Amtrol SX-30V, EX-90, EX-15, SX160V User Manual

EXTROL
®
HYDRONIC EXPANSION TANKS FOR NON-POTABLE WATER
INSTALLATION & OPERATION INSTRUCTIONS
Models EX-15 through EX-90
Models SX-30V through SX-160V
NOTE: Inspect for shipping damage. Notify freight carrier or store where purchased immediately if damage is present. To avoid risk of personal injury and property damage, if the product appears to be malfunctioning or shows signs of corrosion, call a qualified professional immediately. Current copies
of the product manual can be viewed at www.amtrol.com. Use proper safety equipment when installing.
THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS. OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS PROPERTY DAMAGE.
USE ONLY IN RESIDENTIAL CLOSED HYDRONIC
systems, or in open heating systems. Corrosion and tank failure may result. Use a Therm-X-Trol® or Therm-X-Span® for domestic water systems. Use a Radiant EXTROL® for radiant heating systems where air elimination equipment or barrier tubing is not used.
FAILURE TO FOLLOW THE INSTRUCTIONS AND WARNINGS IN THE MANUAL MAY RESULT IN SERIOUS OR FATAL INJURY AND/OR PROPERTY DAMAGE, AND WILL VOID THE PRODUCT WARRANTY. THIS PRODUCT MUST BE INSTALLED BY A QUALIFIED PROFESSIONAL. FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS, IN THE ABSENCE OF SUCH CODES, FOLLOW THE CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND
explode, causing serious or fatal injury, leaking or flooding and/or property damage. To minimize risk, a licensed professional must install and periodically inspect and service the Product. A drip pan connected to an adequate drain must be installed if leaking or flooding could cause property damage. Do not locate in an area where leaking could cause property damage to the area adjacent to the appliance or to lower floors of the structure.
CALIFORNIA PROPOSITION 65 WARNING! This product contains a chemical known by the State of California to cause cancer and to cause birth defects or other reproductive harm. (California Installer/Contractor
- California law requires that this notice be given to consumer/end user of this product.) For more information: www.amtrol.com/prop65.html
NATIONAL ELECTRIC CODE, AS APPLICABLE.
SYSTEMS.
READ CAREFULLY THE PRODUCT INSTALLATION, OPERATING AND MAINTENANCE MANUAL.
This Product, like most Products under pressure, may over time corrode, weaken and burst or
Do not install on domestic water
temperatures in excess of 240°F. Do not adjust the pre-charge or re-charge this Product except during installation or regular inspection. Replace the Product and do not adjust the pre-charge if corroded, damaged or with diminished integrity. Adjustments to pre-charge must be done at ambient temperature only. Failure to properly size the Product or follow these instructions may result in excessive strain on the system and may lead to Product failure, serious or fatal personal injury, leakage, and/or property damage.
working pressure designated in the Product Manual, whichever is less. At least once every 3 years or if discharge is present, a licensed contractor should inspect the pressure relief valve and replace if corrosion is evident or the valve does not function. FAILURE TO
INSPECT THIS VALVE AS DIRECTED COULD RESULT IN UNSAFE PRESSURE BUILD-UP WHICH CAN RESULT IN PRODUCT FAILURE, SERIOUS INJURY OR DEATH AND/OR SEVERE PROPERTY DAMAGE AND VOID THE PRODUCT WARRANTY.
You should test for corrosive elements, acidity, total solids and other relevant contaminants, including chlorine and treat your water appropriately to insure satisfactory performance and prevent premature failure.
RUPTURE OR EXPLOSION HAZARD. Do not expose product to freezing temperatures or
A relief valve must be installed to prevent pressure in excess of local code requirement or maximum
Chlorine & Aggressive Water: The water quality can significantly influence the life of this Product.
PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY
IMPORTANT GENERAL SAFETY INFORMATION -
ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
Pre-Installation
1 Visually inspect for any damage. Ensure expansion tank is sized
properly for application (Figure 1).
2. Remove plastic cap from air valve.
3. With tank empty of water, adjust air precharge to match system fill pressure.
4. Replace and tighten plastic cap on air valve.
FAILURE TO PROPERLY SEAL VALVE CAP WILL RESULT IN LOSS OF PRECHARGE CAUSING PRODUCT TO FAIL.
Mount tank vertically in downward position only. Ensure the piping can support the entire weight of the tank when full of water.
Models SX-30V through SX-160V are floor
standing and may not be hung from the piping.
Do not install the EXTROL on a dead-end pipe
or wherever air can collect. This can cause corrosion and possible leakage.
Installation
1. Drain the boiler system or isolate the area where the EXTROL will be installed.
Figure 1.
Boiler
Net Output
in 1000’S
of BTU/Hr.
25 EX-15 EX-15 EX-15 EX-15 50 EX-15 EX-15 EX-30 EX-30
75 EX-30 EX-30 EX-30 EX-60 100 EX-30 EX-30 EX-60 EX-60 125 EX-30 EX-60 EX-60 EX-90 150 EX-30 EX-60 EX-90 EX-90 175 EX-60 EX-60 SX-30V SX-30V 200 EX-60 EX-60 SX-30V SX-30V 250 EX-60 EX-90 SX-30V SX-40V 300 EX-90 SX-30V SX-30V SX-40V 350 SX-30V SX-30V SX-40V SX-60V 400 SX-30V SX-40V SX-40V SX-60V
Sizing based on: 12 psig Fill; 30 psig Relief Valve; 200°F Average Temperature.
Boiler
Net Output in
1000’s of BTU
200 SX- 30V SX-30V SX-30V SX-30V 250 SX- 30V SX-30V SX-30V SX-40V 300 SX- 30V SX-30V SX-40V SX-40V 350 SX-30V SX-30V SX-40V SX-60V 400 SX-30V SX-40V SX-60V SX-60V 450 SX-40V SX-40V SX-90V SX-90V 500 SX-40V SX-40V SX-60V SX-90V 550 SX-40V SX-60V SX-60V SX-90V 600 SX-40V SX-60V SX-90V SX-90V 650 SX-60V SX-60V SX-90V SX-90V 700 SX-60V SX-60V SX-90V SX-90V 750 SX-60V SX-60V SX-90V SX-110V 800 SX-60V SX-90V SX-90V SX-110V 850 SX-60V SX-90V SX-90V SX-110V 900 SX-60V SX-90V SX-110V SX-110V
950 SX-90V SX-90V SX-110V SX-110V 1,000 SX-90V SX-90V SX-110V SX-110V 1,100 SX-90V SX-90V SX-110V SX-130V 1,200 SX-90V SX-90V SX-110V SX-130V 1,300 SX-90V SX-110V SX-130V SX-160V 1,400 SX-110V SX-130V SX-160V SX-160V 1,500 SX-110V SX-130V SX-160V (2)SX-110V
Sizing based on: Average Boiler Water Volume; Average Water Volume; Fill Pressure 12 psig; Relief Pressure 30 psig
Finned Tube
Baseboard or
Radiant Panel
Finned Tube
Baseboard or Radiant
Panels with Series
Loop System
Type of Radiation and Piping System
Type of Radiation
Convectors
or Unit
Heaters
Convectors or
Unit Heaters
with One Pipe
System
Radiators
Cast Iron
Radiators
or
One Pipe
System
Baseboard
Cast Iron
Cast Iron Radiators
with Series
Loop System
2. Install the EXTROL on the supply side of the boiler, on the suction-side of the heating circulator(s) (Figure 2).
3. Pressurize the system and check for leaks. Repair as necessary.
4. Restart the boiler system and check for relief valve discharge. If the relief valve drips, the tank may be improperly charged or undersized.
5. The EXTROL is now operational and will absorb expanded water during boiler operation.
Maintenance
A professional plumber should check the complete system, including the expansion tank, yearly and more frequently as the system ages. Checking the precharge allows a small quantity of air to escape and can result in an insufficient air charge. Always check the precharge while the tank is isolated and empty of water, and be sure to maintain the proper precharge whenever the tank is inspected.
Warranty
EX Models: Five (5) Year Limited Warranty
SX Models: One (1) Year Limited Warranty
Visit www.amtrol.com for complete warranty details.
Figure 2.
In-Line Models: EX-15 through EX-90
System
Supply
Flow-Check
Valve
Purger
Circulator
Stand Models: SX-30V through SX-160V
System Supply
Flow-Check
Circulator
Valve
Air
Air Vent
Extrol
Expansion
Tank
Air Vent
Air
Separator
Extrol
Expansion
Tank
Pressure­Reducing
Valve
Shut-Off
Valve
Pressure­Reducing
Shut-Off
Valve
Boiler
Valve
System
Purge
Boiler
Backflow Preventer
System
Purge
Backflow Preventer
Relief Valve
Shut-Off
Valve
Shut-Off
Valve
Relief Valve
Water
Supply
Water
Supply
System
Return
System
Return
1400 Division Road, West Warwick, RI USA 02893
T: 800.426.8765 F: 800.293.1519
Mark of the
Originator
www.amtrol.com
© 2015 AMTROL Inc. Part #: 9015-183 (06/15)
Loading...