![](/html/c6/c68f/c68fd2335b998231453e90900c060ae7888ed8c9aa04d149234b4867c0c389b6/bg1.png)
INSTALLATION INSTRUCTIONS
DIATROL
1400 Division Road, West Warwick, RI 02893 T: 401.884.6300 F: 401.885.2567 www.amtrol.com
1. LOCATION:
Install the Diatrol on the supply piping as close as possible to the offending fixture(s). The
Diatrol should be installed upstream of any fast-acting valves. Use the guidelines below
to determine the best placement. Multiple fixtures and long supply lines may require the
installation of multiple Diatrol shock suppressors.
®
Diatrol
A. On branch lines up to 20’ long.
Up to 20 ft.
®
FIXTURE
B. On branch lines over 20’ long.
FIXTURE FIXTURE FIXTURE FIXTURE FIXTURE FIXTURE FIXTURE FIXTURE FIXTURE FIXTURE
2. POSITION:
FIXTURE FIXTURE FIXTURE FIXTURE
Install second Diatrol
Install first Diatrol
half distance between
first and last fixture.
®
More than 20 ft.
between last two fixtures.
®
The Diatrol will function in any position. Ensure the nearby piping is supported adequately.
3. ADJUSTMENT
With the Diatrol empty of water, adjust the factory pre-charge to equal the average flow
pressure. For example: if the line pressure registers 65 psig with the fixtures open, adjust the
Diatrol air charge to 65 psig.
4. MAINTENANCE
A professional plumber should check the complete system, including the Diatrol, yearly and
more frequently as the system ages.
Part #9015-199 (10/12)
![](/html/c6/c68f/c68fd2335b998231453e90900c060ae7888ed8c9aa04d149234b4867c0c389b6/bg2.png)
READ CAREFULLY THE PRODUCT INSTALLATION, OPERATING AND MAINTENANCE MANUAL. FAILURE TO
FOLLOW THE INSTRUCTIONS AND WARNINGS IN THE MANUAL MAY RESULT IN SERIOUS OR FATAL
INJURY AND/OR PROPERTY DAMAGE, AND WILL VOID THE PRODUCT WARRANTY. THIS PRODUCT MUST BE INSTALLED BY A
QUALIFIED PROFESSIONAL. FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS, IN THE ABSENCE OF
SUCH CODES, FOLLOW THE CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE, AS
APPLICABLE.
THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER
HAZARDS. OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY
AS WELL AS PROPERTY DAMAGE.
EXPLOSION OR RUPTURE HAZARD A relief valve must be installed to prevent pressure in excess of local code
requirement or maximum working pressure designated in the Product Manual, whichever is less. Do not expose Product
to freezing temperatures or temperatures in excess of 200° F. Do not adjust the pre-charge or re-pressure this Product except for any adjustments
required at the time of initial installation, especially if Product corroded, damaged or with diminished integrity. Adjustments to pre-charge must
be done at ambient temperature only. Failure to properly size the Product or follow these instructions may result in excessive strain on the system
lead to Product failure, serious or fatal personal injury, leakage and/or property damage.
Chlorine & Aggressive Water: The water quality can significantly influence the life of this Product. You should test for
corrosive elements, acidity, total solids and other relevant contaminants, including chlorine and treat your water
appropriately to insure satisfactory performance and prevent premature failure.
Install or store where Product will not be exposed to temperatures below freezing or above 100°F, do not expose to any
type of weather. Water freezing in the system will break it. Do not attempt to treat water over 100°F. Do not install in
direct sun light. Excessive sun heat may cause distortion or other damage to non-metallic parts.
Use only lead-free solder and flux for all sweat-solder connections, as required by state and federal codes.
Note: Inspect for shipping damage and notify freight carrier or store where purchased immediately if damage is present. To avoid risk of personal
injury and property damage, if the product appears to be malfunctioning or shows signs of corrosion, call a qualified professional immediately.
Current copies of the Product manual can be viewed at www.amtrol.com. Use proper safety equipment when installing.
This Product, like most Products under pressure, may over time corrode, weaken and burst or explode, causing serious
or fatal injury, leaking or flooding and/or property damage. To minimize risk, a licensed professional must install and
periodically inspect and service the Product. A drip pan connected to an adequate drain must be installed if leaking or flooding could cause
property damage. Do not locate in an area where leakage of the tank or connections could cause property damage to the area adjacent to the
appliance or to lower floors of the structure.
IMPORTANT GENERAL SAFETY INFORMATION - ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE
FOLLOWING INSTRUCTIONS.
CALIFORNIA PROPOSITION 65 WARNING! WARNING: This product contains a chemical known by the State of
California to cause cancer and to cause birth defects or other reproductive harm. (California Installer/Contractor - California
law requires that this notice be given to consumer/end user of this product.) For more information: www.amtrol.com/prop65.htm
AMTROL, AMTROL logo, and Diatrol are registered trademarks of AMTROL Inc. and afliates in the U.S. and elsewhere. All rights reserved.