Amtrol BoilerMate RTR, WH-7, BoilerMate Top Down, WH-9 User Manual

Page 1
INSTALLATION, OPERATION
West Warwick, Rhode Island 02893
& MAINTENANCE
INSTRUCTIONS
BOILERMATE
INDIRECT-FIRED WATER HEATERS
®
MODELS COVERED:
• WH-7 & 9 Classic Series
• Top Down
• RTR models
• WHS Premier Series
TD Series
MODELS CODES:
P: Packaged with circulator & Smart Control L: Less Circulator, with Smart Control Z: Dial Aquastat C: High-output commercial exchanger DW: Double-wall heat exchanger RTR: Pre-piped and wired
INSTALLER: LEAVE THIS MANUAL WITH THE OWNER
IMPORTANT GENERAL SAFETY INFORMATION - ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
READ CAREFULLY THE PRODUCT INSTALLATION, OPERATING AND MAINTENANCE MANUAL. FAILURE
FATAL INJURY AND/OR PROPERTY DAMAGE, AND WILL VOID THE PRODUCT WARRANTY. THIS PRODUCT MUST BE INSTALLED BY A QUALIFIED PROFESSIONAL. FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS, IN THE ABSENCE OF SUCH CODES, FOLLOW THE CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE, AS APPLICABLE.
THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS. OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL
INJURY AS WELL AS PROPERTY DAMAGE.
Part #: 9040-586 (07/08)
TO FOLLOW THE INSTRUCTIONS AND WARNINGS IN THE MANUAL MAY RESULT IN SERIOUS OR
The heat transfer medium must be water or other nontoxic fluid having a toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial Products, 5th edition. The pressure of the heat transfer medium must be limited to 30 PSIG by an approved safety or relief valve.
Page 2
1. TABLE OF CONTENTS
2. Pre-Installation Checklist .................................................
3. Required Components and Accessories Checklist .........
4. WH-7 & 9 Classic Series Piping Installation ....................
5. Top Down™ TD-Series Piping Installation ......................
6. Ready-To-Run RTR-Series Piping Installation ................
7. WHS Premier Series Piping Installation ........................
8. Wiring All Smart Control™ Models ...............................
9. Wiring All Dial Control Models (Except RTR Models) .........
2
3
4
6
8
10
12
20
2. PRE-INSTALLATION CHECKLIST
IMPORTANT STEPS AND DECISIONS REQUIRED BEFORE INSTALLATION
M THIS PRODUCT MUST BE INSTALLED AND
MAINTAINED BY A LICENSED PROFESSIONAL. IN ADDITION TO THE INSTRUCTIONS IN THIS MANUAL, FOLLOW ALL APPLICABLE LOCAL AND STATE CODES OR IN THE ABSENCE OF SUCH CODES, THE CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND THE NATIONAL ELECTRIC CODE.
M DRIP PAN AND DRAIN: This appliance should not
be installed in an area where leakage of the tank or connections can result in damage to the area adjacent to the appliance or to lower floors of the structure. When such locations cannot be avoided, a suitable drain pan, adequately drained and kept clear, must be installed under the appliance.
M CAUTION: Determine whether your water is corrosive
or acidic, and that there are no suspended solids, toxic or other substances or abnormally high chlorine levels in the water that could damage or affect the BOILERMATE
MODELS. Glycol is a hazardous substance. To avoid seepage or leakage of glycol to surfaces where humans or animals can ingest it, use glycol only in double-walled units, so that any leaks will most likely be released to the atmosphere. However, a leak to a surface area may still occur, so any use of glycol must be monitored closely and humans and animals should be protected from contact with the unit.
or other space heating units or elements. Any contaminants in the baseboard units will contaminate the potable water in the BOILERMATE® and also adversely affect its performance.
M Wiring Options. Select either a Non-Priority or Priority
System:
Two options are available when wiring the controls of the BOILERMATE distribution elements).
1. Non-Priority System - The controls of the BOILERMATE zone with a standard zone valve or a separate circulator dedicated to the BOILERMATE
NOTICE: In this non-priority option, the BOILERMATE will be supplied just as another zone. This means that if all space heating zones call for hot boiler water at the same
®
or the rest of your plumbing system.
USE GLYCOL ONLY WITH DOUBLE-WALLED HEAT EXCHANGER
Do not connect the BOILERMATE® domestic supply with baseboard
®
in the space heating system (boiler and
®
must be wired as a separate heating
®
“zone”.
®
10. Wiring All Ready-To-Run (RTR) Models .......................
11. Startup Procedure For All Models ................................
12. Setting the Smart Control™ ..........................................
13. Troubleshooting .............................................................
14. Replacement Parts ........................................................
15. Cleaning the BoilerMate® Heat Exchanger ...................
16. General Safety Information ...........................................
time, the BOILERMATE
®
may not be supplied with enough
23
25
26
27
28
29
30
hot boiler water to “recover” adequately. The delivery of domestic hot water will be diminished. In many, but not all cases, this is not a problem because the routine oversizing of boiler output is adequate for both loads.
2. Priority System - Under this wiring option the BOILERMATE
®
will be supplied before space heating.
In limited circumstances, space
heating can be lost in the home in this priority mode. Any demand for space heating is postponed until the BOILERMATE
®
has reached its set temperature. This delay in supplying the space heating zones is usually not noticed by the inhabitants of the living spaces. However, in the event of certain malfunctions such as circulator or thermostat failure, space heating could be delayed indefinitely. If undetected and uncorrected, freezing damage to piping could result.
M Select Circulator versus Zone Valve
The flow of hot boiler water to the BOILERMATE
®
can
be controlled with either a motorized zone valve or a circulator.
1. Separate circulator. The recommended way to provide adequate flow through the BOILERMATE
®
heat exchanger is to use a separate dedicated circulator with a minimum flow rate of 5 gpm. This option may be used even though the heating system utilizes zone valves.
2. Zone valve (system flow of 4-8 gpm). If a zone valve is to be used, a minimum flow rate of 5 gpm with all zones in use is required. A full-port zone valve should be used.
M All installations require a low-water cut-off or automatic fill
valve on your boiler system to reduce the risk of boiler water
loss.
M Steam boiler installations require a low-water cut-off which
is also required by most codes.
M Installation of a vacuum breaker is required to prevent
damage to the BOILERMATE
®
when drained. There must be no valves installed between the vacuum breaker and BOILEMATE®.
-2-
Page 3
3. REQUIRED COMPONENTS AND ACCESSORIES CHECKLIST
SHUTOFF VACUUM RELIEF THERMAL EXPANSION
MODEL CIRCULATOR ZONE VALVE* VALVE BREAKER VALVE TANK DRAIN
Residential = 5GPM *If Circulator not used Required
WH SERIES Commercial = 10GPM 3/4” Full Port 4 1 Included (See Therm-X-Trol® Included Except “P” Models or 1” STD Sizing Guide)
5GPM *If Circulator not used Required TD SERIES Except “P” Models 3/4” Full Port 4 1 Included (See Therm-X-Trol® Included or 1” STD Sizing Guide)
Required RTR SERIES Included N/A 4 1 Included (See Therm-X-Trol® Included Sizing Guide)
Residential = 5GPM *If Circulator not used Required WHS SERIES Commercial = 10GPM 3/4” Full Port 4 1 Included (See Therm-X-Trol® Included Except “P” Models or 1” STD Sizing Guide)
ALL INSTALLATIONS REQUIRE TEFLON® SEALING TAPE OR PIPE DOPE FOR THREADED JOINTS. SEE HEAT EXCHANGER PRESSURE DROP CHART TO DETERMINE PUMP HEAD REQUIREMENTS.
Use this chart to select the proper circulator for your BOILERMATE®.
If a steel hydropneumatic tank is in place, AMTROL® recommends replacing it with a
properly sized EXTROL heat transfer problems can occur by causing air to be trapped in the heat exchanger. If the boiler system has an EXTROL EXTROL
®
or Radiant EXTROL® expansion tank and the boiler temperatures are being changed, resize the
®
or Radiant EXTROL® expansion tank.
®
or Radiant EXTROL® expansion tank. Otherwise, significant
-3-
Page 4
4. WH-7 & 9 CLASSIC SERIES PIPING INSTALLATION
DOMESTIC WATER PIPING
1. Thread the included 3/4” brass tee onto the pipe marked COLD WATER.
2. Screw the
tee.
3. Connect the cold water supply to the remaining port on the brass tee.
4. Temporarily attach the top tee fitting (with o-ring face seal) to the union nut on top of the tank. Test fit the piping near the tee before soldering. Remove the tee before soldering connections to avoid damage to the top o-ring seal or plastic liner.
Note: Do not solder piping within 24 inches of the top tee fitting while attached to the tank.
5. Make an 8-inch “heat trap” as shown in the diagram. This will reduce standby losses from heat migrating up the piping. Continue this line to the domestic hot water system.
6. Install the included T&P relief valve on the top port of the top tee connection. Plumb a blowdown tube to within 6 inches of a floor drain or as directed by plumbing code.
7. When all domestic water piping is complete, open the cold water supply and allow some water to enter the tank. Look and listen for signs of leaks and repair as necessary before continuing.
Note: If installing on a city supply, ensure a dedicated Thermal Expansion tank (Therm-X-Trol used.
3
/4” drain valve into the opposite end of the brass
®
or equivalent) is
BOILER PIPING
1. Plumb the circulator or zone valve on the BOILER SUPPLY line. If using a separate circulator, the pump flange can be mounted directly to the threaded pipe marked BOILER SUPPLY. Alternately, the circulator can be placed anywhere on the boiler supply line.
2. Pipe the BOILER RETURN connection to the boiler return
line.
Be sure the return line is NOT
any heating circulators. This may require moving the heating circulator off the boiler tapping on packaged boilers. Failure to do so will result in overheating and tank damage when the heating system is in operation.
3. Install a weighted flow check on the boiler return line. This
is not necessary on systems utilizing a zone valve to control the BoilerMate® temperature.
4. After completing the boiler piping, slowly open the boiler fill valve and pressurize the BoilerMate® loop. Check for leaks and repair as necessary. Proceed to the appropriate wiring section in this manual.
required with the BoilerMate forth in the THERM-X-TROL
Clearance From Combustible Surfaces
LEFT SIDE ............1”
RIGHT SIDE ...........1”
TOP .................9”
Recommended Clearance For Servicing
LEFT .................12”
RIGHT................12”
FRONT ...............30”
plumbed to the suction side of
If installing on city water supply a properly sized THERM-X-TROL
®
and should be installed as set
®
product installation manual.
®
is
REAR ................1”
FLOOR ...............0”
FRONT ...............1”
HEAD ROOM ..........9”
REAR ................1”
HOT WATER OUTLET
BOILER RETURN (Top Left)
BOILER SUPPLY (Top Right)
COLD WATER INLET (Bottom Center)
T&P RELIEF VALVE
UNION NUT
-4-
Page 5
PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED)
PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR
-5-
Page 6
5. TOP DOWN™ TD-SERIES PIPING INSTALLATION
DOMESTIC WATER PIPING
1. Connect the cold water supply to the pipe labeled COLD WATER
2. Connect the HOT WATER piping to the domestic hot water system.
3. Make an 8-inch “heat trap” on the HOT WATER outlet as shown in the diagram. This will reduce standby losses from heat migrating up the piping.
4. When all domestic water piping is complete, open the cold water supply and allow some water to enter the tank. Look and listen for signs of leaks and repair as necessary before continuing.
Note: If installing on a city supply, ensure a dedicated Thermal Expansion tank (Therm-X-Trol
®
or equivalent) is
used.
5. Install a blowdown tube on the T&P relief valve outlet. Plumb to within 6 inches above a floor drain or as directed by plumbing code.
BOILER PIPING
1. Plumb the circulator or zone valve on the BOILER SUPPLY line. If using a separate circulator, the pump flange
can be mounted directly to the threaded pipe marked BOILER SUPPLY. Alternately, the circulator can be placed anywhere on the boiler supply line.
2. Pipe the BOILER RETURN connection to the boiler return
line.
Be sure the return line is NOT
plumbed to the suction side of any heating circulators. This may require moving the heating circulator off the boiler tapping on packaged boilers. Failure to do so will result in overheating and tank damage when the heating system is in operation.
3. Install a weighted flow check on the boiler return line. This
is not necessary on systems utilizing a zone valve to control the BoilerMate
4. After completing the boiler piping, slowly open the boiler fill valve and pressurize the BoilerMate
®
temperature.
®
loop. Check for leaks and repair as necessary. Proceed to the appropriate wiring section in this manual.
If installing on city water supply a
properly sized THERM-X-TROL required with the BoilerMate forth in the THERM-X-TROL
®
and should be installed as set
®
product installation manual.
®
is
Clearance From Combustible Surfaces
LEFT SIDE ............1”
RIGHT SIDE ...........1”
TOP .................9”
COLD WATER INLET (Top Center)
BOILER SUPPLY (Bottom Right)
BOILER RETURN (Bottom Left)
REAR ................1”
FLOOR ...............0”
FRONT ...............1”
Recommended Clearance For Servicing
LEFT .................12”
RIGHT................12”
HEAD ROOM ..........9”
REAR ................1”
FRONT ...............30”
T&P RELIEF VALVE OUTLET
HOT WATER OUTLET
-6-
DRAIN VALVE
Page 7
PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED)
PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR
-7-
Page 8
6. READY-TO-RUN RTR-SERIES PIPING INSTALLATION
DOMESTIC WATER PIPING
1. Connect the cold water supply to the pipe labeled COLD WATER.
2. Connect the HOT WATER piping to the domestic hot water system.
3. Make an 8-inch “heat trap” on the HOT WATER outlet as shown in the diagram. This will reduce standby losses from heat migrating up the piping.
4. When all domestic water piping is complete, open the cold water supply and allow some water to enter the tank. Look and listen for signs of leaks and repair as necessary before continuing.
Note: If installing on a city supply, ensure a dedicated Thermal Expansion tank (Therm-X-Trol used.
5. Install a blowdown tube on the T&P relief valve outlet. Plumb to within 6 inches above a floor drain or as directed by plumbing code.
COLD WATER INLET
T&P RELIEF VALVE
HOT WATER OUTLET
OUTLET
®
or equivalent) is
BOILER PIPING
1. Plumb the BOILER SUPPLY line. The circulator and flow check are factory installed
2. Pipe the BOILER RETURN connection to the boiler return
line.
Be sure the return line is NOT
heating circulators. This may require moving the heating circulator off the boiler tapping on packaged boilers. Failure to do so will result in overheating and tank damage when the heating system is in operation.
3. After completing the boiler piping, slowly open the boiler fill
valve and pressurize the heat exchanger loop. Check for leaks and repair as necessary. Proceed to the appropriate wiring section in this manual.
required with the BoilerMate forth in the THERM-X-TROL
Clearance From Combustible Surfaces
LEFT SIDE ............1”
RIGHT SIDE ...........1”
TOP .................9”
Recommended Clearance For Servicing
LEFT .................12”
RIGHT................12”
FRONT ...............30”
CIRCULATOR
plumbed to the suction side of any
If installing on city water supply a properly sized THERM-X-TROL
®
and should be installed as set
®
product installation manual.
REAR ................1”
FLOOR ...............0”
FRONT ...............1”
HEAD ROOM ..........36”
REAR ................1”
BOILER SUPPLY
BOILER RETURN
®
is
DRAIN VALVE
TOP VIEW
SIDE VIEW
-8-
Page 9
PIPING MODELS WITH PRE-INSTALLED CIRCULATOR W/INTEGRAL FLOW CHECK
-9-
Page 10
7. WHS PREMIER SERIES PIPING INSTALLATION
DOMESTIC WATER PIPING
1. Thread the included brass tee onto the pipe marked COLD WATER.
2. Screw the drain valve into the opposite end of the brass
tee
3. Connect the cold water supply to the remaining port on the brass tee
4. Thread the included T&P Safety Relief Valve into the offset
3
/4” port on the top plate. Install a blowdown tube to within
6 inches of a floor drain or as directed by plumbing code.
5. Connect the center hot water outlet port on the top plate to the domestic hot water system.
6. Make an 8-inch “heat trap” as shown in the diagram. This will reduce standby losses from heat migrating up the piping.
7. When all domestic water piping is complete, open the cold water supply and allow some water to enter the tank. Look and listen for signs of leaks and repair as necessary before continuing.
Note: If installing on a city supply, ensure a dedicated Thermal Expansion tank (Therm-X-Trol used.
®
or equivalent) is
BOILER PIPING
1. Plumb the circulator or zone valve on the BOILER SUPPLY line. If using a separate circulator, the pump flange can be mounted directly to the threaded pipe marked BOILER SUPPLY. Alternately, the circulator can be placed anywhere on the boiler supply line.
2. Pipe the BOILER RETURN connection to the boiler return
line.
Be sure the return line is NOT
heating circulators. This may require moving the heating circulator off the boiler tapping on packaged boilers. Failure to do so will result in overheating and tank damage when the heating system is in operation.
3. Install a weighted flow check on the boiler return line. This
is not necessary on systems utilizing a zone valve to control the BoilerMate
4. After completing the boiler piping, slowly open the boiler fill valve and pressurize the BoilerMate and repair as necessary. Proceed to the appropriate wiring section in this manual.
required with the BoilerMate forth in the THERM-X-TROL
plumbed to the suction side of any
®
temperature.
®
loop. Check for leaks
If installing on city water supply a properly sized THERM-X-TROL
®
and should be installed as set
®
product installation manual.
®
is
Clearance From Combustible Surfaces
LEFT SIDE ............1”
RIGHT SIDE ...........1”
TOP .................9”
BOILER SUPPLY (Top Right)
REAR ................1”
FLOOR ...............0”
FRONT ...............1”
HOT WATER OUTLET
BOILER RETURN (Top Left)
Recommended Clearance For Servicing
LEFT .................12”
RIGHT................12”
HEAD ROOM ..........36”
REAR ................1”
FRONT ...............30”
T&P RELIEF VALVE
COLD WATER INLET
(Bottom Center)
-10-
Page 11
PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED)
PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR
-11-
Page 12
8. WIRING ALL SMART CONTROL™ MODELS
Normally Open Close on call for hot water Post-Purge function Pre-Purge function
Normally Open Close on call for hot water
Normally Closed Open on call for hot water Priority function
Constant 24VAC or 120VAC
Power In
{
{
{
{
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
The Smart Control™ incorporates all the switching and temperature control functions necessary to control the BoilerMate™. The diagram below shows internal wiring and the associated functions.
After wiring is complete, insert the white thermistor (sensor) plug into the receptacle at the base of the Smart Control™. Select the plug marked CIRCULATOR or ZONE VALVE based on the application. Zone valves can be slow actuating. Therefore, the zone valve sensor contains a built-in temperature offset to account for the time it takes the zone valve to fully close. This results in potable water temperature that is representative of the Smart Control™ temperature set point. This is why it is important to install the correct sensor into the Smart Control™. See Page 2 for information regarding the selection of a circulator or zone valve.
-12-
Page 13
1
2
T
T
L1 L2
L8124 A & C
ZC
ZR
B2
C1
B1
C2
BOILERMATE
®
CIRCULATOR
BOILERMATE
®
JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
HONEYWELL L8124 A & C
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
BOILERMATE
®
JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
HONEYWELL L8124 B & D
BOILERMATE
®
CIRCULATOR
L1 L2
L8124 B & D
B1
B2
C1
C2
2 1
B
R
B
R
W
T
T
HIGH LIMIT
LOW LIMIT/
CIRCULATOR
L8148A
HONEYWELL L8148A
BOILERMATE
®
JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
BOILERMATE
®
CIRCULATOR
L1 L2
T
T
L1
L2
HIGH LIMIT
R
B
C1
C2
B1
B2
3
-13-
Page 14
HONEYWELL L8148 J
WITH MILLIVOLT GAS VALVE
BOILERMATE
®
JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
BOILERMATE
®
CIRCULATOR
L1
L2
L8148J
C1 C2
L1 L2 B1
B2 B3
B
R
T
W TV
TP
Z
HI
LIMIT
HONEYWELL L8148 J
WITH 24 VOLT GAS VALVE
BOILERMATE
®
JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
BOILERMATE
®
CIRCULATOR
L1
L2
L8148J
C1 C2
L1 L2 B1
B2 B3
B
R
T
W TV
TP
Z
HI
LIMIT
WHITE - RODGERS 8J48A
WITH 24 VOLT GAS VALVE
8J48A
BOILERMATE
®
JUNCTION BOX
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
B1
B2
TV
W
T
TP
Z
B
C1
C2
L2
L1
B3
-14-
Page 15
WHITE - RODGERS 8J48A
WITH SELF-GENERATING GAS VALVE
8J48A
BOILERMATE
®
JUNCTION BOX
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
B1
B2
TV
W
T
TP
Z
B
C1
C2
L2
L1
B3
L8124 A & C
2
1
ZC
ZR
B2
B1
C2
C1
T
T
BOILERMATE
®
CIRCULATOR
PRIORITY WIRING
HONEYWELL L8124 A & C
L1 L2
BOILERMATE
®
JUNCTION BOX
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
HEATING
CIRCULATOR
PRIORITY WIRING
HONEYWELL L8124 B & D
BOILERMATE
®
JUNCTION BOX
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
BOILERMATE
®
CIRCULATOR
L8124 B & D
L1
L2
2
1
B1
B2
C2
C1
T
B
B
R
R
W
T
HIGH
LIMIT
LOW LIMIT/
CIRCULATOR
HEATING CIRCULATOR
-15-
Page 16
BOILERMATE
®
CIRCULATOR
BOILERMATE
®
JUNCTION BOX
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
L8148A
L2
L1
C1
C2
B1
B2
3
T
B
R
T
L1 L2
PRIORITY WIRING
HONEYWELL L8148A
HIGH LIMIT
PRIORITY WIRING
HONEYWELL L8148B
B
R
HIGH LIMIT
BOILERMATE
®
CIRCULATOR
BOILERMATE
®
JUNCTION BOX
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
L1 L2
L2
L1
T
T
C1
C2
B1
B2
L8148B
PRIORITY WIRING
HONEYWELL L8148 J
WITH 24 VOLT GAS VA LVE
BOILERMATE
®
JUNCTION BOX
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
L8148J
HI
LIMIT
T
TV W
TP
Z
B
B1
B2
C1
C2
L2
L1
B3
R
BOILERMATE
®
CIRCULATOR
L1
L2
-16-
Page 17
PRIORITY WIRING
HONEYWELL L8148 J
WITH MILLIVOLT GAS VALVE
L8148J
BOILERMATE
®
CIRCULATOR
BOILERMATE
®
JUNCTION BOX
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
HI
LIMIT
T
TV
W
TP
Z
B
B1
B2
C1
C2
L2
L1
B3
R
L1
L2
PRIORITY WIRING
WHITE-RODGERS 8J48A
WITH 24VOLT GAS VALVE
BOILERMATE
®
CIRCULATOR
BOILERMATE
®
JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
TV
W
T
TP Z
B
B1
B2
B3
L1
L2
C1
C2
8J48A
HEATING
CIRCULATOR
PRIORITY WIRING
WHITE-RODGERS 8J48A
WITH SELF-GENERATING GAS VALVE
BOILERMATE
®
CIRCULATOR
BOILERMATE
®
JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
WHITE
BLACK
TV
W
T
TP Z
B
B1
B2
B3
L1
L2
C1
C2
8J48A
HEATING
CIRCULATOR
-17-
Page 18
T T
X X
Boiler Aquastat
Zone Outputs
Priority or
DHW Zone
Thermostat
Inputs
Typical Multi-Zone Relay
Utilizing Post-Purge Feature
Smart Control™
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
BLACK
WHITE
L1 L2
120V
Supply
BoilerMate
®
Circulator
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
Typical Multi-Zone Relay
24V without Post-Purge Feature
T T
X X
Boiler Aquastat
Zone Outputs
Priority or
DHW Zone
Thermostat
Inputs
ORANGE
ORANGE
BLUE
BLUE
VIOLET
VIOLET
BLACK
WHITE
BoilerMate
®
Circulator
24V
Supply
Smart Control™
(PLACE A WIRE NUT OVER EACH WIRE NOT USED)
-18-
Page 19
Water
Sensor
Plug
WATER SENSOR INSTALLATION (IF EQUIPPED)
The Smart Control™ features an error code designed to alert the user to the presence of water on the oor. This is useful to warn of a leaking boiler, water heater, etc., or to alert the owner to a leak in the basement. If equipped with the optional water sensor, follow the installation instructions below:
1. If the sensor will be used to detect a water heater leak, the proper placement is in a drip pan as required in the warning section of this manual. This will both protect the surrounding surfaces from water damage and provide sufficient water depth to activate the alarm. The sensor will function with either side placed toward the floor.
2. If the sensor will be used to detect another potential leak source, such as basement flooding, the sensor must be placed on a flat section of floor in an area where water will first collect. If the level cannot reach 1/32”, the alarm feature may not function. Do not place in a high-traffic area where the sensor could be stepped on or moved. The sensor will function with either side placed toward the floor.
3. After placing the sensor in the appropriate location, plug the water sensor connector into the Smart Control™.
4. Upon wiring the Smart Control™, test the sensor by either immersing it in water or inserting a coin between the two electrodes. The Smart Control should display Er4 and sound an alarm. The error and alarm should disappear when the sensor is dried or the coin is removed. Perform this test during the annual inspection of the BoilerMate in an area known to flood.
5. This sensor should not be the primary means of leak detection.
®
, or more frequently if installed
U.S. Patent Pending 11/948,493 and other patents pending.
-19-
Page 20
9. WIRING ALL DIAL CONTROL MODELS
CAPILLARY TUBE
SENSOR BULB
SHAFT
WIRE LEADS
(EXCEPT RTR MODELS)
Dial Control models utilize a standard dry-contact aquastat with capillary temperature sensor. The dial control contains a make-and-break switch and is suitable for 24V or 120V, 25A Max.
To wire Dial Control models, select the appropriate diagram from the following pages. If a suitable diagram is not available for your application, please contact AMTROL Tech Support at (401)535-1216. Always disconnect power before wiring the control. Ensure that the proper conduit and connectors are used per your local code. In lieu of local code, the National Electric Code should be followed.
SEPARATE CIRCULATOR SEPARATE CIRCULATOR
-20-
Page 21
T T
X X
Boiler Aquastat
Zone Outputs
Priority or
DHW Zone
Thermostat
Inputs
Typical Multi-Zone Relay
BoilerMate
®
Circulator
BoilerMate® Thermostat
ZONE VALVES - SCHEMATIC 3
3-WIRE ZONE VALVES
PRIORITY W/CIRCULATORS - SCHEMATIC 4
-21-
Page 22
BOILER CONTROL - SCHEMATIC 5
ORANGE ORANGE
BLUE BLUE
VIOLET
VIOLET
BLACK WHITE
SMART CONTROL™ JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED IN THE AMTROL BOILER MATE
®
JUNCTION BOX.)
TRANSFORMER
4 WIRE ZONE VALV E
L1
L2
40VA
24 VOLT
L1
L2
NOTE: TAKE L1 AND L2 OFF THE BOILER CONTROL
"T"
"T"
(ON BOILER CONTROL)
END SWITCH
MOTOR
ORANGE
1
ORANGE
BLUE BLUE
VIOLET
VIOLET
BLACK WHITE
SMART CONTROL™ JUNCTION BOX
(PLACE A WIRE NUT OVER EACH WIRE NOT USED IN THE AMTROL BOILER MATE
®
JUNCTION BOX.)
TRANSFORMER
3 WIRE ZONE VALV E
2
3
L1
L2
40VA
110v
L1
L2
"T"
"T"
(ON BOILER CONTROL)
24 VOLT
NOTE: TAKE L1 AND L2 OFF THE BOILER CONTROL
HONEYWELL L8148E
-22-
Page 23
DHW AQUASTAT
FACTORY WIRED
LINE OUT
CANCELS ON
CALL FOR DHW
DRY CONTACT
TO BOILER OR
EXTERNAL RELAY
LINE IN
LIVE
NEUT
PR
OUT
PR
IN
CIRCULATOR RELAY OPERATION
1234
HONEYWELL L8148A OR SIMILAR W/120V HIGH LIMIT
CIRCULATOR RELAY BOX
LIVE
NEUT
PR
OUT
PR
IN
1234
L1 L2 TT
HIGH LIMIT
INPUT
C1 C2
L1
L2
Indirect
Aquastat
10. WIRING ALL READY-TO-RUN (RTR) MODELS
Ready-To-Run models include a circulator with built-in priority zoning relay. The aquastat is pre-wired and controls the circulator. Line voltage must be supplied and a signal wire must be run to fire the boiler.
To wire RTR models, select the appropriate diagram from the following pages. If a suitable diagram is not available for your application, please contact AMTROL Tech Support at (401)535-1216. Always disconnect power before wiring the unit. Ensure that the proper conduit and connections are used per your local code. In lieu of local code, the National Electric Code should be followed.
-23-
Page 24
CIRCULATOR RELAY BOX
1 234
C1 C2
Indirect
A
quastat
LIVE
NEUT
PR
OUT
PR
IN
L1
L2
L1 L2
TT
HEATING
CIRCULATOR
REMOVE JUMPER
BETWEEN 1 & 3
3
HONEYWELL L8148A OR SIMILAR W/PRIORITY
CIRCULATOR RELAY BOX
LIVE
NEUT
PR
OUT
PR
IN
1234
L1
L2
Indirect
A
quastat
L1
L2
B2
B
HONEYWELL L8148J W/MILLIVOLT GAS VALV E
WHITE RODGERS 8J48A W/24V GAS VALV E
CIRCULATOR RELAY BOX
Indirect
A
quastat
L2
LIVE
NEUT
PR
OUT
PR
IN
3
4
2
1
L1
L2
L1
B
W
CIRCULATOR RELAY BOX
Indirect
A
quastat
L2
LIVE
NEUT
PR
OUT
PR
IN
3
4
2
1
L1
MULTI-ZONE
CONTROL
PRIORITY
ZONE
THERMOSTATS
ZONE OUTPUTS
T TT T
T T
TYPICAL MULTI-ZONE CONTROL
-24-
Page 25
11. STARTUP PROCEDURE FOR ALL MODELS
1. PURGE HEAT EXCHANGER: The heat exchanger should be free of large air pockets to allow the circulator to operate properly. Using the diagram below as a guide, isolate the boiler return line and flush the loop until large air pockets are purged. After this, the air elimination equipment will collect smaller air bubbles to maximize efficiency.
2. FILL TANK: Open the hot water fixture furthest from the heater. Open the cold water supply and allow the water to run until air stops emerging. Until all air is purged from the hot water system, air pockets may appear at any hot water fixture. This is considered normal and will clear as hot water is used.
3. START HEATER: Turn power on to the unit. Smart Control™ models come pre-set at 120°F for safety. Dial units should have the knob rotated to the 120°F mark. The circulator and boiler should start momentarily.
If not, check wiring and consult the troubleshooting section in this manual.
4. CHECK OPERATION: The BoilerMate heat. Depending upon the size of the BoilerMate, output of the boiler and the space heating load, the unit should typically reach set temperature within 15 to 60 minutes. If heating does not occur, consult the troubleshooting section in this manual. Note: Large heaters coupled with small boilers may exceed this time period upon initial startup.
5. SET TEMPERATURE: The BoilerMate be set to the minimum temperature consistent with the user’s needs. This maximizes efficiency and reduces scald potential.
®
will begin to
®
control should
-25-
Page 26
12. SETTING THE SMART CONTROL™
The Smart Control™ incorporates multiple features that increase hot water performance and efficiency. All settings are accessed via the MODE button. To change any setting, simply hold the MODE button then tap to cycle through the settings as outlined below.
GREEN LIGHT - CIRCULATOR INDICATOR
READOUT
DISPLAY
MODE SWITCH
• When power is applied to the unit, the display will show the setpoint temperature (default 120°F).
• Pressing and holding the MODE pushbutton once for 6 seconds will display
then 120°F. This is the water temperature setpoint. To raise or lower this temperature setpoint, press the s or t pushbutton. The temperature can be set between 90°F and 150°F. To shut the unit down, scroll below 90°F until 0°F is displayed. Shutting the unit down is benecial if the water heater will not be used for an extended period of time.
WARNING: Temperature settings above 120°F can create a scald hazard.
• Pressing the MODE pushbutton a second time will cause
to be displayed, and releasing the MODE pushbutton will cause 10°F to be displayed. This is the differential setpoint, a setpoint that determines how many degrees the water temperature is allowed to drop before the water heater activates. To change between the available 10°F and 5°F settings, press and release the s or t pushbutton.
• Pressing the MODE pushbutton a third time will cause
to be displayed, and releasing the MODE pushbutton will cause 0°F to be displayed. This is the post purge setpoint, a setpoint that allows the boiler to be shut off when the actual water temperature is a certain number of degrees below the setpoint temperature. Since the circulator continues to run, the post purge feature will remove excess heat from the boiler after the boiler shuts off. To change the post purge setpoint, press and release the s or t pushbutton to select 0°F, 4°F, or 8°F below setpoint temperature. NOTE: If the differential is set to 5°F, then the post purge setting will not be available and will automatically be set to 0°F. NOTE: When using the BoilerMate
®
on a zone valve application, the post
purge feature will not function.
• Pressing the MODE pushbutton a fourth time will cause Pri to be displayed, and releasing the MODE pushbutton will cause ‘y’ to be displayed. This is called the priority setting, a setting that allows the domestic hot water to reach the setpoint temperature before spatial heating is allowed to resume. To disable the ‘priority’ feature, press and release the s or t pushbutton until ‘n’ is displayed.
• Pressing the MODE pushbutton a fth time will cause
to be displayed, and releasing the MODE pushbutton will cause ‘41’ to be displayed. This is the tank volume in gallons. To change this volume, press and release the s or t pushbutton to select the proper tank size (26, 41, 60, 80, or 120 gallons).
• Pressing the MODE pushbutton a sixth time will cause
to be displayed, and releasing the MODE pushbutton will cause a
number to be displayed. This is a BTU heat transfer rate estimate in MBH. This is a diagnostic readout and cannot be changed.
NOTE: Any changes made to the above settings will take effect after 10 seconds. This will be acknowledged by a display of . Thereafter, these changes will be the new control settings even in the event of a power outage.
• An approximation of the actual domestic water temperature in the tank can be displayed in °F by pressing the s pushbutton.
• One or more error messages will be displayed if abnormal operation occurs, and an audible alarm will sound for most error
messages. The audible alarm can be silenced by pressing the t pushbutton. An damaged thermistor (temperature sensor). Check and replace as necessary. An
message indicates an unplugged or
message appears when the stored water temperature exceeds 155°F. Contact your service person to correct the problem. An Er3 message indicates that the actual domestic water temperature did not reach the setpoint temperature after one hour of attempted heating. Contact your service person to correct the problem. For models equipped with a water sensor, an Er4 message indicates that a water puddle has been detected. Contact your service person to correct the problem.
Note: Smart Control
is to be used for indoor applications only. Do not operate the Smart Control™ unit outside
of the following ranges:
• Ambient temperature from 38°F to 125°F.
• Relative humidity ranging from 20% to 90% (non-condensing).
• Boiler load rating up to 15A resistive, 1/4hp inductive @120VAC.
• Circulator load rating up to 15A resistive, 1/4hp inductive @120VAC.
• Space heating load rating up to 8A @ 120VAC.
Note: For models equipped with a water sensor, the water sensor should be placed at on the oor in a low-trafc area. On a regular
basis, verify that the water sensor is functioning properly by placing the orange puck in a water puddle or inserting a coin between the two electrodes and listening for an audible alarm. This water sensor should not be the primary means of leak
detection. See water sensor installation page for more details.
Note: If setpoints were being adjusted when a power outage occurred, then recheck all set points after power has been restored.
-26-
Page 27
13. TROUBLESHOOTING
PROBLEM
No hot water
Insufficient hot water
Water too hot and/ or ER2 message on Smart Control™
Noise from BoilerMate
Relief valve dripping or opening
ER1 message on Smart Control™
Discolored water at faucet
Boiler will not operate when calling for hot water
Circulator or zone valve will not operate when calling for hot water
®
1. No power to unit
2. Air in heat exchanger loop
3. Faulty circulator or zone valve
4. Faulty BoilerMate™ thermostat
5. Faulty Smart Control™
6. Boiler inoperable
1. Demand exceeds capacity
2. Temperature too low
3. Boiler lacks sufficient output
4. Fouled heat exchanger
5. Insufficient heat exchanger flow
1. Improper plumbing
2. Temperature set too high
3. Temperature sensor not fully inserted
4. Stuck zone valve
5. Flow check valve stuck open
1. Air in boiler loop
2. Faulty circulator pump
3. Thermal expansion
4. Normal noise during initial fill
1. No thermal expansion tank
2. Thermal expansion tank set improperly
3. City pressure too high
4. System over temperature
5. Faulty relief valve
1. Temperature sensor unplugged
2. Temperature sensor cut or faulty
3. Water in therm-well
1. Poor water quality
2. Sediment or suspended particles
1. Improper or loose wiring
2. Boiler high limit has been reached
3. Fuse blown in Smart Control™
4. Post Purge (POS) set too high
5. Problem with boiler system
1. Improper or loose wiring
2. Pre Purge (PRE) set too high
3. Fuse blown in Smart Control™
4. Faulty circulator pump
SOLUTION
1. Check circuit breaker, boiler emergency switch and boiler reset switch
2. Purge air. Ensure circulator is on Boiler Supply. Check air vents
3. Check circulator and zone valve. Repair or replace if necessary
4. Check continuity while rotating knob. Circuit should open and close.
5. If blank, check power. Check continuity across two orange and two blue leads while green light is on. If none, open control and replace fuses or replace control.
6. Check boiler system. Boiler must operate to generate hot water
1. Check sizing based on household size and boiler output
2. Increase temperature setpoint
3. Wire for priority. If problem persists add storage or increase tank size.
4. Check Boiler Supply/Boiler Return during cold startup. If difference is less than 20°F, clean heat exchanger as outlined below. Install water treatment equipment to prevent recurrence.
5. Check for undersized or faulty circulator, stuck or undersized zone valve. Ensure all shutoff valves are open. Check for stuck flow check valve. Purge boiler loop to remove air.
1. If Boiler Return is plumbed to the suction-side of a heating circulator, overheat­ing will occur when the home’s heat is on. Fix plumbing.
2. Reduce temperature setpoint
3. Re-insert thermistor wire or temperature sensor.
4. Repair or replace
5. Clean, repair or replace
1. Purge boiler loop. Check air elimination equipment.
2. Repair or replace pump
3. Ensure the proper Therm-X-Trol installed and adjusted properly
4. When first pressurized, a creaking or hissing sound is normal. After pressuriz­ing, the noise should stop. Always check for leaks.
1. Install the proper Therm-X-Trol
2. Ensure precharge air pressure matches static water pressure
3. Install a Pressure Reducing Valve (PRV) if city pressure is over 80psi
4. Determine cause of over temperature condition and correct problem
5. Replace relief valve
1. Sensor is unplugged from factory. Plug into Smart Control™ receptacle
2. Replace sensor wire (thermistor)
3. Replace therm-well
1. Have water tested for contaminants. Typical problems are:
Blue/green color = copper discoloration due to low pH Black staining/sulfur odor = hydrogen sulfide White deposits = hard water Red staining = high iron levels
2. Install sediment filter, purge unit more often to avoid future problems
1. Check connections against wiring diagrams in this manual
2. Boiler will periodically cycle on and off during operation
3. Remove 4 screws inside the Smart Control™ wiring box. Replace glass fuse(s) with those of the same rating
4. Post Purge shuts the boiler off prior to reaching domestic setpoint. If set too high, the boiler may not have enough energy to raise the water temperature to setpoint. Reduce POS or set to 0 if the problem persists
5. Have boiler diagnosed for proper operation
1. Check connections against wiring diagrams in this manual
2. PRE setting delays circulator startup. This is not normally needed in residential applications. Reduce PRE or set to 0 if problem persists
3. Remove 4 screws inside the Smart Control™ wiring box. Replace glass fuse(s) with those of the amp same rating
4. Repair or replace pump
®
or equivalent thermal expansion tank is
®
or equivalent thermal expansion tank
-27-
Page 28
14. REPLACEMENT PARTS
WH-7, 41 WHS 60 & 80 WHS 120 WHS 60 & 80 WHS 120 and 9 Series TD-7 Series TD-7 RTR TD-80 Series Residential Residential Commercial Commercial
Single Wall Heat Exchanger w/Gasket and Nuts 2700-5000 2700-5005 2700-5007 2700-5008 2775-82 2775-81 2700-5001 2700-5001
Double Wall Heat Exchanger w/Gasket & Nuts 2700-5002 2700-5006 N/A N/A 2775-83 2775-83 2775-84 2775-84
Commercial Heat Exchanger w/Gasket & Nuts 2700-5001 N/A N/A N/A N/A N/A See Above See Above
Top Outlet Tee w/O-Ring 2700-635 N/A N/A N/A N/A N/A N/A N/A
Flange Gasket: Bottom & Top 2704-403 2704-403 2704-403 2704-403 2704-403 2704-403 2704-403 2704-403
Thermo-Well Assembly 2700-924 2700-924(exc DW) 2700-924 2700-1167 2700-924 2700-924 2700-924 2700-924
Top Outlet O-Ring or Bottom Drain O-Ring 2500-178 2500-178 2500-178 2500-178 N/A N/A N/A N/A
Smart Control™ 2704A233 2704A233 2704A233 2704A233 2704A233 2704A233 N/A N/A
Sensor (thermistor) wire 2704-259 2704-259 2704-259 2704-259 2704-259 2704-259 N/A N/A
Dial Aquastat (residential) 2704-093 2704-093 2704-093 2704-093 2704-093 2704-093 N/A N/A
Dial Aquastat (commercial) N/A N/A N/A N/A 2775-454 2775-454 2775-454 2775-454
Conversion Kit: Dial Aquastat 2704-227 2704-227 N/A 2704-227 2775-389 2775-389 2775-389 2775-389 to Smart Control™
Conversion Kit: Smart Control™ to 2704-392 2704-392 N/A 2704-392 2775-455 2775-455 2775-455 2775-455 Dial Aquastat plus 2775-454 plus 2775-454
Circulator Pump 245-58 245-58 245-62 245-58 245-58 245-58 N/A N/A
Water Sensor 2704-495 245-58 245-62 245-58 245-58 245-58 N/A N/A
To obtain replacement parts, contact the installer or place of purchase. Technical support is available by calling AMTROL at (401) 535-1216.
-28-
Page 29
15. CLEANING THE BOILERMATE HEAT EXCHANGER COIL
®
A diminished temperature difference between the boiler water entering and leaving the heat exchanger coil may indicate heat exchanger scale buildup. Water treatment equipment and proper maintenance will help to avoid this problem. To clean a scaled heat exchanger coil proceed as follows:
1. Shut off the cold water supply to the BoilerMate®.
2. Make a note of the temperature control setting on the BoilerMate®, then turn the unit off.
3. Relieve the water pressure in the tank by opening a hot water faucet. This will reduce the risk of scalding injury.
4. Remove the relief valve from the top of the BoilerMate®, taking care to avoid contact with the hot water, which may drain out of the plumbing.
5. Drain the BoilerMate® until the water within the tank is even with the top of the heat exchanger
- approximately 15 gallons for 41-gallons units and 5 gallons for 26-gallon units.
Do not over-drain the tank.
Improper thermostatic control could result during Step 6 and lead to damage to the BoilerMate®.
7. Set the temperature control to its highest setting and operate the unit until the control is satisfied. Note: Boiler may cycle on its high limit several times during this period. If the tank temperature setting has not been satisfied after 45 minutes of boiler operation, turn the BoilerMate® control off to stop boiler operation.
8. Allow heated solution to set in tank for 30 minutes, then drain tank completely using fitting and hose, as required.
9. Fill water tank with fresh, cold, conditioned water and drained completely at least two times or until drained water runs clear.
10. Reinstall the safety relief valve.
11. Open the cold water supply and fill the tank with water. Purge plumbing by operating all hot and cold water fixtures in the building.
12. Return the control to the setting noted in Step 2 and verify that the unit is functioning properly.
As an alternative to the above, the teat exchange may
be removed from the BoilerMate® and cleaned. A new gasket must be installed whenever the heat exchanger is removed.
6. Using a funnel, pour one gallon of non­toxic commercial phosphoric acid solution (commercial icemaking cleaning solution) into the water tank through the top opening. Be sure that the manufacturer’s directions and warnings are followed.
-29-
Page 30
15. GENERAL SAFETY INFORMATION
SCALDING HAZARD. If the water
temperature is over 120°F, household members can suffer serious or fatal scalding and painful and permanent injury. • The Consumer Products Safety Commission recommends an initial setting of 120°F, but notes a slower response time of infants, aged, disabled and other persons increases the scalding hazard and may require lower settings. • Always check the water temperature before use, including washing, bathing or showering. • Temperature limiting valves are available from your plumbing supplier. A check valve must be installed in the boiler return line to prevent gravity flow through the heat exchanger. This can cause overheating and result in serious or fatal scalding.
SCALDING HAZARD. If the thermostat
is not working properly or if this product is not installed in accordance with the manual, water temperature can reach excessive levels that may cause serious or fatal scalding. After installation and any servicing of the unit, verify that the thermostat is working and firmly inserted in the thermostat well by following the thermostat testing instructions in the manual.
Failure to use the correct replacement parts may make your product unsafe.
CALIFORNIA PROPOSITION 65 WARNING! WARNING: This product
contains a chemical known by the State of California to cause cancer and birth defects or other reproductive harm. (California Installer/Contractor - California law requires that this notice be given to consumer/end user of this product.) For more information: www.amtrol.com/
prop65
In limited circumstances, space heating
can be lost in the home with unit utilizing priority mode. Any demand for space heating is postponed until the Boiler Mate® has reached its set temperature. This delay in supplying the space heating zones is usually not noticed by the inhabitants of the living spaces. However, in the event of certain malfunctions such as circulator or thermostat failure, space heating could be delayed indefinitely. If undetected and uncorrected, freezing damage to piping could result.
If a steel hydropneumatic tank is in
place, AMTROL® recommends replacing it with a properly sized EXTROL® expansion tank. Otherwise, significant heat transfer problems can occur by causing air to be trapped in the heat exchanger. If the boiler system has an EXTROL® or Radiant EXTROL® expansion tank and the boiler temperatures are being changed, resize the EXTROL® or Radiant EXTROL® expansion tank.
If installing on city water supply a
properly sized THERM-X-TROL® is required with the BoilerMate® and should be installed as set fo rth in the THERM-X-TROL® product installation manual. Contact your water supplier or local plumbing inspector for additional information.
Prevent pressure build-up in any existing
internal tankless coil. Do not plug incoming or outgoing tappings in the internal tankless coil plate. Leave the coil in the boiler and leave system connections open, to prevent pressure build-up.
Electrocution hazard. The BoilerMate®
must be electrically grounded. Electrical supply must come from the boiler side of boiler’s emergency shut-off switch in order to prevent unsafe boiler operation.
Note: Inspect for shipping damage and notify freight carrier or store where purchased immediately if damage present. To avoid risk of personal injury and property damage, if the product appears to be malfunctioning or shows signs of corrosion, call a qualified professional immediately. Current copies of the Product manual can be viewed at www.amtrol. com. Use proper safety equipment when installing.
EXPLOSION HAZARD. The pressure of
the heat transfer medium must be limited to a maximum of 30 psig by an approved safety or relief valve on your boiler. The BoilerMate 150 psig maximum by the installation of a temperature and pressure relief valve (included). The relief tube must be plumbed to a suitable drain per code. No reducing coupling or other restriction may be placed in this line.
This Product, like most Products under
pressure, may over time corrode, weaken and burst or explode, causing serious or fatal injury, leaking or flooding and/or property damage. To minimize risk, a licensed professional must install and periodically inspect and service the Product. A drip pan connected to an adequate drain must be installed if leaking or flooding could cause property damage. Do not locate in an area where leaking could cause property damage.
EXPLOSION OR RUPTURE HAZARD.
A relief valve must be installed to prevent pressure in excess of local code requirement or maximum working pressure designated in the Product Manual, whichever is less. Do not expose Product to freezing temperatures or temperatures in excess of the maximum rated operating temperature.
If not installed by the boiler manufacturer,
install a low water cut-off or pressure reducing valve on your boiler so that leaking will not result in a dry boiler which if the boiler continues to fire, will cause an explosion hazard.
This unit must be installed as a separate
heating zone. Do not connect this unit to an existing heating zone or feed boiler water directly through the coil as dangerous over-heating will result.
Do not drain this appliance before
shutting off the supply valve and opening the relief valve or another downstream fixture, as it will damage this unit. A vacuum breaker should be installed to avoid damaging the liner. Damage to the unit and leakage can occur if a vacuum breaker is not installed.
USE GLYCOL ONLY WITH
DO U B L E-WA L L ED HEA T EXCHANGER MODELS. Avoid risk of ingesting a toxic glycol
fluid. The heat transfer medium should be water. If glycol must be used, it should only be used with double-walled heat exchangers and closely moitored for leakage.
®
pressure must be limited to
Chlorine Aggressive Water: The water
quality can significantly influence the life of this Product. You should test for corrosive elements, acidity, total solids and other relevant contaminants, including chlorine and treat your water appropriately to insure satisfactory performance and prevent premature failure.
-30-
Page 31
-31-
Page 32
West Warwick, Rhode Island 02893
Boiler Mate, AMTROL, AMTROL logo, Therm-X-Trol, Radiant EXTROL and EXTROL are registered trademarks of AMTROL Inc. and affiliates. All rights reserved.
Part #: 9040-586 (07/08)