Data Sheet
DM-III MULTITEST F
Power Quality Recorder
Amprobe’s full-featured Three-Phase Power Quality Recorders provide the essential functions and capabilities required to operate accurately and effectively in today’s demanding electrical environments.
POWER QUALITY ANALYZER/DATA LOGGER
True RMS (TRMS)
Measures & Records Broad Spectrum of Power Quality − Parameters
AC Current•
AC Voltage to 600 V•
Sags and Surges•
Harmonics•
Active, Reactive and Apparent•
Power•
Peak Demand•
Power Factor•
Frequency•
Phase Sequence•
Compatible with wide range of current transducers
Works with single and three phase
Detects & records Sags and Surges
Displacement power factor for power factor correction − determination
Built in scope displays waveforms
Phase sequence indication
Records up to 64 parameters
Selectable fundamental frequency
Special data compression system
Download capabilities, Windows compatible
A complete kit: 3000A Flexible CT, 1000A Clamp, Voltage − Leads, Ground Probes & Leads, PC software & cable
continued on next page
Amprobe® Test Tools
www.Amprobe.com
Page 2
INSULATION TESTER FUNCTIONS:
Tests insulation integrity of wires, cables, transformers & − electrical motors
Selectable test voltages up to 1000 V
Programmable timer to perform the Dielectric Absorption Ratio − Test
Sensitive Ohmmeter for checking resistance of motor windings
Selectable polarization of ohmmeter for checking grounding − continuity
Automatic voltmeter protects against misuse on hazardous − energized systems
GROUND RESISTANCE & RESISTIVITY FUNCTIONS:
Three measuring modes:
2 point continuity/resistance test•
3 point Fall of Potential test•
4 point Earth Resistivity measurement•
Automatic voltage measurement prevents false measurements
Automatically applies three testing frequencies for the most − accurate readings
Detects faulty test conditions such as poor soil conditions and − input noise
PHASE SEQUENCE
Phase sequence indication
Frequency measurement
Phase-to-Phase voltage measurement
Data Sheet
Amprobe® Test Tools
Page 3
DM-III MULTITEST F Power Quality Recorder
Data Sheet
Specifications
Supplied Current Transducer AM-FLEX33 3000A Flexible 7” internal diameter CT Input accuracy ±(0.5% Rdg + 2 LSD) AC Current DM-CT-100: 0.5A to 100A; DM-CT-HTA: 5 – 1000A; AM-FLEX33: Selectable: 5 – 1000A or 15 – 3000A AC Voltage including
Sags and Surges ±(0.5% Rdg + 2 LSD) Harmonics ±(0.5% Rdg + 2 LSD) @DC to 25 harmonics** Power Working (W), Reactive (VAR) and Apparent (VA) ±(1.0% Rdg + 2 LSD) Energy Working (kWh), Reactive (VARh) and Apparent (VAh) ±(1.0% Rdg + 2 LSD) Peak Demand KW ±(1.0% Rdg + 2 LSD) Power Factor 0.00 – 1.00 Frequency measurement 57 to 63.6 Hz at 60Hz fundamental; 47 to 53 Hz at 50Hz fundamental; ±(1.0% Rdg + 2 LSD) Phase sequence 1 - 2 - 3 Co-generation Computes incoming and outgoing energy Selectable Fundamental
Frequencies 50/60 Hz Available Recording Time Several hours to several years depending on setup
Megohmmeter Range Accuracy
Insulation resistance with 50 VDC test voltage 0.01 – 19.99, 49.9 ± (2% Reading + 2 digits)
49.9 – 99.9MΩ ± (5% Reading + 2 digits)
Insulation resistance with 100 VDC test voltage 0.01 – 19.99, 99.9 ± (2% Reading + 2 digits)
99.9 – 199.9MΩ ± (5% Reading + 2 digits)
Insulation resistance with 250 VDC test voltage 0.01 – 19.99, 199.9, 249 ± (2% Reading + 2 digits)
249 – 499 MΩ ± (5% Reading + 2 digits)
Insulation resistance with 500 VDC test voltage 0.01 – 19.99, 199.9, 499 ± (2% Reading + 2 digits)
499 – 999 MΩ ± (5% Reading + 2 digits)
Insulation resistance with 1000 VDC test voltage 0.01 – 19.99, 199.9, 999 ± (2% Reading + 2 digits)
999 – 1999 MΩ ± (5% Reading + 2 digits)
Low Resistance (without timer) 0.01 – 19.99, 99.9Ω ± (2% Reading + 2 digits) Low Resistance (with timer) 0.01 – 9.99Ω ± (2% Reading + 2 digits)
Ground Resistance Range Accuracy
Ground resistance 0 – 19.99, 199.9, 1999 Ω ± (5% Reading + 3 digits) Ground resistivity 0.6 – 125.6 Ωm ± (5% Reading + 3 digits)
0.125 – 1.256, 19.99, 199.9 kΩm ± (5% Reading + 3 digits)
LowΩ : 200mA Continuity Test (AUTO, RT+, RT- Mode)
Range [Ω] Resolution [Ω] Accuracy(*)
0.01 – 9.99 0.01 ±(2% Reading + 2 digit)
10.0 – 99.9 0.1 ± (2% Reading + 2 digit) (*) After Test leads calibration Test Current > 200mA DC per R5Ω (Test leads included) Resolution for Test current 1mA Open Circuit Voltage 4V V0 24V
www.Amprobe.com
Page 4
DM-III MULTITEST F Power Quality Recorder
Specifications (continued)
Insulation Test
Test Voltage [V] Range [MΩ] Resolution [MΩ ] Accuracy 50 0.01 – 9.99 0.01 ±(2% Reading + 2 digit)
10.0 – 49.9 0.1 ±(2% Reading + 2 digit)
50.0 – 99.9 0.1 ±(5% Reading + 2 digit)
100 0.01 – 9.99 0.01 ± (2% Reading + 2 digit)
10.0 – 99.9 0.1 ±(2% Reading + 2 digit)
100.0 – 199.9 0.1 ± (5% Reading + 2 digit)
250 0.01 – 9.99 0.01 ± (2% Reading + 2 digit)
10.0 – 199.9 0.1 ± (2% Reading + 2 digit) 200 – 249 1 ± (2% Reading + 2 digit) 250 – 499 1 ± (5% Reading + 2 digit)
500 0.01 – 9.99 0.01 ± (2% Reading + 2 digit)
10.0 – 199.9 0.1 ± (2% Reading + 2 digit) 200 – 499 1 ± (2% Reading + 2 digit) 500 – 999 1 ± (5% Reading + 2 digit)
1000 0.01 – 9.99 0.01 ±(2% Reading + 2 digit)
10.0 – 199.9 0.1 ± (2% Reading + 2 digit) 200 – 999 1 ± (2% Reading + 2 digit) 1000 – 1999 1 ±(5% Reading + 2 digit) Open circuit Test Voltage <1.3 x Nominal Test Voltage Short Circuit Current <6.0mA with 500V Test Voltage Nominal Test Current 500V: >2.2mA with 230kΩ ;
other: >1mA with 1kΩ*Vnom
Data Sheet
Frequency Measurement
Range [Hz] Resolution [Hz] Accuracy
47.0 – 63.6 0.1 ± (0.1%Reading+1 digit) RCD and LOOP function are active only for 50Hz ± 0.5Hz frequency
Phase Rotation: Voltage Measurement
Range [V] Resolution [V] Accuracy 0 – 460V 1 ±(3%Reading + 2 digit)
Ground Test: Resistance Measurement With Earth Rods
Range RE [Ω] Resolution [Ω]
0.01 – 19.99 0.01
20.0 – 199.9 0.1 200 - 1999 1 Accuracy ±(5% Reading + 3 digit) Test Current <10mA – 77.5Hz Open circuit Test Voltage <20V RM
Amprobe® Test Tools
Page 5
DM-III MULTITEST F Power Quality Recorder
Specifications (continued)
Ground Test: Resistivity Measurement
Range p Resolution
0.60 – 19.99 Ωm 0.01 Ωm
20.0 – 199.9Ωm 0 .1Ωm 200 – 1999Ωm 1 Ωm
2.00 – 99.99kΩm 0.01 kΩm
100.0 – 125.6kΩm(*) 0.1 kΩm (*) setting distance = 10m Accuracy ±(5% Reading + 3 digit) Test Current <10mA – 77.5Hz Open circuit Test Voltage <20V RMS
Voltage Measurement – (Autorange)
Range [V] Resolution [V] 15 – 310V 0.2V 310 – 600V 0.4V Accuracy ±(0.5% Reading+2digit)
Voltage Sag And Surge Detection –(Manual Range)
Range [V] Resolution (Voltage) 15 – 310V 0.2V 30 – 600V 0.4V Resolution (Time) 10ms ( _ period) Accuracy (Voltage) ±(1.0% Reading+2digit) Accuracy ( Rif. 50hz) (Time) 10ms (_ period) Input Impedance 300kΩ (Phase-Neutral); 300kΩ (Phase-Phase)
Data Sheet
Current Measurement – STD & FlexEXTclamps
Range [V] Resolution [Mv]
0.005 – 0.26V 0.1
0.26 – 1V 0.4 (*): Example : with a 1000A/1V full scale clamp, the instrument detect only current higher than 5A Accuracy ±(0.5% Reading+2digit) Input Impedance 200kΩ Overload Protection 5V
Current Measurement – FlexINT clamp – 1000A Range
Current Range Input Voltage Range Resolution Accuracy
5.00 – 20.00A 425µV – 1.7mV 0.850µV ± (4.0%rdg + 8.5µV)
20.00 – 99.99A 1.7mV – 8.499mV 0.850µV ± (1.0% rdg + 8.5µV)
100.0 – 999.9A 8.5mV – 84.99mV 8.5µV ± (1.0% rdg + 85µV) Input Impedance 9.16 6kΩ Overload Protection 5V
www.Amprobe.com
Page 6
DM-III MULTITEST F Power Quality Recorder
Specifications (continued)
Current Measurement – FlexINT clamp – 3000A Range
Current Range Input Voltage Range Resolution Accuracy
15.00 – 99.99A 1.27mV – 8.499mV 0.850µV ± (1.0% rdg + 8.5µV)
100.0 – 270.0A 8.5mV – 22.75mV 8.5µV ± (1.0% rdg + 42.5uV
270.0 – 999.9A 22.75mV – 84.99mV 8.5µV ± (1.0% rdg + 85uV)
1.00 – 3.00kA 85mV – 255mV 850µV ± (0.5% rdg + 8.5mV)
Input Impedance 9.7kΩ Overload Protection 5V
Power Measurement – (Autorange)
Quantity Range Resolution Active Power 0 – 999.9W 0.1W 1 – 999.9kW 0.1kW 1 – 999.9MW 0.1MW 1000 – 9999MW 1MW Reactive Power 0 – 999.9VAR 0.1VAR 1 – 999.9kVAR 0.1kVAR 1 – 999.9MVAR 0.1MVAR 1000 – 9999MVAR 1MVAR Apparent Power 0 – 999.9VA, 0.1VA 1 – 999.9kVA, 0.1kVA 1 – 999.9MVA 0.1MVA 1000 – 9999MVA 1MVA Active Energy (Classe2 EN61036) 0 – 999.9Wh, 0.1Wh 1 – 999.9kWh, 0.1kWh 1 – 999.9MWh 0.1MWh 1000 – 9999MWh 1MWh Reactive Energy (Classe3 IEC1268) 0 – 999.9VARh, 0.1VARh 1 – 999.9kVARh, 0.1kVARh 1 – 999.9MVARh 0.1MVARh 1000 – 9999MVARh 1MVARh Accuracy ±(1.0%Reading+2digit)
Data Sheet
Cos j Measurement
Cos J Accuracy [°]
1.00 – 0.80 0.6
0.80 - 0.50 0.7
0.50 – 0.20 1.0 Resolution 0.01
Voltage and Current Harmonics Measurement
Range Accuracy DC – 25H ±(5% + 2 digit) 26H – 33H ±(10% + 2 digit) 34H – 49H ±(15% + 2 digit) Resolution 0.1V / 0.1A Harmonics values are null under fixed threshold:
- DC: its values is null if it is < 2%of Fundamental or is <2% of Full Scale clamp
- 1st Current Harmonic: its values is null if it is < 0.2% Full Scale clamp
- 2nd – 49th: its values is null if it is < 0.5% of fundamental or is < 0.1% of Full Scale clamp
Amprobe® Test Tools
Page 7
DM-III MULTITEST F Power Quality Recorder
Technical Data – General Information
General
Safety EN 61010-1 + A2 (1997) Protection Classification Class 2 - Double Insulation Pollution Degree 2 Degree of Protection IP50 Over-Voltage Category CAT II 600V~ / 350V~ (phase –earth); CAT III 600V~ / 300V~ (phase –earth) Usage Indoor; max height 2000m EMC EN61326-1 (1997) + A1 (1998)
The Instrument complies with European Guidelines for CE mark
Safety Test
Low½ (200mA) IEC 61557-4 Insulation Test IEC 61557-2 Phase Sequence IEC 61557-7 Ground Test IEC 61557-5
Power Quality
Voltage Sag and Surge EN50160 Alternating Current Static Watt-hour meters for Active Energy EN61036 (CLASS 2) Alternating Current Static VAR-hour Meters for Reactive Energy IEC1268 (CLASS 3)
General Specifications
Mechanical Data Dimensions 225 (L)x165 (W) x 105 (H)mm Weight 1,2Kg approx Power Supply 6 x 1.5-LR6-AA-AM3-MN 1500 batteries
Battery Life
Low½ ~ 800 test Insulation Test ~ 500 test Ground Test ~ 1000 test Phase Sequence ~ 1000 test Power Quality (recording) ~20 hours External Power Supply Adapter Code DMT-EXTPS (only for POWER QUALITY function)
Display
Display Type Graphic with Backlight Resolution 128x128 Visible Area 73mmx73mm
Memory
Safety Test Memory 999 measurement Power Quality 2MByte (with 63 channels select and Integration Period = 15min -> more than 30 days).
Environment
Reference Temperature 23° ± 5°C Working Temperature Range 0° – 40°C Working Humidity < 80% Storage Humidity Range -10 – 60°C Storage Humidity < 80%
Data Sheet
www.Amprobe.com
Page 8
Includes Amprobe's Download Suite Software
Replacement Parts (supplied with product)
AM-FLEX33 3000A Flexible CT DM-CT-HTA 1000AClamp HW1254A Soft Carrying case DMT-EXTPS External power supply 12VDC MTL-VOLT Complete set of voltage and megohmmeter
test leads and alligator clips
MTL-EARTH Carrying case containing: 4 earth rods and 4
test leads (banana – alligator clip) C-2001 Special RS-232 Computer Cable www.amprobe.com PC Software www.amprobe.com Instruction Manual
Data Sheet
Optional Accessories
DM-CT-HTA 1000A Clamp DM-CT-100 100A Compact Clamp (0.5Ato 100A) RS-USB USB-RS-232 Adapter CC-DM-III Hard Case
Amprobe® Test Tools
website: www.Amprobe.com email: info@amprobe.com Everett, WA 98203 Tel: 877-AMPROBE
Amprobe® Test Tools Europe
Amprobe Test Tools Europe Beha-Amprobe GmbH In den Engematten 14 79286 Glottertal, Germany Tel.: +49 (0) 7684 8009 - 0
Amprobe® Test Tools
©2009 A mprobe Test Tools. All rights re served. 04/200 9 34653 48 Rev A
www.Amprobe.com
Loading...