Amprobe DM-II-PLUS Data sheet

Data Sheet
DM-II Plus
Power Quality Recorder
Amprobe’s DM-II PLUS is a full-featured three phase power quality recorder to maintain, diagnose and troubleshoot electrical systems. It measures and records a broad spectrum of power quality parameters. Easy to use, it’s capable of measuring and recording voltage, current, voltage anomalies (sags or surges), harmon­ics, energy and power (active, reactive and apparent), power factor (true and displacement), and frequency. This unique product comes as a complete kit with current transducers and an increased memory size for data storage, larger display size, and real-time downloading using Amprobe’s unique Download Suite software.
No hassle warranty
No waiting.
No shipping charges.
(note: $500 MSLP limit)
AC Current up to 1000A, AC Voltage, Active, Reactive and Apparent Power, Energy, Peak Demand & Power Factor
All readings are True RMS
5 built-in selectable languages: English, French, Italian, German and Spanish
User selectable rates allow recording from one hour to
several months
Works with single & three phase systems (Y & delta)
Readings and charts can be viewed on the DM-II LCD screen or downloaded to a PC
Capable of recording all parameters (single or three phase)
simultaneously
Optional transducers available for 100A and 3000A (flexible)
current capability.
Amprobe® Test Tools
www.Amprobe.com
DM-II Plus Power Quality Recorder
General Specifications
Mechanical Features Dimensions: 444.5(L) x 273.05(La) x 190.5(H) mm
17.50”(L) x 10.75” (La) x 7.50”(H) Weight: 11.5 Lb (5.2kg) Internal power supply: 6 batteries 1.5V D size NEDA 13A, IEC L20R Battery Life: 22 hours External power supply Use only Amprobe power supply Adapter code DMT-EXTPS. Display: dot matrix with backlight resolution 128 x 128 dots (16384 dots) dot size 0.5mm x 0.5mm visible area 73mm x 73mm (2.9” x 2.9”) No. of samples per period 128 Clamp: Opening: 53 mm (2.15”) Maximum diameter of the cable: 50 mm (2.00”) Reference temperature: 23°C ± 1°C (73°F ± 2°F) Operating temperature: 0°C to 50 °C (32°F to 122°F) Relative humidity: <70% Storage temperature: -10°C to 60 °C (14°F to 140°F) Storage humidity: <80% Location: Indoor operation, < 2000 m EMC/EMI/ESD EN61326-1:2006
Safety
The instrument complies to the standards: EN 61010-1 :2002 Insulation: Class 2 / Pollution Degree 2 Over-voltage category: CAT III 370V~ (Phase-Earth) CAT III 635V~ (Phase-Phase) Clamps: IEC 61010-2-032 Ed. 2.0 Phase Sequence Detection: EN 61557-7:2003
Data Sheet
Specifications Accuracy
Voltage measurement (Autoranging)
Range Accuracy Resolution Input impedance 15-370V ±(0.5% + 2 digit) 0.2V 300kW (phase-neutral) 310-635V ±(0.5% + 2 digit) 0.4V 600kW (phase-phase)
Voltage Anomalies Detection (Manual Selection of Range)
Voltage Range Accuracy Resolution Input impedance 15-370V ±(0.5% + 2 digit) 0.2V 300kW (phase-neutral) 30- 635V ±(0.5% + 2 digit) 0.4V 600kW (phase-phase)
Current measurement (DM-II Plus only)
Range Accuracy Resolution Input impedance Protection against overloads
0.005-0.26V ±(0.5%+2digit) 0.0001V 100kW 5V 0.26-1V 0.0004V
Current measurement (Using DM-CT-HTA)
Range Accuracy Resolution Protection against overloads 5 to 1000 A ±(1.5% of range) 0.1 A 600 V
Minimal Current measurable is equal to 1.5% of Clamp Full Scale
Amprobe® Test Tools
73°F± 2°F (23°C ± 1°C) with relative humidity < 75%
www.Amprobe.com
Loading...