Most Compact High Performance Power Quality Analyzer in its Class
Poor power quality is costly – not only can it drive up energy
bills with excessive power usage, but equipment failure or
damage caused by poor power quality is expensive and timeconsuming to diagnose and repair. Productivity and process
also suffer with faulty equipment or unscheduled outages.
The new Amprobe DM-5 Power Quality Analyzer allows you
to easily and quickly discover the source and magnitude of
power quality issues.
DM-5 Highlights
At half the size of previous models, the compact DM-5
brings speed and efciency to power quality jobs ranging
from routine maintenance to in-plant troubleshooting of
individual machinery and power distribution panels. Built
for use in even the largest facilities, the DM-5 is safety tested
to meet the world’s most prestigious safety standards and is
rated to CAT IV 300 V, CAT III 600 V, CAT II 1000 V.
Real-Time Checks with Large, Full-Color
Screen. During and after measurements, the
on-board screen displays data graphs and values
in full color for easy comparison. Additionally, the
Print Screen quick-button makes it simple to save
momentary readings for later comparison.
Full Analysis with Included Software
Quickly analyze your recorded data to identify
potential issues with report generation and data
visualization.
Quick Setup with On-Screen Guide. A stepby-step setup guide helps ensure you capture the
right measurements. Simply select the parameters
to test, follow the on-screen guide for wiring
conguration, and be alerted to any incorrect
settings before testing begins.
Complete Power Quality Kit.
The DM-5 comes complete with the accessories
needed to quickly get to work, including light
weight ex clamps with user selectable input
ranges of 300 A, 1000 A, or 3000 A.
Wireless Control for Remote Checks
and Adjustments. Adjust settings and
transfer data remotely by connecting the DM-5
to compatible Bluetooth® enabled Windows®
and Android® devices. This provides added
convenience and safety, allowing for easy testing
modications even when the main unit is in
difcult to access locations.
Applications
Harmonics
Harmonics often cause tripped circuit breakers,
blown fuses, irregular electrical noises and
overheating of electrical systems. Use the DM-5 to
identify problematic harmonics, evaluate both the
magnitude of harmonic frequencies present and
the amount of total harmonic distortion.
Analyze Power Efciency
With the DM-5, you can simultaneously measure
up to 1,000 parameters to analyze wherever
excessive power loss or other power problems
may exist.
Pinpoint Transients
Transients can cause problems ranging from
simple equipment malfunction to full equipment
failure. Recording data over a prolonged period
can help isolate when and where infrequent
transients occur, helping identify root causes
ranging from nearby lightning strikes to the
switching of loads.
Capture Sags and Swells
The high performance processor of the DM-5
captures sags and swells, common causes of
equipment failure and irregular electrical noises.
Monitor Voltage Unbalance
Monitoring for unbalance with the DM-5 can
help identify issues before they result in costly
equipment damage. Unbalance often causes
excessive overheating, leading to motor failure
and other problems within distribution systems.
Page 3
Specifications
FeaturesDM-5 Power Quality Analyzer
Wiring connection
Measurements and parameters
Voltage (rms)
Current (rms)
Swell / dip / interruption
Power and energy
Power factor
Harmonics
Flicker
Unbalance
Transient
Inrush current
Capacitance
Voltage, current, frequency, active power, reactive power, apparent power, active energy, reactive energy, apparent energy, power factor (cos ø), neutral current,
demand, harmonics, quality (swell/dip/interruption, transients/overvoltage, inrush current, unbalance rate), capacitance calculation for PF correction unit, icker
Allowable input: 1% to 120% of each range (rms). 200% of each range (peak)
Accuracy: ±0.2% + 0.2%f.s. + accuracy of ex current sensor (sine wave, 40 Hz to 70 Hz)
Allowable input: 1% to 110% of each range (rms). 200% of each range (peak)
Active power accuracy: ±0.3% + 0.2%f.s. + accuracy of ex current sensor (PF 1, sine wave, 40 Hz to 70 Hz)
accuracy (<10% to max. input range): ±1.0% + ex current sensor
Watts: 0.0% to 100.0%, accuracy: ±0.3% + 0.2%f.s. + accuracy of ex current sensor (PF 1, sine wave, 50/60 Hz)
Volts: 0.00% to 100.00%, accuracy: ±0.3% at 50/60 Hz, sine wave (0.00% to 5.00% according to IEC 61000-4-030)
Amps: 0.0% to 100.0%, accuracy (≥10% to max. input range): ±10% + ex current sensor.
Measurement method: Complied with IEC 61000-4-30 and IEC 61000-4-15 Ed.2
Accuracy: ±0.2% + 0.2%f.s.(sine wave, 40 Hz to 70 Hz)
Threshold value: In percentage of nominal voltage value
Inuence of power factor: ±1.0% (PF 0.5, 40 Hz to 70 Hz )
Accuracy: ±1dgt against each calculated value (for sum: ±3dgt)
Volts: 0.0% to 100.0%, accuracy (≥3% at 100 V nominal voltage): ±10%
accuracy (<3% at 100 V nominal voltage): ±0.3% of nominal voltage
THD: 0.0% to 100.0%, Phase angle: 0.0°⁰ to ± 180°⁰
Displayed items: Pst(1min), Pst, Plt, Max Pst, Max Plt, V, time left
Accuracy: Pst (max.20): ±10% according to IEC 61000-4-15
Accuracy: ±0.4% + 0.4%f.s. + accuracy of ex current sensor
Threshold value: In percentage of the measurement range
Range: 0.000 nF to 9999 F, 0.000 kvar to 999 kvar
1P2W, 1P3W, 3P3W, 3P4W
Range: 600.0 / 1000 V
Display range: 0.15% to 130 % of each range
Display range: 0.15% to 130 % of each range
CT-53 ex current sensor (3-ch): max. 6000 kW
CT-500 ex current sensor (1-ch): max. 1000 kW
Crest factor: 3 or less
Sampling speed of voltage transient: 24 µs
Input impedance: approx. 1.67 MΩ
Crest factor: 3 or less
Input impedance: approx. 100 kΩ
Range: same as Voltage (rms)
Accuracy: ±1.0% of nominal voltage
Wh: 0.00000 mWh to 9999.99 TWh
VAh: 0.00000 VAh to 9999.99 TVAh
varh: 0.00000 varh to 9999.99 Tvarh
Display range: -1.000 to 0.000 to 1.000
Harmonics order (n): 1 to 50th
Inter-harmonics order (n): 1 to 50th
accuracy (1000 V range): ±0.2% + 0.2%f.s
Current: 0.00% to 100.00%
Approx. 40.96 ksps (every 2.4 µs)
Range: 50 V to 2200 Vdc
Accuracy: ±0.5% at 1000 Vdc
Range: same as Current (rms)
amprobe.com
General Specications
Display
Display update
Operating temperature and
humidity
*There may be time lag in display update (max. 2 seconds) due to arithmetic processing. However, no time lag between the recorded data and the time stamp.
32°F to 104 °F (0 °C to 40 °C), ≤ 85 %RH (no condensation)
Guaranteed accuracy at 73 °F ± 9 °F (23 °C ± 5 °C), ≤ 85 %RH (no condensation)
Operating altitude
Pollution degree
Dust/water proof
Drop proof
Storage temperature and humidity
Power supply
-4 to 140 °F (-20 °C to 60 °C), ≤ 85 % RH (no condensation)
AC power supply: AC100 V to AC 240 V, 50 Hz to 60 Hz, 7 VAmax.
Battery life
EMC
Safety compliance
Power quality measurement
Certication
Dimensions (L x W x D):
Weight:
Accessories included: Test leads with alligator clips (4), US power cord, CT-53 ex AC current clamp, CT-500 ex AC current clamp, SD card, User manual, PC software, AA batteries (6)
3.5inch, TFT, QVGA(320xRGBx240)
Every 1 second*
0 to 6,561 ft (0 to 2,000 m)
2
IP 40
3.3 ft (1 m)
Battery: 6 x AA 1.5 V Alkaline battery (LR6)
Current consumption: 1.0 A at 3.0 Vdc (typical)
UL/IEC 61010-1, IEC 61010-031, IEC 61010-2-030
Complies with IEC 61000-4-030 ed.2 Class S
3 hours (typical)
Meets EN 61326-1
6.9 x 4.7 x 2.7 in (17.5 X 12 X 6.8 cm)
Approx. 2.0 lb (900 g) with batteries installed
Page 4
amprobe.com
Specifications
FeaturesCT-53 Flex Current SensorCT-500 Flex Current Sensor
Current ranges
Output voltage
Measuring range
Accuracy (sine wave)
Phase characteristics
Working voltage
Max allowed input
Measurable conductor size
Head circumference
Head cable diameter
Cable length (head to electronics)
Cable length (output cable)
Output terminal
Output impedance
Current consumption
(at power supply 3 V)
Operating temperature and
humidity
Storage temperature and humidity
Operating altitude
EMC
Safety compliance
Certication
Weight
32 °F to 122 °F (0 °C to 50 °C), ≤85 %RH (no condensation)
Guaranteed accuracy at 73 °F ± 9 °F (23 °C ± 5 °C), ≤85 %RH (no
-4 to 140 °F (-20 °C to 60 °C), ≤ 85 % RH (no condensation)-4 to 140 °F (-20 °C to 60 °C), ≤ 85 % RH (no condensation)
300 A / 1000 A / 3000 A, AC rms1000 A, AC rms
300 A range: 500 mVac / 300 Aac (1.67 mV / A)
1000 A range: 500 mVac / 1000 Aac (0.5 mV / A)
3000 A range: 500 mVac / 3000 Aac (0.167 mV / A)
300 A range: 30 A to 300 A (424 Apeak)
1000 A range: 100 A to 1000 A (1414 Apeak)
3000 A range: 300 A to 3000 A (4243 Apeak)
±1.0% (45 Hz to 65 Hz)
300 A range: 30 A to 300 A (45 Hz to 65 Hz)
1000 A range: 100 A to 1000 A (45 Hz to 65 Hz)
3000 A range: 300 A to 3000 A (45 Hz to 65 Hz)
3600 Aac continuous (45 Hz to 65 Hz)1300 Aac continuous
UL/IEC 61010-1, IEC 61010-2-030, IEC 61010-2-032
Measurement CAT III 600 V, Pollution degree 2
Within ±1°⁰
600 Vac rms600 Vac rms
Max. 5.9 in (15 cm) diameterMax. 4.3 in (11 cm) diameter
21.65 in (55 cm)15.75 in (40 cm)
0.56 in (14.3 mm)0.33 in (8.5 mm)
Approx. 6.56 ft (2 m)Approx. 8.56 ft (2.7 m)
Approx. 3.28 ft (1 m)Approx. 0.66 ft (0.2 m)
Mini-DIN-6 connectorMini-DIN-6 connector
100 Ω or less100 Ω or less
15 mA (typical)Max. 2 mA (typical)
14 °F to 122 °F (-10 °C to 50 °C), ≤85 %RH (no condensation)
condensation)
0 to 6,561 ft (0 to 2,000 m)0 to 6,561 ft (0 to 2,000 m)
EN 61326EN 61326
(UL tested with DM-5) (UL tested with DM-5)
Approx. 2.1 lb (950 g)Approx. 0.4 lb (180 g)
Guaranteed accuracy at 73 °F ± 9 °F (23 °C ± 5 °C), ≤85 %RH (no
Measurement CAT III 600 V, CAT IV 300 V, Pollution degree 2
500 mVac / 1000 Aac (0.5 mV / A)
0 to 1000 A (1850 Apeak)
±0.8% ± 0.2 mV (45 Hz to 65 Hz)
±1.5% ± 0.2 mV (40 Hz to 1 kHz)
45 Hz to 65 Hz within ±2°⁰
40 Hz to 1 kHz within ±3°⁰
condensation)
UL/IEC 61010-1, IEC 61010-2-030, IEC 61010-2-032
Optional AccessoriesPC-5 AC Line Power AdaptorCC-5 Carrying Case with Magnet
Rated voltage
Max. input voltage
Fuse
Safety compliance
Certication
Dimensions (L x W x D)
Approx. 3.0 x 2.2 x 1.8 in (7.6 x 5.5 x 4.6 cm) excludes the cord and plug5.3 X 3 X 5.4 in. (13.5 X 7.5 X 13.7 cm)
Weight
All Amprobe tools, including the Amprobe DM-5, are rigorously tested for safety, accuracy, reliability and ruggedness in our state-of-the-art Fluke test lab. In
addition, Amprobe products that measure electricity are listed by a 3rd party safety lab, either UL or CSA. This system assures that Amprobe products meet or exceed safety
regulations and will perform in a tough, professional environment for many years to come.
100 Vac to 240 Vac rms, 45 Hz to 60 Hz–
240 Vac rms–
AC 500 mA / 600 V min., fast-acting, Ø6.3 x 32 mm–