Page 1
INSTRUCTION MANUAL
ACD-10 PRO & TRMS PRO
AMPROBE
®
Page 2
1
Congratulations! You are now the owner of an AMPROBE Instrument. It has been quality crafted according to quality standards and contains quality components and workmanship. This instrument has been inspected for proper operation of all of its functions. It has been tested by qualified factory technicians according to the long-established standards of AMPROBE.
1) SAFETY
This manual contains information and warnings that must be followed for operating the instrument safely and maintaining the instrument in a safe operating condition. If the instrument is used in a manner not specified by the manufacturer, the protection provided by the instrument may be impaired.
The meter meets the requirements for double insulation to IEC61010-2-032 (1994), EN61010-2-032 (1995), UL3111-2-032 (1999).
ACD-10 PRO/TRMS PRO
Category II 600 Volts ac and dc. Category III 300 Volts ac and dc.
PER IEC61010 OVERVOLTAGE INSTALLATION CATEGORY
OVERVOLTAGE CATEGORY II
Equipment of OVERVOLTAGE CATEGORY II is energy-consuming equipment to be supplied from the fixed installation. Note – Examples include household, office, and laboratory appliances.
OVERVOLTAGE CATEGORY III
Equipment of OVERVOLTAGE CATEGORY III is equipment in fixed installations. Note – Examples include switches in the fixed installation and some equipment for industrial use with permanent connection to the fixed installation.
OVERVOLTAGE CATEGORY IV
Equipment of OVERVOLTAGE CATEGORY IV is for use at the origin of the installation. Note – Examples include electricity meters and primary over-current protection equipment.
Page 3
2
TERMS IN THIS MANUAL
WARNING
identifies conditions and actions that could result in serious injury or
even death to the user.
CAUTION identifies conditions and actions that could cause damage or malfunction
in the instrument.
WARNING
To reduce the risk of fire or electric shock, do not expose this product to rain or moisture. The meter is intended only for indoor use.
To avoid electrical shock hazard, observe the proper safety precautions when working with voltages above 60 VDC or 30 VAC RMS. These voltage levels pose a potential shock hazard to the user.
Inspect test leads, connectors, and probes for damaged insulation or exposed metal before using the instrument. If any defects are found, replace them immediately.
Do not touch test lead tips or the circuit being tested while power is applied to the circuit being measured. To avoid accidental short circuit of bare (uninsulated) hazardous live conductors or busbars, switch them off before insertion and removal of the current clamp jaws. Contact with the conductor could result in electric shock. Keep your hands/fingers behind the hand/finger barriers that indicate the limits of safe access of the meter and the test leads during measurement.
CAUTION
Disconnect the test leads from the test points before changing meter functions.
Page 4
INTERNATIONAL ELECTRICAL SYMBOLS
Caution ! Refer to the explanation in this Manual Caution ! Risk of electric shock
Earth (Ground)
Double Insulation or Reinforced insulation
Fuse
AC--Alternating Current
DC--Direct Current
3
2) CENELEC Directives
The instruments conform to CENELEC Low-voltage directive 73/23/EEC and Electromagnetic compatibility directive 89/336/EEC.
Page 5
4
3) PRODUCT DESCRIPTION
This user's manual uses only representative model(s) for illustrations. Please refer specification details for function availability to each model.
1) Transformer Jaw Clamp for AC current magnetic field pick up
2) Hand/Finger Barrier to indicate the limits of safe access of the meter during measurement
3) Push-buttons for special functions & features
4) Push-buttons for special functions & features on Slide-switch Selector functions
5) Input Jack for all functions EXCEPT non-invasive ACA current function
6) Common (Ground reference) Input Jack for all functions EXCEPT non-invasive ACA current function
7) Slide-switch Selector to turn the display power ON/OFF and Select a function
8) 3-3/4 digits 4000 counts LCD display
9) Jaw trigger for opening the transformer clamp jaw
Page 6
4) OPERATION
5
DC Voltage, AC Voltage, Hz Frequency functions
Inputs are made through the test leads terminals. Slide-switch on defaults at DC voltage. Press
SELECT
button momentarily to select AC voltage.
Press the
Hz
push-button momentarily to activate Hz Frequency function in the following slide-switch functions: DCV & ACV via the test leads; ACA via the jaw clamp
Page 7
6
Note: DC 400.0mV range is designed with 1000MΩ high input impedance for least current drain in measuring small signals, and can cope better with most commercially available voltage output transducers/adapters. The non-zero display reading is normal when the meter inputs are open circuit, which will not affect actual measurement accuracy. The meter will show close to zero reading when the inputs are shorted. Open input is actually a floating condition, which is not a zero-volt-input condition.
Note: Hz input sensitivity varies automatically with function range selected while activating the Hz function. Lowest range has the highest sensitivity, and the highest range has the lowest sensitivity. Activating the Hz function while measuring the specific function signal (auto ranging) can automatically select the best sensitivity range to avoid electrical noise which may cause unstable Hz reading. However, if the Hz reading shows zero due to insufficient sensitivity, activate the Hz function BEFORE measuring the specific function signal. The meter is then in the lowest range and can select the highest sensitivity.
Page 8
7
CAUTION Measuring Resistance, Continuity, Diode or Capacitance function on a live circuit will produce false results and may damage the instrument. In many cases the suspected component must be disconnected from the circuit to obtain an accurate measurement reading.
Page 9
8
Resistance, and
Continuity functions
Inputs are made through the test leads terminals. Slide-switch on defaults at Ω. Press SELECT button momentarily to select
Continuity function which is convenient for checking wiring connections and operation of switches. A continuous beep tone indicates a complete wire.
Diode test function
Inputs are made through the test leads terminals. Slide-switch on defaults at Ω.
SELECT
button momentarily 2 times to select
Press
Diode test function. Normal forward voltage drop (forward biased) for a good silicon diode is between 0.400V to 0.900V. A reading higher than that indicates a leaky diode (defective). A zero reading indicates a shorted diode (defective). An OL indicates an open diode (defective). Reverse the test leads connections (reverse biased) across the diode. The digital display shows OL if the diode is good. Any other readings indicate the diode is resistive or shorted (defective).
Capacitance
function
Inputs are made through the test leads terminals. Slide-switch on defaults at Ω. SELECT button momentarily 3 times to select
Press
Capacitance function. Relative zero
mode can be used to zero out the parasitic capacitance of the leads and the internal protection circuitry of the meter when measuring low capacitance in the order of Pico Farad (pF).
CAUTION
Discharge capacitors before making any measurement. Large value capacitors should be discharged through an appropriate resistance load.
Page 10
9
ACA Current clamp-on function
Inputs are made through the jaws clamps for non-invasive ACA current measurements.
CAUTION
Press the jaw trigger and clamp the jaws around only one single conductor of a circuit for load current measurement. Make sure the jaws are completely closed, or else it will introduce measurement errors. Enclosing more than one conductor of a circuit will result in differential current (like identifying leakage current) measurement.
Strong Electro-magnetic field environments such as high-current transformers, motors and conductors may affect measurement accuracy.
Page 11
HOLD
10
The hold feature freezes the display for later viewing. Press the
HOLD
button
momentarily to activate or exit this feature.
MAX
The max feature compares and displays the measured maximum value as fast as 30ms with auto-ranging capability. Press the
MAX
button for 1 second or more to activate or
exit the max feature in the following functions: DCV, ACV & ACA
Relative zero
Relative zero
mode
mode allows the user to offset the meter consecutive measurements with the displaying reading as the reference value. The display will now show readings relative to the stored reference value. That is, display = reading - stored value. Press the
button momentarily to activate and to exit relative zero mode.
Auto-ranging
Where there is more than one measuring range under a selected meter function, the LCD annunciator “a” turns on. The meter will automatically switch to the best resolution range when making measurements. No manual ranging selection is required.
Auto Power Off (APO)
When the meter is on, the Auto Power Off (APO) feature will switch the meter into a sleep mode automatically to extend battery life after approximately 30 minutes of the last front panel activity. To wake up the meter from APO, press the buttons momentarily or set the slide-switch to the OFF position and then slide back on again. Always set the slide-switch to the OFF position manually when the meter is not in use.
5) MAINTENANCE
WARNING To avoid electrical shock, disconnect the meter from any circuit, remove the test leads from the input jacks and turn OFF the meter before opening the case. Do not operate with open case.
Page 12
11
Trouble Shooting
If the instrument fails to operate, check batteries and test leads etc., and replace as necessary. Double check operating procedure as described in this user’s manual.
If the instrument voltage-resistance input terminal has been subjected to high voltage transient (caused by lightning or switching surge to the system) by accident or abnormal conditions of operation, the series fusible resistors will be blown off (become high impedance) like fuses to protect the user and the instrument. Most measuring functions through this terminal will then be open circuit. The series fusible resistors and the spark gaps should then be replaced by qualified technician. Refer to the LIMITED WARRANTY section for obtaining warranty or repairing service.
Cleaning and Storage
Periodically wipe the case with a damp cloth and mild detergent; do not use abrasives or solvents. If the meter is not to be used for periods of longer than 60 days, remove the batteries and store them separately.
Battery replacement
The meters use standard 3V alkaline button battery (ANSI/NEDA-5004LC, IEC-CR2032). In models ACD-10 PRO & ACD-10 TRMS PRO, one battery are used.
Loosen the two screws from the case bottom and remove the bottom case. Slide the battery out the side of the holder and replace with a new battery (observe polarity). Replace the bottom case. Re-fasten the screws.
6) Specifications General Specifications
Display : 3-3/4 digits 4000 counts LCD display(s) Update Rate : 3 per second nominal Polarity : Automatic Low Battery Indication: Below approx. 2.4V Operating Temperature : 0°C to 40°C Relative Humidity : Maximum relative humidity 80% for temperature up to 31°C
decreasing linearly to 50% relative humidity at 40°C Altitude : Operating below 2000m Storage Temperature : -20°C to 60°C, < 80% R.H. (with battery removed) Temperature Coefficient : nominal 0.15 x (specified accuracy)/°C @(0°C - 18°C or 28°C
- 40°C), or otherwise specified
Page 13
12
Sensing : Average sensing for ACD-10 PRO. True RMS for ACD-10TRMS PRO Safety : Meets IEC61010-2-032 (1994), EN61010-2-032 (1995), UL3111-2-032 (1999) For ACD-10 PRO/TRMS PRO: Category II 600 Volts AC & DC, and Category III 300
Volts AC & DC Transient protection : 6.5kV (1.2/50µs surge) for all models Pollution degree : 2
E.M.C. : Meets EN61326 (1997, 1998/A1), EN61000-4-2 (1995), and EN61000-4-3
(1996) In an RF field of 3V/m: Capacitance function is not specified Other function ranges: Total Accuracy = Specified Accuracy + 45 digits. Performance above 3V/m is not specified Overload Protections : ACA Clamp-on jaws : AC 400A RMS continuous “+” & “COM” terminals (all functions) : 600VDC/VAC RMS Power Supply : 3V alkaline button battery (ANSI/NEDA-5004LC, IEC-CR2032). One
battery for ACD-10 PRO & ACD-10 TRMS PRO. Power Consumption : 2.5 mA typical APO Timing : Idle for 30 minutes
APO Consumption : 0.8µA typical on all functions except on ACD-10 TRMS PRO
Amps and Volts where it is 25µA Dimension : L 7.8” X W 2.48” X H 1.25” Weight : 0.412 Lb approx. Jaw opening & Conductor diameter : 1.02” max Accessories : Test leads (pair), battery installed, user's manual, & soft carrying pouch
Electrical Specifications
Accuracy is ±(% reading digits + number of digits) or otherwise specified, at 23°C ± 5°C & less than 75% R.H.
1)
Model ACD-10 PRO TRMS. True RMS accuracy of ACV is specified from 5% to 100%
of range, and ACA is specified from 10% to 100% of range, or otherwise specified. Maximum Crest Factor < 1.75 : 1 at full scale & < 3.5 : 1 at half scale, with frequency components within the specified frequency bandwidth for non-sinusoidal waveforms.
Page 14
DC Voltage: ACD-10 PRO/TRMS PRO RANGE Accuracy
AC CURRENT: ACD-10 PRO/TRMS PRO RANGE Accuracy
13
1)
400.0mV 0.3% + 4d
4.000V, 40.00V,
0.5% + 3d
400.0V 600V 1.0% + 4d NMRR : >50dB @ 50/60Hz CMRR : >120dB @ DC, 50/60Hz, Rs=1k Input Impedance : 10M, 30pF nominal
(1000MΩ for 400.0mV range)
AC Voltage: ACD-10 PRO/TRMS PRO RANGE Accuracy
1)
50Hz -- 500Hz
4.000V, 40.00V,
1.5% + 5d
400.0V 600V 2.0% + 5d
CMRR : >60dB @ DC to 60Hz, Rs=1k Input Impedance : 10M, 30pF nominal
50Hz / 60Hz
40.00A 1.9% + 8d
400.0A 1.9% + 8d* 600A** unspecified *Accuracy specified to 350A continuous, and 400A for 60 second max with 5 minutes cool down interval **Added range to indicate instantaneous over-range current values
OHMS: ACD-10 PRO/TRMS PRO RANGE Accuracy
400.0Ω
4.000kΩ, 40.00kΩ,
400.0k
4.000M
40.00M Open Circuit Voltage : 0.4VDC typical
Max Hold (where applicable)
Specified accuracy ± 50 digits for changes >
Diode Tester: ACD-10 PRO/TRMS PRO
25ms in duration
Open Circuit Voltage Test Current
Audible Continuity Tester Audible threshold : between 20Ω and 120Ω.
Capacitance: ACD-10 PRO/TRMS PRO RANGE* Accuracy**
500.0nF, 5.000µF,
50.00µF, 500.0µF,
3.5%*** + 6d
< 1.6 VDC 0.25mA
Hz Frequency: ACD-10 PRO/TRMS PRO Function Sensitivity
400.0mV 150mV 10Hz -- 2kHz
4.000V 3.2V 5Hz -- 40kHz
3000µF
40.00V 25V 5Hz -- 100kHz
*Additional 50.00nF range accuracy is not
400.0V 100V 5Hz -- 100kHz
specified **Accuracies with film capacitor or better ***Specified with battery voltage above 2.8V (approximately half full battery). Accuracy decreases gradually to 12% at low battery warning voltage of approximately 2.4V
600V 400V 5Hz -- 5kHz
400.0A 55A 40Hz -- 400Hz Display counts: 5000
Best resolution: 0.001Hz Accuracy: 0.5%+4d
0.8% + 6d
0.6% + 4d
1.0% + 4d
2.0% + 4d
(Typical)
Range
(Sine RMS)
Page 15
14
Page 16
LIMITED WARRANTY
Your AMPROBE instrument has a limited warranty against defective materials and/or workmanship for one year from the date of purchase provided that, in the opinion of the factory, the instrument has not been tampered with or taken apart.
Should your instrument fail due to defective materials, and/or workmanship during this one-year period, please have your dated bill of sale, which must identify the instrument model number and serial number and call the number listed below:
Repair Department
ATP - AMPROBE
MIRAMAR, FL
Tel: 800-327-5060
www.amprobe.com
Advanced Test Products
Miramar, FL Tel.: (954)499-5400 Fax: (954)499-5454
PRINTED ON RECYCLABLE PAPER, PLEASE RECYCLE
COPYRIGHT © MMII Btc, ALL RIGHTS RESERVED
P/N:7M1C-0461-0000 PRINTED IN TAIWAN