Amprobe TIC300-PRO Operating Manual

TIC 300 PRO
High Energy Tic Tracer –
Non Contact AC Voltage Detector
User Manual
Mode d’emploi Bedienungshandbuch Manual d’uso Manual de uso
TIC 300 PRO
High Energy Tic Tracer –
Non Contact AC Voltage Detector
User Manual
07/2017, Rev005 ©2017 Amprobe Test Tools. All rights reserved. Printed in China
English
Limited Warranty and Limitation of Liability
Your Amprobe product will be free from defects in material and workmanship for 1 year from the date of purchase. This warranty does not cover fuses, disposable batteries or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling. Resellers are not authorized to extend any other warranty on Amprobe’s behalf. To obtain service during the warranty period, return the product with proof of purchase to an authorized Amprobe Test Tools Service Center or to an Amprobe dealer or distributor. See Repair Section for details. THIS WARRANTY IS YOUR ONLY REMEDY. ALL OTHER WARRANTIES - WHETHER EXPRESS, IMPLIED OR STAUTORY - INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, ARE HEREBY DISCLAIMED. MANUFACTURER SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, ARISING FROM ANY CAUSE OR THEORY. Since some states or countries do not allow the exclusion or limitation of an implied warranty or of incidental or consequential damages, this limitation of liability may not apply to you.
Repair
All test tools returned for warranty or non-warranty repair or for calibration should be accompanied by the following: your name, company’s name, address, telephone number, and proof of purchase. Additionally, please include a brief description of the problem or the service requested and include the test leads with the meter. Non-warranty repair or replacement charges should be remitted in the form of a check, a money order, credit card with expiration date, or a purchase order made payable to Amprobe® Test Tools.
In-Warranty Repairs and Replacement – All Countries
Please read the warranty statement and check your battery before requesting repair. During the warranty period any defective test tool can be returned to your Amprobe® Test Tools distributor for an exchange for the same or like product. Please check the “Where to Buy” section on www.amprobe.com for a list of distributors near you. Additionally, in the United States and Canada In-Warranty repair and replacement units can also be sent to a Amprobe® Test Tools Service Center (see address below).
Non-Warranty Repairs and Replacement – US and Canada
Non-warranty repairs in the United States and Canada should be sent to a Amprobe® Test Tools Service Center. Call Amprobe® Test Tools or inquire at your point of purchase for current repair and replacement rates.
In USA In Canada Amprobe Test Tools Amprobe Test Tools Everett, WA 98203 Mississauga, ON L4Z 1X9 Tel: 877-AMPROBE (267-7623) Tel: 905-890-7600
Non-Warranty Repairs and Replacement – Europe
European non-warranty units can be replaced by your Amprobe® Test Tools distributor for a nominalv charge. Please check the “Where to Buy” section on www.amprobe.com for a list of distributors near you. European Correspondence Address*
Beha-Amprobe® Test Tools Europe In den Engematten 14 79286 Glottertal, Germany Tel.: +49 (0) 7684 8009 - 0 *(Correspondence only – no repair or replacement available from this address. European customers please contact your distributor.)
TIC 300 PRO
1) Voltage sensor
2) ON/OFF Button
3) Circuit TEST button
4) HIGH range switch
5) HIGH range LED
6) LOW range switch
7) LOW range LED
8) Battery compartment
9) HOT STICK attachment point
10)
Detection Blue LED indicators
CONTENTS
SYMBOLS .......................................................................... 2
UNPACKING AND INSPECTION .......................................3
INTRODUCTION ................................................................ 4
Features ........................................................................ 4
OPERATION .......................................................................5
ON/OFF Button ............................................................. 5
TEST Button .................................................................. 5
Voltage Detection ........................................................6
LOW Range ...................................................................6
HIGH Range .................................................................. 6
Locate breaks in insulated wire & heating elements
Check Outlets and Switches ........................................8
MAINTENANCE AND REPAIR ..........................................9
Cleaning ........................................................................9
Battery Replacement ...................................................9
SPECIFICATIONS ...............................................................10
Sensitivity: LOW Voltage .............................................11
Sensitivity: HIGH Voltage .............................................11
...... 7
1
SYMBOLS
MSHA
United States Department of Labor
Mine Safety and Health Administration
Refer to the manual
X
Caution Dangerous Voltage Double insulated
T
In compliance with the United States Department Of Labor Mine Safety and Health Administration
Conforms to relevant Australian standards.
Conforms to relevant South Korean EMC standards.
Do not dispose of this product as unsorted
=
municipal waste.
For Use By Trained Personnel Only
Anyone using this instrument should be knowledgeable and trained about the risks involved with measuring medium and high voltage, especially in an industrial setting, and the importance of taking safety precautions and of testing the instrument before and after using it to ensure that it is in good working condition.
WARNING and PRECAUTIONS
• Use extreme caution when testing live electrical circuits due to risk of injury from electrical shock.
• Do not exceed the maximum overload limits (see specifications) or the limits marked on the instrument itself. Never test voltage more than 122 kV AC RMS.
• When using the HIGH range, the TIC 410A HOT STICK or equivalent extension pole MUST be used.
• Comply with local and national safety requirements.
• Use proper protective equipment as required by local and national authorities.
2
• Observe the proper safety precautions when working with voltages above 33 VAC RMS to avoid electrical shock hazard.
• Before and after hazardous voltage measurements, test the TIC 300 PRO by pressing the TEST button and/or on a known source such as line voltage to determine proper operation.
• Never ground yourself when taking measurements. Do not touch exposed circuit elements.
• Do not operate the instrument in an explosive atmosphere.
• Do not expose this product to rain or moisture. This increases the risk of fire or electric shock.
Do not rely on the TIC 300 PRO for testing shielded wire.
• Do not let the unit make contact with a live line with voltage higher than 20 kV.
• Three phase feeder cables with conductors close to each other may self-cancel the electric field and will not be detected by the TIC 300 PRO tracer. Verify that the phase conductors are separated by at least 15 in (38.1 cm) before testing for AC voltage.
UNPACKING AND INSPECTION
Your shipping carton should include: 1 TIC 300 PRO 1 9 V Alkaline Battery 1 User Manual 1 Carrying Case
If any of the items are damaged or missing, return the complete package to the place of purchase for an exchange.
3
INTRODUCTION
The TIC 300 PRO safely checks for the presence of AC voltage without making any disconnection in cables, wall sockets, fuses, circuit breakers, junction boxes, etc. No current flow is needed for correct operation.
Rugged and reliable for utility, industrial and mine safety applications, the TIC 300 PRO warns against dangerous voltages in low and medium voltage applications up to 122 KV without contacting the energized conductor.
Features
Utility tool for checking transmission lines, power distribution equipment, down power lines, fuses, and load break connectors
Lower voltage setting for checking voltage presence in breaker panels, breakers, power outlets and wiring
Verifies presence of voltage from 30 VAC to 122,000 VAC (122 kV)
Non-contact AC voltage detection
Visual and audible voltage indication
Self-test for verifying that the tester is working properly
Ergonomic design with a convenient handle
Drop proof up to 6 ft (1.83 m)
Use with the Hot Stick 410A when voltage exceeds 1500 V
4
OPERATION ON/OFF Button
When the TIC 300 PRO is activated, the blue LEDs and beeper will pulse at a slow rate about twice a second. The red LED of the range (HIGH) will turn ON.
TEST Button
The TEST button should be used prior to testing actual power circuits. The TEST function will cause the blue LEDs and beeper of the range selected (LOW or HIGH) to pulse at a fast rate.
OSHA listed clearance distances for working with voltage. National or local requirements may be different.
Line voltage (kV) Phase to ground Phase to phase
phase to phase (ft-in) (m) (ft-in) (m)
0.03 to 1.0 Note1 Note1 Note1 Note1
1.1 to 15.0 2-1 0.64 2-2 0.66
15.1 to 36.0 2-4 0.72 2-7 0.77
36.1 to 46.0 2-7 0.77 2-10 0.77
46.1 to 72.5 3-0 0.90 3-6 1.05
72.6 to 121 3-2 0.95 4-3 1.29
Note1 – No contact necessary
Caution: If a three phase circuit is being checked and one phase is open, the voltage from another phase maybe detected and will give a faulty indication. Always make sure that the phase cables are separated by at least 20 in (50.8 cm).
5
Voltage Detection
LOW Range
1. Push the ON/OFF push button to turn the unit ON.
2. The high voltage detection circuit is activated. A beep will sound and the blue LEDs will flash twice per second.
3. Push the LOW range push button. The unit is ready for low voltage detection.
4. Place the probe tip of the TIC 300 PRO near, but not touching, a low (<1000 V) voltage line (Fig. 1).
5. If voltage is present, the blue LEDs will blink and the beeper will sound at an increased rate. Continuous visual (blue LEDs) and audible indicators will increase when the probe tip makes contact with or is very close to the voltage line.
Fig. 1 Voltage detection in a line
HIGH Range (HOT STICK must be used)
(See Fig. 2)
1. Push the ON/OFF push button to turn the unit ON.
2. The high voltage detection circuit is activated. A beep will sound and the blue LEDs will flash twice per second.
3. Approach the probe tip near, but not touching, a high voltage (>1500 V and <122 kV) conductor.
6
4. If voltage is present, the blue LEDs will blink and the beeper will sound at an increased rate. Continuous visual (blue LEDs) and audible indicators will increase when the probe tip makes contact with or is very close to the high voltage line.
TIC 300 PRO
HOT STICK
Fig. 2 Voltage detection in transmission lines
Locate breaks in insulated wire and heating elements (See Fig. 3)
1. Push the ON/OFF push button to turn the unit on.
2. Push the LOW range push button.
3. Make sure the wire or the heating element is energized.
4. Place the tip of the probe near the wire and start tracing along it. When the fast or continuous beeping stops, the point of the break or “open” is indicated.
7
Fig. 3 Finding a break/open
Check Outlets and Switches (See Figs. 4 & 5)
1. Push the ON/OFF push button to turn the unit on.
2. Push the LOW range push button.
3. Place the probe tip of the TIC 300 PRO against the hot prong of an outlet or switch contact.
4. Increased beeping indicates higher voltage presence.
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Detecting voltage in an
Fig. 4
outlet (Note: disconnect all power cords from the outlet before testing)
Fig. 5
Finding a breaker
8
MAINTENANCE AND REPAIR
If there appears to be a malfunction during the operation of the voltage detector, the following steps should be performed in order to isolate the cause of the problem:
1. Check the battery.
2. Review the operating instructions for possible mistakes in operating procedure.
Except for the replacement of the battery, repair of the voltage detector should be performed only by a Factory Authorized Service Center or by other qualified instrument service personnel.
Cleaning
The front panel and case can be cleaned with a mild solution of detergent and water. Apply sparingly with a soft cloth and allow to dry completely before using. Do not use aromatic hydrocarbons or chlorinated solvents for cleaning.
Battery Replacement
Use a Phillips blade screwdriver to remove the battery hatch screw. Lift the hatch. Remove the battery and replace it with a 9 V alkaline battery. Make sure the seal is in place. Close the battery hatch and replace the screw.
9
SPECIFICATIONS
Operating voltage LOW Range: 30 to 1500 VAC; HIGH Range: 1500 VAC to
122 kVAC
Operating Temperature: 0°C to +52°C (32°F to +125°F); RH < 90%
Storage Temperature: 0°C to +52°C (32°F to +125°F) battery removed
Environment: < 2000 m (1.24 mi), outdoor operation Power: 9 V alkaline battery Power Consumption:
OFF: 60 uA
Low Detection mode: 39 mA
High Detection mode: 39 mA
Duty Cycle: Continuous Response Time: Instantaneous Dimensions: 345(L) x 75(W) x 47(H) mm (13.5 x 3.0 x 1.8 in) Weight: 243 g (0.5 lb) Optional Accessory: TIC 410A Hot Stick Electromagnetic Compatibility (EMC): EN 61326-1
Korea (KCC): Class A Equipment (Industrial Broadcasting & Communication Equipment)
[1]
This product meets requirements for industrial (Class A) electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and is not to be used in homes.
[1]
10
Sensitivity: LOW Voltage Hold the TIC 300 PRO when making the detection range measurement for LOW voltage range.
Voltage
(Phase to neutral with
890K Ohm load)
30 V 3.8 cm (1.5 in)
75 V 16.5 cm (6.5 in)
100 V 21.6 cm (8.5 in)
120 V 25.4 cm (10 in)
220 V 33 cm (1 ft 1 in)
500 V 48.3 cm (1 ft 7 in)
1000 V 86.4 cm (2 ft 10 in)
Sensitivity: HIGH Voltage The TIC 410A Hot Stick must be used when making detection range measurement for HIGH voltage range.
Voltage
(Open Phase with no load)
1.5 kV 12.7 mm (0.5 in)
2.0 kV 25.4 mm (1 in)
4.0 kV 5.1 cm (2 in)
10.0 kV 20.3 cm (8 in)
15.0 kV 35.6 cm (1 ft 2 in)
20.0 kV 50.8 cm (1 ft 8 in)
25.0 kV 66 cm (2 ft 2 in)
Detection Range
(From the TIP of probe to
the target line)
Average
Detection Range
(From the TIP of probe to
the target line)
Average
11
TIC 300 PRO
TIC Tracer haute tension –
Détecteur de tensions alternatives sans contact
Mode d’emploi
07/2017, Rev005 ©2017 Amprobe Test Tools. Tous droits réservés. Imprimé en Chine
Français
Limites de garantie et de responsabilité
Amprobe garantit l’absence de vices de matériaux et de fabrication de ce produit pendant une période d’un an prenant effet à la date d’achat. Cette garantie ne s’applique pas aux fusibles, aux piles jetables ni à tout produit mal utilisé, modifié, contaminé, négligé ou endommagé par accident ou soumis à des conditions anormales d’utilisation et de manipulation. Les revendeurs n’ont pas l’autorisation de prolonger toute autre garantie au nom d’Amprobe. Pour bénéficier de la garantie, renvoyez le produit accompagné d’un justificatif d’achat auprès d’un centre de services agréé par Amprobe Test Tools ou d’un distributeur ou d’un revendeur Amprobe. Voir la section Réparation pour tous les détails. LA PRESENTE GARANTIE EST LE SEUL ET EXCLUSIF RECOURS DE L’UTILISATEUR. TOUTES AUTRES GARANTIES, EXPLICITES, IMPLICITES OU STATUTAIRES, NOTAMMENT LES GARANTIES DE QUALITE MARCHANDE OU D’ADAPTATION A UN OBJECTIF PARTICULIER SONT EXCLUES PAR LES PRESENTES. LE FABRICANT NE SERA EN AUCUN CAS TENU RESPONSABLE DE DOMMAGES PARTICULIERS, INDIRECTS, ACCIDENTELS OU CONSECUTIFS, NI D’AUCUNS DEGATS OU PERTES DE DONNEES, SUR UNE BASE CONTRACTUELLE, EXTRA­CONTRACTUELLE OU AUTRE. Etant donné que certaines juridictions n’admettent pas les limitations d’une condition de garantie implicite ou l’exclusion ou la limitation de dégâts accidentels ou consécutifs, il se peut que les limitations et les exclusions de cette garantie ne s’appliquent pas à votre cas.
Réparation
Tous les outils de test renvoyés pour être réparés au titre de la garantie doivent être accompagnés des éléments suivants : nom, raison sociale, adresse, numéro de téléphone et justificatif d’achat. Ajoutez également une brève description du problème ou du service demandé et incluez les cordons de test avec l’appareil. Les frais de remplacement ou de réparation hors garantie doivent être acquittés par chèque, mandat, carte de crédit avec date d’expiration, ou par bon de commande payable à l’ordre de
®
Test Tools.
Amprobe
Remplacements et réparations sous garantie – Tous pays
Veuillez lire la déclaration de garantie et vérifiez la pile avant de demander une réparation. Pendant la période de garantie, tout outil de test défectueux peut être renvoyé auprès de votre distributeur Amprobe produit identique ou similaire. Consultez la section « Where to
®
Test Tools pour être échangé contre un
Buy » sur le site www.amprobe.com pour obtenir la liste des distributeurs dans votre région. Les appareils sous garantie devant être remplacés ou réparés au Canada et aux Etats-Unis peuvent également être envoyés dans un centre de services Amprobe Tools (voir les adresses ci-dessous).
Remplacements et réparations hors garantie – Canada et Etats-Unis
Les appareils à réparer hors garantie au Canada et aux Etats-Unis doivent être envoyés dans un centre de services
®
Test Tools. Appelez Amprobe® Test Tools ou
Amprobe renseignez-vous auprès de votre lieu d’achat pour connaître les tarifs en vigueur de remplacement ou de réparation.
Aux Etats-Unis Au Canada Amprobe Test Tools Amprobe Test Tools Everett, WA 98203 Mississauga, ON L4Z 1X9 Tél. : 877-AMPROBE (267-7623) Tél. : 905-890-7600
Remplacements et réparations hors garantie – Europe
Les appareils européens non couverts par la garantie peuvent être remplacés par votre distributeur Amprobe somme nominale. Consultez la section « Where to Buy » sur le site www.amprobe.com pour obtenir la liste des distributeurs dans votre région. Adresse postale européenne*
®
Test Tools Europe
Amprobe In den Engematten 14 79286 Glottertal, Allemagne Tél. : +49 (0) 7684 8009-0 *(Réservée à la correspondance – Aucune réparation ou remplacement n’est possible à cette adresse. Nos clients européens doivent contacter leur distributeur.)
®
Test Tools pour une
®
Test
TIC 300 PRO
1) Capteur de tension
2) Bouton MARCHE/ARRÊT
3) Bouton TEST du circuit
4) Commutateur de gamme haute (HIGH)
5) Témoin de gamme
haute (HIGH)
6) Commutateur de gamme basse (LOW)
7) Témoin de tension basse (LOW)
8) Compartiment de pile
9) Point de fixation de la perche isolante (HOT STICK)
10) Témoin bleu de détection
TABLE DES MATIÈRES
SYMBOLES ........................................................................ 2
DÉBALLAGE ET INSPECTION ............................................ 3
INTRODUCTION ................................................................ 4
Fonctionnalités ............................................................. 4
FONCTIONNEMENT .......................................................... 5
Bouton MARCHE / ARRÊT ............................................ 5
Bouton TEST ................................................................. 5
Détection des tensions .................................................6
Gamme LOW ................................................................ 6
Gamme HIGH ................................................................6
Localisation des coupture de fils isolés et
éléments chauffants.....................................................7
Vérification des prises de courant et interrupteurs ... 7
ENTRETIEN ET RÉPARATION ............................................. 8
Changement des piles ..................................................8
CARACTÉRISTIQUES ......................................................... 9
BASSE tension ...............................................................10
HAUTE tension ............................................................. 10
1
SYMBOLES
MSHA
United States Department of Labor
Mine Safety and Health Administration
Reportez-vous au mode d’emploi
Attention ! Tension dangereuse
X
Double isolation
T
Conforme aux directives de l’Admistration du travail de la Sécurité des Mines et de la Santé du Départment du travail des États-Unis
Conformes aux normes australiennes pertinentes
Conforme aux normes CEM sud-coréennes.
Ne pas mettre ce produit au rebut parmi les
=
déchets ménagers.
Utilisation exclusive par le personnel formé à cet effet.
Toute personne utilisant cet appareil doit connaître les risques de la mesure des haute et basse tensions, y être formée et reconnaître l’importance de mesures de sécurité et du test de l’appareil avant et après son utilisation pour s’assurer qu’il est en bon état de fonctionnement.
MISES EN GARDE et PRÉCAUTIONS
• Faire preuve d’une extrême prudence en testant des circuits électriques sous tension car ils présentent un risque d’électrocution.
• Ne dépassez pas les limites de surcharge maximum (voir les caractéristiques techniques) ou les limites indiquées sur l’appareil lui-même. Ne testez jamais les tensions alternatives supérieures à 122 kV efficaces.
• Lors de l’utilisation de la gamme haute (HIGH), utilisez OBLIGATOIREMENT une perche isolante TIC 410A HOT STICK ou une perche d’extension équivalente.
• Conformez-vous aux exigences de sécurité locales et nationales.
• Utilisez un équipement de protection
2
conformément aux exigences locales et nationales.
• Pour éviter les chocs électriques, observez les précautions de sécurité appropriées en cas d’intervention sur des tensions supérieures à 33 V c.a. eff.
• Avant et après les mesures de tension dangereuses, testez le TIC 300 PRO en appuyant sur le bouton TEST et/ou sur une source connue telle qu’une tension de ligne pour confirmer son bon fonctionnement.
• Ne vous reliez jamais à la terre en prenant des mesures. Ne touchez pas aux éléments de circuit exposés.
N’utilisez pas l’appareil dans une atmosphère explosive.
• N’exposez pas ce produit à la pluie ou à l’humidité, afin de ne pas augmenter le risque d’incendie ou de choc électrique.
• Ne vous reposez pas sur ce testeur pour les conducteurs blindés.
• L’appareil ne doit pas entrer en contact avec une ligne d’une tension supérieure à 20 kV.
• Les câbles d’alimentation triphasée avec des conducteurs proches l’un de l’autre risquent d’annuler automatiquement le champ électrique et de ne pas être détectés par le TIC Tracer. Assurez­vous que la distance entre les conducteurs de phase est d’au moins 381 mm (15 po.) avant de tester des tensions alternatives.
DÉBALLAGE ET INSPECTION
Le carton d’emballage doit inclure les éléments suivants : 1 TIC 300 PRO 1 Pile alcaline de 9 V 1 Mode d’emploi 1 Mallette de transport Si l’un de ces éléments est endommagé ou manquant, renvoyez le contenu complet de l’emballage au lieu d’achat pour l’échanger.
3
INTRODUCTION
Le TIC 300 PRO est un appareil qui permet de vérifier en toute sécurité la présence d’une tension c.a. sans devoir débrancher les câbles, prises murales, fusibles, disjoncteurs, boîtiers de dérivation, etc. Aucune alimentation électrique n’est nécessaire pour le bon fonctionnement de l’appareil.
Robuste et fiable pour les applications de sécurité dans les services publics, l’industrie et le secteur minier, le TIC 300 PRO avertit des tensions dangereuses dans les applications en basse et moyenne tensions jusqu’à 122 kV sans entrer en contact avec le conducteur sous tension.
Fonctionnalités
Outil multifonction pour vérifier les lignes de transport d’énergie, le matériel de distribution d’énergie, les lignes électriques coupées, les fusibles et les connecteurs de rupture de charge
Réglage pour les tensions inférieures, pour contrôler la présence de tension dans les panneaux sectionneurs, sectionneurs, prises de courant et câblage
Vérifie la présence de la tension de 30 V c.a. à 122 000 V c.a. (122 kV)
Détection de tension c.a. sans contact
Indication visuelle et sonore de tension
Autotest pour vérifier le bon fonctionnement
du testeur
Forme ergonomique avec une poignée pratique
Résiste aux chutes d’une hauteur de 1,8 m
À utiliser avec une perche isolante TIC 410A Hot Stick pour les tensions supérieures à 1500 V
4
FONCTIONNEMENT Bouton MARCHE / ARRÊT
Lorsque le TIC 300 PRO est activé, le témoin à diode bleue et l’avertisseur sonore émettent des impulsions lentes au rythme de deux par seconde environ. Le témoin à diode rouge de la gamme HIGH s’allume.
Bouton TEST
Le bouton TEST doit être utilisé avant tout test d’un circuit d’énergie. La fonction TEST provoque l’émission Continue par les témoins bleus et l’arrêt de l’avertisseur sonore dans le mode LOW ou HIGH.
Distances d’isolement OSHA pour le travail en présence de tension électrique. Les conditions nationales ou locales peuvent être différentes.
Tension de ligne (kV)
phase à phase (pi.-po.) (m) (pi.-po.) (m)
0,03 à 1,0 note 1 note 1 note 1 note 1
1,1 à 15,0 2-1 0,64 2-2 0,66
15,1 à 36,0 2-4 0,72 2-7 0,77
36,1 à 46,0 2-7 0,77 2-10 0,77
46,1 à 72,5 3-0 0,90 3-6 1,05
72,6 à 121 3-2 0,95 4-3 1,29
Note 1 – Contact n’est pas nécessaire
Attention : en cas de test d’un circuit triphasé, si l’une des phases est ouverte, la tension provenant d’une autre phase peut être détectée et être à l’origine d’une indication erronée. Vérifiez toujours que les câbles de phase sont distants d’au moins 381 mm (15 po.) les uns des autres.
Phase à masse Phase à phase
5
Loading...
+ 63 hidden pages