch on Wallplate TX (remove mounting bracket) and on Decor Wallplate TX
USB Port (Rear)
FIG. 12 TX USB port = host (top); RX USB port = keyboard/mouse (bottom)
DX-TX and HDMI TX
The USB-B port on the rear of the DX-TX and HDMI TX can be connected to a PC to support a USB device. This port is considered
the Host port, which is used in conjunction with the USB-A port on the rear of the DX-RX. As the Host port, it is connected to a PC
and passes through informatio n via the DXLink connection to the DX-RX. A USB (mini-B) Host port is also available on the Wallplate
TX and a USB (mini-AB) Host port is available on the Decor Wallplate TX.
DX-RX
The USB-A port on the rear of the DX-RX supports passthrough information from the USB Host port on the Transmitter to an HID
(Human Interface Device), which is most commonly a keyboard or mouse.
HID Devices and Windows 8
Windows 8 will not wake up from a DXLink connected keyboard or mouse unless the properties for the HID device are set to allow
the device to wake the computer. (No te that even a hot plug of the USB cable will not restore connectivity.)
To set Windows 8 to work with DXLink modules and HID devices:
1.On the PC, go to Start > Control Panel > Device Manager and expand “Keyboards.”
2.Right-click the HID Keyboard Device and select Properties.
The HID Keyboard Device Properties dialog box opens.
3.Select the Power Management tab and click “Allow this device to wake the computer.”
4.Click OK.
5.Repeat steps for HID mouse (in the Device Manager dialog box, expand “Mice”).
HID Devices
A list is available of HID devices which have been tested and found to be working well with the latest f irmware (see “DXLink - HID
supported Devices” on the DXLink Receiver’s product page at www.amx.com
).
USB LED
The USB LED on the front of a Transmitter or Receiver Module monitors the USB port on the rear of the unit. The USB LED
illu minates (yellow) when a USB device is detected (th e po rt default is “enabled ”).
To disable the port on the Transmitter, either disconnect the cable or send the following SEND_COMMAND: USB_HID_SERVICE-DISABLE. The enable/disable co mmand pers ists through power cycling. To enable the port, send: USB_HID_SERVICE-ENABLE.
The USB ports support a limited number of SEND_COMMANDs, see page 77.
HDCP Compliance
If the connected downstream sink is not HDCP compliant, then the HDMI output on the Receiver will no t send the signal. This does
not affect additional displays the source may be routed to, i.e., HDCP compliant displays will still show content from the source
device even when the source device is also routed to non-compliant displays. Non-compliant devices can be easily identified
because they display a dark red image or an orange image to indicate the authentication process failed.
IR Control on DX-TX, HDMI TX, and DX-RX (Optional)
The following two items are required for IR control. In addition, a compatible remo te control unit can be used with the system. (The
two items listed are not included with the modules.)
IR03 – External IR Receiver Module (FG-IR03). The IR03 can be connected to the IR RX port on the DX-TX or HDMI TX or to
the IR RX port on the DX-RX, allowing IR signals to be received from a compatible IR remote control. The IR03 allows the
DX-TX or HDMI TX to be placed behind the display device if desired.
CC-NIRC – NetLinx IR Emitter Cable (FG10-000-11). The CC-NIRC can be connected to the IR TX port on the Transmitter
or to the IR TX port on the DX-RX. This allows IR signals to be sent to the source device from the DX-TX or HDMI TX or to
the display device from the Receiver.
The modes listed in the following three tables are those supported by DXLink Transmitters and Receivers. The Quick Reference
Tables are intended to help users navigate the many modes available for system setup and use. For complete information on any of
the modes listed, see the relevant sections or chapter referenced at the end of the Descriptions.
Quick Reference Table – Modes for Handling System Architecture
ModeDescription
DXLink ModesDXLink Modes refer to the type of physical components and how they are connected to make up the system. When
Quick Reference Table – Modes for Handling Addressing/Networking
ModeDescription
IP Addressing
Modes
ID ModeID (Identify) Mode refers to the protocol for enabling a user to establish device addresses. This Mode, accessible
Ethernet ModesEthernet Modes refer to the LAN conf iguration settings.
Master
Connection
Modes
Transmitters and Receivers are cabled into a system and powered on, they automatically detect the DXLink Mode they
are being used in.
Endpoint Mode:
• When the system is setup to use Transmitters and/or Receivers with an Enova DGX Digital Media Switcher or an
applicable Enova DVX Solution, the system is in Endpoint Mode (see example on page 28).
Or
• When a TX is directly connected to an RX but, in addition, the TX and/or RX is connected to a NetLinx Central
Controller via a LAN or directly connected to the Controller, the system is in Endpoint Mode (see example on
page 30).
Extender Mode:
• When a TX is directly connected to an RX, the system is in Extender Mode (see example on page 31).
For further information, reference #2 Toggle DIP switch settings for DXLink Mode (see page 35) and DXLink System
SEND_COMMANDs (see page 79).
IP Addressing Modes refer to network connection settings. By default, all network connection settings are turned OFF.
Static I P Mode:
• This mode configures the network connection to one stable IP address the device will use continuously.
DHCP Mode:
• This mode configures the network connection to choose a new IP address for each network session.
To enable network capability, see “Network Configuration” on page 52.
through NetLinx Studio, places the entire system on hold while it waits for an event from a NetLinx device in the
named system (e.g., pressing the ID Pushbutton on the TX or RX). For further information, see “Assign a Device
Address (ID Mode)” on page 57.
Auto Mode:
• This mode configures the LAN driver to discover its own settings based on the network it is connected to.
Speed/Duplex Mode:
• This mode configures the LAN driver to calculate its speed as either 10 or 100 and to communicate in either
half- or full-duplex.
Ethernet Mode discovery and configuration information is available through Telnet commands. For further
information, see “Establishing a Terminal Connection Via Telnet” on page 90.
Master Connection Modes refer to the modes of communication used for connection to the Master as specif ied via
the SET CONNECTION Telnet command.
Auto Mode:
This mode utilizes TCP communication. It looks for a matching System Number and attempts to come online with the
first Master it sees with that System Number.
TCP URL Mode:
TCP; the Master is specif ied via URL.
UDP URL Mode:
UDP; the Master is specified via URL.
NDP Mode (Default):
UDP; utilizes the NDP binding process to assign the DXLink Module (the physical device) to a Master (or Virtual
Master) via NetLinx Studio. Once bound, communications are conducted via UDP.
For further information, see “Master Connection Modes” on page 97.
Quick Reference Table – Modes for Handling Addressing/Networking (continued)
Auto-setup ModeIn auto-setup mode, endpoints are automatically discovered by and connected to an Enova DGX
IR SEND_COMMAND ModesIR SEND_COMMAND Modes refer to displaying and setting the IR port active system settings as IR,
100 Series Switcher using a single IP address. For this mode, all of the following requirements must
be met. If not, the endpoint will no longer reside in auto-setup mode and must be either bound to
the integrated Master (see page 52) or reconfigured to meet the requirements.
Endpoint must be connected to a DXLink Input Board in an Enova DGX 100 Series
Switcher (or Enova DGX 8/16/32/64 with upgraded 100 Series CPU)
Endpoint must have IP mode set to DHCP for setup (self-configures to Static IP on
private LAN)
Endpoint must have the master connection type set to NDP
Endpoint must not be bound to a Master via NDP (traditional binding process)
IMPORTANT: If auto-setup is being used, Telnet is the only way to access some of the network
settings. Also note that some network settings will disable auto-setup.
For additional information on the auto-setup feature, see the Hardware Reference Manual –
Enova DGX 100 Series Digital Media Switchers.
Serial, or Data modes.
GET MODE SEND_COMMAND:
• The GET MODE SEND_COMMAND reveals the active system (IR, Serial, or Data) settings.
SET MODE SEND_COMMAND:
• The SET MODE SEND_COMMAND changes the active system settings.
For further information, see “IR SEND_COMMANDs” on page 73.
Quick Reference Table – Modes for Handling Video Processing
ModeDescription
Scaling ModesScaling Modes refer to how the system alters or maintains a source device’s resolution as it is passed along to the
destination device. The Scaling Mode can be set on the DX-RX with the Scaling button (see page 49), or with
SEND_COMMANDs (see page 66), or through DGX Configuration Software when scaling is being done via an Enova
DXLink Output Board.
Auto Mode (Default):
•Auto Mode (SmartScale®) allows the destination device to choose the resolution it needs.
Manual Mode:
• Manual Mode allows the user to configure the resolution the video will display through a destination device.
Bypass Mode:
• Bypass Mode allows the video signal to display over the destination device without altering the signal’s resolution.
DXLink Transmitters and Receiver Specif ications
The specifications in the table below apply to the following Transmitters and Receiver:
* A limited set of specifications apply, as the Wallplate TX and Decor Wallplate TXhave a limited set of features when compared to
the DX-TX and HDMI TX.
General Specifications
ParameterValue
ApprovalsCE, UL, cUL, FCC Class A, RoHS, WEEE
AC Power (Modules Only)• 100 to 240 VAC single phase, 50 Hz to 60 HZ
DXLink Power• DXLink Twisted Pair Transmitters (DX-TX, DX-TX-DWP, and DX-TX-WP): Power can also be
Power Consumption,
Local 12 V Supplied (max.)
Power Consumption,
Enova DXLink Power Supplied (max.)
Thermal Dissipation,
Local 12 V Supplied (max.)
Thermal Dissipation,
Enova DXLink Power Supplied (max.)
Power Connector (Modules Only)2.1 mm DC power jack
Operational Temperature32° F to 104° F (0° C to 40° C)
Storage Temperature-22° F to 158° F (-30° C to 70° C)
Operational Humidity5 to 85% RH (non-condensing)
Storage Humidity0 to 90% RH (non-condensing)
Module - Dimensions
Depth
Width
Height
Module - Weight Approximately 1.1 lb. (0.50 kg)
Module - Shipping WeightApproximately 2.2 lb. (1.00 kg)
Modules - Mounting OptionsCompatible with all V Style versatile mounting options including rack, surface, or pole (for V Style
Wallplate TX - Dimensions
Depth
Width
Height
Wallplate TX - Weight Approximately 1.4 lb. (0.64 kg)
Wallplate TX - Shipping Weight Approximately 2.0 lb. (0.91 kg)
Wallplate TX - Mounting OptionsWallplate TX mounts onto standard double-gang US, UK, or EU back boxes
supplied by a DXLink Power sourcing device such as an Enova DGX 8/16/32/64 Digital Media
Switcher or compatible Enova DVX All-In-One Presentation Switcher (DVX-3155HD, 3156HD,
or 2155HD), PS-POE-AT-TC High Power PoE Injector (FG423-84) or PDXL-2 Power over DXLink
Controller (FG1090-170). AMX does not support the use of any other power supplies or
PoE injectors as these may potentially damage the DXLink equipment. To use PS-POE-AT-TC as a
power source the DX-TX Transmitter and the DX-TX-DWP and DX-TX-WP Transmitter Wallplates
require f irmware v1. 2.40 or above.
• DXLink Twisted Pair Receiver (DX-RX):
Power can also be supplied by a DXLink Power sourcing device such as an
Enova DGX 8/16/32/64 Digital Media Switcher or compatible Enova DVX
All-In-One Presentation Switcher (DVX-2150HD, or 2155HD), PS-POE-AT-TC High Power
PoE Injector (FG423-84), PDXL-2 Power over DXLink Controller (FG1090-170), or
SDX-510M-DX Solecis 5x1 Multi-Format Digital Switcher (FG1010-315). AMX does not
support the use of any other power supplies or PoE injectors as these may potentially
damage the DXLink equipment. To use PS-POE-AT-TC as a power source the DX-RX
Receiver requires firmware v1.0.80 or above.
• Power Budget for Transmitters and Receiver:
When installed in conjunction with the Enova DGX Digital Media Switcher, use the Enova
DGX Configuration Tool located at www.amx.com/enova to determine the power
requirements of the conf iguration and whether any of the DXLink Transmitters or Receivers
should be powered with the local power supplies or the supported Power over DXLink
injector. The conf iguration tool contains instructions on how to determine power
requirements.
COMPATIBILITY NOTE: DXLink Transmitters and Receivers are compatible with other DXLink products (see the Compatible AMX
Products listed in the table above). The Wallplate TX and the Decor Wallplate TX require an approved DXLink power injector (see table
above) when connecting directly to an DX-RX (Transmitters require firmware v1.2.40 or later; Receivers require firmware v1.0.80 or
later). AMX does not support the use of power supplies other than the one provided or power injectors other than those listed as they
may potentially damage DXLink equipment.
2.25 in. (5.72 cm)
3.48 in. (8.84 cm)
4.06 in. (10.31 cm)
IMPORTANT: DXLink twisted pair cable runs for DXLink equipment shall only be run within a
common building. “Common building” is defined as: Where the walls of the structure(s) are
physically connected and the structure(s) share a single ground reference.
* For more details and helpful cabling information, reference the white paper titled “Cabling for
Success with DXLink” available at www.amx.com or contact your AMX representative.
All DXLink Transmitters can connect directly to the DXLink DX-RX. The Wallplate TX and Decor
Wallplate TX require either PDXL-2 (FG1090-170) or PS-POE-AT-TC (FG423-84) to do so.
•DX-RX
• Enova DGX Digital Media Switchers
•Enova DVX-3156HD
•Enova DVX-3155HD
•Enova DVX-2155HD
•DX-TX
•HDMI TX
•Wallplate TX
• Decor Wallplate TX
• Enova DGX Digital Media Switchers
•Enova DVX-3156HD
•Enova DVX-3155HD
•Enova DVX-2155HD
•Enova DVX-2150HD
• Solecis SDX-410-DX
•Solecis SDX-510M-DX
•Solecis SDX-810-DX
®
qualified): 1 per module
IMPORTANT: Only the provided desktop power supply should be used, and it must not be
altered in any way.
• IR03 External IR Receiver Module (FG-IR03)
• PDXL-2 (FG1090-170)
•PS-POE-AT-TC (FG423-84)
• CC-USB, USB programming cable (FG10-5965)
(for use with DXLink Twisted Pair Transmitters only)
ID Pushbutton• Toggle between DHCP and static IP addressing
• TCP/IP port (ICS LAN 10/100)
•RJ-45
• Standard NetLinx baud rate 1200 to 115K
• Parity support: Odd/Even/None
• 3.5 mm pluggable Phoenix terminal block
• Port for use with CC-NIRC Emitter (optional accessory FG10-000-11)
• Places system in NetLinx Device ID assignment mode
• Reset the factory default settings
•Restore the factory firmware image
USB (HID) Keyboard and Mouse Specifications
ParameterValue
USB (HID) DX-TX• (1) USB Type B connector (“Host”)
• Connect a DXLink Twisted Pair TX to a PC and emulate keyboard and mouse commands from
a DXLink Twisted Pair Receiver or a DXLink Fiber Receiver
USB (HID) Wallplate TX and
Decor Wallplate TX
USB (HID) DX-RX• (1) USB Type A connector (“Device”)
• DX-TX-WP: (1) USB Mini-B (“Host”); DX-TX-DWP: (1) USB Mini-AB (“Host”)
• Connect a DXLink Twisted Pair Decor Transmitter to a PC and emulate keyboard and mouse
commands from a DXLink Twisted Pair Receiver or a DXLink Fiber Receiver
• Connect a keyboard and mouse and send commands to a PC connected to a DXLink Twisted Pair
Transmitter or a DXLink Fiber Transmitter
NOTE: A list of HID devices which have been tested and found to be working well with the latest firmware is available (see “DXLink HID supported Devices” on the DXLink Receiver’s product page at www.amx.com
).
HDMI Specifications
ParameterValue
Compatible FormatsHDMI, HDCP, DVI (DVI requires conversion cable)
Signal Type SupportHDMI, DVI-D (Single Link with a DVI-to-HDMI cable adapter), DisplayPort++
Video Data Rate (max.)4.95 Gbps / 6.75 Gbps*
Video Pixel Clock (max.)165 MHz / 225 MHz*
Progressive Resolution Support480p up to 1920x1200,60Hz (including but not limited to those resolutions listed on page 110
Interlaced Resolution Support480i, 576i, 1080i(including but not limited to those resolu tions listed on page 110 and page 113)
• Input signal support for YCbCr 4:4:4 and 4:2:2; outpu t color-space is converted to RGB 4:4:4.
• Frame Packing 1080p up to 24 Hz
• Frame Packing 720p up to 50/60 Hz
• Frame Packing 1080i up to 50/60 Hz
• Top-Bottom 1080p up to 24 Hz
• Top-Bottom 720p up to 50/60 Hz
• Side-by-Side Half 1080i up to 50/60 Hz
NOTE: Scaler on the corresponding output board or DX-RX must be set to Bypass mode.
• Dolby Digital and DTS support up to 48 kHz, 5.1 channels.
* Only supported when the DX-RX scaler is in Bypass mode using CTA-861 formats and the resolution is 1080p,60 or less.
NOTE: Interlaced and progressive video are supported into the Transmitter; progressive is only supported out of the Receiver unless in
non-scaling Bypass mode
• When used with an Enova DGX 8/16/32/64 Digital Media Switcher or Enova DVX-2155 or
DVX-3155, the key support is up to 16 sinks per output, independent of the source device.
• When used as a single point-to-point solution, key support is defined by the source device.
CEC supportCEC is not currently supported
TX
Input Signal Type• HDMI
• DVI-D (Single Link with a DVI-to-HDMI cable adapter)
• DisplayPort ++ (input only with HDMI cable adapter)
DDC/EDID Support• The HDMI EDID in point to point mode is passed up from the sink device.
• When used with Enova DGX 8/16/32/64 Digital Media Switcher or Enova DVX-2155, DVX-3155,
the HDMI EDID is passed from the Enova Switcher input to the TX and is user re-programmable.
• The analog video input connection provides a fixed EDID set.
• For the EDID list, see the specif ications in the “Enova DGX DXLink Twisted Pair Boards” chapter
in the Hard ware Refe rence Manual – Enova DGX 100 Series Digital Medial Switchers or the Instruction Manual – Enova DGX 8/16/32/64 Digital Media Switchers.
Input Voltage (nominal)1.0 Vpp differential
Input Re-clocking (CDR)Yes
Input EqualizationYes, adaptive
Input ConnectorHDMI Type A female
Propagation Delay (typical)5 μs
RX
Output Signal Type• HDMI
• DVI-D (Single Link with a DVI-to-HDMI cable adapter)
When placing the DXLink Transmitters and Receivers in an installation, follow the recommendations and precautions in this section
to reduce potential setup and operation hazards.
Environment
□ Choose a clean, dust free, (preferably) air-conditioned location.
□ Avoid areas with direct sunlight, heat sources, or high levels of EMI (Electromagnetic Interference).
DX-TX, HDMI TX and DX-RX Accessibility
Make sure the front of each module is accessible, so that you can monitor the LED indicators. Leaving adequate clearance at the
rear will also allow for easier cabling and service.
Power
The power source’s electrical outlet should be installed near the module, easily accessible, and properly grounded. Power should
come from a building branch circuit. To avoid an overload, note the power consumption rating of all the equipment connected to
the circuit breaker before applying power.
Ge n e r a l H a z a r d P r e c a u t i o n s
These recommendations address potential hazards that are common to all installations.
IMPORTANT: DXLink twisted pair cable runs for DXLink equipment shall only be run within a common building. “Common building”
is defined as: Where the walls of the structure(s) are physically connected and the structure(s) share a single ground reference.
Elevated Operating Temperature
The maximum rated ambient temperature is 104° F (40° C) for DXLink Transmitters and Receivers. All equipment should be
installed in an environment compatible with the manufacturer’s maximum rated ambient temperature. In a closed or multi-unit rack
assembly, the operating ambient temperature of the rack environment may be greater than the ambient room temperature.
CAUTION:
clearance recommendation below for adequate airflow.
Airflow Restriction
The modules are designed to adequately dissipate the heat they produce under normal operating conditions; however, this design
is defeated when high heat producing equipment is placed directly above or below the modules.
CAUTION:
recommend allowing plenty of clearance above the vent holes on top of the modules. Do not place anything directly on top of the
modules that would restrict airflow through the vent holes on top.
Reliable Earthing (Grounding)
Reliable earthing of rack-mounted equipment should be maintained. If no t using a direct connection to the branch circuit (e.g.,
plugging into a power strip), pay particular attention to supply connections (not applicable when power is supplied from an
Enova DGX Digital Media Switcher or Enova DVX Solution via a DXLink line). When using DXLink Power from a switcher, we
recommend wiring a technical ground for the ungrounded sources/destinations with respect to the DXLink Transmitters/Receivers
and switcher (see page 37).
Unpacking Tips
□ Before fully unpacking the Transmitters and Receivers, inspect the shipping box(es) for any signs of damage. If a box is
□ Once unpacking is complete, closely check the physical condition o f the units.
□ Collect all documentation.
NOTE: Please save the original shipping container and packing materials. AMX is not responsible for damage caused by insufficient
packing during return shipment to the factory. Shipping boxes are available; for details, contact your AMX representative.
To protect the equipment from overheating, do not operate in an area that exceeds 104° F (40° C) and follow the
To prevent overheating, avoid placing high heat producing equipment directly above or below the modules. We
partially crushed or any sides have been broken open, notify the shipping agency immediately and contact your AMX
representative (see the warranty at www.amx.com
Installation and Setup
).
Setup Information
IMPORTANT: The setup information in this manual applies to TXs and RXs in an Enova DGX 8/16/32/64 system or in an Enova DGX
100 Series system with the auto-setup feature disabled. When the auto-setup feature for an Enova DGX 100 Series Switcher is
enabled (the default), any modules or wallplates are automatically discovered and connected to the switcher using a private network
hosted by the integrated Master (for complete information, see the “Hardware Reference Manual – Enova DGX 100 Series Digital
Media Switchers”). In an Enova DGX 8/16/32/64 system, each module or wallplate bound to the system with traditional NetLinx
binding (see page 52) acquires its own IP address from the public network (for network configuration, see page 52).
A PC with NetLinx Studio v4.0 or later installed.
An understanding of which DXLink Mode the system will be used in (see below and page 31).
An understanding of the DIP switch settings (see page 36).
When used with an Enova DGX Digital Media Switcher the system’s power requirements must be determined (see page 31).
When used with an Enova DVX Solution – The SEND_COMMANDs for enabling network activity (Ethernet traffic) over the
DXLink line must be used (see page 81).
IMPORTANT: We recommend that DXLink equipment be installed by a technician with knowledge of networks and experience with
NetLinx Studio and its Telnet interface. NetLinx experience should include changing device addresses, binding devices, updating
firmware, etc.
The remainder of the “Setup Information” section covers information for system setup, power budget planning, network loop
concerns, binding to an integrated Master, DIP switch settings, mounting options, chassis grounding, cable requirements and
recommendations (including RJ-45 pinouts and LED behavior), and audio type precedence.
The specific installation’s requirements dictate the system setup, which generally takes one of the following three forms.
Endpoint Mode (Switcher) – One or more Transmitters and/or Receivers are connected to a switcher* containing a Master
(see below).
Endpoint Mode (Standalone) – A standalone DXLink TX/RX pair are connected directly to each other but, in addition, either
the TX or RX is connected to a NetLinx Central Controller via a LAN or directly to the Controller (see page 30).
Extender Mode (Standalone) – A standalone DXLink TX/RX pair are connected directly to each other as a simple extender
solution (see page 31).
* The switcher can be either an Enova DGX Switcher or an applicable Enova DVX Solution (see “Product Compatibility Tables” on
page 8).
Endpoint Mode (Switcher): Example of Typical System Setup
The primary function of the Transmitters and Receivers is to work with compatible DXLink equipment as an endpoint solution for
transmission of HDMI over twisted pair cable (or DVI-D signals with the use of a DVI-to-HDMI cable adapter, or analog video signals
through a DX-TX, Wallplate TX, or Decor Wallplate TX).
The Transmitter rece ives an HDMI signal and a n audio sig nal from a source device. The audio can b e either digit al audio embedded
with the HDMI signal, digital audio over S/PDIF (S/PDIF is not available on the Wallplate TX or Decor Wallplate TX), or analog stereo
audio. Both the video and embedded audio are transmitted over twisted pair cable to the RJ-45 connector on the DXLink Input
Board. The HDMI signal is then routed through any (or all) of the connectors on one or more output boards.
When the HDMI signal is routed through a DXLink Output connector to a Receiver, the Receiver sends the HDMI signal with
emb edded audio on to the destinatio n device. The audio can also be output on the Receiver ’s stereo audio port.
In systems where DXLink Transmitters and Receivers are used in conjunction with a switcher (e.g., Enova DGX 16), the cable runs
from a Transmitter to a DXLink Input Board and from a DXLink Output Board to a Receiver can each be up to 328 feet (100 m).
TIP: For systems with special requirements – Before installing in the f inal location, place the equipment close together, so that the
destination monitor and a PC for control can be seen simultaneously if adjustments are necessary. Scaling adjustments can be made
using SEND_COMMANDs (see page 64). For Enova DGX 8/16/32/64 Switchers, DGX Configuration Software can also be used to make
scaling adjustments via the switcher (see the switcher’s manual). For Enova DGX 100 Series Switchers, scaling can also be adjusted
via the System Configuration interface(see the switcher’s manual).
CAUTION:
Be careful not to create a network (Ethernet) loop. To avoid doing so, see page 33.
Custom EDID Settings
If Transmitters are part of an Enova DGX system which requires custom EDID settings, see the switcher’s manual for
information on the EDID programming functionality in DGX Configuration Software (available at www.amx.com
).
SEND_COMMANDs can also be used (see page 64).
If Receivers are part of an Enova DGX 8/16/32/64 system which requires scaler control and settings, see the switcher’s
manual for information on the scaling functionality in DGX Configuration Software (available at www.amx.com
).
SEND_COMMANDs can also be used (see page 64).
Options for System Setup with Enova DGX DXLink Boards
The following table contains options for using DXLink Transmitters and Receivers in conjunction with DXLink Twisted Pair Input and
Output Boards in an Enova DGX Digital Media Switcher.
System Setup Options – Enova DGX DXLink Boards with DXLink Transmitters/Receivers
* If the board is an SC Optical Board in an Enova DGX Digital Media Switcher, it will need the appropriate DGX Fiber Module. For
information, see the DGX Fiber Module’s manual.
Options for System Setup with Enova DVX Solutions
The following table contains options for using DXLink Transmitters and Receivers in conjunction with DXLink Input and Output
connectors on Enova DVX Solutions. Note that on the input side, four Transmitter options are available. The Transmitters used with
the inputs can be of the same type or different, depending on the installation needs.
Unless otherwise indicated, the Enova DVX Solutions in the table below have 2 DXLink input and/or output connectors.
System Setup Options – Enova DVX DXLink Solutions with DXLink Transmitters/Receivers
When a Receiver acts like a source, its key does not count. Source device sees 1 key (Transmitter).
Example B: When a Transmitter acts like a sink, the source device sees 1 key (Transmitter).
Example C: When a source device is connected directly to a switcher, the source sees 1 key (switcher input).
Example D: When a Transmitter is part of a standalone pair, its key does not count. Source device sees 2 keys.
RX acts like a repeater
RX acts like a source
RX acts like a source
HDMI Out
DXLink
DXLink
HDMI In
DXLink In
DXLink
Example B
Example C
Example D
Example A
Acts like
a sink
Twisted pair cable
NetLinx Central Controller
Destination device
DXLink
Transmitter
DXLink Receiver
Source device
Functions of DXLink Transmitters and Receivers
The diagram in FIG. 14 shows the functions of DXLink Transmitters and Receivers. The example descriptions contain the device
HDCP key count when used in conjunction with DXLink Boards in an Enova DGX Digital Media Switcher and when using a
Transmitter and Receiver as a standalone pair.
FIG. 14
Endpoint Mode (Standalone): Example of Typical System Setup
A standalone DXLink TX/RX pair are connected directly to each other but, in addition, either the TX or RX is connected to a NetLinx
Central Controller via a LAN or directly to the Controller.
FIG. 15 Endpoint Mode (Standalone) with NetLinx Central Controller
Repeater and source functions of TX/RX Modules (A, B, D also apply to Wallplate TX and Decor Wallplate TX)
Extender Mode (Standalone): Example of Typical System Setup
A Transmitter and Receiver standalone pair can also work together as an extender solution for transmission of HDMI over twisted
pair cable up to 328 feet (100 m). The standalone setup supports DVI-D signals with the use of a DVI-to-HDMI cable adapter.
A DX-TX and DX-RX pair can also support an analog video source.
In systems with a Wallplate TX or Decor Wallplate TX, power can be provided to the units via the DXLink line by connecting a DXLink
power injector to the Wallplate and using either the desktop power supply or another DXLink power injector with the DX-RX.
FIG. 16
Extender Mode (Standalone) system
Important Power Considerations for Enova DGX Systems
Local power – Local power (the desktop power supply) always takes precedence over power via the DXLink line from the
switcher. However, if a locally powered unit is connected to a switcher and the local power is lost (i.e., unplugged or turned
off), the unit will power down and then automatically power back up using power from the switcher via the DXLink
connection (increasing the overall power draw on the switcher). When local power is restored, it automatically replaces the
power over the DXLink line.
DXLink power – When modules are being powered by an Enova DGX DXLink board, PDXL-2, or PS-POE-AT-TC (using power
via the DXLink line), to maintain the switcher’s power redundancy, we recommend that you:
Determine the power budget based on the Input/Output boards used and the quantity of powered endpoints (modules);
see below.
Do not use the local DC power jack on the module (even if the local power adapter is turned off).
NOTE: When using DXLink Power from an Enova DGX Switcher, we recommend wiring a technical ground for ungrounded sources/
destinations with respect to the DXLink Transmitters/Receivers and switcher (see page 37).
Power Budget Planning for System Setup with an Enova DGX
NOTE: This section does not apply to the Enova DVX Solutions due to their minimal number of DXLink connections.
Before installing an Enova DGX Digital Media Switcher and connecting any required DXLink Transmitters and Receivers, the total
power draw for the system should be calculated in order to maintain the redundancy of the power supplies in the enclosure. (Each
Enova DGX enclosure ships with two mutually-redundant power supplies.)
IMPORTANT: If you do not plan to draw power from the Enova DGX enclosure’s power supplies, you must
Transmitter and Receiver Modules with local power (desktop power supply) or remote power (DXLink power injector), which always
overrides power from the switcher. If that power source is turned off, the DXLink Transmitters and Receivers will reboot and then start
drawing power from the switcher.
Calculating the power budget helps determine how many DXLink Transmitters and Receivers can be powered through the Enova
DGX Digital Media Switcher while maintaining power redundancy if one of the power supplies should fail. The Enova DGX Configuration Tool is used to determine the switcher’s power budget. Simply enter
the types of boards and the number of DXLink Transmitters and Receivers to be
powered through the switcher, and the calculator shows the resulting power draw.
The EnovaDGX Configuration Tool is at www.amx.com/enova.
If more DXLink units are required than the switcher can support while maintaining
redundancy, any DXLink Modules can be powered using the provided desktop
power supplies or DXLink Power Injectors: PDXL-2 (FG1090-170) or
PS-POE-AT-TC (FG423-84).
Wallplate and Decor Wallplate Transmitters must be included in the power
calculations unless they are being powered by a DXLink power injector (must be
AMX approved).
IMPORTANT: AMX does not support the use of any power supplies other than the
provided ones or power injectors other than the ones approved as they may
potentially damage the DXLink equipment.
Foregoing Power Supply Redundancy
Depending on particular Enova DGX input and output board configurations, operating over the redundant power supply level may
be necessary on a permanent basis for some installations. While foregoing the benefits associated with a redundant power supply
should be understood, operating without redundancy is in no way detrimental to the system, as long as both power supplies are
operational. In this case, necessary power will be pulled evenly from both supplies. However, the loss of one power supply will
result in the system being non-operational from a normal “non-redundant” system capability perspective.
In the Event of a Power Supply Failure
If an Enova DGX power supply fails, check the table below to determine which condition* applies and any actions that may be
required:
SystemConditionResult/Required Action
Within power budgetThe system will continue to run; okay to leave it powered until the failed
Enova DGX 8/16 and 800/1600
Enova DGX 32 and 3200
Over power budgetThe system will continue to run; however, we do not recommend leaving
Within power budgetThe system will continue to run; okay to leave it powered until the failed
Over power budgetThe remaining power supply will turn off. If enough DXLink Transmitter
In all of the situations above, the power supply should be replaced as soon as possible to restore power redundancy to the system
or to allow the system to become fully operational again. Unless the Enova DGX Digital Media Switcher has exceeded its power
budget, it should operate normally with a failed power supply.
* The over power budget condition does no t apply to Enova DGX 64/6400 Switchers (which have four power supplies).
For additional information on power supplies and power supply troubleshooting for an Enova DGX Switcher, see the Installation
Manual – Enova DGX 8/16/32/64 Digital Media Switchers or Hardware Reference Manual – Enova DGX 100 Series Digital Media
Switchers at www.amx.com
. For power supply replacement information, contact technical support (see page 85).
power supply is replaced.
it powered until the failed power supply is replaced, unless enough
DXLink Transmitter or Receiver Modules are removed (or otherwise
powered) to bring the system’s power budget within its maximum limit.
(Another option is to remove some of the input and/or output boards.)
power supply is replaced.
or Receiver Modules are removed (or otherwise powered) to bring the
system’s power budget within its maximum limit, the system will be able
to run until the failed power supply is replaced. (You can also remove
some input and/or output boards.)
NOTE: A network loop is created when
an enclosure and one or more DXLink
Transmitters or Receivers within the
system are connected to a common
LAN (or when two DXLink Modules are
connected to the same network as a
standalone pair).
Avoiding Network (Ethernet) Loops
CAUTION:
Only one connection to a LAN is permitted within a switching system with DXLink support. Network loops must be avoided (see
FIG. 17). This applies to systems with DXLink Twisted Pair Modules and/or DXLink Fiber, Duplex units in Bidirectional Mode.
Example
In the example in FIG. 17, a network loop was created when the Enova DGX 16 was connected to a LAN and one of its DXLink
Transmitters was connected to the same LAN. The DXLink Transmitter must be disconnected from the LAN. The same problem
would also occur if an enclosure and one (or more) of its DXLink Receivers were connected to a common LAN. Remember to avoid
network loops.
Be careful not to create a network (Ethernet) loop.
FIG. 17
Avoid network loops
NetLinx Binding of DXLink Modules or Wallplates with an Enova DGX/DVX
NOTE: If a DXLink module or wallplate has been configured for auto-setup mode and then auto-setup mode has been disabled, the
unit may take longer to appear in NetLinx Studio than expected (1-2 minutes).
DXLink Transmitters and Receivers must have their DIP switch toggles set before they will display as part of an Enova DGX system in
NetLinx Studio (v4.0 or later is required). DIP switch information, including settings for common scenarios, is on the next three
pages.
In NetLinx Studio, the DXLink TXs and RXs can be bound to the integrated Master by right-clicking on the device and selecting
Network Bind/Unbind Device. This is considered the traditional method of binding. If the integrated Master runs on a 100 Series
CPU, see the Hardware Reference Manual – Enova DGX 100 Series Digital Media Switchers for auto-setup information (which does
not require binding).
To bind DXLink units to Enova DGX integrated Master:
1.Verify the following:
a. Verify that an Ethernet/RJ-45 cable is connected from the Enova DGX Switcher’s integrated Master to the network
(e.g., from the switcher’s LAN 100/1000 port to a LAN).
b. Verify that the target Transmitter or Receiver is connected via its DXLink connector to a DXLink Input or Output Board
(respectively) on the switcher.
c. Verify that the switcher is powered on.
2.Launch NetLinx Studio and open the OnLine Tree.
3.Bind the target Transmitter or Receiver to the integrated Master:
a. Select and right-click the TX or RX.
b. From the context sensitive menu, select Network Bind/Unbind Device (be sure the check box is selected).
c. Click OK.
TIP: For easiest access to the DIP switch toggles, we recommend setting them before installation.
DIP switch toggles for enabling/disabling special Receiver/Transmitter functionality are located on the bottom of the Receiver
and the Transmitters (FIG. 18), on the rear of the Wallplate TX (left in FIG. 19), and on the front of the Decor Wallplate TX (right in
FIG. 19).
NOTE: DIP switch settings on any of these DXLink products are read only on reboot. After the settings are read, any adjustments of
the toggles will not be implemented and will not affect the system.
FIG. 18
DIP switch on bottom of Receiver and Transmitters
FIG. 19 DIP switch on rear of Wallplate TX (remove mounting bracket) and front of the Decor Wallplate TX
Setting DIP Switch #1 to Enable/Disable Access to ICS LAN 10/100 Port
The #1 Toggle is used for enabling/disabling network activity over the physical ICS LAN 10/100 port, which allows Ethernet
passthrough. It does not affect network activity over DXLink. (For SEND_COMMANDs to disable/enable ICS LAN functionality, see
page 79.)
NOTE: #1 Toggle settings do not apply to Wallplate TX & Decor Wallplate TX – leave #1 Toggle OFF.
TIP: Common setup scenarios and their DIP switch settings are provided in a table on page 36.
#1 Toggle Settings
OFF (default) – When the #1 Toggle is set to OFF, network activity over the ICS LAN 10/100 port is disabled.
ON – When the #1 Toggle is set to ON, network activity over the ICS LAN 10/100 port is enabled.
Installation Options
Option A – For a network connection between a Transmitter and a Receiver where only one of them is connected to a LAN,
set the #1 Toggle to ON for the unit that is connected to the network.
CAUTION:
information on avoiding network loops, see page 33.
CAUTION:
10/100 port on the Transmitter or Receiver to the same LAN as the switcher because a network loop will result. For information on
avoiding network loops, see page 33.
Option A – Do not connect both the Transmitter and the Receiver to a common LAN as a network loop will result. For
Option B – When a Transmitter or Receiver is connected to a DXLink input or outpu t on an Enova DGX Digital Media Switcher
or Enova DVX switcher, the switcher provides a network connection allowing the Transmitter or Receiver to appear in the
online tree in NetLinx Studio (#3 Toggle must be set to ON). For connecting the Transmitter or Receiver to other equipment
using the ICS LAN 10/100 port, the #1 Toggle must be set to ON.
Option B – Because the DXLink connection carries network activity passed from the switcher, do not connect the ICS LAN
#2 Toggle can be set to automatically or manually select the DXLink Mode (to either Extender or Endpoint) for a given Transmitter/
Rec eiver Module. Default state for #2 Toggle OFF is au to selection o f DXLink Mode based on connection to another device . When it’s
ON, the default is Endp oint Mode (us ed for Master controlled serial/IR data transfer) .
NOTE: #2 Toggle settings do not apply to Wallplate TX & Decor Wallplate TX – leave #2 Toggle OFF.
TIP: Common setup scenarios and their DIP switch settings are provided in a table on page 36.
#2 Toggle Settings
OFF (default) – When #2 Toggle is set to OFF, the Transmitter and Receiver will each auto-discover* what type of DXLink
equipment they are connected to and will automatically self-configure to be in one of two DXLink Modes based on the
connection:
Extender Mode – This mode is automatically selected when a TX and RX are connected directly to each other (a
standalone pair). The Transmitter and Receiver act like a simple extender, and serial and IR data is passed through
them.
Endp oint Mode – This mode is automatic ally selected when a module is connected directly to a DXLink port on a
switcher. Serial and IR operations are handled by the host providing control of endpoints. The Master’s programming
specifies where IR and serial commands are sent (this is handled independently from the routing of the video signals).
* Any time the DXLink connection is re-established or power is cycled on a module, the auto-discovery process will take place, as
long as the #2 Toggle remains in the OFF position.
ON – When #2 Toggle is set to ON, the auto-discover feature is disabled and the module can be manually set to either
Endp oint Mode (default) or Ex ten der Mode. In Endpoint M ode, when t he module is conne cted to a switcher or a separate
NetLinx Master**, IR and serial operation are only handled via the host.
** When standalone modules require IR and/or Serial control by a separate NetLinx Master, then they need to be in Endpoint Mode.
Only one must be connected via the ICS LAN 10/100 port to the Master or to a LAN with the Master on it. This requires #1 Toggle
to be ON to enable the ICS LAN port. #2 Toggle needs to be ON to place the modules in Endpoint Mode (if needed), and #3 Toggle
needs to be ON to enable network connectivity.
NOTE: On either setting, the DXLink Mode may be set via SEND_COMMANDs (see page 79). When #2 Toggle is set to the OFF position,
the auto-discovery process will overwrite the DXLink Mode setting. However, when the #2 Toggle is set to the ON position, autodiscovery is disabled and the mode set by SEND_COMMANDs will persist (i.e., the DXLink Mode setting cannot be overwritten).
Setting DIP Switch #3 for Network Connectivity
The #3 Toggle is used for enabling/disabling network connectivity (IP addressing) of the DXLink Transmitter or Receiver. If enabled
it allows the Transmitter or Receiver to be conf igured to connect to a NetLinx Central Controller (used for controlling the DXLink
unit and allowing Ethernet traffic).
NOTE: Wallplate TX – Before the DIP switch toggles can be set, the mounting bracket must be removed (unscrew the four screws from
the bracket and set it aside). Decor Wallplate TX – Set switches before adding customer provided decor style front cover plate
(requires four screws).
TIP: Common setup scenarios and their DIP switch settings are provided in a table on the next page.
#3 Toggle Settings
OFF (default) – When the #3 Toggle is set to OFF, the Transmitter or Receiver will not try to connect to the network and will
not acquire an IP address.
ON – When the #3 Toggle is set to ON, the Transmitter or Receiver will attempt to connect to the network via DHCP or static
IP, depending on how the unit has been set up (see page 49). The Transmitters and Receivers will not display in NetLinx
Studio and will not accept commands or queries unless the #3 Toggle is ON.
NOTE: After the #3 Toggle is set to ON, a network connection is established, and the NetLinx Studio screen is refreshed, Transmitters
and Receivers display in the OnLine Tree as Unbound NDP (Network Detect Proxy) Devices. To facilitate IRL and KIT f ile transfers, th ey
can be bound to the integrated NetLinx Master in a switcher or to another NetLinx Master. A Virtual NetLinx Master can also be used
for file transfers.
The table below contains the most common scenarios for setting up Transmitters and Receivers as a standalone pair or with other
equipment. Find the scenario in the table that you want to use and then set the Dip switches accordingly. A detailed explanation
of functions for each toggle is provided above and on the previous page.
NOTE: The #1 and #2 Toggles do not apply to the Wallplate TX and Decor Wallplate TX.
TIP: Each toggle’s ON position is toward the connectors on the rear of the DXLink Modules or toward the top of the unit for the DXLink
Wallplate TX and Decor Wallplate TX (see page 34).
Common ScenariosDIP Switch Toggle Settings
Standalone Setup – TX/RX pair direct connection1234
AV signals only (plus serial/IR passthrough)OFFOFFOFFOFF
AV with Ethernet passthrough to networked device* (plus serial/IR
passthrough)
AV with NetLinx control of TX/RX unit and serial/IR ports**ONONONOFF
AV with NetLinx control of TX/RX unit and serial/IR ports, plus Ethernet
passthrough to networked device*
Switcher Setup – TX/RX with Enova DVX/DGX Switcher1234
AV signals onlyOFFOFFOFFOFF
AV with Ethernet passthrough to networked device*ONOFFOFFOFF
AV with NetLinx control of TX/RX unit and serial/IR portsOFFOFFONOFF
AV with NetLinx control of TX/RX unit and serial/IR ports, plus Ethernet
passthrough to networked device*
ONOFFOFFOFF
ONONONOFF
ONOFFONOFF
* Connect the ICS LAN 10/100 port of the DXLink unit to the network device (e.g., laptop, IP controlled projector, AMX ICSLan EXB
Device). In a standalone setup, connect the ICS LAN 10/100 port of the other DXLink unit to the network.
** In a standalone setup using NetLinx control of the DXLink serial/IR ports, only one of the DXLink units should be connected to
the network (the unit with #1 Toggle enabled).
IMPORTANT: When connecting a Transmitter or a Receiver in a standalone pair setup to a Master (or Virtual Master) for upgrade
purposes, #1 and #3 Toggles must
be ON. #2 is only required on each module if serial and/or IR control is required from the Master.
Mounting Options for Modules (Rack Trays and Mounting Brackets)
CAUTION:
recommend allowing plenty of clearance above the vent holes on top of the modules. Do not place anything directly on top of the
modules that would restrict airflow through the vent holes on top.
The DX-TX, HDMI TX, and DX-RX are classified as V Style modules, which have optional V Style mounting hardware. These versatile
mounting options include rack trays and mounting brackets for desktops, under desks, on walls, and on poles.
For details on V Style Mounting Kit options, see www.amx.com
To prevent overheating, avoid placing high heat producing equipment directly above or below the modules. We
.
FIG. 20 V Style mounting hardware
IMPORTANT: When mounting under a surface, the module should be mounted upright and lowered in the slots to provide an airflow
surface for heat to escape.
gap between the surface and the vent holes. If not using V Style brackets, be sure to leave a gap between the top of the unit and the
Wallplate TX – The holes in the Wallplate TX’s mounting bracket are designed to accommodate a variety of double-gang back boxes
using two or four screws. Two types of screws are provided: standard and metric. Be sure to orient the mounting bracket as shown
in FIG. 21.
FIG. 21
Decor Wallplate TX – The Decor Wallplate TX mounts in a standard US double-gang back box. Standard decor style cover plates are
customer provided to allow matching the individual decor of an environment or matching o ther standard decor covers in a room/
area.
IMPORTANT: Be sure to measure the back box and any other components used to mount the Decor Wallplate TX prior to installation/
construction to ensure the unit fits (e.g., some mud rings do not work unless their corners are modified).
Wallplate mounting bracket used with variety of double-gang back boxes
Attaching a Ground Wire to DXLink Transmitters/Receivers
NOTE: Technically this type of grounding is only required when a DXLink Transmitter or Receiver is connected to an ungrounded
device, but this added grounding measure can be used at the discretion of the installer.
If the system is experiencing problems with delivery of DXLink signals to/from an Enova DGX Digital Media Switcher or Enova DVX
Solution, adding a ground wire from the TX/RX to the switcher may improve performance. The problem is likely caused by the use
of a single phase powered system that does not provide an earth ground for a source or destination’s chassis and shields. This can
inject unnecessary AC voltage on the HDMI cable shield that can lead to DXLink signal integrity issues. To check for indications of
this type of power in the system, look for a two pronged plug or a cord that has only two wires.
Items Required
□ Phillips #1 screwdriver
□ 6 foot ground wire with ring terminal ends (provided)
NOTE: Currently shipping DXLink Transmitters and Receivers provide a designated ground location on the rear of the chassis for
attaching a ground wire. For instructions on attaching a ground wire to DXLink Modules without a designated ground location, see
page 114.
Attaching a Ground Wire to a Common Earthed Ground
Connect the running end of the ground wire (fixed end attached to a DXLink Transmitter or Receiver) to a common earthed ground
(ideally, referenced to the Enova DGX Switcher or Enova DVX Solution).
IMPORTANT: If one DXLink Transmitter or Receiver is grounded, any remaining ungrounded units that are connected to the same
board on the Enova DGX Switcher must
Attaching Ground Wire to Module
also be grounded.
IMPORTANT: Before attaching the ground wire to the chassis, ensure all connectors are clear.
2.Remove the designated ground screw and washer from the rear of the module.
Designated ground screw and washer
Correctly positioned ground wires
Designated ground screw
DXLink connector
Installation and Setup
FIG. 22
3.Secure the ring terminal of the ground wire against the chassis with the ground screw and washer.
4.Ensure the ground wire is positioned so that it does not interfere with any of the connectors.
FIG. 23 Position ground wire away from connectors
5.Attach the ground wire to a common earthed ground (see “Attaching a Ground Wire to a Common Earthed Ground” on the
6.Continue the DXL ink Module i nst allation process (or reapply power to the module).
Remove designated ground screw and washer
previous page).
Attaching Ground Wire to Wallplate TX or Decor Wallplate TX
The Wallplate TX and Decor Wallplate TX each have a designated ground screw on the rear; look for the grounding symbol. If the
DXLink Wallplate does not have a designated screw, use the screw directly above the DXLink (RJ-45) connector on the rear for
grounding.
To attach a ground wire to a DXLink Wallplate or Decor Wallplate TX:
1.If powered, power down the unit by removing the DXLink cable from the rear.
2.Remove the ground screw and washer for the applicable unit, as indicated in FIG. 24.
FIG. 24 Wallplate TX and Decor Wallplate TX - Remove ground screw and washer
3.Secure the ring terminal of the ground wire against the chassis with the ground screw and washer.
DXLink twisted pair cable runs for DXLink equipment shall only be run within a common building.*
DXLink delivers 10.2 Gb/s throughput over shielded category cable. Based on this bandwidth requirement, we recommend
following industry standard practices designed for 10 Gigabit Ethernet when designing and installing the cable
infrastructure.
The cables should be no longer than necessary to reach the end-points. We recommend terminating the cable to the actual
distance required rather than leaving any excess cable in a service loop.
For complete cable specifications, see page 23.
For more details and helpful cabling information, reference the white paper titled “Cabling for Success with DXLink” available at
www.amx.com
or contact your AMX representative.
* “Common building” is defined as: Where the walls of the structure(s) are physically connected and the structure(s) share a single
ground reference.
Twisted Pair Cable Pinouts
The pinout in FIG. 26 is for twisted pair cable that connects to the ICS LAN 10/100 connector or to the DXLink connectoron the
Transmitters and Receivers. Use either the T568A or T568B pinout specification for termination of the twisted pair cable used
between the modules in a standalone setup or between Transmitters and Receivers and an enclosure in a full system
.
FIG. 26 Twisted pair cable pinouts for Ethernet connectors
In a typical installation, the cables should be stretched to their full length between Transmitters and Receivers and the enclosure or
between modules in a standalone system. Service loops or coils of the cable may reduce the overall cable performance and should
be minimized whenever possible.
On – Speed status is 100 Mbps
Off – Speed status is 10 Mbps
On bottom edge of Wallplate TX
L/A - Green
S - Green
Front of Decor Wallplate TX
NetLinx LEDs
Status - Green
Link/Act - Green
J-45 Connector LEDs
RJ-45 LEDs
ICS LAN 10/100 Connector LEDs (modules only)
The following information applies to the LEDs on the ICS LAN 10/100 connector on the modules (FIG. 27). Note that #1 Toggle
must be set to ON or ICS LAN functionality will not be provided.
The following information applies to the NetLinx LEDs on the bo ttom edge of the Wallplate TX and on the front of the Decor
Wallplate TX, which reflect NetLinx communication and status via their DXLink lines (FIG. 28).
Module ICS LAN 10/100 connector LEDs
EDs
FIG. 28 Wallplate TX and Decor Wallplate TX NetLinx LEDs
L/A or Link/Act Green LED – Link/Activity LED indicates network communication activity.
S or Status Green Led – The Status LED indicates unit status.
TIP: If the Wallplate TX is installed in a location where it is diff icult to check the LEDs on the bottom edge, slide a white piece of paper
or a small mirror under the edge to view LED status.
DXLink Connector LEDs
The following information applies to the LEDs located on the DXLink (RJ-45) connectors on the rear of all DXLink Transmitters and
Receivers. It also applies to the DXLink LEDs on the bottom edge of the Wallplate TX and the DXLink LEDs on the front of the Decor
Wallplate TX.
Yel low:
On – Authenticated HDCP (handshaking has occurred successfully)
Flashing – Video active; no HDCP
Off – No Video
Green:
On – DXLink connection established (Endpoint Mode between TX/RX and switcher; Extender Mode between TX and RX)
Off – DXLink connection not established
The LEDs in FIG. 29 provide information for the DXLink connector.
The connectors for bringing audio into the system on the Transmitters are as follows:
HDMI In co nnector – Emb edded audio signal
Digital Audio In jack – Digital audio signal (S/PDIF); not available on the Wallplate TX and Decor Wallplate TX
Stereo Audio In jack – Analog stereo audio signal
The hierarchy for audio type precedence* is listed in the following table for the Transmitters:
Audio Type Precedence on Transmitters
Incoming SignalAudio Type Selected
HDMI w/ embedded digital au dioHDMI w/ Embedded dig ital au dio
S/PDIF digital audio only
(not applicable for Wallplate TX and Decor Wallplate TX)
Stereo audio onlyStereo audio
S/PDIF digital audio and stereo audio
(not applicable for Wallplate TX and Decor Wallplate TX)
HDMI w/ embedded digital audio and S/PDIF digital audio
(not applicable for Wallplate TX and Decor Wallplate TX)
HDMI w/ embedded digital au dio and stereo audioHDMI w/ Embedded dig ital au dio
HDMI w/ embedded digital audio, S/PDIF digital audio, and stereo audio
(not applicable for Wallplate TX and Decor Wallplate TX)
* Audio precedence as specified in the table above is applicable when the AUDIN_FORMAT_AUTO command is set to ENABLE; this
precedence can be overridden by SEND_COMMANDs (see page 72).
The audio selected by the Transmitters is embedded on the HDMI signal (if not already embedded ) and sent to the switcher (or to
DX-RX in a standalone pair) via the DXLink cable.
The DX-RX will take the embedded audio it receives from a Transmitter** and output the following types of audio:
HDMI Out connector – Embedded digital audio signal
Stereo Audio Out connector – Analog stereo audio signal
** These exceptions apply: In order for audio to be sent out of the analog stereo audio connector on the DX-RX, the audio must
have originated or be embedded in the HDMI signal on the Enova DGX Digital Media Switcher, Enova DVX Solution, or Transmitter as
a 2 channel signal (either analog stereo or 2 channel L-PCM). Multi-channel (>2 channel) L-PCM formats will pass incomplete audio
(only 2 of the multiple channels will be sent). All other audio formats will be muted at the connector.
IMPORTANT: If network connection is required – before attaching cables, set DIP switch #3 Toggle.
IMPORTANT: Do not
To attach signal and transport cables to a Wallplate TX or Decor Wallplate TX:
1.Install double-gang back box. (For Wallplate TX mounting options, see page 36. The Decor Wallplate TX uses a standard US
double-gang back box).
use the RJ-45 connector on rear for connecting to a standard Ethernet Network.
FIG. 30
Attach signal and transport cables (Wallplate TX shown)
Mount Unit, Set DIP switches, and Cable DXLink –
2.Wallplate TX –
a. Remove the four screws from the front that fasten it to the mounting bracket.
b. Important – If a network connection is required, set #3 Toggle to ON (see page 35).
c. Attach bracket (arrows inside point up) to double-gang back box per illustrations on page 36.
d. DXLink connector – Attach a twisted pair cable from the DXLink Input Board on the switcher through the mounting
bracket to the DXLink (RJ-45) connector on the rear of the unit.
Decor Wallplate TX –
a. DXLink connector – Attach a twisted pair cable from the DXLink Input Board on the switcher to the DXLink (RJ-45)
connector on the rear of the unit.
b. Attach unit to the back box with four screws through the large screw holes.
IMPORTANT: If a network connection is required, set #3 Toggle to ON (see page 35).
3.Wallplate TX – Reattach unit to the mounting bracket with the four screws removed in Step 2a.
Decor Wallplate TX –
a. Check LEDs for normal display (see the table on the next page).
b. Attach standard decor style front cover plate (customer provided) to the unit.
Cable front (note that connector arrangement differs between unit types) –
4.HDMI In connector – Attach the HDMI cable from the source device to the HDMI In connector.
5.Video In connector – Attach the HD-15 cable from the source device to the Video In connector (for VGA, component, S-Video,
and composite pinouts, see page 104).
6.Stereo Audio In jack (optional) – Plug in the analog audio cable from the stereo audio source into the Stereo Audio In jack.
For audio precedence information, see page 41.
7.If necessary, set the video and audio formats using SEND_COMMANDs (see page 64).
8.USB Host port (optional) – Attach USB cable from PC. The port’s default is “enabled.” For USB port information, see page 18.
For USB SEND_COMMAND information, see page 77.
9.Check LEDs for normal display (see the table on the next page).
Additional Wallplate TX and Decor Wallplate TX Functionality
The following items are on the left edge of the Wallplate TX and on the front of the Decor Wallplate TX.
Reset Button
The Reset button resets the unit’s CPU (acts like a power cycle soft reboot).
Program Port
This port (USB mini-B connector) supports DGX Configuration Software for programming a customer VGA EDID.
ID Pushbutton
The ID Pushbutton places the unit in ID Mode for setting the NetLinx ID (device only) and provides additional functionality, such as
placing the unit in Static IP Mode or DHCP Mode (see page 56).
Wallplate TX and Decor Wallplate TX – Indicator LEDs
The Wallplate TX and Decor Wallplate TX receive power from a switcher through the DXLink (RJ-45) connection to a DXLink Input
Board in the switcher. They can also receive power via either PDXL-2 (FG1090-170) or PS-POE-AT-TC (FG423-84).
IMPORTANT: We recommend determining the power budget to maintain power redundancy for the system (see page 31).
TIP: If the Wallplate TX is installed in a location where it is diff icult to check the LEDs on the bottom edge, slide a white piece of paper
or a small mirror under the edge to view LED status.
Wallplate TX and Decor Wallplate TX Indicator LEDs
LEDsNormal DisplayIndicates
Digital Video (default)GreenThe Wallplate TX and Decor Wallplate TX have been configured* to pass HDMI
Analog VideoOne of the 3 LEDs
will be Green
AudioGreenThe Wallplate TX and Decor Wallplate TX have been configured* to pass analog audio as
PowerGreenPower (from switcher or DXLink power injector) is applied
LEDs (bottom edge of Wallplate TX)
NetLinx - L (Link)GreenActive LAN connection to an AMX Network (Blinking = #3 Toggle OFF)
NetLinx - S (Status) Green
Off
DXLink YellowYellow
Flashing
Off
DXLink Green GreenDXLink connection is established
LEDs (on front of Decor Wallplate TX)
HDCPYellow
Flashing
Off
DXLink GreenDXLink connection is established
StatusGreen
Off
Link/Act Active LAN connection to an AMX Network (Blinking = #3 Toggle OFF)
(for SEND_COMMAND information, see page 68)
The Wallplate TX and Decor Wallplate TX have been configured* to pass one of the
following types of analog video (for SEND_COMMAND information, see page 68):
• C (composite) or Y/C (two component)
• Y/PB/PR or RGB (three component)
• RGBHV (five component) or RGBS (four component)
the audio source being embedded on the DXLink output connection (coupled with either
the analog or digital video input path); for SEND_COMMAND information, see page 72
• Speed status is 100 Mbps
• Speed status is 10 Mbps
• Authenticated HDCP (handshaking has occurred successfully)
• Video is active; no HDCP
•No Video
• Authenticated HDCP (handshaking has occurred successfully)
• Video is active; no HDCP
•No Video
• Speed status is 100 Mbps
• Speed status is 10 Mbps
* The LEDs for Digital Video, Analog Video, and Audio each indicate the configured state of the connectors, not necessarily the
presence of signals through the Wallplate TX or Decor Wallplate TX.
IMPORTANT: If the indicator LEDs for the Wallplate TX or Decor Wallplate TX do not respond with a normal display as stated in the
table above, check all of the connections and the suggestions in the “Troubleshooting” chapter (see page 82) before contacting
technical support (see page 85).
DX-TX or HDMI TX – Attaching Signal, Transport, and Control Cables
IMPORTANT: Before attaching cables, be sure to set the DIP switch’s toggles if necessary (see page 36).
IMPORTANT: Do not use the RJ-45 connector labeled “DXLink” for connecting to a standard Ethernet Network.
NOTE: Power, IR, and RS-232 ports are covered in their own sections.
To attach signal, transport, and control cables to DX-TX or HDMI TX:
FIG. 31
1.DX-TX only – Attach the HD-15 cable from the source device to the Video In connector (for pinouts for VGA, component, S-
2.HDMI In connector – Attach the HDMI cable from the source device to the HDMI In connector.*
3.DXLink connector – Attach a twisted pair cable to the DXLink connector for UTP transport to the switcher (or DX-RX).
4.Stereo Audio In jack (optional) – Plug in the analog audio cable from the stereo audio source into the Stereo Audio In jack.
5.Digital Audio In jack (optional) – Insert the S/PDIF (RCA) plug on the digital audio cable from the digital audio source into the
6.ICS LAN 10/100 connector (optional) – Attach a twisted pair cable from this connector to a LAN.
7.If necessary, set the video and audio formats using commands (for NetLinx programming information, see page 64).
8.USB Host port (optional) – Attach USB cable from PC. The port’s default is “enabled.” For USB port information, see page 18.
* DVI cable can be used instead (via a DVI-to-HDMI cable adapter); however, the advanced audio support from HDMI will not be
available.
NOTE: The ID Pushbutton places the module in ID Mode for setting the NetLinx ID (device only) and provides additional functionality,
such as placing the device in Static IP Mode or DHCP Mode. For complete information, see page 56.
Attach signal and control cables (DX-TX shown)
Video, and composite, see page 104).
For audio precedence information, see page 41.
Digital Audio In jack. For audio precedence information, see page 41.
For USB SEND_COMMAND information, see page 77.
DX-TX or HDMI TX – Applying Power
IMPORTANT: If desktop power is used to power the Transmitter, only the provided desktop power supply should be used and it must
not be altered in any way. Remote power can only be provided via a switcher or a DXLink power injector. AMX does not support the use
of any other power supplies or power injectors as these may potentially damage the DXLink equipment.
Important Power Considerations for Enova DGX Systems
Local power – Local power (desktop power supply) always takes precedence over power via the DXLink line from the
switcher. However, if a locally powered module is connected to a switcher and the local power is lost (i.e., unplugged or
turned off), the module will power down and then automatically power back up using power from the switcher via the
DXLink connection (increasing the overall power draw on the switcher). When local power is restored, it automatically
replaces the power over the DXLink line.
DXLink power – When modules are being powered by an Enova DGX DXLink board or DXLink power injector (using power via
the DXLink line), to maintain the switcher’s power redundancy, we recommend that you:
Determine the power budget based on the Input/Output boards used and the quantity of powered endpoints (modules);
NOTE: When using DXLink Power from an Enova DGX Switcher, we recommend wiring a technical ground for the ungrounded sources/
destinations with respect to the DXLink Transmitters/Receivers and switcher (see page 37).
see page 31.
Do not use local DC power jack on module (even if local power adapter is turned off ).
The following instructions do not apply if you are using power from the switcher via the DXLink line in an Enova DGX system.
To apply power to the DX-TX or HDMI TX:
1.Plug the cord from the desktop power supply (provided) into the power jack on rear of the module (2.1 mm DC jack for 12 V
local power).
2.Plug the desktop power supply into an AC external power source.
The Power LED on the front of the module turns a constant green, which indicates a ready state.
Some of the additional LEDs also turn a constant green. For normal LED display, see table below.
DX-TX and HDMI TX – Indicator LEDs
The LED indicators are listed in the table as they appear on the front of the module from left to right.
DX-TX and HDMI TX LEDsNormal DisplayIndicates
PowerGreenPower is applied to the Transmitter
Digital Video GreenA digital signal is present through the Transmitter
AudioGreenA digital audio signal is present through the Transmitter
Analog Video (DX-TX only)One o f the 3 LEDs
is Green
IR TXRedIR TX active communication
IR RXYellowIR RX active communication
232 (Serial) TXRedSerial TX active communication
232 (Serial) RXYellowSerial RX active communication
NetLinx Link/ActGreenActive LAN connection to an AMX Network (Blinking = #3 Toggle OFF)
NetLinx StatusGreenLAN connection is active
Type of analog video present through the DX-TX:
• C (composite) or Y/C (2 component)
• Y/PB/PR or RGB (3 component)
• RGBHV (5 component) or RGBS (4 component)
DX-TX and HDMI TX – LED Troubleshooting
If indic ato r LEDs for mo dules do not respond with a normal display as stated in table above:
□ Check all power connections.
□ Check the “Detailed NetLinx (Link/Act and Status) LED Behavior” section on page 50.
□ Try the suggestions in the “Troubleshooting” chapter (see page 82).
For information on restoring the module’s default settings on power up, see page 57.
DX-RX – Attaching Signal and Control Cables
IMPORTANT: Before attaching cables, be sure to set DIP switch’s toggles if necessary (see page 36).
IMPORTANT: Do not
NOTE: Power, IR, and RS-232 ports are covered in their own sections.
To attach signal, transport, and control cables to the HDMI RX:
FIG. 32 Attach signal and control cables to HDMI RX
1.DXLink (input) connector – Attach a twisted pair cable from the switcher (or DX-TX or HDMI TX) to the DXLink connector on
the DX-RX.
2.HDMI Out connector – Attach the HDMI cable that goes to the destination device.*
3.ICS LAN 10/100 connector (optional) – Attach a twisted pair cable from this connector to a LAN. (For NetLinx programming
information, see page 64.)
use the RJ-45 connector labeled “DXLink” for connecting to a standard Ethernet Network.
4.USB port (optional) – Connect to a hub using a USB-A cable; connect keyboard and mouse to the hub. (This port is for
sending keyboard / mouse commands to a PC.) For USB port information, see page 18. For USB SEND_COMMAND
information, see page 77.
5.Stereo Audio Out connector (optional) – Plug the audio cable (that goes to the audio destination) into the stereo audio jack.
For audio precedence information, see page 41. For information on audio SEND_COMMANDs (including enabling the analog
audio format), see page 68.
* DVI cable can be used instead (via a DVI-to-HDMI cable adapter); however, the advanced audio support from HDMI will not be
available.
NOTE: The ID Pushbutton places the DX-RX in ID Mode for setting the NetLinx ID (device only) and provides additional functionality,
such as placing the device in Static IP Mode or DHCP Mode. For information, see page 56.
TIP: If scaling adjustments are necessary, use SEND_COMMANDs (see page 64). If connected to an Enova DGX output, use DGX
Configuration Software via the switcher for scaling.
DX-RX – Applying Power
IMPORTANT: If desktop power is used to power the Receiver, only the provided desktop power supply should be used and it must not
be altered in any way. Remote power can only be provided via the switcher, PDXL-2 (FG1090-170), or PS-POE-AT-TC (FG423-84).
IMPORTANT: The “Important Power Considerations for Enova DGX Systems” also apply to the DX-RX (see page 31).
To apply power to the DX-RX:
1.Plug the cord from the desktop power supply (provided) into the power jack on rear of the DX-RX (2.1 mm DC jack for 12 V
local power).
2.Plug the desktop power supply into an AC external power source.
The Power LED on the front of the DX-RX illuminates a constant green, which indicates a ready state. Some of the additional
LEDs will also turn a turn a constant green. For normal LED display, see the table below.
IMPORTANT: If any Receivers are being powered through an Enova DGX, we recommend determining the power budget to maintain
power redundancy for the system (see page 44).
DX-RX – Indicator LEDs
The LED indicators are listed in the table as they appear on the front of the RX from left to right.
DX-RX LEDNormal DisplayIndicates
PowerGreenPower is applied to the Receiver
VideoGreenA video signal is present through the Receiver
AudioGreenAn embedded audio signal is present through the Receiver
Scaling:
– Bypass
– Auto
– Manual
IR TXRedIR TX active communication
IR RXYellowIR RX active communication
Serial TXRedSerial TX active communication
Serial RXYellowSerial RX active communication
NetLinx Link/Act GreenActive LAN connection to an AMX Network (Blinking = #3 Toggle OFF)
NetLinx StatusGreenLAN connection is active
* When the output cable is disconnected from the DX-RX or if no EDID can be found on the destination device, the last used Scaling
Mode LED will be ON. In either case, the DX-RX will continue to hold its output resolution to the last known preferred resolution
until a power cycle or reconnection of a sink with a valid EDID. On power up without a valid EDID, the default preferred output
resolution presented will be 1280x1024,60Hz until a different EDID is detected.
DX-RX – LED Troubleshooting
If t he indicato r LEDs for the mo dules do not respond with a normal display as stated in the table above:
□ Check all power connections.
□ Check the “Detailed NetLinx (Link/Act and Status) LED Behavior” section on page 50.
□ Try the suggestions in the “Troubleshooting” chapter (see page 82).
For information on restoring the module’s default settings on power up, see page 57.
One LED is green
The other two are off
Receiver is in one of the three modes for scaling
• At initial power up, the Receiver defaults to the Auto scaling option*
• Press the Scaling button to turn on the Bypass option or the Manual option
The illustration in FIG. 33 shows the bidirectional serial data transfer and IR flow control when DXLink Mo dules are used in Endpoint
Mode with an Enova Digital Media Switcher. The switcher has an integrated NetLinx Central Control Processor which provides native
AMX control at each remote location fed by a DXLink Transmitter or Receiver. Control is sent over twisted pair cable (via the DXLink
ports). This also holds true when Enova DVX Solutions are used.
FIG. 33
Serial data transfer and IR flow control
Optional: DX-TX, HDMI TX, and DX-RX – Wiring for Serial Data Transfer
The RS-232 (serial) ports are the 3-position screw terminal blocks on the rear of the modules to the right of the ICS LAN 10/100
connector. Wire these ports to supply serial data along with the associated video and audio signals from a source device (over the
twisted pair cable between the DX-TX or HDMI TX and the DX-RX) to a destination device or vice versa from the DX-RX to the DX-TX
or HDMI TX. In additi on to being directl y co nnected to a device, this port can be connected as an independent native NetLinx
control port from a networked NetLinx Central Controller.
IMPORTANT: For serial strings to pass through a standalone TX and RX pair (in Extender Mode) without a NetLinx Master acting as
the host, DIP switch #2 Toggle must
The RS-232 port labels are relative to the data flow. On the DX-TX or HDMI TX, data enters the system at the RX label and leaves the
system at the TX label on the Receiver (FIG. 34). The flow is reversed from the Receiver to the Transmitter.
NOTE: On both modules, the RS-232 connector pinout is “TX - RX - Ground.”
To wire the RS-232 (serial) connectors on the modules for data transfer:
1.Wire the RS-232 connectors on the modules according to the pinou t directly above the connector.
FIG. 34 Wire RS-232 ports for serial data transfer
2.Use the command RXON to enable this port on the Transmitter and the Receiver. (For complete Serial SEND_COMMAND
programming information, see page 76.)
be set to OFF on each module.
Serial Control – Endpoint Mode and SEND_COMMANDs
In Endpoint Mode (modules are connected to a switcher), serial operations are handled by the host providing control of the
endpoints. The Master’s programming specifies where the serial commands are sent (this is handled independently from the
rou ting o f the video sig nals). For additional inform ation on Endpoint Mo de, see page 28. Fo r Serial SEND_CO MMAND s, see page 76.
For additional information on the IR03 and CC-NIRC, which are required for IR control, see page 19. (The IR03 and CC-NIRC are
not included with the modules.) A compatible remote control unit can also be used with the system. In addit ion to being directly
connected to a device, this port can be connected as an independent native NetLinx control port from a networked NetLinx Central
Controller.
IMPORTANT: When a Transmitter and Receiver are used as a standalone pair, the IR control will be passed through directly in
Extender Mode when #2 Toggle is set to OFF (default). When #2 Toggle is set to ON, the Master handles the IR control. When a
Transmitter and Receiver are connected to a switcher, they will default to Endpoint mode and the integrated Master handles the
SEND_COMMANDs.
The IR Receiver is connected to the IR RX port on the Transmitter, and the IR Emitter is connected to the IR TX po rt o n the Receiver,
or the connections can be reversed.
IR03 External IR Receiver (not included)
FIG. 35
IR Receiver cable (FG-IR03)
To connect an IR Receiver to a module:
1.Connect the jack on the IR03 External IR Receiver Module cable (FG-IR03) to the IR RX port on the module.
2.Run the cable and attach the IR receiver bud so that it has a clear line-of-sight with the intended remote control device.
CC-NIRC NetLinx IR Emitter Cable (not included)
FIG. 36 IR Emitter cable (FG10-000-11)
To connect an IR Emitter to a module:
1.Connect the Phoenix connector on the CC-NIRC NetLinx IR Emitter cable (FG10-000-11) to the IR TX port on the module.
2.Run the o ther end of the IR Emitter cable to the display device and locate the IR window.
3.Attach the IR Emitter bud over the device’s IR sensor by removing the cover on the reverse side of the Emitter and sticking the
bud directly over the IR window.
IMPORTANT: For systems that include a switcher – when installation of the IR Receiver and IR Emitter is complete, load the
appropriate driver (for instructions, see page 60) and program the IR remote according to the product’s documentation.
IR Control – Endpoint Mode and SEND_COMMANDs
In Endpoint Mode (modules are connected to a switcher), IR operations are handled by the host providing control of the endpoints.
The Master’s programming specifies where the IR commands are sent (this is handled independently from the routing of the video
signals). For additional information on Endpoint Mode, see page 28. For IR SEND_COMMANDs, see page 73.
The ID Pushbutton is located on the right front of the modules, on the left edge of the Wallplate TX, and on the front of the Decor
Wallplate TX.
The ID Pushbutton can be used to perform four types of initial configuration settings:
Toggle between DHCP and static IP addressing
Assign a device address
Reset the factory default settings
Restore the factory firmware image
The functions performed depend on when and for how long the ID Pushbutton is pressed and held. For complete ID Pushbutton
information, see page 56.
NOTE: ID Pushbutton functions can also be implemented using Telnet commands (see page 90).
DX-RX Scaling Button and Scaling Modes
The Scaling button is located on the front of the Receiver Module. Pressing the Scaling button cycles the module through the three
scaling options: Bypass, Auto, and Manual.
Bypass Mode – allows the video signal to display over the destination device without altering the signal’s resolution.
Au to Mode (default) – allows the destinatio n device to cho ose the resolution it needs (this mode is AMX’s SmartScale
Tech n o logy i n a c tion).
Manual Mo de – allo ws the user to conf igure the reso lutio n that the video will di splay throu gh a destination de vice.
Selecting a Scaling Mode results in the module maintaining or altering the source device’s resolution as it is passed along to the
destinatio n device.
The Scaling Mode can be set on the DX-RX with the Scaling button (see instructions below), with DGX Configuration Software, or
with SEND_COMMANDs (see page 66).
To set the scaling option (mode):
1.Press the Scaling button on the DX-RX once or twice until the LED for the desired scaling option illuminates solid green.
®
Bypass Mode
Bypass Mode allows the video signal to display over the destination device without altering the signal’s resolution.
NOTE: Interlaced and progressive video are supported into the Transmitters; progressive is only supported out of the Receiver unless
it is in the Bypass mode, which is non-scaling.
Auto Mode
At initial power up, the DX-RX defaults to the Auto scaling option.
NOTE: When the output cable is disconnected from the DX-RX or if no EDID can be found on the destination device, the last used
Scaling Mode LED will be ON. In either case, the DX-RX will continue to hold its out put resolution to the last known preferred resolution
until a power cycle or reconnection of a sink with a valid EDID. On power up without a valid EDID, the default preferred output
resolution presented will be 1280x1024,60Hz until a different EDID is detected.
Manual Mode
Man ual Mode al lows the user to conf igure the reso lutio n that t he video will display th rough a destinatio n device. Manual M ode
defaults to 1280x1024p,60Hz. This default resolution can be changed in two ways:
Use the SEND_COMMAND VIDOUT_RES_REF to set the resolution and refresh rate (for details, see page 66).
When used as a direct output of an Enova DGX DXLink Output Board, use DGX Configuration Software to set and persist the
Manual scaling resolution for the connector on the DXLink Output Board; the DXLink Output Board sends the scaling
resolution data to the DX-RX.
NOTE: The scaling mode (and the aspect ratio) can also be set on the DXLink Output Board using DGX Configuration Software. The
data is persisted on the board and sent to the DX-RX.
Persistence of Scaling Options
The DX-RX defaults to “Auto” when power is cycled. The scaling option can be persisted using one of the following methods:
Using the SEND_COMMAND: PERSISTAV (for details, see page 79).
Using DGX Configuration Software to set and persist the scaling option for the connector on the DXLink Output Board on
the Enova DGX Digital Media Switcher; the DXLink Output Board sends the scaling option data to the DX-RX.
Detailed NetLinx (Link/Act and Status) LED Behavior
The tables below provide detailed descriptions of all blink patterns for the NetLinx Link/Act and Status LEDs on the front of the
Transmitter and Receiver Modules.
NOTE: The term “light show” refers to the back-and-forth scanning pattern of the LEDs associated with the LEDs on the modules.
Module Operational State as Indicated by LEDs
To determine the operational state (normal boot) of a module by its LEDs, check both the Link/Act and Status LED columns.
NetLinx LED Behavior and Operational States
Link/Act LEDStatus LEDModule Operational State
ON if connected to a system
with an integrated Master.
Blink OFF with data.
OFFONNormal Boot (DHCP found)
Fast blink, then normal
operation.
OFF during light show, then
normal operation (OFF until
connected to Master).
Follow Master’s instruction for Blink Message
if online with Master, o therwise ON.
Normal Online with Master (rest)
NOTE: This state continues from the time an IP
address is obtained until the device is online with the
Master.
ONNormal Boot (DHCP, no server)
NOTE: This state continues until a valid IP address is
obtained.
Fast blink (continues only during light show),
then ON until first blink from Master.
Normal Boot (Static IP)
NOTE: This state continues until the device finishes
its light show.
ID Pushbutton Boot State and LED Behavior
To monitor the ID Pushbutton boo t state of a module by its LEDs, check both the Link/Act and Status LED columns.
ID Pushbutton Boot and NetLinx LED Behavior
ID Pushbutton Boo t StatesLink/Act LEDStatus LED
Boot with ID Pushbutton held down.Slow blink (1 Hz)Slow blink (1 Hz)
ID Pushbutton held down long enough
for reset to default parameters.
ID Pushbutton held down long enough
for reset to default firmware image.
In Auto ID mode.NormalBlink (2 Hz)
ID Pushbutton held down long enough to
accept new ID.
After boot: ID Pushbutton held down, but
not long enough for IP mode change.
After boot: ID Pushbutton held down
long enough for IP mode change.
Fast blink until ID Pushbutton is
released, then OFF
Solid ON, transitions to OFF once
the unit completes writing to flash
and is ready to rebo ot.
2 blinks, then normal2 blinks, then normal
Slow blink (1 Hz)Slow blink (1 Hz)
Fast blink, then OFFFast blink, then OFF
Fast blink until ID Pushbutton is released, then OFF
Solid ON, transitions to OFF once the unit completes
writing to flash and is ready to reboot.
Downloading Firmware State and LED Behavior
To monitor the state of a module by its LEDs when downloading firmware, check both the Link/Act and Status LED columns.
NetLinx LED Behavior when Downloading Firmware
Downloading FirmwareLink/Act LEDStatus LED
Downloading firmware to flash due to an
upgrade via NetLinx Studio.
Fast blink, alternating with Status LEDFast blink, alternating with Link/Act LED
When switching systems with DXLink Technology support (e.g., an Enova DGX Digital Media Switcher and an Enova DVX-3155HD)
are connected via their DXLink ports, DXLink Transmitters and Receivers can be used to extend the video and audio transport.
IMPORTANT: This section does not refer to the linking of enclosures from CPU to CPU, which is not
Media Switcher or the Enova DVX Solutions.
In an installation with DXLink equipment in a multiple-stage switching system, the following apply:
Network loops must be avoided (see page 33). The DXLink line’s Ethernet functionality is disabled between the enclosures;
therefore, no IR, serial, or Ethernet communication can be passed between them.
When two switching systems with DXLink support are connected via their DXLink ports, only video and audio will be passed
through the DXLink connection.
When a DXLink input or output on one switching system determines that it is connected to a DXLink input or ou tput on
another switching system, the DXLink port will au tomatically disable all Ethernet, power, and control on that connection
port so that the only things passed down the DXLink line are the video and audio signals.
When connecting switching systems via DXLink ports, AMX recommends no more than three switcher throughputs (see the
“Example” below).
Example
This example shows how DXLink Transmitters and Receivers can be used in a system where switchers are connected via their
DXLink ports.
The signal path through three switchers could be: source device
DXLink output)
DXLink Receiver
IMPORTANT: If the TXs/RXs are connected to an Enova DGX 100 Series Switcher using auto-setup, see the “Hardware Reference
Manual – Enova DGX 100 Series Digital Medial Switchers” for network conf iguration information.
NOTE: If a DXLink module or wallplate has been configured for auto-setup mode and then auto-setup mode has been disabled, the
unit may take longer to appear in NetLinx Studio than expected (1-2 minutes).
DXLink Modules support two IP Addressing Modes: Static IP and DHCP (with link-local fallback*).
To avoid having a large system consume numerous IP addresses, the Transmitter and Receiver default to disabling the network
connection functionality. Therefore, the #3 Toggle must be set to ON before the Transmitter or Receiver can establish a network
connection (see page 35).
When #3 Toggle is ON, the DXLink Modules are automatically placed in DHCP Mode, but they can be conf igured for either of the
IP Addressing Modes via two methods:
The front-panel ID Pushbutton (see page 56)
Telnet commands (see page 90)
* “Link-local fallback” is a method by which an IP host, as a fallback from DHCP, can derive a local network-unique IP address by
negotiating with the other IP hosts on the same network. Link-local can also be used in its own right as the primary method of
IP address allocation. For details, see “DHCP Mode” below.
Static IP Mode – Default Parameters
Network Configuration
IMPORTANT: Static IP Mode will not function until the #3 Toggle on the DIP switch is set to ON (see page 35). The #3 Toggle must be
ON before the device is accessible via SEND_COMMANDs.
Default Parameters for Static IP Mode
Address192.168.1.2
Netmask255.255.255.0
Gateway192.168.1.1
DNS1192.168.1.1
DNS2192.168.1.1
DNS3192.168.1.1
DHCP Mode
IMPORTANT: DHCP Mode will not function until the #3 Toggle on the DIP switch is set to ON (see page 35). The #3 Toggle must be ON
before the device is accessible via SEND_COMMANDs.
DHCP Mode requires a connection to a network with a DHCP server located on it. This connection can be either indirect or direct.
Indirect connection – In the case of an Enova DGX Digital Media Switcher or an Enova DVX Solution (Endpoint Mode) that
is connected to a DHCP server device, the DHCP connection can be propagated through the system’s DXLink layer. First you
must complete the following:
Set the #3 Toggle to ON to enable the network connectivity.
Direct connection – In the case of a st andalone pa ir (Extende r Mode) , to place th e DXLink Mo dules in DHCP Mo de yo u must
complete the following:
Set the #1 Toggle to ON to enable access to the physical ICS LAN 10/100 port.
Set the #3 Toggle to ON to enable network connectivity (DHCP).
Connect the ICS LAN 10/100 port to a network where a DHCP server is located.
When in DHCP Mode (default setting), the module will attempt to get a DHCP lease (consisting of IP address, gateway, and other
network parameters). Should the attempt fail, the module will then configure itself for a link-local address.
DXLink Modules utilize a modified link-local addressing procedure. The f irst address to be tried is a known address in the
link-local space: 169.254.2.2. That add ress will be probed, and if unclaimed will be used by the DXLink Module.
If 169.254 .2.2 is already claimed, the DXLi nk Module will c hoose a ra ndom add ress within the 169.254.x.x link-local address
space (again probing to ensure that it is unclaimed).
Once the module is operating with a link-local address, it will periodically re-try DHCP and re-assign the IP to a valid DHCP grant if
successful.
At any time, if the module determines that its IP address has changed, it will disconnect from the Master (if necessary, depending on
the connection state) and then reconnect to the Master.
DXLink Modules support IPV4 network addresses, gateway addresses, DNS server addresses, and network names. They also
support NDP (NetLinx Discovery Protocol) capabilities as well as IP discovery via NetLinx Studio.
NOTE: NDP is a device discovery method used by NetLinx Masters. With NDP Beacon enabled, the Master will transmit NDP Beacons
for AMX’s proprietary device discovery.
Telnet IP Conf iguration Commands
The SET IP and GET IP Telnet commands listed in the tables in Appendix B (which start on page 91) can be sent directly to the
device via a Telnet terminal session. These commands can be used for initial network configuration o f the DXLink Modules.
The default Telnet port is 23.
Telnet is e nabled by default.
A value of 0 disables the telnet server.*
For details, see “Appendix B – Telnet (Terminal ) Commands” on page 90. The appendix also includes a section on “Master
Connection Modes” on page 97.
* If you set the Telnet port to “0” to disable it, you will need to perform a factory reset using the ID Pushbu tton to re-enable it (see
page 57).
External Master Versions
If the DXLink Module is bound to an external Master, we recommend using the versions listed in the table below, which can be found
on the product’s page at www.amx.com
Offline Recovery Mechanism – A new, optional, recovery mechanism for DXLink devices in the rare occurrence that these devices
move from online to offline status for an extended period of time.
The default setting for the recovery mechanism is OFF, but may be enabled for environments where the DXLink device could lose
connectivity to the Master for 5 minutes or longer.
IMPORTANT: A reboot is required after setting the recovery mechanism before the new setting takes effect.
The following Telnet Commands enable, disable, and query the Offline Recovery Mechanism:
Set recovery mechanism to ON: WD ON
Set recovery mechanism to OFF: WD OFF
Query recovery mechanism’s current status: WD
Once the device’s recovery mechanism is set to the ON state via Telnet, the recovery mechanism monitors the ICSP connection to
the Master. The recovery mechanism is not armed until the DXLink device is brought online. Entering an offline state triggers an
internal timer in the DXLink device which, after 5 continuous minutes in the offline state, in turn triggers the recovery mechanism to
issue a full reboot command to the DXLink device. During this time the DXLink device will reboot and all functions (including video
and audio delivery) will be disabled while th e reboot occurs. This process takes up to 45 seconds to complete.
This functionality is an option intended to be a safety net for the rare occasions when a device falls offline and remains there for
a long enough period of time that the likelihood of the device coming back online on its own diminishes. The reboot is intended to
restart the device and allow it another opportunity to connect with the Master it is bound to.
Usage considerations include:
Once a device reboots, the recovery mechanism will not become armed again until the device reaches an online state
with a Master.
Because video is lost during the reboot process, consideration should be given to certain installation designs where a
Master or the network connection between the Master and a DXLink endpoint might regularly be disabled or turned off,
but video might continue to flow through the DXLink device. In these environments, we recommend not enabling the
Offline Recovery Mechanism.
Additional capabilities of recovery mechanism – Although highly unlikely, the recovery mechanism also monitors the
following states and provides a self-recovery mechanism if these states are ever encountered.
If a DXLink device processor enters an unstable processing condition
If the DXLink device’s allowable minimum memory threshold is exceeded
HostnameModel (e.g., DX-RX); after factory reset, model with last 7 digits of serial #
Master Connection ModeNDP - For details, see page 20.
Master URL
(for TCP and UDP URL modes)
Master Connection Port Number
(for TCP and UDP URL modes)
Friendly-Name“” (blank)
Location“” (blank)
Stored MAC Address of Master
(for NDP binding)
ICSP Device Number0 (0 = receive dynamic device number from Master)
System Number0
Telnet Port23
SET BAUD9600, N, 8, 1
CTOF Time 5 (0.5 seconds)
CTON Time 5 (0.5 seconds)
Receivers Only
VIDOUT_ASPECT_RATIO STRETCH
VIDOUT_RES_REF 1280x1024,60 (for Manual Mode)
AUDOU T_FORMAT All
Transmitters Only
VIDIN_AUTO_SELECTENABLE
VIDIN_FORMATHDMI (on Port 7), VGA (on Port 8)
VIDIN_RES_REF1280x1024,60
VIDIN_PREF_EDID1920x1080p,60
VIDIN_EDIDMIRROR OUT 1 (on Port 7), ALL RESOLUTIONS (on Port 8)
VIDIN_HDCPENABLE
VIDIN_VSHIFT0
VIDIN_HSHIFT0
VIDIN_PHASE0
AUDIN_FORMAT_AU TOENABLE
AUDIN_FORMATAnalog
“” (blank)
1319
NOTE: If the Friendly Name is non-blank, both Friendly Name and Location are concatenated
to make NDPSTRING2, otherwise NDPSTRING2 is generated from the unit’s serial number.
00:00:00:00:00:00
A value of 0 disables the Telnet server. Telnet is enabled by default.
The ID Pushbutton is located on the right front of the modules, on the left edge of the Wallplate TX, and on the front of the Decor
Wallplate TX.
FIG. 37 ID Pushbutton on module (HDMI TX shown)
The ID Pushbutton can be used to perform four types of initial configuration settings:
Toggle between DHCP and static IP addressing (see below)
Assign a device address (page 57)
Reset the unit to its factory default settings, which affects the parameters but not the f irmware version (see page 57)
Restore the unit to its factory firmware image, which affects both the firmware version and the parameters (see page 58)
The functions performed depend on when and for how long the ID Pushbutton is pressed and held. ID Pushbutton functions can
also be implemented using Telnet commands (see page 90).
TIP: To monitor the ID Pushbutton boot state of a module by its NetLinx LED behavior, see page 59.
Toggling Between IP Addressing Modes: DHCP and Static IP
DXLink Transmitters and Receivers support both DHCP and static IP addresses. When the #3 Toggle is ON (see page 35), the
modules automatically use DHCP with link-local fallback. However, you can use a static IP address which can be set via a Telnet
command (SET IP), or you can use the factory default static IP address. The default static IP address can be recalled at any time
by resetting the unit to its factory default conf iguration (see page 57). The default dynamic (DHCP) address is 169.254.2.2.
The ID Pushbutton can be used to toggle between the DHCP and Static IP Modes.
To toggle between DHCP and Static IP Modes:
1.Once the module has booted up, press and hold the ID Pushbutton until the Control/NetLinx LEDs toggle back and forth in
unison approximately 10 times.
2.Release when it starts to blink faster.
When the Pushbutton is released, the module toggles either from static to dynamic (DHCP) IP addressing or vice versa and
remains in that mode until the ID Pushbutton is used to set it again or a factory reset is performed.
The module automatically reboots to complete the process.
The ID Pushbutton can be used in conjunction with the ID (Identify) Mode feature in NetLinx Studio. A momentary press of the ID
Pushbutton assigns a device address to the Transmitter or Receiver(which must be bound to the Master).The device must first be
placed in ID Mode in NetLinx Studio or the momentary press will be ignored.
NOTE: The latest version of NetLinx Studio is available to download and install from www.amx.com
help for instructions on using the application.
To set the device address on a Transmitter or Receiver:
1.Check to be sure #3 Toggle on the bottom of the Transmitter or Receiver is set to ON.
2.In NetLinx Studio’s OnLine Tree, select the Master to which the Transmitter or Receiver is bound.
3.From the Diagnostic menu, select Device Addressing.
The Device Addressing dialog box opens.
. Refer to the NetLinx Studio online
4.In the ID Mode section, enter the Device and System numbers that you want assigned to the device in the appropriate text
boxes.
5.Click Start Identify Mode to place the named system in ID Mode.
The button changes to “Cancel Identify Mode” (click to cancel ID Mode).
The text box below the button displays a “Waiting...Press Cancel to Quit” message.
NOTE: When in ID Mode, the entire system is put on hold while it waits for an event from any NetLinx device in the named system
(e.g., pressing the ID Pushbutton on the Receiver). The device that generates the first event is the device that will be “identified.”
6.Briefly press and release the ID Pushbutton on the Transmitter or Receiver.
The Transmitter or Receiver will exhibit the following behavior:
Respond with an ID Mode address response.
Report its old address offline.
Report its new address online.
The OnLine Tree will refresh to display the new device address for the Transmitter or Receiver.
NOTE: NetLinx Studio (v4.0 or later) provides the ability to auto-increment IP Addresses and Hostnames as well as Device and System
Numbers. Refer to the NetLinx Studio online help for details.
Reset the Factory Default Settings
During power up – if the ID Pushbutton is held until the Control/NetLinx LEDs toggle back and forth in unison approximately
10 times, then released when the faster blinking starts, the Transmitter or Receiver will reset to its factory default settings, which
affect the parameters but not the firmware version.
Factory Parameters*
Default static IP address of 192.168.1.2
Default dynamic (DHCP) address of 169.254.2.2
Default device number of 0
NDP mode (see page 97)
Unbound state
No IRL files
* For a complete list of factory parameters, see the table on page 55.
Instructions for the modules are given first followed by the instructions for the Wallplate TX and the Decor Wallplate TX, which
receive power over DXLink from the switcher.
IMPORTANT: If a Transmitter or Receiver Module is receiving power from a switcher, disconnect the DXLink connector on the module
and reattach to apply power.
To reset a Transmitter or Receiver Module to its factory default settings:
1.Press and hold the ID Pushbutton while plugging in the power connector. Start counting when the NetLinx LEDs begin to flash
in unison, not when the power connector is inserted.
Once the Transmitter or Receiver Module has started booting up, both NetLinx LEDs flash in unison at the rate of once per
second.
After 10 flashes at that rate, the LEDs will blink in unison at a faster rate.
NOTE: A press-and-hold of the ID Pushbutton at power up will prevent the Transmitter or Receiver from attempting to come online
until the ID Pushbutton is released. The Transmitter or Receiver will only attempt to come online if you release the Pushbutton prior to
the faster blink rate.
2.At the point that the blink rate increases, release the ID Pushbutton.
The Transmitter or Receiver will automatically reboot to complete the process.
To reset Wallplate TX or Decor Wallplate TX to its factory default settings:
1.The ID Pushbutton and the Reset button are located on the left edge of the Wallplate TX and on the front of the Decor
Wallplate TX.
2.Press and hold the ID Pushbutton. While the ID Pushbutton is down, press and release the Reset button. Start counting when
the NetLinx LEDs begin to flash in unison, not when the Reset button is released.
Once the unit has started booting up, both NetLinx LEDs (on bottom edge) flash in unison at the rate of once per second.
After 10 flashes at that rate, the LEDs will blink in unison at a faster rate.
NOTE: A press-and-hold of the ID Pushbutton at boot will prevent the unit from attempting to come online until the ID Pushbutton is
released. The unit will only attempt to come online if you release the Pushbutton prior to the faster blink rate.
3.At the point that the blink rate increases, release the ID Pushbutton.
The unit will automatically reboot to complete the process.
TIP: In the following two procedures – if you start a press and hold sequence with the ID Pushbutton and then decide not to change
the settings, before you release the ID Pushbutton remove power from the unit to abort the procedure (remember, power can be
applied via the external power supply or over DXLink, so one or both sources of power may need to be removed).
Restore the Factory Firmware Image and Factory Default Parameters
During power up – if the ID Pushbutton is held until the Control/NetLinx LEDs toggle back and forth in unison approximately
30 times (10 slow, 20 fast) and then released when they go solid, the module’s factory firmware image will be restored. Th is
procedure affects both the f irmware version and the parameters.
Instructions for the modules are given first followed by the instructions for the Wallplate TX and the Decor Wallplate TX, which
receive power over DXLink from the switcher, PDXL-2 (FG1090-170), or PS-POE-AT-TC (FG423-84).
IMPORTANT: If a Transmitter or Receiver Module is receiving power from a switcher, on the module disconnect the RJ-45 cable from
the DXLink connector before starting the instructions below.
To restore the Transmitter or Receiver Module to its factory default f irmware image:
1.Press and hold the ID Pushbutton while plugging in the power connector (if the power source is a switcher, plug in the RJ-45
connector into the DXLink port instead). Start counting when the NetLinx LEDs begin to flash in unison, not when the power
connector is inserted.
After the LEDs complete the following sequence, release the ID Pushbu tton:
Once the Transmitter or Receiver has started booting up, all LEDs flash in unison at the rate of once per second.
After 10 flashes at that rate, the LEDs will blink in unison at a faster rate.
After 10 seconds of flashing at the increased rate, all LEDs go to solid on.
2.Upon release of the ID Pushbutton, the Transmitter or Receiver executes the following actions:
a. Restores itself to its factory firmware image.
b. Resets to factory default parameters*:
Deletes all IRL f iles sto red on t he device.
Resets to the default static IP address of 192.168.1.2 and default DHCP address of 169.254.2.2.
Resets to the default device number of 0 (when bound to a Master, receives a dynamic device number from the Master).
Resets to NDP mode and being unbound.
3.Once all actions in Step 3 are completed, the LEDs all turn off, indicating the Transmitter or Receiver is ready to reboot.
The Transmitter or Receiver automatically reboots to complete the process.
* For a complete list of factory parameters, see the table on page 55.
To restore Wallplate TX or Decor Wallplate TX to its factory default f irmware image:
NOTE: ID Pushbutton and the Reset button are located on the left edge of the Wallplate TX and on the front of the Decor Wallplate TX.
1.Press and hold the ID Pushbutton. While the ID Pushbutton is down, press and release the Reset button. Start counting when
the NetLinx LEDs begin to flash in unison, not when the Reset button is released.
After the LEDs complete the following sequence, release both buttons:
Once the unit has started booting up, all LEDs flash in unison at the rate of once per second.
After 10 flashes at that rate, the LEDs will blink in unison at a faster rate.
After 10 seconds of flashing at the increased rate, all LEDs go to solid on.
2.Upon release, the unit executes the following actions:
a. Restores itself to its factory firmware image.
b. Resets to factory default parameters*:
Deletes all IRL f iles sto red on t he device.
Resets to the default static IP address of 192.168.1.2 and default DHCP address of 169.254.2.2.
Resets to the default device number of 0 (when bound to a Master, receives a dynamic device number from the Master).
Resets to NDP mode and being unbound.
* For a complete list of factory parameters, see the table on page 55.
3.Once all actions in Step 3 are completed, the LEDs all turn off, indicating the unit is ready to reboot.
The unit automatically reboots to complete the process.
TIP: To monitor the ID Pushbutton boot state of a module, see the “ID Pushbutton Boot and NetLinx LED Behavior” table below.
ID Pushbutton Boot State and LED Behavior
To monitor the ID Pushbutton boo t state of a module by its LEDs, check both the Link/Act and Status LED columns.
ID Pushbutton Boot and NetLinx LED Behavior
ID Pushbutton Boot StatesLink/Act LEDStatus LED
Boot with ID Pushbutton held downSlow blink (1 Hz)Slow blink (1 Hz)
ID Pushbutton held down long enough for reset to
default parameters
ID Pushbutton held down long enough for reset to
default firmware image
In Auto ID modeNormalBlink (2 Hz)
ID Pushbutton held down long enough to accept
new ID
After boot: ID Pushbutton held down, but not long
enough for IP mode change
After boot: ID Pushbutton held down long enough
for IP mode change
Fast blink until ID Pushbutton is
released, then OFF
Solid ON, transitions to OFF once
the unit completes writing to
Fast blink until ID Pushbutton is released, then
OFF
Solid ON, transitions to OFF once the unit
completes writing to flash and is ready to reboo t
The NetLinx Studio software application (available for free download from www.amx.com) provides the ability to transfer IR Library
files to NetLinx devices such as DXLink Transmitters and Receivers.
When a Transmitter and/or a Receiver are being used in conjunction with a switcher, the switcher’s integrated Master is used for
the IRL file transfer. FIG. 38 shows a Transmitter and a Receiver bound to the integrated Master in an Enova DGX 32 in NetLinx
Studio’s OnLine Tree. Follow the instructions on the top of page 61 to prepare for IRL file transfer and the instructions on page62
for the actual transfer.
IRL File Transfers
FIG. 38
NetLinx Studio – Integrated Master, Enova DGX 32, DXLink Transmitter, and DXLink Receiver
1.Check to be sure #3 Toggle on the bottom of the Transmitter or Receiver is set to ON.
2.Verify that you have the latest version of NetLinx Studio on your PC.
If the version is not the latest –
Use the Web Update option in NetLinx Studio’s Help menu to obtain the latest version.
Or
Go to www.amx.com and login as a Dealer to download the latest version.
3.Downlo ad t he applicable IRL f ile fro m www.amx.com
4.Verify the following:
a. Verify that an Ethernet/RJ-45 cable is connected from the switcher’s integrated Master to the network (e.g., from the
LAN 100/1000 port on the Enova DGX to a LAN).
b. Verify that the target Transmitter or Receiver is connected via its DXLink connector to a DXLink Input or Output Board
(respectively) on the switcher.
c. Verify that the switcher is powered on.
5.Launch NetLinx Studio and open the OnLine Tree.
6.Bind the target Transmitter or Receiver to the integrated Master:
a. Select and right-click the TX or RX in the Online Tree.
b. From the context sensitive menu, select Network Bind/Unbind Device.
c. Verify that the check box is selected. If not selected, select it now.
d. Click OK.
(Partners / Search Devices) to your PC.
7.Determine the Device Number assigned to the target Transmitter or Receiver when it was bound. For the Device Number
location, see FIG. 38 on the previous page.
The Transmitter or Receiver is ready for the IRL file transfer (see page 62).
The File Transfer tool in NetLinx Studio is used to map IRL files to DXLink Transmitters and Receivers. The instructions below
assume that the preparations on the previous pages have been completed.
To send an IR Library (*.IRL) f ile to a Transmitter or Receiver:
1.In NetLinx Studio, select Tools > File Transfer to open the File Transfer dialog box.
2.Clic k Add to o pen the Select Files for File Transfer dialog box.
3.Open the Other tab (if the file you want to transfer is not included in the open workspace.)
The Other tab consists of a display of different types of files that can be transferred to a Master or System devices on the bus.
4. Select the type of file (in this case, IRL/IRV Files) that you want to add to the File list for transfer.
5.Click Add.
A standard Open dialog box opens with the Files of type selection set to IR Code files (*.IRL/*.IRV).
NOTE: IRL f iles must be sent to Port 3 (IR Device Port)
on the Transmitter or Receiver.
6.Locate and select the IRL file that you want to add.
7.Click Open.
The Enter Device Mapping Information dialog box opens.
8.If the f ields are empty – Enter the Device, Port, and System numbers for the selected device.
If the fields are populated – Verify that the mapping information is correct for the selected device.
IRL files are sent to Port 3 (IR Device Port) on the Transmitter or Receiver.
Refer to the “Device Numbering” section on page 64 for information on device numbering for the Transmitter or Receiver.
If the device’s assigned device number has been changed, use the OnLine Tree to determine it.
9.Clic k OK to retu rn to th e Select Files for File Tran sfe r dialog box.
The selected IRL file and its mapping information are indicated in the File and Mapping lists.
10. Click OK to close the Select Files for File Transfer dialog box and return to the File Transfer dialog box. The IRL file appears in
the File queue.
11. Click Send to transfer the file to the Transmitter or Receiver that the file is mapped to.
Additional Documentation
For additional information on using NetLinx Studio, refer to the WebConsole & Programming Guide – NI & DVX Central Controllers
and the WebConsole & Programming Guide – NX-Series Controllers (available at www.amx.com
).
Additional IRL Information
Unlike NetLinx NI-Controllers, ICSLan powered devices (such as the DXLink Transmitter and Receiver units) are not capable of
having their IRL files received via the File Transfer dialog box, nor do they support the SEND_COMMAND: LOADIRL.
NetLinx Programming of DXLink Transmitters and Receivers
Also provided in this chapter are DXLink SEND_COMMANDs specifically for Enova DVX Switchers (see page 81).
NOTE: For a listing of all supported Telnet commands, see page 92.
Device Numbering and Ports
Each DXLink Transmitter and Receiver has its own Device Number (which is assigned when the unit is bound to a Master) and the
following ports.
Transmitters and Receivers (Modules)
Port 1 – Serial
Port 2 – Not used
Port 3 – IR TX
Port 4 – IR RX
Port 5 – USB
Port 6 – Video/Au dio O utpu t
Port 7 – Video/Au dio I nput
Port 8 (DX-TX only) – Analog Video Input
Transmitters (Wallplate TX and Decor Wallplate TX)
Port 1 – Serial
Port 2 – Not used
Port 3 – Not used
Port 4 – Not used
Port 5 – USB
Port 6 – Video/Au dio O utpu t
Port 7 – Video/Au dio I nput
Port 8 – Analog Video Input
For an example of port numbering, see the NetLinx Studio illustration in FIG. 39 on the next page.
IMPORTANT: Best practices for using SEND_COMMANDs with DXLink endpoints include sending commands to the specif ic input or
output port of the Enova DGX 100 Series switcher (i.e. 5002:4:0 for input/output channel 4). For a complete list of NetLinx
Programming Commands, Channels, Levels and Port mapping see the “Enova DGX 100 Series Digital Media Switchers Hardware
Reference Manual” at www.amx.com
.
NetLinx Programming of DXLink Transmitters and Receivers
Ports 1-7 DXLink Transmitter
(device number 32004)
Ports 1-7 DXLink Receiver
(device number 32006)
DXLink Transmitter
Port 1 - Serial ICSP (COM)
Port 2 - Not used
Port 3 - IR Output*
Port 4 - IR Input*
Port 5 - USB (HID) Input and Output
Por t 6 - Au dio/Video O utpu t
Por t 7 - Au dio/ Video I nput
Port 8 - Analog Video Input**
*IR Input and Output ports are not used on
the Wallplate TX or on the Decor Wallplate TX.
**DX-TX, Wallplate TX, and Decor Wallplate TX
DXLink Receiver
Port 1 - Serial ICSP (COM)
Port 2 - Not used
Port 3 - IR Output
Port 4 - IR Input
Port 5 - USB (HID) Host Data
Por t 6 - Au dio/Video O utpu t
Por t 7 - Au dio/ Video I nput
In NetLinx Studio’s OnLine Tree, the DXLink Transmitters and Receivers each display their ports.
FIG. 39
NetLinx Studio OnLine Tree - Ports 1 through 7 on a DXLink Transmitter and Receiver
NOTE: For additional information on NetLinx Studio, refer to the “WebConsole & Programming Guide – NI & DVX Central Controllers”
and the “WebConsole & Programming Guide – NX-Series Controllers” (available at www.amx.com).
NOTE: All command text is based on a Unicode index.
TIP: Occasionally new firmware versions affect SEND_COMMANDs. If a command does not produce the expected results, we suggest
checking the product’s current firmware version against the information in the “Firmware Version” table on page 88.
IMPORTANT: Before DXLink TXs and RXs can receive any NetLinx SEND_COMMANDs, the DIP switch’s #3 Toggle must
the devices will not be accessible from a NetLinx control system.
NOTE: Since not all devices support both upper and lower case, for best results all commands and parameters should be sent in
upper case.
be set to ON or
NetLinx Programming of DXLink Transmitters and Receivers
DXLink Receiver Video SEND_COMMANDs are sent to Port 6.
NOTE: Asynchronous notif ications are not available for the Receivers via NetLinx Studio (or Telnet).
Video SEND_COMMANDs (Receivers), continued
CommandDescription
?VIDOUT_SCALE
Requests the current Scaling Mode
that the Receiver is set to. The modes
are AUTO (SmartScale®), MANUAL,
and BYPASS.
VIDOUT_SCALE
Sets the Scaling Mode on the
Receiver to AUTO (SmartScale®),
MANUAL, or BYPASS.
?VIDOUT_RES_REF
Requests the resolution and refresh
rate of the video through the
Receiver.
NOTE: If the Scaling Mode is set to
Bypass, the response will be
“BYPASS.”
VIDOUT_RES_REF
Sets the resolution and refresh rate
of the video through the Receiver and
also sets the Scaling Mode to
MANUAL.
IMPORTANT: The “valid responses”
used must come from the
Resolution Names listed in the table
in the “Supported Output
Resolutions” appendix on
page 109.
NOTE: The default for Manual Mode
is 1280x1024,60.
?VIDOUT_RES
Requests the resolution and refresh
rate of the video through the
Receiver.
NOTE: If the Scaling Mode is set to
Bypass, the response will be
“BYPASS.”
?VIDOUT_ASPECT_RATIO
Requests the aspect ratio preference
of the video through the Receiver.
(For explanations of the ratio
options, see page 67.)
Syntax:
SEND_COMMAND <DEV>,"'?VIDOUT_SCALE'"
Example:
SEND_COMMAND dvRX,"'?VIDOUT_SCALE'"
Returns a COMMAND of the form: VIDOUT_SCALE-<AUTO/MANUAL/BYPASS>
Sets the aspect ratio preference of
the video through the Receiver to
Stretch, Maintain, Zoom, or
Anamorphic.
(For explanations of the ratio
options, see page 67.)
?VIDOUT_TESTPAT
Requests the test pattern setting on
the Receiver.
VIDOUT_TESTPAT
Sets the test pattern to display. Can
be sent in any Scaling Mode.
?VIDOUT_MUTE
Requests the setting for the Mute
preference applied to the image from
the Receiver (Enable or Disable).
VIDOUT_MUTE
Sets the Mute preference of the
image from the Receiver to Enable
(displays a blank screen) or Disable.
NetLinx Programming of DXLink Transmitters and Receivers
Aspect Ratio Options
Stre tch (to f it) – This option (default) scales the video to full screen size in both horizontal and vertical directions regardless of the
input aspect ratio. No data is cropped. However, the image may be distorted as needed to fill the screen. When Stretch is selected,
black bars are not added by the scaler. However, if an image has originated from a source device with either horizontal or vertical
black bars (e.g., letter box from a movie), the black bars will be considered as active video and will be included in the stretched
video.
Maintain (aspect ratio) – This option maintains the incoming video’s aspect ratio, but will scale the image until the display fills
either horizontal or vertical direction first. If the vertical direction is filled first, then the video will have pillar box black bars on the
sides of the display. If the horizontal direction is filled first, then the video will have letter box black bars on the top and bottom of
the display.
Zoom – This option maintains the input aspect ratio while zooming the image to fill the screen in all directions. Image data may be
lost on the top and bottom or to the left and right of the displayed image.
Anamorphic – This option is used with anamorphic formatted video sources so that images appear correctly on the display.
NetLinx Programming of DXLink Transmitters and Receivers
DXLink Transmitter Video SEND_COMMANDs are sent to Port 7 unless o therwise noted.
NOTE: Asynchronous notif ications are available for the Transmitters via NetLinx Studio (and Telnet).
NOTE: All text is based on a Unicode index.
Video SEND_COMMANDs (Transmitters)
CommandDescription
?VIDIN_AUTO_SELECT
Requests setting for the Auto Select
mode for the video inp ut signal on
the DX-TX, Wallplate TX, or Decor
Wallplate TX (Enable or Disable).
NOTE: This command applies to all
DXLink Transmitters except the
HDMI TX.
VIDIN_AUTO_SELECT
Enables or disables the Auto Select
mode for the video inp ut signal on
the DX-TX, Wallplate TX, or Decor
Wallplate TX.
NOTE: This command applies to all
DXLink Transmitters except the
HDMI TX.
IMPORTANT: This command must
be sent to Port 1 of the DXLink Transmitter.
IMPORTANT: If a Solecis switcher is used to transport the source’s signal to an Enova DGX
switcher, this command must be sent directly to the Solecis unit.
Syntax:
SEND_COMMAND <DEV>,"'?VIDIN_AUTO_SELECT'"
Example:
SEND_COMMAND dvMFTX,"'?VIDIN_AUTO_SELECT'"
Returns a COMMAND of the form: VIDIN_AUTO_SELECT-ENABLE
IMPORTANT: This command must
be sent to Port 1 of the DXLink Transmitter.
IMPORTANT: If a Solecis switcher is used to transport the source’s signal to an Enova DGX
switcher, this command must be sent directly to the Solecis unit.
Requests the video input being used
on the DX-TX, Wallplate TX, or Decor
Wallplate TX: either the digital video
(Input 7) or the analog video
(Input 8).
The output is always 6.
NOTE: This command applies to all
DXLink Transmitters except the
HDMI TX.
VI<input>O<output>
Sets the DX-TX, Wallplate TX, or
Decor Wallplate TX to route either the
digital vi deo (Inpu t 7) or the analog
video (Input 8) to the output (which
is always output 6).
NOTE: This command applies to all
DXLink Transmitters except the
HDMI TX.
?VIDIN_STATUS
Requests the status of the video
input on the Transmitter.
?VIDIN_FORMAT
Requests the video format on the
Transmitter.
NOTE: All DXLink Transmitters
except the HDMI TX support
component, S-Video, composite,
and VGA signals.
VIDIN_FORMAT
Sets the video format on the
Transmitter (prior to sending,
VIDIN_AUTO_SELECT must be set to
DISABLE).
NOTE: All DXLink Transmitters
except the HDMI TX support
component, S-Video, composite,
and VGA signals
?VIDIN_RES_REF
Requests the resolution and refresh
rate of the video through the
Transmitter.
IMPORTANT: This command must
Syntax:
SEND_COMMAND <DEV>,"'?INPUT-VIDEO,6'"
Example:
SEND_COMMAND dvMFTX,"'?INPUT-VIDEO,6'"
Returns a COMMAND of the form: SWITCH-LVIDEOI8O6
IMPORTANT: This command must
Syntax:
SEND_COMMAND <DEV>,"'VI<input>O<output>'"
Valid responses:
• inpu t = 7 for digital video; 8 for analog video
•output = 6
Example:
SEND_COMMAND dvMFTX,"'VI8O6'"
IMPORTANT: Send to Port 7 for digital video or to Port 8 for analog video.
Syntax:
SEND_COMMAND <DEV>,"'?VIDIN_STATUS'"
Valid response:
status = NO SIGNAL, UNKNOWN SIGNAL, VALID SIGNAL
Example:
SEND_COMMAND dvMFTX,"'?VIDIN_STATUS'"
Returns a COMMAND of the form: VIDIN_STATUS-<status>
NOTE: Send to Port 7 or Port 8.
Syntax:
SEND_COMMAND <DEV>,"'?VIDIN_FORMAT'"
Valid response:
• format (port 8) = COMPONENT, S-VIDEO, COMPOSITE, VGA
• format (port 7) = HDMI, DVI
Example:
SEND_COMMAND dvMFTX,"'?VIDIN_FORMAT'"
Returns a COMMAND of the form: VIDIN_FORMAT-<format>
NOTE: Send to Port 7 or Port 8.
Syntax:
SEND_COMMAND <DEV>,"'VIDIN_FORMAT-<format>'"
Valid response:
• format (port 8) = COMPONENT, S-VIDEO, COMPOSITE, VGA
• format (port 7) = HDMI, DVI
Example:
SEND_COMMAND dvMFTX,"'VIDIN_FORMAT-COMPONENT'"
NOTE: Send to Port 7 or Port 8.
Syntax:
SEND_COMMAND <DEV>,"'?VIDIN_RES_REF'"
Valid responses:
• horizontal = An integer value representing the horizontal.
• vertical = An integer value representing the vertical. May have an additional qualifier such as
'i' or 'p'.
• rate = An integer value representing the refresh rate.
Example:
SEND_COMMAND dvMFTX,"'?VIDIN_RES_REF'"
Returns a COMMAND of the form:
VIDIN_RES_REF-<horizontal>x<vertical>,<rate>
NetLinx Programming of DXLink Transmitters and Receivers
* “USER EDID 1” must be written to the TX using DGX Configuration Software (see page 119).
** The HDMI port mirrors downstream EDID of the connected DXLink device.
TIP: For troubleshooting purposes, “MIRROR OUT 1” can be sent to Port 7 of the TX
(or Port 6 of the RX), which effectively acts like a hotplug and refreshes the EDID.
IMPORTANT: Send to Port 7.
Syntax:
SEND_COMMAND <DEV>,"'?VIDIN_HDCP'"
Example:
SEND_COMMAND dvTX,"'?VIDIN_HDCP'"
Returns a COMMAND of the form: VIDIN_HDCP-<ENABLE|DISABLE>
IMPORTANT: Send to Port 7.
NOTE: When VIDIN_HDCP is disabled, the addressed video input will appear to any source as
not being HDCP compliant. For PC sources that encrypt all video when connected to an HDCP
compliant display, disabling HDCP compliance on the input will cause the PC to send
non-encrypted video which can then be routed to non-compliant displays and video
conferencing systems.
This command is not applicable to the analog video port.
NOTE: After changing this setting, it may be necessary to disconnect and re-connect PC
sources.
DXLink Transmitter Audio SEND_COMMANDs are sent to Port 7.
Audio SEND_COMMANDs (Transmitters)
CommandDescription
?AUDIN_FORMAT_AUTO
Requests the setting (Enable or
Disable) for automatically detecting
the audio source format through the
TX.
AUDIN_FORMAT_AUTO
Sets audio source format to
automatically detect the audio
through the TX.
?AUDIN_FORMAT
Requests the setting for the audio
source format.
AUDIN_FORMAT
Selects the audio input source that
will be embedded on the HDMI signal
through the TX.
NOTE: When the DX-TX is set to
route digital video (input 7), you
can select from the HDMI, SPDIF, or
ANALOG audio inputs. When it is set
to route analog video (input 8), you
can only select the SPDIF or
ANALOG audio input (see the
VI<input>O<output> command).
IMPORTANT: The order of precedence (HDMI embedded audio, S/PDIF, analog) can be
overridden with this command; however, you must
to disable the auto format function, or the audio format will automatically switch back
anytime the order of precedence is violated.
NOTE: S/PDIF signals are not available over the Wallplate TX or Decor Wallplate TX.
first send AUDIN_FORMAT_AUTO-DISABLE
NetLinx Programming of DXLink Transmitters and Receivers
DXLink Transmitter and Receiver Module IR CHANNELS and SEND_COMMANDs are sent to Port 3 (IR output).
IR CHANNELs
ChannelFunction
1-255Generate the IR or serial command assigned to that channel.
IR SEND_COMMANDs
IR SEND_COMMANDs (Transmitters and Receivers)
CommandDescription
CAROFF
Disable the IR carrier signal until a
'CARON' Send Command is received.
CARON
Enable the IR carrier signals
(default).
CH
Send IR pulses for the selected
channel.
CP
Halt and clear all active or buffered
IR commands, and then send a single
IR pulse.
CTOF
Set the duration of the Off time (no
signal) between IR pulses for
channel and IR function
transmissions. Off time settings are
sto red i n no n-volatile memory.
Syntax:
SEND_COMMAND <DEV>,"'CAROFF'"
Example:
SEND_COMMAND IR_1,"'CAROFF'"
Stops transmitting IR carrier signals to the IR port.
Syntax:
SEND_COMMAND <DEV>,"'CARON'"
Example:
SEND_COMMAND IR_1,"'CARON'"
Starts transmitting IR carrier signals to the IR port.
• All channels below 100 are transmitted as two digits.
• If the IR code for ENTER (function #21) is loaded, an Enter will follow the number.
• If the channel is greater than or equal to (>=) 100, then IR function 127 or 20 (whichever
exists) is generated for the one hundred digit.
NOTE: Set the Pulse and Wait times with 'CTON' and 'CTOF' (see the next page).
Syntax:
SEND_COMMAND <DEV>,"'CH',<channel number>"
Valid response:
channel number = 0 to 199 channels
Example:
SEND_COMMAND IR_1,"'CH',18"
The IR port on the DXLink TX or RX performs the following:
• Transmits IR signals for 1 (IR code 11).
• The transmit time is set with the CTON command.
• Waits until the time set with the CTOF command elapses.
• Transmits IR signals for 8 (IR code 18).
• Waits for the time set with the CTOF command to elapse.
If the IR code for Enter (IR code 21) is programmed, the module performs the following steps:
• Transmits IR signals for Enter (IR code 21).
• Waits for the time set with the CTOF command to elapse.
Pulse and Wait times can be set with the 'CTON' and 'CTOF' commands.
Syntax:
SEND_COMMAND <DEV>,"'CP',<code>"
Valid response:
code = IR port’s channel value 0 to 252 (253 to 255 reserved).
Example:
SEND_COMMAND IR_1,"'CP',2"
Clears the active/buffered commands and pulses IR port’s channel 2.
This command sets the delay time between pulses generated by the 'CH' or 'XCH' Send Commands
in tenths of seconds.
Syntax:
SEND_COMMAND <DEV>,"'CTOF',<time>"
Valid response:
time = 0 to 255. Given in 1/10th of a second increments. Default is 5 (0.5 seconds).
Example:
SEND_COMMAND IR_1,"'CTOF',10"
Sets the off time between each IR pulse to 1 second.
Set the total time of IR pulses
transmitted and is stored in nonvolatile memory.
GET BAUD
Get the IR port’s current
communication parameters.
GET MODE
Poll the IR/Serial port’s
configuration parameters and report
the active mode settings to the
device requesting the information.
NOTE: Works with Port 3 only.
IROFF
Halt and clear all active or buffered
IR commands being output on the
desi gnated port.
SET BAUD
Use to set the IR communication
parameters.
NOTE: Before sending the SET
BAUD command, you must
set the
IR port to Data mode (for the SET
MODE command, seepage 74)
SET MODE
Set an IR port to either IR, Serial,
or Data mode.
SP
Generate a single IR pulse.
This command sets the pulse length for each pulse generated by the 'CH' (see previous page) or
'XCH' (see next page) Send Commands in tenth of a second increments.
Syntax:
SEND_COMMAND <DEV>,"'CTON',<time>"
Valid response:
time = 0 to 255. Given in 1/10th of a second increments. Default is 5 (0.5 seconds).
Example:
SEND_COMMAND IR_1,"'CTON',20"
Sets the IR pulse duration to 2 seconds.
The port sends the parameters to the device that requested the information.
Syntax:
SEND_COMMAND <DEV>,"'GET BAUD'"
Example:
SEND_COMMAND dvRXRS232,"'GET BAUD'"
The port responds with:
Port <port #>,<baud>,<parity>,<data>,<stop>
Syntax:
SEND_COMMAND <DEV>,"'GET MODE'"
The port responds with:
<port #> <mode>,<carrier>,<io link channel>.
Example:
SEND_COMMAND IR_1,"'GET MODE'"
The system could respond with:
PORT 3 IR,CARRIER,IO LINK 0
Syntax:
SEND_COMMAND <DEV>,"'IROFF'"
Example:
SEND_COMMAND IR_1,"'IROFF'"
Immediately halts and clears all IR output signals on the IR port.
NOTE: This value is not saved in non-volatile memory and is reset to default (9600, N, 8, 1) at
power-up.
DXLink Receiver USB SEND_COMMANDs are sent to Port 5.
USB SEND_COMMANDs (Transmitter)
CommandDescription
?USB_HID_ROUTE
Requests the IP address or hostname
of the host device (Transmitter)
sending USB keyboard/mouse data
to the Receiver.
USB_HID_ROUTE
Set the IP address or hostname of
the host device (Transmitter) that will
be sending USB keyboard/mouse
data to the Receiver.
Syntax:
SEND_COMMAND <DEV>,"'?USB_HID_ROUTE'"
Example:
SEND_COMMAND dvRX,"'?USB_HID_ROUTE'"
Returns a COMMAND of the form:
USB_HID_ROUTE-<IP address or hostname>
NOTE: When a hostname is specified, a maximum of 50 characters can be used.
Syntax:
SEND_COMMAND <DEV>,"'USB_HID_ROUTE-<IP address or hostname>'"
Example:
SEND_COMMAND dvRX,"'USB_HID_ROUTE-192.168.1.5'"
NOTE: To eliminate the connection, specify 0.0.0.0 as the IP address. To redirect to a new host
device (Transmitter), send the new IP address or hostname.
Common DXLink Transmitter / Receiver SEND_COMMANDs
Common NetLinx SEND_COMMANDs for the DXLink Transmitters and Receivers are provided in the following table.
These commands can be sent to any port (the #3 Toggle must be set to ON).
Common NetLinx SEND_COMMANDs (Transmitters and Receivers)
CommandDescription
?FWVERSION
Requests the firmware version of the
TX or RX.
LED-DIS
Disable all LEDs to the right of the
Program port.
LED-EN
Enable all LEDs to the right of the
Program port (default).
REBOOT
Reboot the module.
SET_NDX_DESC
Set Friendly name and location for
NDP.
Syntax:
SEND_COMMAND <DEV>,"'?FWVERSION'"
Example:
SEND_COMMAND dvRX,"'?FWVERSION'"
Returns a COMMAND of the form:
FWVERSION <version-string>
Syntax:
LED-DIS
Example:
SEND_COMMAND DEVICE_1,"'LED-DIS'"
Disables all LEDs to the right of the Program port on DEVICE_1.
NOTE: This parameter does not get stored in non-volatile memory. LEDs are enabled by
default at each power-up.
Syntax:
LED-EN
Example:
SEND_COMMAND DEVICE_1,"'LED-EN'"
Enables all LEDs to the right of the Program port on DEVICE_1.
Syntax:
REBOOT
Example:
SEND_COMMAND DEVICE_1,"'REBOOT'"
Reboots DEVICE_1.
Syntax:
SET_NDX_DESC-friendly name:location
• Max of 25 characters for friendly name and max of 25 characters for location. If more than
25 characters are sent for either friendly name or location, they will be truncated to a max of
25 characters.
• Neither the friendly name nor the location should contain a “:” character, as that is used as a
delimite r.
NOTE: This command requires a reboot to enable new settings.
NetLinx Programming of DXLink Transmitters and Receivers
DXLink System SEND_COMMANDs
DXLink System SEND_COMMANDs can be sent to any port on the Transmitters or Receiver.
DXLink System SEND_COMMANDs (Transmitters and Receivers)
CommandDescription
?DXLINK
Requests the current mode for the TX
or RX.
DXLINK
Sets the TX or RX to Extender Mode
(for a standalone, direct connection
fro m module to modu le) or E ndpoint
Mode (for use in conjunction with a
switcher).
ICSLAN
Sets the ICS LAN connection to
Enable or Disable.
PERSISTAV
DX-RX: Only used to save the
Receiver’s Power-On Scaler settings/
mode to the DGX DXLink Output
Boards for DGX Configuration
Software.
Not required to save A/V settings to
the receiver. These are automatically
saved when changes are made.
All Transmitters: Disables the
AUDIN_FORMAT_AU TO and
persists the current audio format.
FACT ORYAV
DX-RX: Clears the persisted settings
for the Scaler mode,* resolution,
aspect ratio policy, and audio output
type and restores them to their
factory defaults.
* The “Power-On” Scaler mode on an
Enova DGX DXLink Output Board will
not get reset to default (AUTO), but
will remain as whatever was last
persisted.
All Transmitters: Clears the persisted
setting for the audio and video
formats and restores them to their
factory defaults. Also restores the
preferred EDID to the factory default
on the HD-15 input to
1920x1080P,60.
SET TELNET PORT 0
Sets the Telnet port to “0” (disabled
state).
SET TELNET PORT 23
Sets the Telnet port to “23” (default
port).
Syntax:
SEND_COMMAND <DEV>,"'?DXLINK'"
Example:
SEND_COMMAND dvRX,"'?DXLINK'"
Returns a COMMAND of the form:
DXLINK-<DXLINK-EXTENDER/DXLINK-ENDPOINT>
Syntax:
SEND_COMMAND <DEV>,"'DXLINK-<EXTENDER|ENDPOINT>'"
Example:
SEND_COMMAND dvRX,"'DXLINK-EXTENDER'"
Syntax:
SEND_COMMAND <DEV>,"'ICSLAN-<ENABLE|DISABLE>'"
Example:
SEND_COMMAND dvRX,"'ICSLAN-ENABLE'"
Syntax:
SEND_COMMAND <DEV>,"'PERSISTAV'"
Example:
SEND_COMMAND dvRX,"'PERSISTAV'"
Syntax:
SEND_COMMAND <DEV>,"'FACTORYAV'"
Example:
SEND_COMMAND dvTX,"'FACTORYAV'"
NOTE: A reboot is required after sending the FACTORYAV command.
Syntax:
SEND_COMMAND <DEV>,"'SET TELNET PORT 0'"
Example:
SEND_COMMAND dvRX,"'SET TELNET PORT 0'"
NOTE: A reboot is required after sending the SET TELNET PORT 0 command.
Syntax:
SEND_COMMAND <DEV>,"'SET TELNET PORT 23'"
Example:
SEND_COMMAND dvRX,"'SET TELNET PORT 23'"
NOTE: A reboot is required after sending the SET TELNET PORT 23 command.
NetLinx Programming of DXLink Transmitters and Receivers
The DXLink Modules support several special SEND_STRING escape sequences. If any of the character combinations listed below are
found anywhere within a SEND_STRING program instruction, they will be treated as a command and not the literal characters.
Use the ESCSEQON and ESCSEQOFF NetLinx SEND_COMMANDS to control whether these are active or not. The ESCSEQON
command must precede the Escape Sequences, otherwise strings will be processed normally. These commands are sent to Port 1.
SEND_STRING Escape Sequences
CommandDescription
27, 17
Send a break character for a
specified duration to a specific
device.
27, 18, 0
Clear the ninth data bit by setting it
to 0 on all character transmissions.
27, 18, 1
Set the ninth data bit to 1 for all
subsequent characters to be
transmitted.
27, 19
Insert a time delay before
transmitting the next character.
Syntax:
27,17,<time>
Valid response:
time = 1 to 255 (measured in 100 microsecond increments)
Example:
SEND_STRING RS232_1,"27,17,10"
Sends a break character of 1 millisecond to the RS232_1 device.
Used in conjunction with the 'B9MON' command (see page 76).
Syntax:
27,18,0
Example:
SEND_STRING RS232_1,"27,18,0"
Sets the RS232_1 device’s ninth data bit to 0 on all character transmissions.
Used in conjunction with the 'B9MON' command (page 76).
Syntax:
27,18,1
Example:
SEND_STRING RS232_1,"27,18,1"
Sets the RS232_1 device’s ninth data bit to 1 on all character transmissions.
Syntax:
27,19,<time>
Valid response:
time = 1 to 255. Measured in 1 millisecond increments.
Example:
SEND_STRING RS232_1,"27,19,10"
Inserts a 10 millisecond delay before transmitting characters to the RS232_1 device.
NetLinx Programming of DXLink Transmitters and Receivers
The following table contains two DXLink SEND_COMMANDs that are specifically for Enova DVX Switchers. These commands persist
during a power cycle, on reboot, or from a low power setting.
Additional SEND_COMMANDs for Enova DVX Switchers can be found in the specific product manual at www.amx.com
IMPORTANT: The #3 Toggle on the Transmitter or Receiver must
be set to ON before the commands in the table below are sent to the
switcher.
Enova DVX Solution DXLink SEND_COMMANDs
CommandDescription
?DXLINK_ETH
Requests the control setting for the
DXLink output card on an Enova DVX
Switcher.
DXLINK_ETH
Controls Ethernet traffic through the
DXLink output card on an Enova DVX
Switcher.
?DXLINK_IN_ETH
Requests the control setting for the
DXLink input card on an Enova DVX
Switcher.
DXLINK_IN_ETH
Controls Ethernet traffic through the
DXLink input card on an Enova DVX
Switcher.
Syntax:
SEND_COMMAND <DEV>, "'?DXLINK_ETH'"
Example:
SEND_COMMAND SWITCHER,"'?DXLINK_ETH'"
Returns a COMMAND of the form:
DXLINK_ETH-<AUTO|OFF>
This command instructs the DXLink output card on an Enova DVX Switcher to disable Ethernet
traffic or go to Auto mode. In Auto mode, Ethernet traffic is controlled after negotiation through
PDIF.
Syntax:
SEND_COMMAND <DEV>, "'DXLINK_ETH-<AUTO|OFF>'"
Example:
SEND_COMMAND SWITCHER,"'DXLINK_ETH-AUTO'"
Syntax:
SEND_COMMAND <DEV>, "'?DXLINK_IN_ETH'"
Example:
SEND_COMMAND SWITCHER,"'?DXLINK_IN_ETH'"
Returns a COMMAND of the form: DXLINK_IN_ETH-<AUTO|OFF>
This command instructs the DXLink input card on an Enova DVX Switcher to disable Ethernet traffic
or go to Auto mode. In Auto mode, Ethernet traffic is controlled after negotiation through PDIF.
Syntax:
SEND_COMMAND <DEV>, "'DXLINK_IN_ETH-<AUTO|OFF>'"
Example:
SEND_COMMAND SWITCHER,"'DXLINK_IN_ETH-AUTO'"
.
NOTE: For a listing of all supported Telnet commands, see page 92.
The troubleshooting suggestions/strategies provided apply to the Transmitters and the Receiver, unless otherwise noted.
Five potential types of issues are covered in this chapter:
Basic troubleshooting
Determining HDCP compliance
Power
DXLink connections
Network setup
This chapter also provides technical support contact information on page 85.
Basic Troubleshooting
We suggest using the following general list to rule out basic troubleshooting issues.
□ Check the power indicator LEDs on all of the equipment. If any are not illuminated, see the “Power Issues” section below.
□ Check all link and signal connections to make sure everything is physically set up correctly.
□ Isolate source and destination equipment and cable problems by cabling direct without the DXLink units.
□ Check the DIP switch’s toggle settings (see page 34).
□ SEND_COMMANDs – double-check the command and the port number specif ied and re-send the command (see page 64).
□ If any changes have been made, try resetting the unit to the factory defaults (see page 57).
Additional Resources for Troubleshooting Switching Systems
Enova DGX Digital Media Switchers
When the DXLink units are used in conjunction with an Enova DGX Switcher, we suggest checking the troubleshooting information
in that product’s manual.
Enova DVX Solutions
When DXLink units are used in conjunction with an Enova DVX Solution, we suggest: pressing the Status button on the front panel
and using the UP and DOWN navigational buttons to scroll through the menu options to Diagnostic Codes (the codes can be helpful
for technical support if a call is necessary).
Tro ub le sh oo tin g
Determining HDCP Compliance
A dark red or an o range screen on an outpu t display is the visual cue f rom DXLink devices that the display device cannot display the
HDCP compliant signal from the source.
Power Issues
Upon power up, the Power indicator LED on the front of the DXLink units illuminates solid green.
If the Power LEDs on any of the system’s equipment are not illuminated:
□ Check the power cords or DXLink (RJ-45) connection if using power over the DXLink line.
□ Check the power connections on the switcher if using power over the DXLink line.
□ Check the power connections on the source and destination devices.
DXLink Power Delivery Issues
Unexpected power interruptions o f DXLink Transmitters and Receivers may be caused by the Enova DGX Digital Media Switcher
being powered by single phase power. Connecting a ground wire to the DXLink unit’s chassis and a common earthed ground
(ideally, referenced to the switcher) will stop power interruptions. For information on when and how to attach ground wires to
DXLink units, see page 37.
Important Power Considerations for Enova DGX Systems
Local power – Local power (the desktop power supply) always takes precedence over power via the DXLink line from the
switcher. However, if a locally powered module is connected to a switcher and the local power is lost (i.e., unplugged or
turned off), the module will power down and then automatically power back up using power from the switcher via the
DXLink connection (increasing the overall power draw on the switcher). When local power is restored, it automatically
replaces the power over the DXLink line.
DXLink power – When Transmitters/Receivers are being powered by an Enova DGX DXLink board or DXLink power injector
(using power via the DXLink line), to maintain the switcher’s power redundancy, we recommend that you:
Determine the power budget based on the Input/Output boards used and the quantity of powered endpoints
(Transmitters/Receivers); see page 31.
Do not use the local DC power jack on the module (even if the local power adapter is turned off).
Power Issues with Enova DGX Systems
In an Enova DGX System when multiple endpoints (Transmitters/Receivers) cycle their power and the DXLink connection fails,
check the following:
□ Check to be sure that Transmitters/Receivers being powered by the local DC jack have power. (Local power always takes
precedence.)
□ Check to be sure that Transmitters/Receivers intended to be powered via the DXLink line do not have a DC jack plugged in
(even if the local power adapter is turned off). This can cause inadvertent ground loops that can negatively affect DXLink
power sensing circuits.
DXLink Connection Issues
One method for determining DXLink connection issues is to compare the pattern of the green and yellow DXLink LEDs on the
Transmitter or Receiver against the tables below and then check the suggested items in the Troubleshooting column in the second
table.
DXLink LED Patterns When Connection is Working as Expected
Check the status of the green and yellow DXLink LEDs (on rear of the modules – on lower edge of the Wallplate TX, or on the front
of the Decor Wallplate TX – under customer provided standard decor style cover plate) against the following table to determine the
status of the video signal over the DXLink line. All of the green / yellow patterns in this table indicate that the unit is working as
expected given its current connections. If the LED pattern does not correspond to any of the green / yellow patterns in this table,
check the table below.
LED Patterns – Working as Expected
GreenYellowLED Pattern Description
Solid greenSolid yellowThe DXLink link is established and the video stream is passing HDCP protected content.
Solid greenFlashing yellowThe DXLink link is established and the video stream is passing unprotected content.
Solid greenOffThe DXLink link is established but no video content is being passed.
OffOffThe DXLink link is not established and the accompanying DXLink unit is not powered on or is
If the green / yellow DXLink LEDs on a unit do not have one of the normal patterns as stated in the table above, check the patterns
in the table below and then check the items listed in the corresponding Troubleshooting column.
LED Patterns – Connection Failing
Green YellowLED Pattern DescriptionProblem
Solid greenSporadic flashing
Fully illuminated,
sporadic flashing green
Very dimly illuminated,
rapid / sporadic
flashing green
yellow
OffBad DXLink signal qualityCheck for:
OffVery bad DXLink signal qualityNo video / audio /
Poor DXLink signal qualityVideo drops
Symptoms
occasionally
Ethernet
Troubleshooting
Check for:
• Cable installation p roblems
•Alien crosstalk
• If possible, identify the hostile
cable
• Cable installation p roblems
•Alien crosstalk
• If possible, identify the hostile
cable
• Cable quality
Check for:
• Cable installation p roblems
•Alien crosstalk
• If possible, identify the hostile
cable
Cable quality
NOTE: For installations where the DXLink Twisted Pair device could lose connectivity for an extended period of time (greater than
5 minutes), the Offline Recovery Mechanism is an option that allows the device to detect its offline state and reconnect to a Master
(see page 54).
Network Setup Issues
The instructions below can be used for f irst time setup of DXLink Modules on a network with no NetLinx Master (integrated or
standalone).
NOTE: Before setting up the network, we recommend plugging all required Ethernet cables into the network before applying power to
the DXLink Modules.
To set the IP, connection, and device parameters on a DXLink Module:
1.Set the DIP switch on the DXLink Module to:
#1 and #3 Toggles – ON
#2 and #4 Toggles – OFF
2.Attach the DXLink Module via its ICS LAN 10/100 port to the network or PC.
3.Power up the DXLink Module.
The DXLink Module will get a DHCP address or default to 169.254.2.2 (or if the module is in Static IP Mode, the address will be
192.168.1.2).
4.Establish a Telnet connection to the DXLink Module and set up the network parameters using the following three commands:
SET IP
SET CONNECTION
SET DEVICE
5.Enter REBOOT.
6.Reset the DIP switches to conf igure the DXLink Module for the specific type of system setup being used (see the “Common
Scenarios” table on page 36).
NOTE: If you cannot locate the DXLink Module in the Online Tree, you can reset the factory default by holding the ID button during
power up until the LEDs blink in unison and then releasing the ID button. This will revert the DXLink Module to DHCP mode. Start again
at Step 1 above.
If this manual has not satisfactorily answered your questions regarding the DXLink Transmitters and Receivers or they are not
operating as expected, please contact your AMX representative or technical support. Have the serial numbers for the modules
ready. If the modules are connected to a switcher, locate the serial number for the switcher too.* We recommend recording the
serial numbers in an easily accessible location.
AMX Contact Information
3000 Research Drive, Richardson, TX 75082
800.222.0193
469.624.8000
Fax 469.624.7153
Technical Support 800.932.6993
www.amx.com
* When DXLink units are used in conjunction with an Enova DVX Solution, having Diagnostic Codes ready can be helpful for
technical support in analyzing problems. (Press the Status button on the Enova DVX front panel and use the UP and DOWN
navigational buttons to scroll through the menu options to the Diagnostic Codes.)
The NetLinx Studio so ftware application (available for free download from www.amx.com) provides the ability to transfer KIT files to
NetLinx devices such as DXLink Transmitters and Receivers. The firmware on the Transmitters and Receivers can be upgraded in the
field.
When a Transmitter and/or a Receiver are being used in conjunction with a switcher, the switcher’s integrated Master is used for
the KIT file transfer. FIG. 40 shows a Transmitter and a Receiver bound to the integrated Master in an Enova DGX 32 in NetLinx
Studio’s OnLine Tree. Follow the instructions on the top of page 87 to prepare for KIT file transfer and the instructions on page 89
for the actual transfer.
Appendix A - Upgrading the Firmware
FIG. 40
NetLinx Studio – Integrated Master, Enova DGX 32, DXLink Transmitter, and DXLink Receiver
1.Check to be sure #3 Toggle on the bottom of the Transmitter or Receiver is set to ON.
2.Verify that you have the latest version of NetLinx Studio on your PC.
If the version is not the latest –
Use the Web Update option in NetLinx Studio’s Help menu to obtain the latest version.
Or
Go to www.amx.com and login as a Dealer to download the latest version.
3.Download the latest Firmware (KIT) f ile from www.amx.com
(Place KIT files on a local drive for speedy throughput.)
4.Verify the following:
a. Verify that an Ethernet/RJ-45 cable is connected from the switcher’s integrated Master to the network (e.g., from the
LAN 100/1000 port on an Enova DGX 32 to a LAN).
b. Verify that the target Transmitter or Receiver is connected via its DXLink connector to a DXLink Input or Output Board
(respectively) on the switcher.
c. Verify that the switcher is powered on.
5.Launch NetLinx Studio and open the OnLine Tree.
6.Bind the target Transmitter or Receiver to the integrated Master: select and right-click the TX or RX; from the context sensitive
menu, select Network Bind/Unbind Device (be sure the check box is selected); click OK.
on the DXLink Transmitter or Receiver product page to your PC.
7.Determine the Device Number assigned to the target Transmitter or Receiver when it was bound. For the Device Number
location, see FIG. 40 on page 86. The Transmitter or Receiver is ready for the KIT file transfer.
Important Upgrade Information
CAUTION:
In the Event of Power Loss During an Upgrade
If power loss occurs before any firmware information has been transferred – when power is restored, the module will remain
operational using the original firmware.
If power loss occurs after some of the f irmware information has been transferred but before the transfer is complete – when power
is restored, the module will time out and will not operate until a successful upgrade takes place.
CAUTION:
firmware again, as the module is in an unknown state and cannot be guaranteed to be operational.
Upgrading the f irmware is a serious action in that if the upgrade fails, it can leave the system completely non-operational.
If the application signals a failure, you must immediately reboot the Transmitter or Receiver and attempt to upgrade the
The system will be non-operational during the upgrade procedure below.
The Firmware Transfers tool in NetLinx Studio is used to map KIT f iles to DXLink Transmitters and Receivers. The instructions below
assume that the preparations on the previous pages have been completed.
To send a KIT f ile to a DXLink Transmitter or Receiver:
1.In NetLinx Studio from the Tools menu, select “Firmware Transfers > Send to NetLinx Device” to open the Send to NetLinx
Device dialog box.
2.Click Browse (...) to navigate to the target directory. The selected directory path is displayed in the Location text box. KIT files
in the target directory display under Files.
3.Sele ct the appropriat e KIT f ile from t he list.
4.Enter the Device and System numbers (see FIG. 40 on page 86) for the target module in the Device and System text boxes.
5.Review the File and Target Device information for accuracy before you send.
6.Click Send to upgrade the firmware on the DXLink Transmitter or Receiver.
The Power LED blinks during the process for upgrading the firmware (this is normal).
The progress of the upgrade displays in the Upload Status field. Status is also indicated in the Status bar at the bottom.
The success of the upgrade or any errors that occur will be reported.*
* If an incorrect file has been selected or if the upgrade has failed, the Power LED will briefly illuminate solid green then change to
a slow blink. To recover (in either case), reboot the Transmitter or Receiver and browse to select the correct file and then re-send.
7.Close the window when the transfer is complete.
8.When the process is complete, cycle power using the new image on the DXLink Module:
a. Unplug the desktop power supply from the AC power source and plug it back in.
Or
b. If the power source is the switcher, unplug the RJ-45 connector from the DXLink port on the module and plug it back in.
9.Wait 60 seconds and refresh the System OnLine Tree, and check to be sure the firmware version matches the version selected
for the upgrade.
Reminders
When the file transfer is complete, remember to do the following:
Set the #1 Toggle on the DXLink Module to OFF.
If you set the PC to Static IP Mode for a Virtual NetLinx Master file transfer, return the setting to “Obtain an IP address
Te lne t terminal communication is accessed remotely via TCP/IP. The Transmitter or Receiver must have its own TCP/IP address for
a Telnet connection. The connection can be started from the Windows taskbar (see below) or in NetLinx Studio (see the following
page).
By default, a User Name and Password are not applied to the Telnet port (Port 23). Therefore, the port does not require login
credentials.
Welcome Banner with and without Security Enabled:
Witho ut Telnet security enabled, a session wil l begin with a welc ome banner similar to the fo llo wing:
Welcome to DXLINK-HDMI-RX 0.0.106.0 Copyright AMX LLC 2011
>
If Telnet security is enabled, user credentials are required:
Enter username: admin
Enter protected password: ****
Welcome to DXLINK-HDMI-RX 0.0.106.0 Copyright AMX LLC 2011
>
NOTE: When security is enabled, a user can retry logging in three times before being disconnected (for information on setting a
username and password, see page 91).
IMPORTANT: If auto-setup mode is being used, Telnet is the only way to access some of the network settings. Also note that some
network settings will disable the auto-setup feature (for auto-setup requirements, see the “Quick Reference Table – Modes for
Handling Addressing/Networking” on page 20).
To establish a terminal connection via Telnet at the CMD prompt:
1.From your Windows Taskbar (at the far left), select Start > Run to open the Run dialog box.
2.Type
cmdin the Open field.
3.Click OK to open an instance of the Windows command interpreter (cmd.exe).
4.At the prompt (>), type telnet
Example:
>telnet XXX.XXX.XXX.XXX
A Telnet session opens for the Transmitter or Receiver and the welcome banner appears.*
5.At the prompt, type the Telnet command (see the table starting on page 92) and press Enter.
* If you are using Windows 7 and receive an error message, you may need to enable Telnet by completing the following: (1) go to
Start / Control Panel / Programs and Features, (2) on the left, select “Turn Windows features on or off,” (3) select the check-boxes
Telnet Client and Telnet Server, and (4) click OK.
followed by a space and the Transmitter or Receiver’s IP address.
To establish a terminal connection via NetLinx Studio:
1.In the Online Tree, select the DXLink unit and right-click to access the short-cut menu.
2.Select Launch Telnet Window via NetLinx Studio.
The Telnet window opens and the welcome banner appears.
3.At the prompt (>), type the Telnet command and press Enter.
Telnet Username and Password
The following commands are used to set the Telnet username and password for a Telnet connection:
Set Telnet Username
Set Telnet Password
By default, both the username and password are blank (empty strings). Performing a factory reset on the device with the
Pushbu tton will return these values to that default. For details, see pa ge 58.
Username – Setting the Username will have no effect if the password remains blank (empty string). That is, defining the
username alone will not result in Telnet prompting for a user login.
Password – Setting the Password will cause Telnet to prompt for a user login, whether the username has been defined or
not. If the username has been defined, this value must be entered.
However, since the password can be set independently of the username, it’s possible to have a password def ined, but the
username still at its default (blank, empty string). In this case do not enter anything for the username when prompted.
Simply press Enter, which will then present the password prompt. Here, the defined password must be entered in order to
successfully open the Telnet session.
Additional Notes
Both the Telnet username and password are case-sensitive.
Three consecutive, unsuccessful attempts to log in to Telnet will cause the Telnet window to close.
Re-launching Telnet will again present the login prompt, with a fresh “batch” of login attempts.
If a Telnet login fail s because of an inc orrect username, an “Invalid Password” message will appear
(as opposed to an “Invalid Username” message).
The username and password are saved after reboot or power cycle.
The username and password are deleted/removed after a factory reset.
NOTE: Enova DGX 100 Series Switchers support Telnet commands and BCS commands over Telnet, while Enova DGX 8/16/32/64
Switchers support BCS tunneling access over TCP/IP. For information, see the applicable manual.
1.Establish a terminal connection via Telnet (see page 90).
2.Type Set Telnet Username, and press Enter.
a. The program will prompt you to enter a new Telnet username; enter a username and press Enter.
b. The program will indicate that the username is being stored.
3.Type Set Telnet Password, and press Enter.
a. The program will prompt you to enter a password; press Enter twice to clear both the Telnet username and password.
b. Enter a password and press Enter.
c. The program will prompt you to re-enter the password; re-enter the password and press Enter.
The program will indicate that the password is being stored.
Telnet Commands
The Telnet commands listed in the table below can be sent directly to the Transmitter or Receiver via a Telnet terminal session.
The default Telnet port is 23. A value of 0 (zero) disables the Telnet server.
Telnet is e nabled by default.
In the terminal program, type Help or a question mark (?) and press Enter to access the Help Menu and display the terminal
commands described in the table below.
Telnet Commands
CommandDescription
? or HelpDisplay the commands listed in this table.
DEVICE STATUSDisplays device status of a specified device, port, system (<D:P:S>).
NOTE: Devices other than the DXLink Transmitter or Receiver itself will be ignored.
7 Ports
Port 1 - Channels:255 Levels:8
MaxStringLen=64 Types=8 bit MaxCommandLen=64 Types=8 bit
The following input channels are on:None
The following output channels are on:None
Level 1=0 Supported data types=UByte,UInt
Level 2=0 Supported data types=UByte,UInt
Level 3=0 Supported data types=UByte,UInt
Level 4=0 Supported data types=UByte,UInt
Level 5=0 Supported data types=UByte,UInt
Level 6=0 Supported data types=UByte,UInt
Level 7=0 Supported data types=UByte,UInt
Level 8=0 Supported data types=UByte,UInt
>
DIPSWITCHDisplays the current value for each of the DIP switch’s four toggles.
Example:
>dipswitch
Dipswitch - ON OFF OFF OFF
>
EXITExit the Telnet session
FACT ORYFWI MAGEResets unit to factory firmware image and reboots DXLink Transmitter or Receiver.
• MSG ON [error|warning|info|debug] sets the terminal program to display log messages generated by the
Master. The level of log printed to the terminal window depends both on the level used when sending the
message and the output level selected with “msg on.”
For example if log output is enabled via “msg on warning” then logs produced at levels AMX_ERROR and
AMX_WARNING will be displayed, but not logs produced at levels AMX_INFO or AMX_DEBUG.
The order of severity from highest to lowest is ERROR, WARNING, INFO, DEBUG.
If no severity is supplied with “msg on,” the default setting is WARNING.
• MSG OFF disables the display.
Example:
> MSG ON
Extended diagnostic information messages turned on.
> MSG OFF
Extended diagnostic information messages turned off.
NDP UNBINDClears the NDP binding to a Master (requires reboot to take effect).
PING [ADDRESS]Pings an address (IP or URL), to test network connectivity to and confirms the presence of another
REBOOTReboots the DXLink Transmitter or Receiver.
RENEW DHCPRenews / releases the current DHCP lease for the DXLink Transmitter or Receiver.
RESET FACTORYResets the device’s stored parameters to factory default state including removal of all security settings,
SEND_COMMAND
[D:P:S,"'command'"]
SEND_STRING
[D:P:S,"string"]
networked device.
The syntax matches the PING application in Windows or Linux.
Example:
>ping 192.168.29.209
192.168.29.209 is alive.
Example:
>REBOOT
Rebooting...
NOTE: Because sending this command can result in the unit acquiring a new DHCP address and the
functionality of the endpoints is dependent on the mated IP addresses of the TX (host) and RX (device),
the USB connection may need to be re-established.
Example:
>RENEW DHCP
resetting to DHCP.
This command will cause an automatic reboot.
NOTE: This command does not reset the device to the factory software image.
Sends the specified SEND_COMMAND (does not work with queries) to the current DXLink Transmitter or
Receiver.
NOTE: Commands cannot be forwarded to other D:P:S. Asynchronous notif ications are available for the
Transmitters via Telnet (and NetLinx Studio).
SET CONNECTIONSets the Master connection settings interactively, allowing the user to specify the mode (for descriptions of
SET DEVICESets the device number, and stores it in non-volatile memory.
SET DNSSets the DNS configuration of the DXLink Transmitter or Receiver, only as applied to Static IP Mode (DNS
SET ETHERNET MODEThis command sets the current LAN configuration settings per new mode.
SET FRIENDLYSet the device’s friendly name for NDP to <name>.
various connection modes, see page 20).
• If the mode is TCP or UDP, the Master URL and port number can be specified as well.
• If Auto is selected, the System number can be specified.
• After all data is entered, if the parameters have changed, the DXLink Transmitter or Receiver will
disconnect from the Master, and begin trying to connect with the new settings.
NOTE: These changes do not require a reboot to take effect.
Syntax:
SET DEVICE <num>
The valid range of device numbers is 0 to 31999.
• If the user enters a number outside that range, then no change will be made and the DXLink Transmitter
or Receiver will issue an error message.
• A Device Number of ‘0’ means that the DXLink Transmitter or Receiver will accept the
auto-assigned device number from the Master.
• If the new device number is different from the old device number, the DXLink Transmitter or Receiver will
disconnect from the Master, and begin trying to connect with the new settings.
NOTE: These changes do not require a reboot to take effect.
settings in DHCP Mode are received from the DHCP server).
Syntax:
SET DNS
This command prompts you to enter a Domain Name, DNS IP #1, DNS IP #2, and DNS IP #3.
Enter Y (yes) to approve/store the information in the Master.
Enter N (no) cancels the operation.
NOTE: The device must be rebooted to enable new settings.
Example:
>SET DNS
-- Enter New Values or just hit Enter to keep current settings - Enter Domain Suffix: amx.com
Enter DNS Entry 1 : 192.168.20.5
Enter DNS Entry 2 : 12.18.110.8
Enter DNS Entry 3 : 12.18.110.7
You have entered: Domain Name: amx.com
DNS Entry 1: 192.168.20.5
DNS Entry 2: 12.18.110.8
DNS Entry 3: 12.18.110.7
Is this correct? Type Y or N and Enter -> Y
Settings written. Device must be rebooted to enable new settings
Syntax:
SET ETHERNET MODE <newmode>
Values for newmode are:
auto
Or
100 full or 10 half
NOTE: This command requires a reboot to enable new settings.
Examples:
set ethernet mode auto
set ethernet mode 100 full
NOTE: See GET ETHERNET MODE.
Syntax:
SET FRIENDLY <name>
• Maximum length = 25 characters. If the name entered exceeds 25 characters, it will be truncated.
• The value is stored in non-volatile memory.
• If no value specified, an automatic name consisting of AMX, the product name, and serial number will be
used.
NOTE: This command requires a reboot to enable new settings.
SET IPSets the IP conf iguration of a specified device.
Enter a Host Name, Type (DHCP or Fixed), IP Address, Subnet Mask, and Gateway IP Address.
IMPORTANT: Host Names may only contain ASCII letters “a” through “z” (not case-sensitive), digits
“0” through “9”, and the hyphen (“-”).
NOTE: DHCP implies “DHCP with link-local fallback”.
NOTE: For NetLinx Masters, the Host Name can only consist of alphanumeric characters.
• Enter Y (yes) to approve/store the information on the Master.
• Enter N (no) to cancel the operation.
NOTE: This command requires a reboot to enable new settings.
Example:
>SET IP
--- Enter New Values or just hit Enter to keep current settings -- Enter Host Name: DXL-RX-36d0110
Enter IP type. Type D for DHCP or S for Static IP and then Enter: DHCP
You have entered: Host Name DXL-RX-36d0110
Type DHCP
Is this correct? Type Y or N and Enter -> y
Settings written. Device must be rebooted to enable new settings.
NOTE: DXLink Modules can also be set to Static IP or DHCP Mode via the front panel
ID Pushbutton.
SET LOCATIONSets the location parameter for NDP.
Syntax:
SET LOCATION <location>
• Maximum length = 25 characters. If the name entered exceeds 25 characters, it will be truncated.
NOTE: This command requires a reboot to enable new settings.
SET TELNET PORTSets the device’s IP port listened to for Telnet connections.
Example:
>SET TELNET PORT
Current telnet port number = 23
Enter new telnet port number (Usually 23)(0 = disable Telnet):
Once you enter a value and press the Enter key, you get the following message:
Setting telnet port number to 23
New telnet port number set, reboot the device for the change to take effect.
NOTE: This command requires a reboot to enable new settings.
IMPORTANT: If you set the Telnet port to “0” to disable it, you will need to reset it with a
SEND_COMMAND in NetLinx Studio (see page 79).
SET TELNET USERNAME
SET TELNET PASSWORD
SHOW CONNECTION LOGShows the Master connection log for the device.
SHOW CONNECTION
STATS
NOTE: This command is supported but is not presently in the Help file list of commands.
Sets the Username for a secure Telnet session.
Default = blank (no username required)
For details, see page 91.
NOTE: This command is supported but is not presently in the Help file list of commands.
Sets the Password for a secure Telnet session.
• Default = blank (no password required)
•For details, see page91.
Shows the connection statistics for the device.
Output similar to the following example:
>show connection stats
Connection Statistics
Total Last 15 Minutes
===== ===============
ICSP Messages: 10039 received 333 received
10038 transmitted 333 transmitted
Blink Messages: 5014 received 166 received
Appendix B - Telnet (Terminal) Commands
IP Statistics:
RX packets:29298 errors:0 discarded:0
TX packets:15286 errors:0 discarded:0
SHOW VS100 STATSDisplays DXLink transport information (MSE values, length, etc.).
WDQueries/enables/disables the Offline Recovery Mechanism (for complete information see page 54).
IMPORTANT: A reboot is required after setting the recovery mechanism before the new setting takes
effect.
Syntax:
WD
Queries the module for the setting of the Offline Recovery Mechanism.
WD ON
Sets the recovery mechanism to ON.
WD OFF
Sets the recovery mechanism to OFF (default).
Master Connection Modes
The mode of communication used for connection to the Master is specified via the SET CONNECTION Telnet command (see
page 95).
Connection mode setting options are AUTO, TCP URL, UDP URL, or NDP (default) as described:
AUTO – This mode utilizes TCP communication. It looks for a matching System Number and attempts to come online with
the first Master it sees with that System Number.
TCP URL – TCP; the Master is specified via URL.
UDP URL – UDP; the Master is specified via URL.
NDP – UDP; this mode utilizes the NDP binding process to assign the DXLink Module (the physical device) to a Master
(or Virtual Master) via NetLinx Studio. Once bound, communications are conducted via UDP.
NOTE: In URL modes, the Master can use either an IP address or a DNS name.
Guidelines
UDP mode is recommended for the following types of installations:
Small-to-medium residential and corporate installations on a single subnet
Segmented control network installations (control network is a separate switching domain and subnet from other network
equipment)
Installations with the total number of NetLinx / ICSNET devices on a single Master exceeding 128
TCP mode is recommended for installations where (a) the switching domain of the network is subject to “bursty” traff ic or heavy
streaming activity (>20 Mbps consumption by streaming) and where (b) the total number of NetLinx / ICSNET devices on a single
Master is less than 128.
TCP vs. UDP
TCP – Protocol has a built-in retry mechanism.
UDP – Protocol does not have a built-in retry mechanism, but consumes fewer resources on the Master. AMX’s UDP
implementation of NetLinx employs a retry mechanism to provide the reliability of TCP with the resource efficiency of UDP.
Determining which connection method to use for Master Connection Mo de is essentially a matter of decidin g wh at i nfo rmation the
device should use to identify the correct Master to connect to.
The defa ult mode is NDP ; the mode c an be changed via the SET CONNECTION Telnet command (see page 95).
URL – The device connects to the Master with the specified URL. The device must be configured with the URL of a specific
Master via the SET CONNECTION Telnet command (see page 95).
NDP – The device connects to the Master it’s been bound to, which is based on the Master’s MAC address. The binding is
configured via NetLinx Studio. Once bound, the device must be unbound using either NetLinx Studio or the Telnet
NDP UNBIND command before being re-bound to a different Master.
Alternatively, NDP devices can be bound/unbound via options on the Master’s Web Configuration pages (System > Manage
NetLinx). For details, refer to the WebConsole & Programming Guide – NX-Series Controllers (System - Manage NetLinx
section).
Auto – The device connects to the f irst Master it finds with the specif ied System Number.
The device must be configured with the desired system number via the SET CONNECTION Telnet command (see page 95).
Use of this method requires that only one Master has any particular system number and is visible to the subnet. If this is the case,
then Auto is the simplest choice. However, with Auto, you are not hard-bound to a particular Master. Therefore, if at some point in
the future, another Master is configured with the same system number, the result is that the DXLink Module could show up on that
other Master.
Notes on Specific Telnet Clients
Telnet and terminal clients exhibit different behaviors in some situations. This section states some of the known anomalies.
Windows Client Programs
Anomalies occur when using a Windows® client if you are not typing standard ASCII characters (i.e., using the keypad and the Alt
key to enter decimal codes). Most programs will allow you to enter specific decimal codes by holding Alt and using keypad numbers.
Example
For example, hold Alt, hit the keypad 1, then hit keypad 0, then release Alt. The standard line feed code is entered (decimal 10).
Windows will perform an ANSI to OEM conversion on some codes entered this way because of the way Windows handles languages
and code pages.
The following codes are known to be altered, bu t others may be affected depending on the computer’s setup.
Characters 15, 21, 22, and any characters above 127.
This affects both Windows Telnet and Terminal programs.
Linux Telnet Client
The Linux Telnet client has three anomalies that are known at this time:
A null (\00) character is sent after a carriage return.
If an “Alt 255” is entered, two of the “255” characters are sent (per the Telnet RAFT).
If the code to return to Command mode is entered (Alt 29 which is CTRL+]), the character is not sent, but the Telnet
A Virtual NetLinx Master can be created using your PC, which allows NetLinx Studio to facilitate direct file transfers to a DXLink
Transmitter or Receiver when a Master is not available.
Four basic procedures must be completed for Virtual Master file transfers:
Set the PC to a static IP address (see below).
Create a Virtual Master in NetLinx Studio (see page 100).
Prepare the DXLink Transmitter or Receiver by placing it in Static IP Mode, assigning a device ID, and setting the connection
type to TCP (see page 101).
Transfer the files using a Virtual Master TCP/IP connection (for IRL file transfers, see page 60; for Firmware file transfers,
see page 86).
Setting PC to Static IP Address
IMPORTANT: When you change the PC’s settings to a static IP address, the address must be in the same subnet as the DXLink unit
(the default static IP address for DXLink Transmitters and Receivers is 192.168.1.2).
Important Information for PCs with Multiple Network Access Points
If the PC has more than one point of network access (multiple NIC cards or wireless networking), check to see if one of the
connections uses an IP address of 192.168.1.x before proceeding.
To check for mu l t i p l e netwo r ks:
1.Open the PC’s Start menu (at the lower left of the desktop on the Taskbar) and select Run.
2.Enter cmd and click OK.
3.At the prompt, enter ipconfig /all and press the Enter key.
4.Check the IP Addresses under Connection.
Appendix C - Virtual NetLinx Master
If the PC or Laptop is currently using a connection with an IP address of 192.168.1.x, you will need to disconnect the connection.
To disconnect a network connection:
1.Modem: From the Start menu on the desktop taskbar, select Settings \ Network Connections.
Wireless: From the Start menu on the desktop taskbar, select Control Panel \ Network and Internet \ Manage Wireless
Networks.
2.Right-click the network connection and select Disable.
NOTE: The following procedure uses the most current version of Windows available at the time of publication.
To set a PC to Static IP Mode:
1.From the Start menu on the desktop taskbar, select Control Panel / Network Sharing Center.
2.Click “Change adapter settings” (top left).
3.Right-click on Local Area Connection and select Properties.
The Local Area Connection Properties dialog box opens.
Click to open the
Communication Settings
dialo g box
4.From the list of “This connection uses the following items” (see previous step), highlight Internet Protocol Version 4
(TCP/IPv4) and click Properties.
The Internet Protocol Version 4 (TCP/IPv4) Properties dialog box opens.
5.Select “Use the following IP address” and enter 192.168.1.50 (or the IP range of the Enova DGX or Enova DVX).
6.Press the Tab key on your keyboard to auto-f ill the Subnet mask field.
7.Click OK and click Close.
IMPORTANT: When finished using the PC as a Virtual Master, change the setting in the dialog box shown in Step 4 back to “Obtain an
IP address automatically.”
Creating a Virtual Master
To create a Virtual Master in NetLinx Studio:
1.Open NetLinx Studio.
2.From the Settings menu, select Workplace Communication Settings.
3.Click the Default Settings button.
The Communication Settings dialog box opens.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.