Amprobe CT-53 Users Manual

Page 1
CT-53
3000 A Flexible 3-Sensor Current Transducer
Instruction Manual
Manual de usuario
Manuel de l’utilisateur
Page 2
Page 3
CT-53
Instruction Manual
11/2015, 6006998 A ©2015 Amprobe. All rights reserved. Printed in Japan
English
Page 4
Limited Warranty and Limitation of Liability
Your Amprobe product will be free from defects in material and workmanship for one year from the date of purchase unless local laws require otherwise. This warranty does not cover fuses, disposable batteries or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling. Resellers are not authorized to extend any other warranty on the behalf of Amprobe. To obtain service during the warranty period, return the product with proof of purchase to an authorized Amprobe Service Center or to an Amprobe dealer or distributor. See Repair Section for details. THIS WARRANTY IS YOUR ONLY REMEDY. ALL OTHER WARRANTIES - WHETHER EXPRESS, IMPLIED OR STATUTORY - INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, ARE HEREBY DISCLAIMED. MANUFACTURER SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, ARISING FROM ANY CAUSE OR THEORY. Since some states or countries do not allow the exclusion or limitation of an implied warranty or of incidental or consequential damages, this limitation of liability may not apply to you.
Repair
All Amprobe returned for warranty or non-warranty repair or for calibration should be accompanied by the following: your name, company’s name, address, telephone number, and proof of purchase. Additionally, please include a brief description of the problem or the service requested and include the test leads with the meter. Non-warranty repair or replacement charges should be remitted in the form of a check, a money order, credit card with expiration date, or a purchase order made payable to Amprobe.
In-warranty Repairs and Replacement – All Countries
Please read the warranty statement and check your battery before requesting repair. During the warranty period, any defective test tool can be returned to your Amprobe distributor for an exchange for the same or like product. Please check the “Where to Buy” section on www.Amprobe.com for a list of distributors near you. Additionally, in the United States and Canada, in-warranty repair and replacement units can also be sent to an Amprobe Service Center (see address below).
Non-warranty Repairs and Replacement – United States and Canada
Non-warranty repairs in the United States and Canada should be sent to an Amprobe Service Center. Call Amprobe or inquire at your point of purchase for current repair and replacement rates.
USA: Canada: Amprobe Amprobe Everett, WA 98203 Mississauga, ON L4Z 1X9 Tel: 888-993-5853 Tel: 905-890-7600 Fax: 425-446-6390 Fax: 905-890-6866
Page 5
CT-53 3000 A Flexible 3-Sensor Current Transducer
CONTENTS
INTRODUCING THE CT-53 ................................................................................. 2
SYMBOL ............................................................................................................. 4
SAFETY INFORMATION ..................................................................................... 4
MEASUREMENTS ............................................................................................... 5
MAINTENANCE .................................................................................................. 8
SPECIFICATIONS ................................................................................................ 8
1
Page 6
INTRODUCING THE CT-53
The CT-53 Flexible 3-Sensor Current Transducer is an optional accessory that is used to measure current up to 3000A on the Amprobe DM-5 Power Quality Analyzer. The flexible and light weight measuring head is ideal for current measurement on thick and hard to reach conductors without breaking the circuit. The circuit box contains measuring circuits for 3-channel.
Coupling point of the measuring head
Current
range
indicator
Flexible measuring head
Output terminal plug
Cable
Circuit box
Range selection button
Output cable
2
Page 7
Pins of output terminal
Match the and
and connect the Cable.
mark under CH No.
mark on the Output Cable
Output signal
Power supply
Output Terminal
• Output signal is between pin 3 and 5 of output terminal and between 4 and 6 of output connector.
• The current clamp is powered via pin 1 and 3 (2.7 to 5.5 V, 200 mA) of output terminal and pin 2 and 4 of output connector.
• Resistance between 3 and 6 of Output terminal and between 4 and 5 of Output connector is as stated below: 300A range: 910 kΩ 1000A range: 360 kΩ 3000A range: 510 kΩ (Resistance cannot be measured while the instrument is powered off.)
• Connecting terminal on DM-5 is symmetrical to above pin configurations.
2.7~5.5V
COM(Output(-))
Output(+)
Output Connector
3
2.7~5.5V
COM(Output(-))
Output(+)
Page 8
SYMBOLS
Do not apply around, or remove from, HAZARDOUS LIVE conductors.
Caution! Risk of electric shock.
Caution! Refer to the explanation in this manual.
W
Alternating current (AC).
B
The equipment is protected by double insulation or reinforced
T
insulation.
Underwriters Laboratories (applies to Canada and U.S.A.)
Complies with European directives.
P
Cumple las normas australianas pertinentes
Do not dispose this product as unsorted municipal waste.
=
Contact aqualified recycler.
SAFETY INFORMATION
The current transducer complies with:
• UL/IEC 61010-1, Measurement CAT III 600 V, Pollution degree 2
• IEC 61010-2-030
• IEC 61010-2-032
• EMC IEC 61326-1
CENELEC DIRECTIVES
The instruments conform to CENELEC Low-voltage directive 2006/95/EC and Electromagnetic compatibility directive
2004/108/EC.
W
Warning: Read before Using
To ensure safe operation and service of the current transducer, follow these instructions:
• Read the operating instructions before use and follow all safety instructions.
• Use the current transducer only as specified in the operating instructions; otherwise the current transducer’s safety features may be compromised.
• Adhere to local and national safety codes. Individual protective equipment must be used to prevent shock and arc blast injury where hazardous live conductors are exposed.
4
Page 9
• Before each use, inspect the current transducer and its latching system for any damage. Pay particular attention to the insulation surrounding the flexible measuring head. Look for cracks or missing portions of the current transducer housing or output cable insulation. Also look for loose or weakened components.
• Do not use a current transducer that is cracked, damaged, or has a defective cable.
• Never use the current transducer on a circuit with voltages higher than 600 V CAT III.
−CATIIIequipmentisdesignedtoprotectagainsttransientsin equipment in fixed equipment installations, such as distribution panels, feeders and short branch circuits, and lighting systems in large buildings.
• De-energize the installation on which current will be measured or adopt safe operating procedures during application and removal of the current transducer.
• Use extreme caution when working around bare conductors or bus bars.
• Do not use the current transducer to measure bare conductors carrying a
voltage from 30V up to 600V unless you are wearing protective clothing suitable for high-voltage work. Contact with the conductor could result in electric shock. Always use appropriate equipment for personal protection.
• Use caution when working with voltages above 60 V dc, 30 V ac rms or 42 V ac peak. Such voltages pose a shock hazard.
• Never apply to current exceeding the measuring range.
• Ensure that no foreign object obstructs the latching mechanism.
• Do not operate the current transducer around explosive gas, vapor, or dust.
• Do not step on or pinch the cord. It may damage the insulation.
• Do not expose the current transducer to direct sunlight, high
temperatures/humidity or dew. It may cause deformation or insulation degradation.
MEASUREMENTS
W
Warning
To avoid electric shock or personal injury:
• Do not use the current transducer on a circuit with voltages higher than 600 V CAT III.
• De-energize the installation on which current will be measured or adopt safe operating procedures during application and removal of the current transducer.
• Disconnect CT-53 from DM-5 by removing CT-53 output terminal plug. Do not pull CT-53 output cable.
5
Page 10
To measure AC current:
1. Connect CT-53 output terminals to DM-5 current input terminals (A1, A2, A3). Observe the arrow marks for correct connection.
2. Power on DM-5 (unit auto-detects the current transducer connected).
3. Unlock the flexible measuring head according to the followings:
Joint
1
Sensor
Press
2
Unlock
6
Page 11
4. Connect the flexible measuring head around the conductor.
5. Make sure the arrow marked on the measuring head coupling points towards the current flowing direction of the conductor, and position the conductor under test as shown below.
LoadSource
Note 2
Note 1
Note 2
Note 1: Reference measurement position of the conductor. Maximum
Guide arrow mark
coupling diameter: 20 mm for published accuracy. Note 2: Keep minimum 65 mm to ensure published accuracy.
6. Ensure the coupling point of the flexible measuring head is firmly locked.
7. Press RANGE button to select any desirable range (300A/ 1000A/ 3000A). When powering off the instrument once and powering on again, the range will be the same one selected prior to powering off the instrument.
W
Caution
• The coupling point may disconnect if excessive pulling force is applied.
• Clamp onto one conductor only. Measurement cannot be made when clamping single-phase (2-wire) or threephase (3-wire) at the same time.
7
Page 12
MAINTENANCE
Before each use, inspect the flexible current transducer and its latching system for any damage for continued safety. Pay particular attention to the insulation surrounding the flexible measuring head. The flexible current transducer and its latching system require no special care. Ensure that no foreign object obstructs the latching mechanism. Clean the CT-53 with a damp cloth and a mild detergent. Do not use abrasives,
solvents, or alcohol.
If CT-53 does not perform properly, use the following steps to help isolate the problem:
• Inspect the coupling system for any damage. If a foreign material is present, the coupling system will not close properly and errors will result.
• Inspect the cables between the flexible measuring head and CT-53 circuit box. Also inspect between the CT-53 circuit box and DM-5 for any damage.
• Check the selected RANGE on the circuit box and ensure that the RANGE indicator is ON.
• Verify the transducer setting on DM-5 is correct.
SPECIFICATIONS
Current range
Output voltage
Measuring range
Conductor size Ø20 mm (0.787 in) maximum for published accuracy
Accuracy (sine wave)* ±1.0% (45 Hz to 65 Hz)
Phase characteristics
300 A / 1000 A / 3000 A AC rms
300 A range: 500 mVac / 300 Aac (1.67 mV / A) 1000 A range: 500 mVac / 1000 Aac (0.5 mV / A) 3000 A range: 500 mVac / 3000 Aac (0.167 mV / A)
300 A range: 30 A to 300 A (424 Apeak) 1000 A range: 100 A to 1000 A (1414 Apeak) 3000 A range: 300 A to 3000 A (4243 Apeak)
Within ±1 300 A range: 30 A to 300 A (45 Hz to 65 Hz) 1000 A range: 100 A to 1000 A (45 Hz to 65 Hz) 3000 A range: 300 A to 3000 A (45 Hz to 65 Hz)
o
8
Page 13
Working voltage 600 Vac rms
Max allowed input 3600 Aac continuous (45 Hz to 65 Hz)
Possible measurable conductor size
Max. Ø150 mm (5.9 in) (accuracy error not specified)
Head circumference 550 mm (21.65 in)
Head cable diameter 14.3 mm (0.56 in)
Cable length (head to electronics)
Cable length (output cable)
Approx. 2 m (6.56 ft)
Approx. 1 m (3.28 ft)
Output terminal Mini-DIN-6 connector
Output impedance 100 Ω or less
Current consumption (at power supply 5 V)
Operating temperature and humidity
Storage temperature and humidity
15 mA (typical)
o
F to 122 oF (0 oC to 50 oC), 85 %RH (no
32 condensation) Guaranteed accuracy at 73
o
F ± 9 oF (23 oC ± 5 oC),
85 %RH (no condensation)
o
-4 to 140
F (-20 oC to 60 oC), 85 % RH (no
condensation)
Operating altitude 0 to 2000 m
EMC EN 61326-1
UL/IEC 61010-1, IEC 61010-2-030,
Safety compliance
IEC 61010-2-032 Measurement CAT III 600 V, Pollution degree 2
Certification
P
Weight Approx. 950 g (2.1 lbs)
* See Note 1 and Note 2 on page 7 for reference measurement position of the conductor.
9
Page 14
Visit www.Amprobe.com for
• Catalog
• Application notes
• Productspecications
• User manuals
Amprobe
®
www.Amprobe.com info@amprobe.com Everett, WA 98203 Tel: 877-AMPROBE (267-7623)
Please
Recycle
Loading...