AMETEK Programmable Power, Inc., a Division of AMETEK, Inc., is a global leader in the design
and manufacture of precision, programmable power supplies for R&D, test and measurement,
process control, power bus simulation and power conditioning applications across diverse
industrial segments. From bench top supplies to rack-mounted industrial power subsystems,
AMETEK Programmable Power is the proud manufacturer of Elgar, Sorensen, California
Instruments and Power Ten brand power supplies.
AMETEK, Inc. is a leading global manufacturer of electronic instruments and electromec hanical
devices with annualized sales of $2.5 billion. The Company has over 11,000 colleagues working
at more than 80 manufacturing facilities and more than 80 sales and service centers in the United
States and around the world.
Trademarks
AMETEK is a registered trademark of AMETEK, Inc. Sorensen is a trademark owned by AMETEK,
Inc. Other trademarks, registered trademarks, and product names are the property of their
respective owners and are used herein for identification purposes only.
Notice of Copyright
XTR 850 Watt Series Programmable DC Power Supply Operating Manual (firmware v 1.11 and
higher)
UNLESS SPECIFICALLY AGREED TO IN WRITING, AMETEK PROGRAMMABLE POWER, INC.
(“AMETEK”):
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER
DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR
EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL,
WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH
INFORMATION WILL BE ENTIRELY AT THE USER’S RISK, AND
(c) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH,
ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE
TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED AMETEK CONTENT
IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION, WHICH IS POSTED AT
WWW.PROGRAMMABLEPOWER.COM.
Product Family: XTR 850 Watt Series Programmable DC Power Supply
Warranty Period: Five Years
WARRANTY TERMS
AMETEK Programmable Power, Inc. (“AMETEK”), provides this written warranty covering the
Product stated above, and if the Buyer discovers and notifies AMETEK in writing of any defect in
material or workmanship within the applicable warranty period stated above, then AMETEK may,
at its option: repair or replace the Product; or issue a credit note for the defective Product; or
provide the Buyer with replacement parts for the Product.
The Buyer will, at its expense, return the defective Product or parts thereof to AMETEK in
accordance with the return procedure specified below. AMETEK will, at its expense, deliver the
repaired or replaced Product or parts to the Buyer. Any warranty of AMETEK will not apply if the
Buyer is in default under the Purchase Order Agreement or where the Product or any part
thereof:
• is damaged by misuse, accident, negligence or failure to maintain the same as
specified or required by AMETEK;
• is damaged by modifications, alterations or attachments thereto which are not
authorized by AMETEK;
• is installed or operated contrary to the instructions of AMETEK;
• is opened, modified or disassembled in any way without AMETEK’s consent; or
• is used in combination with items, articles or materials not authorized by AMETEK.
The Buyer may not assert any claim that the Products are not in conformity with any warranty
until the Buyer has made all payments to AMETEK provided for in the Purchase Order Agreement.
PRODUCT RETURN PROCEDURE
1. Request a Return Material Authorization (RMA) number from the repair facility (must be
done in the country in which it was purchased):
• In the USA, contact the AMETEK Repair Department prior to the return of the
product to AMETEK for repair:
Telephone: 800-733-5427, ext. 2295 or ext. 2463 (toll free North America)
858-450-0085, ext. 2295 or ext. 2463 (direct)
• Outside the United States, contact the nearest Authorized Service Center
(ASC). A full listing can be found either through your local distributor or our
website, www.programmablepower.com, by clicking Support and going to the
Service Centers tab.
2. When requesting an RMA, have the following information ready:
• Model number
• Serial number
• Description of the problem
NOTE: Unauthorized returns will not be accepted and will be returned at the shipper’s expense.
NOTE: A returned product found upon inspection by AMETEK, to be in specification is subject to
an evaluation fee and applicable freight charges.
ii
Page 5
About This Manual
Purpose
The Operating Manual provides installation and operating information for
the XTR 850 Watt Series Programmable DC Power Supply.
Scope
The Manual provides safety information, features and specifications,
installation procedures, functional test procedures, and operating procedures
for both local (front panel) operation and remote operation.
The Manual does not provide information on the GPIB and Ethernet
(ENET) interface options. See the XTR 850 Watt GPIB and Ethernet Interface Option Operating Manual (Part number M370046-06).
Audience
The Manual is intended for the user who is familiar with electronic power
supplies, Constant Voltage and Constant Current operating modes, and the
control of output power. The user should be familiar with practicing safe
techniques while making supply or pin connections.
(firmware v1.11 and higher)
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions or practices that could result in personal injury or
loss of life.
CAUTION
Cautions identify conditions or practices that could result in damage to the unit or
other equipment.
Important:
know. They are not as serious as Warnings or Cautions.
M370185-01iii
Important notes provide information that is important for you to
Page 6
About This Manual (firmware v1.11 and higher)
Related Information
For related information on this product, see also:
•XTR 850 Watt GPIB and Ethernet Interface Option Operating Manual (Part number M370046-06) provides information on the
GPIB and Ethernet interface option.
•XTR 850 Watt Series Programmable DC Power Supply: Quick Reference Guide (Part number M370185-04) is included with your
power supply and provides an introduction to using the front panel
interface.
•Rack Mount Kit Options Installation Instructions (Part number M370046-05) provides information on rack mounting a single or
dual XTR 850 Watt.
More information about AMETEK Programmable as well as its products
and services, is available at
Acronyms
AcronymDefinition
APGAnalog Programming
www.programmablepower.com.
AUXAuxiliary
ENETEthernet
FGAFinished Goods Assembly
ISOLIsolated Analog Programming
OTPOver Temperature Protection
OVPOver Voltage Protection
PSUPower Supply Unit
TVSTransient Voltage Suppressor
UVPUnder Voltage Protection
Font Conventions
This Manual uses the following typographical conventions:
7 segment
Command body text
ivM370185-01
For display and readback information on the
output voltage and current displays.
Represents SCPI commands.
Page 7
Important Safety Instructions
WARNING: High energy and high voltage
Exercise caution when using a power supply. High energy levels can be stored at
the output voltage terminals on a power supply in normal operation. In addition,
potentially lethal voltages exist in the power circuit and on the output and sense
connectors of a power supply with a rated output greater than 40
capacitors store potentially dangerous energy for some time after power is
removed.
WARNING: Fire hazard
Operate the power supply in an environment free of flammable gases or fumes.
To ensure that the power supply's safety features are not compromised, use the
power supply as specified in this Manual and do not substitute parts or make any
unauthorized modifications. If service is necessary, please return the power
supply to the Authorized Service Center. See
Policy” on page WA –3 .
WARNING: Limitations on use
The XTR 850 Watt Series Programmable DC Power Supply is not intended for
use in connection with life support systems or other medical equipment or
devices.
“Return Material Authorization
V. F i lte r
CAUTION: For use as a battery charger
When you are using a power supply for battery charging applications, it is
essential to provide an appropriately sized fuse or circuit breaker in series
between the power supply output and the battery.
Installation of a protector (fuse or DC circuit breaker), rated for about 115% of
the maximum current rating of the power supply and designed specifically to
interrupt the DC voltage of the battery, will provide adequate current protection.
Where several power supplies are in parallel, it is best to fuse each power supply
rather than use one fuse at the battery.
Power Supply Safety Markings
Alternating CurrentOn (Supply)
Earth (Ground) TerminalOff (Supply)
Protective Conductor
Term inal
M370185-01v
Caution (Check the Manual
for additional information.)
Page 8
Safety
Standard Warnings
WARNING: Keep these instructions
This chapter contains important safety and operating instructions. Read and keep
this Operating Manual for future reference.
1.Before installing and using the XTR 850 Watt Series Programmable
DC Power Supply, read all instructions and cautionary markings on
the XTR and all appropriate sections of this Manual.
2.The XTR is for indoor use only. Do not expose the XTR to moisture.
To reduce risk of fire hazard, do not cover or obstruct the ventilation
openings. Be sure to install the XTR in a compartment which allows
air to reach the ventilation inlets on the front and rear of the unit to
prevent overheating. For more information, see
page 2–4.
3.To avoid a risk of fire and electric shock, make sure that the existing
wiring is in good condition and the wire is not undersized. Do not
operate the XTR with damaged or substandard wiring.
“Ventilation” on
4.Do not operate the XTR if it has received a sharp blow, been dropped,
or otherwise damaged in any way. If the XTR is damaged, see
“Warranty and Product Information” on page WA – 1.
5.Do not disassemble the XTR. It contains no user-serviceable parts.
See the
instructions on obtaining service. Attempting to service the XTR
yourself may result in a risk of electrical shock or fire. Internal
capacitors remain charged after all power is disconnected.
6.To reduce the risk of electrical shock, disconnect AC power from the
XTR before attempting any maintenance or cleaning or working on
any circuits connected to the XTR. Turning off controls will not
reduce this risk.
“Warranty and Product Information” on page WA – 1 for
Chapter 1, Introduction, describes the features of the XTR
850 Watt Series Programmable DC Power Supply.
Page 22
Introduction
Features and Options
The XTR 850 Watt Series Programmable DC Power Supply provides
stable, variable output voltage and current for a broad range of
development and system requirements. The power supplies have a high
power density and numerous industry standard interfaces:
•RS-232, RS-485, analog programming (APG), isolated analog
programming (ISOL), and USB built-in ports.
•Optional GPIB or Ethernet (ENET) control for remote operation and
readback.
•Seamless switching between front panel and any digital interface
(RS-232, RS-485, USB, GPIB or ENET).
•Simultaneous digital displays for both voltage and current.
•Front panel control by rotary Adjust/Enter knob, permitting high
resolution output setting.
•Active Power Factor Correction (PFC) reduces input current and
input current harmonics.
•Automatic crossover system allowing the power supply to switch
between Constant Current and Constant Voltage operating modes.
•Parallel or series connection among multiple units to produce greater
diversity or to use in higher power applications.
•Short-circuit protection of DC outputs provideing greater operating
safety.
•Built-in APG and ISOL interface to provide a galvanically isolated
analog voltage control of the output, master/slave output tracking,
and remote Enable/disable for safety and precision.
•Remote output voltage sensing to automatically compensate for cable
losses.
•Software calibrated.
•Three user setting memory locations.
•M10 Option preprograms the voltage to reset to zero upon power on
and upon output enable.
1-2M370185-01
Page 23
XTR 850 Watt Models (firmware version 1.11 and higher)
XTR 850 Watt Models (firmware version 1.11 and higher)
Table 1-1 lists the models in the XTR 850 Watt series covered by this
Manual.
1
Table 1-1
ModelOutput VoltageOutput Current
6-1100–6 V0–110 A
8-1000–8 V0–100 A
12-700–12 V0–70 A
20-420–20 V0–42 A
33-250–33 V0–25 A
40-210–40 V0–21 A
60-140–60 V0–14 A
80-10.50–80 V0–10.5 A
100-8.50–100 V0–8.5 A
150-5.60–150 V0–5.6 A
300-2.80–300 V0–2.8 A
600-1.40–600 V0–1.4 A
XTR 850 Watt Series Voltage and Current Ranges
M370185-011-3
Page 24
Introduction
Front Panel
Figure 1-1
ItemDescription
1Front panel power switch
2Front panel display. See Figure 1-2 for details.
3Air Intake Vents
XTR 850 Watt Front Panel
1-4M370185-01
Page 25
Front Panel Display and Controls
Front Panel
1
Figure 1-2
ItemDescription
1Rotary Adjust/Enter control
2Constant Voltage (CV) Mode LED (green)
3Model Identification Label
4Output Voltage Display
5Constant Current (CC) Mode LED (green)
6Output Current Display
7Alarm Indicator LED (red)
8OUTPUT ENABLE Main button
9OUTPUT ENABLE Aux button
109-Position Mode Control (For detailed information, see “Configuring Settings from the
Front Panel Display and Controls
Front Panel” on page 3–2).
M370185-011-5
Page 26
Introduction
Rear Panel Connectors
1
6
Figure 1-3
1
Rear Panel: 6 V to 40 V Models
SN
2
J2
J3
J1
7
2
J2
J3
J1
61110879
3
J5
8
9
3
J5
4
J4
J6
10
11
4
J4
J6
100 - 240 Vac
47-63 Hz, 11.5 –6A
MADE IN CANADA
100 - 240 Vac
47-63 Hz, 11.5 –6A
MADE IN CANADA
5
5
Figure 1-4
611
Figure 1-5
Rear Panel: 60 V to 150 V Models
12
SN
J2
J3
J1
3
Rear Panel: 300 V to 600 V Models
4
J4
J5
J6
100 - 240 Vac
47-63 Hz, 11.5 –6A
MADE IN CANADA
5
10987
1-6M370185-01
Page 27
ItemDescription
Rear Panel Connectors
16 V– 40 V Models: DC Output Terminal Positive
60 V–150 V Models: DC Output Connectors Positive (6.5 mm hole diameter)
300 V–600 V Models: DC Output Connectors Positive (6.5 mm hole diameter)
26 V– 40 V Models: DC Output Terminal Negative
60 V–150 V Models: DC Output Connectors Negative (6.5 mm hole diameter)
300 V–600 V Models: DC Output Connectors Negative (6.5 mm hole diameter)
3 (J2)Ethernet (ENET) or GPIB Connector (optional)
4 (J4)RS-232/RS-485 Connector In Port
5AC Input Connector (IEC Type)
6Chassis Ground Stud
7 (J1)Analog Programming (APG) Connector. For pin information, see page 4–5.
8 (J3)AUX Output and Isolated Analog Programming (ISOL) Connector. For pin information, see
page 4–20.
9 (J5)USB Connector
10 (J6) RS-485 Connector Multichannel Port
11Fan Exhaust Vents
1
M370185-011-7
Page 28
1-8
Page 29
2
Installation
Chapter 2, Installation, provides information and
procedures for inspecting, installing, and testing the power
supply.
Page 30
Installation
Basic Setup Procedure
Table 2-1 provides a summary of the basic setup procedure with
references to the relevant sections in this chapter. Refer to this table if you
are unfamiliar with the installation requirements for the power supply.
Complete each step in the sequence given.
Table 2-1
Step DescriptionActionReference
1InspectInspect the power supply.“Step 1: Inspecting and Cleaning”
2InstallInstall the power supply
3Connect Input
4Select WiresSelect wires that are correctly
5TestPerform functional tests for
6Connect LoadsConnect the load wires to the
7Connect Remote
Basic Setup Procedure
Power
Sensing (if
required)
on page 2–3.
“Step 2: Location and Mounting” on
(benchtop or rack mount).
Ensure adequate ventilation.
Connect AC input power. “Step 3: Connecting AC Input
rated for the maximum DC
output current.
voltage mode operation, current
mode operation, and front panel
controls.
DC output.
Connect remote sensing
connectors on power supply to
load.
page 2–4.
Power” on page 2–5.
“Step 4: Selecting Load Wires” on
page 2–6.
“Step 5: Performing Functional
Tests” on page 2–8.
“Step 6: Connecting Loads” on
page 2–10.
“Step 7: Connecting Remote
Sensing” on page 2–13.
2-2M370185-01
Page 31
Step 1: Inspecting and Cleaning
Initial Inspection
When you first receive your unit, perform a physical check:
1.Inspect the unit for any scratches and cracks, broken switches,
connectors or displays.
2.Ensure that the packing box contains the 7.5 foot (2.5 m) power cord.
3.If you see external damage or suspect internal damage, contact the
carrier immediately.
Periodic Cleaning
The power supply only requires periodic cleaning, not routine servicing.
Whenever a unit is removed from operation, clean the metal surfaces with
naptha or an equivalent solvent, and clean the front panel with a weak
solution of soap and water. Use low-pressure compressed air to blow dust
from components on the printed circuit boards.
Step 1: Inspecting and Cleaning
2
M370185-012-3
Page 32
Installation
Step 2: Location and Mounting
The power supply may be rack-mounted or used in benchtop applications.
Rack Mounting
The XTR 850 Watt power supply is designed to fill half of a standard
inch (483 mm) equipment rack.
19
Units can be combined with the same models in the 850 W series for
customer applications.
Purchasing Rack Mount Kits
Contact Customer Service (see “Contact Information” on page i) about
purchasing the Rack Mount Kit options for XTR 850 Watt. For a list of
the part numbers, see
Installation information for the different rack mount options are provided
with the rack mount kits.
For XTR product support, visit www.programmablepower.com and
navigate to the XTR home page.
“Part Numbers for Rack Mount Kits” on page iii.
Ventilation
Whether operating the power supply in a rack or on a bench, allow air to
reach the ventilation inlets on the front and rear of the unit for cooling.
The direction of airflow is from the front of the unit to the back of the
unit. Ventilation space is not required at the top, bottom or sides of the
power supply.
2-4M370185-01
Page 33
Step 3: Connecting AC Input Power
WARNING: Shock hazard
Disconnect AC power from the unit before removing the cover. Even with the
front panel power switch in the Off position, live line voltages are exposed when
the cover is removed. Repairs must be made by an Authorized Service Center.
Step 3: Connecting AC Input Power
WARNING: Shock hazard
There is a potential shock hazard if the power supply chassis and cover are not
connected to an electrical ground via the safety ground in the AC input
connector. Ensure that the power supply is connected to a grounded AC outlet
with the recommended AC input cord configured for the available line voltage as
described in this section.
WARNING: Shock hazard
The AC input cord is the disconnect device for the power supply. The plug must
be a non-locking plug which is readily identifiable by and accessible to the
operator. The input cord must be no longer than 9.84 feet (3 m).
AC Input Connector
The AC input connector is a standard IEC 16 A 250 V male connector
located on the rear panel of the power supply. The AC input cord
provided is rated for 30
2
A, 300 V and appropriate for use in any country.
M370185-012-5
Page 34
Installation
Step 4: Selecting Load Wires
This section provides recommendations for selecting minimum load wire
sizes.
Load Wiring
To select the wiring for connecting the load to the power supply, consider
the following factors:
•Insulation rating of the wire.
•Current carrying capacity of the wire.
•Maximum load wiring length for operation with remote sense lines.
•Electrical noise and impedance effects of the load lines.
Insulation Rating
Use load wiring with a minimum insulation rating equivalent to the
maximum output voltage of the power supply.
Current Carrying Capacity
The load wiring must have a current carrying capacity greater than the
output rating of the power supply to ensure that the load wiring will not be
damaged if the load is shorted.
rating for various gauges of wire rated for 105 °C operation, based on a
maximum current density of 450
Table 2-2 shows the maximum current
A/cm2.
Operating at the maximum current rating shown in Table 2-2 results in an
approximately 30 °C temperature rise for an appropriately-sized load wire
operating in free air. Where load wiring must operate in areas with
elevated ambient temperatures or bundles with other wiring, use larger
gauges or wiring rated for higher temperatures.
Maximum Load Wiring Length For Operation With Sense Lines
2
Figure 2-1
Noise and Impedance Effects
T o minimize noise pickup or radiatio n, use shielded twisted pair wiring of
the shortest possible length for load sense wires. Connect the shield to the
power supply chassis. Where shielding is impossible or impractical,
simply twisting the wires together will offer some noise immunity.
Maximum Load Wire Length for 1 V Line Drop
M370185-012-7
Page 36
Installation
Step 5: Performing Functional Tests
The functional test procedures include:
•Power-on and front panel functional checks
•Voltage mode operation and current mode operation checks.
For information on local operation, see “Local Operation” on page 3–1
for adjusting front panel controls and settings.
Powering the Power Supply On/Off
To power on the power supply:
1.Ensure that the front panel power switch is in the Off position.
2.Ensure that the AC line voltage is within operating range.
3.Connect the line cord to a grounded AC outlet.
4.Turn the front panel power switch to the On position.
After a short power-on delay, 8888 8888 illuminates on the output
voltage and current displays, followed by PSU On.
After approximately 1 second, the display returns to normal status.
To power off the power supply:
◆ Turn the front panel power switch to the Off position.
AC FAIL will blink on the display. The ALARM LED illuminates.
After a short delay, all lights on the display will not be illuminated.
2-8M370185-01
Page 37
Voltage and Current Mode Operation Checks
To perform the voltage and current mode operation checks:
1. Ensure that the front panel power switch is in the On position and the
output is disconnected.
2. If the OUTPUT ENABLE Main button is illuminated, press the
button to turn off the output.
3. To check voltage mode operation, turn the 9-position mode control to
the VOLTS position.
The voltage set point will blink dimming and then return to full
brightness. For more information, see
4. Adjust the voltage to 5 V.
5. To check current mode operation, turn the 9-position mode control to
AMPS position.
Verify that the current set point is blinking in the output current
display.
6. Adjust the current to 1 A.
7. Press the OUTPUT ENABLE Main button to turn On.
Step 5: Performing Functional Tests
2
“Local Operation” on page 3–1.
8. Turn the front panel power switch to the Off position.
9. Turn the front panel power switch to the On position.
10. Connect a short circuit across the output terminals. Use leads of
sufficient current carrying capacity. (See
Wires”.)
11. Press the OUTPUT ENABLE Main button to enable the output. The
button will be illuminated when the output is enabled.
CC Mode LED illuminates and the voltage and current are displayed.
CV Mode LED illuminates and the preset load current is displayed.
12. Turn the front panel power switch to the Off position.
M370185-012-9
“Step 4: Selecting Load
Page 38
Installation
Step 6: Connecting Loads
This section describes how to connect loads to the power supply for both
single and multiple loads.
WARNING: Shock hazard
There is a shock hazard at the power supply output when operating at an output
greater than 40 V. T o protect personnel against accidental contact with hazardous
voltages, ensure that the load and its connections have no accessible live parts.
CAUTION: Cable damage
When making connections to the output terminals, ensure terminals of opposite
polarity do not touch. Load cables and sense wires should be provided with strain
relief.
DC Output Connectors
WARNING: Shock hazard
Disconnect the AC input before making any connections. A shock hazard may be
present at the output terminals. Allow 15 seconds after the AC power has been
removed before making any connections.
6 V–40 V Models
The 6 V–40 V models are equipped with output terminals, as shown in
Figure 1-3.
60 V–150 V Models
The 60 V–150 V models are equipped with output connectors, as shown
Figure 1-4. These models have output currents that may require users
in
to use wire diameters that would not fit into a single output connector, so
there are two output connectors in parallel to increase the potential current
carrying capacity of load wiring.
300 V–600 V Models
The 300 V–600 V models are equipped with output connectors, as shown
Figure 1-5.
in
2-10M370185-01
Page 39
Inductive Loads and Batteries
CAUTION
The XTR power supply requires freewheeling and blocking diodes across the
output while driving inductive loads or batteries to protect the power supply from
damage caused by power being fed back into the supply and from high voltage
transients.
Step 6: Connecting Loads
Selecting
Diodes
The diode must have a voltage rating at least 20% greater than the power
2
supply's output voltage and have a current rating greater than or equal to
the power supply's output rating. Connect the cathode to the positive
output and the anode to the return.
Where positive load transients such as back EMF from a motor may
ocAMPS, connect a Transient Voltage Suppressor (TVS) or a varistor
across the output to protect the power supply. The breakdown voltage
rating for the TVS or varistor must be approximately 10% higher than the
rated supply output.
Figure 2-2
For a detailed Application Note, please go to:
www .programmablepower.com and click SUPPORT.
M370185-012-11
Diode Placement
Page 40
Installation
Connecting Single Loads
Figure 2-3 shows the recommended load connections for a single load
which is sensing its voltage locally. Local sense lines shown are the
default connections at the rear panel APG J1 connector (see
page 4–5). The load lines should use the largest gauge and shortest length
of wire possible to ensure optimal performance.
You do not need remote sensing for basic operation of your power supply .
However, if you wish to correct any small drops in your load lines, then
use the remote sensing feature. See
on page 2–13 for more information.
Figure 4-1 on
“Step 7: Connecting Remote Sensing”
Local Sense
–
Power Supply
Local Sense
+
Figure 2-3
Connecting Single Loads
Connecting Multiple Loads
The proper connection of distributed loads is an important aspect of
power supply use. The common method of connection is a radial load
connection. Power is connected to each load individually from a single
pair of terminals designated as the positive and negative distribution
terminals. This pair of terminals may be the power supply output
terminals, the load terminals, or a distinct set of terminals especially
established for distribution use. In this scheme, there are no ground loops
and the effect of one load upon another is minimized.
+
Output
–
J1.1
J1.2
Output
J1.5
J1.6
+
Terminal
–
Terminal
Load
2-12M370185-01
Page 41
Step 7: Connecting Remote Sensing
WARNING: Shock hazard
There is a potential shock hazard at the sense connectors when using a power
supply at an output greater than 40 V. Select wiring with a minimum insulation
rating equivalent to the maximum output voltage of the power supply for use as
local sense jumpers or for remote sense wires. Ensure that connections at the load
end are shielded to prevent contact with hazardous voltages.
Remote sensing permits you to shift the regulation point of the power
supply from the output terminals to the load or other distribution
terminals.
Use shielded twisted pair wiring of 20 to 26 AWG for best noise
performance. Make sure that the shielded twisted pair wiring insulation is
rated higher than the maximum output voltage of the power supply. If
possible, one end of the shield of the sense lines should be attached to the
chassis ground of the power supply.
Step 7: Connecting Remote Sensing
2
Pin J1.6 on APG
connector
Pin J1.1 on APG
connector
Output terminals on
power supply
Figure 2-4
Remote Sense Connection
-SNS
+SNS
load
output +
output -
Chassis ground stud
To connect the remote sense wires:
1. Ensure that the front panel power switch is in the Off position.
2. Using a small flat blade screwdriver, remove the two sense jumpers
from pins J1.1 and J1.2, and from pins J1.5 and J1.6 on the APG
Connector. See
Figure 4-1, “APG Connector Terminals” on page 4–5.
M370185-012-13
Page 42
Installation
3. Connect one end of the shield of the twisted pair wire to the chassis
ground point on the power supply.
4. Connect the positive sense line (+SNS) from the positive regulation
point as close as possible to the load terminals to pin J1.1.
5. Connect the negative sense line (–SNS) from the return of the load to
pin J1-6.
To compensate for losses in power leads connected to the output, the
power supply provides sense connections beside the output terminals.
With remote sense leads in place, the power supply regulates to the
displayed voltage at the point where the sense lines are connected to
the output leads. With the sense lines disconnected, the power supp ly
regulates the voltage at the output terminals.
CAUTION: Equipment damage
Do not operate the power supply with sense lines connected to the load without
also connecting the load power leads to the output terminals.
CAUTION: Reverse polarity
Avoid reversing positive (+) and negative (–) sense connections.
When using remote sense to compensate for load line losses, ensure that the
positive sense line is connected to the positive load terminal and the negative
sense line is connected to the negative load terminal. Do not reverse these
connections or the power supply may be damaged.
Important:
sensing can cause voltage instability due to inductance of the load leads.
Measures to reduce inductance and/or capacitance (raising resonant frequency)
or using local sense can be beneficial in stabilizing the system.
2-14M370185-01
Long load leads with large capacitance at the load and remote
Page 43
3
Local Operation
Chapter 3, Local Operation, provides the procedures for
local (front panel) operation such as:
•Configuring settings.
•Operating in constant voltage mode and constant
current mode.
•Using the protection features.
•Using multiple power supplies.
Page 44
Local Operation
Introduction
Once you have installed the power supply and connected both the AC
input power and the load (covered in “Installation” on page 2–1), the
power supply is ready for local operation. To turn the power supply on,
see “Powering the Power Supply On/Off” on page 2–8.
Configuring Settings from the Front Panel
Using the 9-Position Mode Control
The 9-position mode control is used with the rotary Adjust/Enter control
to configure settings in local operation. See Figure 1-2, “Front Panel
Display and Controls” on page 1–5 for location of the front panel
features.
Using the 9-position mode control, select one of nine modes: VOLTS,
AMPS, FLD, PRT, SAV, RCL, CAP, and VAP. See Figure 3-1 and Table
3-1 for detailed information on the nine modes.
Figure 3-1
9-Position Mode Control
Using the Rotary Adjust/Enter Control
The rotary Adjust/Enter control is used to change settings and set the
value selected. The front panel displays information on the output voltage
and output current displays. Each display has a maximum of four
characters that are made up of 7 segments.
3-2M370185-01
Page 45
Coarse and Fine Adjustment Modes
The coarse and fine adjustment modes are used for setting the voltage and
current set points, OVP and UVP settings.
Coarse
adjustment
mode
When using local operation to set the current and voltage set points, use
the coarse adjustment mode (default) followed by the fine adjustment
mode (see next). The coarse adjustment mode quickly adjusts the settings
in large increments to reach the desired value.
Configuring Settings from the Front Panel
Fine adjustment
mode
Pressing the rotary Adjust/Enter control to change the mode to fine
adjustment mode, provides the ability to manipulate the last significant
digit. Once the exact desired value for the setting has been selected, press
the rotary Adjust/Enter control to commit the value to the unit.
Table 3-1
9 Positions on the Mode
Control Knob
VOLTS (Volt a ge
Programming)
AMPS (Current
Programming)
FLD (Foldback)Select Foldback option: CC, CV or
PRT (Protection)Select the OVP set point (see
Select and Set from the Front Panel
Turning the rotary Adjust/Enter
control lets you…
Select the voltage set point in coarse
or fine adjustment modes. See
“Automatic Mode Crossover” on
page 3–13.
Select the current set point in coarse
or fine adjustment modes. See
“Constant Current Mode Operation”
on page 3–13.
none. See “Setting Foldback Mode”
on page 3–24.
page 3–26).
Select the UVP set point (see
page 3–28.)
Select OTP temperature and
Shutdown (see page 3–30.)
Pressing the rotary Adjust/
Enter control lets you…
Set the value selected and
cycle to the next setting.
Set the value selected and
cycle to the next setting.
Set the value selected and
cycle to the next setting.
Set the value selected and
cycle to the next setting.
3
SAV (Save User Preset)Select the user setting memory
RCL (Recall User Preset)Select the user setting memory
M370185-013-3
location. See “Saving User Setting
Memory Locations” on page 3–37.
location. See “Recalling User
Setting Memory Locations” on
page 3–38.
Save user setting memory
values.
Load user setting memory
values into the power supply.
Page 46
Local Operation
Table 3-1
9 Positions on the Mode
Control Knob
CAP (Current Analog
Programming)
VAP (Voltage Analog
Programming)
PGM (Programming Options) Select the remote interface to be
Select and Set from the Front Panel
Turning the rotary Adjust/Enter
control lets you…
Select the programming source and
select the range.
Select the programming source and
select the range.
used for control, local lockout or
current sharing.
Pressing the rotary Adjust/
Enter control lets you…
Set the value selected and
cycle to the next setting.
Set the value selected and
cycle to the next setting.
Select interface/Option and
cycle to the next setting.
3-4M370185-01
Page 47
Navigating the Menu System
The menu system of the XTR follows a select and set model with the
exception of the VOLTS and AMPS modes. See “Setting VOLTS and
AMPS Modes”.
The general procedure for setting up the features in the select and set
model is:
1. To select a mode, rotate the 9-position Mode control to the desired
mode or press the rotary Adjust/Enter control once to activate the
current selection on the mode control knob. See Figure 3-3.
2. To select the feature or setting, rotate the rotary Adjust/Enter control
to scroll through the different available settings of that mode.
The settings appear on the output current display.
3. Press the rotary Adjust/Enter control to select the feature or setting.
4. Set each value using the rotary Adjust/Enter control. When the value
has been selected, press the rotary Adjust/Enter control to commit the
updated value. Additional values may become available, depending
on the setting that is being configured.
Navigating the Menu System
3
Setting VOLTS and AMPS Modes
The only exceptions to the select and set model are the VOLTS and
AMPS modes which do not allow the selection of tracking and select and
set mode by turning the rotary Adjust/Enter control. In VOLTS and
AMPS modes, the default entry mode setting is automatically selected as
either voltage or current tracking, respectively.
Voltage and current values can be set in tracking mode or select and set
mode using the rotary Adjust/Enter control:
•Tracking mode—the new values take effect as the rotary Adjust/Enter
control is rotated.
•Select and set mode—the new values do not take effect until the
rotary Adjust/Enter control is pressed. See “Normal Display Mode
and Inactivity Timeout” on page 3–7.
M370185-013-5
Page 48
Local Operation
To access the tracking mode for entering voltage and current:
1. Select the VOLTS or AMPS position on the 9-position mode control.
If the set point is blinking, the unit is in coarse tracking mode.
•When the VOLTS mode is selected, the voltage set point will
blink in the output voltage display.
•When the AMPS mode is selected, the current set point will blink
in the output current display.
2. Use the rotary Adjust/Enter control to adjust the set point.
The adjustments you make to the set point affect the opposing output
value (voltage when in AMPS mode or current when in VOLTS
mode), which will update in the non-blinking display.
3. Press the rotary Adjust/Enter control to enter fine adjust tracking
mode.
The set point blinks faster when the unit is in fine adjust tracking
mode.
4. Use the rotary Adjust/Enter control to fine tune the set point.
5. Once the set point has been selected, press the rotary Adjust/Enter
control to exit tracking mode and return to normal display mode.
To access the select and set entry mode for the voltage and current set
points:
1. Select VOLTS or AMPS position on the 9-position mode control.
2. Press the rotary Adjust/Enter control three times in succession to
enter coarse Pre-Set Adjustment.
3. Press the rotary Adjust/Enter control one more time to enter fine PreSet Adjustment.
4. Press the rotary Adjust/Enter control once again to set the value.
The units can also timeout (adjustable) to exit the menu. Once Pre-Set
Mode is entered, crpc and fnpc will appear in the voltage display.
3-6M370185-01
Page 49
Normal Display Mode and Inactivity Timeout
Normal display mode appears on the output voltage and current displa ys
when the configuration changes from the front panel have been completed
or when the inactivity timeout occurs (default is 3 seconds). Normal
display mode shows the output voltage and current values.
If a timeout occurs before the changes made to the value have been set,
the changes will not be saved and you will have to re-enter the changes.
The inactivity timeout is variable from 1 to 20 seconds and can only be
changed using the SCPI command.
The SCPI command (s) for these instructions are:
[:]SYSTem[<channel>]:FPANel[:TIMeout]
Navigating the Menu System
Figure 3-2
Important:
beginning users and expert users don't have to use the same timeout
Front Panel
Each user memory setting location stores the timeout so that
3
M370185-013-7
Page 50
Local Operation
Figure 3-3
3-8M370185-01
Front Panel Menu System
Page 51
Display Messages on the Front Panel
Display Messages on the Front Panel
The front panel displays on the power supply will use text as shown in
Table 3-2 to indicate the status or mode.
Table 3-2
Display TextText Description
0Negative Polarity
232 RS 232
485RS 485
8888All segments On, Power Up
|Positive Polarity
ACAlternating Current
ADDrRS 485 Address
ANPRAnalog Programming
ASPower On Autostart
AvASAuxiliary Autostart
CAPrCurrent Analog Programming
CLrClear
CCConstant Current
COn7Controller
CUConstant Voltage
CrPCCoarse Current Pre-set Mode
CrPUCoarse Voltage Pre-set Mode
CShrCurrent Share (same as CUrrShAr)
CUrrCurrent
CUrrShArCurrent Share (same as CShr)
deLaFold Delay
doneDone
ErrError (debug)
F0LDFoldback
FAILFail
FAnFan
FLAFlash
FnpCFine Current Preset Mode
FnPUFine Voltage Preset Mode
FLdFoldback
HBP5Data rate (kbps)
6PIBGPIB Interface
Front Panel Display Text
3
M370185-013-9
Page 52
Local Operation
Table 3-2
Display TextText Description
InInterlock
LAnENET Interface
LE CCurrent APG Level
LE UVoltage APG Level
LocLock
LOCLLocal
OFFOff
OnOn
OU7POutput Protection
OCPOver Current Protection
O7POver Temperature Protection
OUPOver Voltage Protection
OvPFOver Voltage Protection fine adjustment
OUPCOVP Calibration
POLPolarity
Pr0Protection mode
PSUPower Supply Unit
R ISIsolated Resistive Analog Programming
rCLRecall Preset
rERemote Programming/Interface
rnISNon-Isolated Resistive Analog Programming
Con7Controller (current share controller)
5hArShare (current share)
ChAnMultichannel Remote Int e rf ace
S rSSoft reset
SAUESave Preset
SdShutdown
SLASlave (current share slave)
U ISIsolated Analog Voltage Programming
UN ISNon-Isolated Analog Voltage Programming
USbUSB Interface
UUPUnder Voltage protection coarse adjustment
UvPFUnder Voltage protection fine adjustment
UAPrVoltage Analog Programming
UOLVolt age
Front Panel Display Text
3-10M370185-01
Page 53
Display Messages on the Front Panel
A blinking numeric value is either a vol tage o r c urr ent se t p oint in tracking
mode. The display in which the set point appears, output voltage or output
current display, indicates the type of set point, voltage or current.
3
M370185-013-11
Page 54
Local Operation
Standard Operation
The power supply can be controlled by two methods, either from the front
panel or from any of the remote interfaces. Front panel control is referred
to as local operation (default setting) while control via any of the remote
interfaces is called remote operation. To set up the power supply for
remote operation, see Chapter 5, “Remote Operation”. Once the remote
connection has been established, the power supply can switch seamlessly
between local operation and any digital interface (RS-232, RS-485,
GPIB, USB and Ethernet).
Local lockout is a feature that allows the front panel to be locked so that
accidental button presses are ignored. This feature is often used to lock
out the front panel while a user is controlling the power supply from a
remote location.
The output of the power supply has two modes of operation: Constant
Voltage (CV) mode (see page 3–13) and Constant Current (CC) mode
(see page 3–13). Both of the operating modes are available regardless of
which control method (local or remote) is used.
Operating Modes
The output mode in which the power supply operates at any given time
depends on the following factors:
•Output voltage set point V
SET
Note: the M10 Option includes a preset function to automatically
reset the output voltage to zero Volts at both power on and output
enabled, unless deliberately programmed otherwise (see Output
Protection, page 3-33).
•Output current set point I
•Impedance of the attached load R
SET
L
The two output modes of operation are Constant Voltage (CV) mode (see
page 3–13) and Constant Current (CC) mode (see page 3–13).
Output enabledWhen the output is turned on, both the voltage and current rise as quickly
as possible to try and reach the set points (V
SET
and I
SET)
that were
configured prior to enabling the output. Initially the unit will operate in
CV mode, which is the default mode. As the voltage and current rise to
meet the requirements of the load, the set point that is reached first (based
on the R
3-12M370185-01
either V
L,
SET or ISET
) will determine which mode the power
Page 55
Standard Operation
supply will remain in. The operating mode is indicated by either the CC
mode LED or the CV mode LED, one of which will illuminate on the
front panel.
Output disabledThe mode of operation is not determined until the output is enabled. The
CV and CC mode LEDs will not indicate the mode while the output is
disabled.
Constant Voltage Mode Operation
If the output is enabled and the configured current set point is much
higher than the requirements for the attached load, then the voltage will
rise until it reaches the voltage set point. When the output voltage reaches
the voltage set point, it stops rising. The unit will continue to operate in
CV mode. The load current will still vary to meet any changes in required
load current draw resulting from a change in the attached load.
Constant Current Mode Operation
If the output is enabled, the voltage and current start to rise. At this time
the unit is operating in CV mode (default operational mode). As the load
current drawn reaches the value of the output current setting, the unit will
switch to CC mode and not allow any additional current to be drawn
above the value of I
voltage will still vary to meet any changes in required output voltage
resulting from a change in the attached load.
. The unit is now operating in CC mode. The
SET
3
Automatic Mode Crossover
Mode crossover occurs when the unit makes the switch between operating
modes. Crossover can occur from CV to CC or vice versa, depending on
how the attached load resistance changes. Figure 3-4 shows the
relationships between the variables.
For example, if the unit was initially operating in CV mode with the
output voltage at the voltage set point and the load current below the I
and the attached load resistance began to decrease, the current would rise
to meet this change in the load. The load current will increase in
proportion to the decrease in the load resistance until the load current
drawn reaches the current set point. At this point further decreases in load
resistance (increased load current requirements) will cause the unit to
cross over into CC mode where the output voltage will vary with
changing load resistance and the load current will remain at the I
value.
M370185-013-13
SET
SET
Page 56
Local Operation
The reverse operating mode change can also occur if the load resistance is
increased to the point that the required load current drops below the I
SET
value. At that point the power supply would crossover to CV mode and
the load current would be free to vary as the load resistance changed.
Figure 3-4
Operating Modes
To set
the voltage set point (V
SET):
1. Turn the 9-position mode control to the VOLTS position or press the
rotary Adjust/Enter control if the 9-position mode control is already
at the VOLTS position.
The voltage set point is blinking in the output voltage display. The
output current will be displayed in the output current display.
2. Set the desired voltage value using the rotary Adjust/Enter control.
Important:
change the set points for OVP.
If you can’t get the set point to the desired level, you may need to
3. Press the rotary Adjust/Enter control to transition to Fine Adjust
mode.
The set point will blink faster to indicate fine adjust tracking mode.
4. Set the desired voltage value using the rotary Adjust/Enter control.
3-14M370185-01
Page 57
Standard Operation
5. Once the desired value has been set, press the rotary Adjust/Enter
control to commit the setting.
Quick Tip
Remote operation
uses these SCPI
commands. See
page 5–1.
Important:
output voltage up to 105% over the model-rated maximum value. The power
supply will operate within these extended ranges, but full performance to
specification is not guaranteed.
The control circuits have been designed to allow you to set the
are limited by the Over Voltage Protection and Under Voltage Protection settings.
To set the current set point (I
The maximum and minimum setting values of the output voltage
):
SET
1. Turn the 9-position mode control to the AMPS position or press the
rotary Adjust/Enter control if the 9-position mode control is already
at the AMPS position.
The voltage set point is blinking in the output voltage display. The
output current will be displayed in the output current display.
2. Set the desired current value using the rotary Adjust/Enter control.
3. Press the rotary Adjust/Enter control to transition to Fine Adjust
mode.
The set point blinks faster to indicate fine adjust tracking mode.
4. Set the desired current value using the rotary Adjust/Enter control.
3
5. Once the desired value has been set, press the rotary Adjust/Enter
Important:
current can be set up to 105% over the model-rated maximum values. The power
supply will operate within these extended ranges, but full performance to
specification is not guaranteed.
The control circuits have been designed so that output
Page 58
Local Operation
Shipped Configuration (Local Operation)
The power supply is configured for local operation at the factory. See
Table 3-3 for a summary of this configuration. For more information on
default settings, see Table 3-9 on page 3–40.
Table 3-3
Local Control ConfigurationAdditional References
Use the front panel controls to
adjust the output voltage and
current set point settings.
The OVP set point is adjusted at
the front panel to 105% above the
maximum rated output voltage.
Shipped Configuration
Enabling the Output
Enabling the output on will also turn off the ALARM LED if the ALARM
LED has been latched on due to an alarm triggering and automatically
clearing. See “Alarms and Errors” on page 3–19.
To enable the output power:
uPress the OUTPUT ENABLE Main button on the front panel or enter
the SCPI command.
The OUTPUT ENABLE Main button will illuminate.
To disable the output power:
uPress the OUTPUT ENABLE Main button when the OUTPUT
ENABLE Main button is illuminated.
The output will be disabled and the LEDs will not be illuminated.
See Chapter 3, “Local Operation” for front
panel operation. See Chapter 4, “Analo g
Programming (APG) and Isolated Analog
Programming (ISOL)” for analog
programming procedures.
See “Using Over Voltage Protection
(OVP)” on page 3–26 for the adju stment
procedure.
Important:
activated. See “Using the External Shutdown Function” on page 3–31.
Quick Tip Remote
Operation uses
these commands.
See page 5–1.
3-16M370185-01
The SCPI command (s) for these instructions are:
[:]OUTPut[<channel>][:POWer][:STATe]
The main output will not turn on if the shutdown function is
Page 59
Enabling the Auxiliary Output
To enable on the auxiliary output:
uPress the OUTPUT ENABLE Aux button on the front panel.
The OUTPUT ENABLE Aux button will illuminate.
Enabling the Auxiliary Output
Important:
AUX_ON_OFF signal line is being used to disable the auxiliary outputs.
See “AUX Output and Isolated Analog Programming (ISOL) Connector” on
page 4–20.
To disable the auxiliary output:
uPress the OUTPUT ENABLE Aux button on the front panel again.
The OUTPUT ENABLE Aux button will not be illuminated.
If the auxiliary output is activated, +5 V on J3.9 (+AUX1) and +15 V on
J3.11 (AUX2) will be present with respect to Pin J3.2 or Pin J3.6
(COM_ISOLATED). (See also “AUX Output and Isolated Analog
Programming (ISOL) Connector” on page 4–20 for more details.)
The SCPI command (s) for these instructions are:
[:]OUTPut[<channel>]:AUXiliary[:STATe]
The auxiliary output will not be enabled if the external
Output Auto Start Mode (Auto Restart)
The Auto Start mode establishes the state of the output of the power
supply after recovery from a complete power cycle (all front panel LEDs
are not illuminated).
If Auto Start mode is set to On, the power supply output will return to its
previous value when the power supply is powered up again.
3
If Auto Start mode is set to Off, the power supply output will remain off
after the power supply is powered up again.
To change the Auto Start mode:
1. Press and hold the OUTPUT ENABLE Main button for 1 second.
The Auxiliary Auto Start mode determines the state of the auxiliary
output after a complete power cycle (all front panel LEDS are not
illuminated). With Auxiliary Auto Start mode turned to On, the auxiliary
output will be activated after the power supply is powered up again.
To define the Auxiliary Auto Start mode:
1. Press and hold the OUTPUT ENABLE Aux button for 1 second.
AuAS On or AuAS Off is displayed.
2. To change to status to On or Off, press the OUTPUT ENABLE Aux
button.
The SCPI command (s) for these instructions are:
[:]OUTPut[<channel>]:AUXiliary:PowerON[:STATe]
3-18M370185-01
Page 61
Alarms and Errors
Several conditions can cause alarms in the XTR. Some conditions are:
•From user configurable features.
•Controlled in hardware and will trigger regardless of configuration.
All alarms, with the exception of the Fan alarm, will result in the output of
the power supply being disabled. The Fan alarm does not affect the output.
When an alarm is triggered, the appropriate alarm message will begin
blinking on the display and the Alarm LED will be illuminated.It is
possible that more than one alarm will trigger at the same time. When this
occurs, the alarm with the highest precedence will blink on the display.
Table 3-4 lists the precedence of alarms. If the alarm is cleared and the
event which caused the alarm has not been corrected, then the alarm may
trigger again immediately . Fix the reason for the alarm before you clear it.
Alarms and Errors
3
Table 3-4
AlarmPrecedenceOutput
AC Fail1 (Highest)YesNo
Over Temperature Protection (OTP)2YesNo
Fan4NoYes
Interlock6NoNo
Over Voltage Protection (OVP)7AlwaysNo
Over Current Protection (OCP)8AlwaysNo
Foldback9YesYes
External Shutdown10NoYes
Under Voltage Protection (UVP)11 (Lowest)NoYes
Flash Checksum Failure
1.The Flash Checksum Failure alarms are an exception as they can only occur during boot up
or recalling a user setting slot. If a checksum error is detected when recalling a user slot, no modification of settings will occur, and an error will be pushed to the SCPI error queue. If a checksum occurs at boot-up, then this checksum error can be cleared by doing a soft reset or by power
cycling the unit.
Alarm Order of Precedence
1
MaskableDisplay
Latch
N/AN/AN/A
AC Fail
O7P Pro
FAn Pro
In Loc
OVP Pro
OCP pro
FLD Pro
SD POL
UUP Pro
FLA FAIL
M370185-013-19
Page 62
Local Operation
Clearing Alarms
Clearing Triggered and Manual Alarms
To clear a triggered alarm, use one of the following methods:
• Turn the power supply Off and then On.
• Press and hold the rotary Adjust/Enter control for 3 seconds.
To clear a manual alarm:
1. Press and hold the rotary Adjust/Enter control for 3 seconds.
The ALr CLr message will be displayed on the front panel for a few
seconds.
Important:
highest precedence alarm is cleared. If another alarm has occurred, then this
alarm will now become the highest precedence alarm and will begin blinking on
the display.
2. Repeat the alarm clearing until you have cleared all alarms.
Clearing a Flash Failure Alarm
The Flash Failure alarm is the only exception for clearing alarms. If a
flash failure occurs at boot time, it can only be cleared by a soft reset key
combination press (see “Resetting the Power Supply” on page 3–40) or
by power cycling the unit. If a checksum error is detected when recalling
a user slot, no modification of settings will occur, and an error will be
pushed to the SCPI error queue. The alarm will clear after a duration per
the currently configured front panel timeout setting.
To clear a triggered alarm, use one of the following methods:
•Turn the power supply Off and then On.
•For failures that occur during a recall of user memory settings, wait
the duration of the currently configured front panel timeout.
•Press and hold the reset key combination (Flash Fail ONLY). See
“Resetting the Power Supply” on page 3–40.
When an alarm is cleared by using this method, only the current
The SCPI command (s) for these instructions are:
[:]OUTPut[<channel>]:PROTection:CLEar
3-20M370185-01
Page 63
Clearing Automatic Alarms
Some alarms will clear automatically when the condition that caused the
alarm is no longer present. When an alarm automatically clears, the
output voltage and current displays will return to normal, but the ALARM
LED will remain illuminated to indicate that an alarm has occurred. If an
automatic alarm is triggered, the normal alarm clearing procedure still
applies.
To clear the ALARM LED after an automatic alarm has cleared, use
one of the following methods:
•Send the SCPI Clear Alarm command.
•Press the OUTPUT ENABLE Main button to reenable the output.
The ALARM LED will no longer be illuminated.
For example, if one of the fans in the XTR was temporarily blocked,
causing a Fan alarm,then the blockage was cleared and the fans restarted,
the alarm would clear. The output voltage and current displays would be
in normal mode, but the ALARM LED would be illuminated. See “Front
Panel ALARM LED” on page 3–21 for information on other events that
affect the ALARM LED.
Alarms status is tracked in the SCPI status registers. For more details on
how and where the alarms are tracked, see “Standard SCPI Register
Structure” on page 5–34.
Alarms and Errors
3
Front Panel ALARM LED
The Alarm LED will illuminate due to one or more of the following
events occurring:
•OTP has been tripped.
•A fan has stopped.
•OVP has tripped.
•OCP has tripped.
•UVP has tripped
•Interlock is open circuit.
•AC power falls out of range.
•Foldback has tripped.
•Persistent storage checksum is wrong (Flash Fail alarm).
•Internal malfunction of power supply.
•Any alarm has tripped and been cleared automatically.
M370185-013-21
Page 64
Local Operation
Alarm Masking
The alarm LED will remain illuminated until the alarm is manually
cleared (see “Clearing Triggered and Manual Alarms” on page 3–20) or
by turning the main output on if the alarm has automatically been cleared.
It is possible to completely disable some alarms through the use of the
alarm mask. If an alarm is masked then this masking will prevent it from
registering in the SCPI conditions registers as well as not triggering the
alarm. The alarms that can be masked are identified in Table 3-4 on
page 3–19. Setting the bit position (1) of an alarm will result in the alarm
being enabled. Clearing the bit position (0) of an alarm will result in the
alarm being masked/disabled.
For Example:
If you wanted to enable the OTP, Foldback and UVP alarms, you
would take the foldback value of 256 and the UVP value of 1024 to
get a mask of 1280. This is the value you would send with the SCPI
command.
Control of the alarm mask is only available using the SCPI command.
The SCPI command (s) for these instructions are:
[:]SYSTem[<channel>]:PROTection:MASK
The mask command takes a single parameter made up of the sum of the
values for the alarms that are to be masked. See Table 3-5 for the alarm
values associated with each maskable alarm.
Table 3-5
AlarmBit PositionValue
Fan38
Foldback8256
External Shutdown9512
Under Voltage Protection (UVP)101024
Alarm Mask Bit Positions
The SCPI command (s) for these instructions are:
[:]SYSTem[<channel>]:PROTection:MASK
3-22M370185-01
Page 65
Alarm Output Latching
When an alarm is triggered, the output will be disabled with the exception
of the Fan alarm. When an alarm is cleared, the alarm output latch
determines if the output should be re-enabled to the state before the alarm
occurred or if the output should remain in the off state.
Where setting the bit position (1) of an alarm latch will result in output
latching to the off state when the alarm is cleared and if cleared (0) output
will be re-enabled to the state before the alarm triggered.
To define the values for the bit position you determine which alarms you
want to latch. Read the value for this bit position from Table 3-6 and sum
them together. The result is the alarm last mask. Which you should send
with the SCPI command.
For Example:
If you wanted to enable latching for OTP and Foldback you would
take the OTP value of 2 and add it to the foldback value of 256 to get
a mask of 258. This is the value you would send with the SCPI
command.
The output latches are accessible through the SCPI command.
Alarms and Errors
3
The SCPI command (s) for these instructions are:
[:]SYSTem[<channel>]:PROTection:LATCh
The latch command take a single decimal parameter made up of the sum
of the values for the alarms to determine if they are to be latched in the off
state on clearing. See Table 3-6 for the values associated with each
latchable alarm.
Table 3-6
Alarm
AC Fail01
Over Temperature Protection (OTP)12
Foldback8256
M370185-013-23
Alarm Latch Bit Positions
Bit
PositionValue
Page 66
Local Operation
Setting Foldback Mode
Foldback mode is used to disable the output when a transition is made
between the operating modes. The power supply will turn off/disable the
output and lock in foldback mode after a specified delay if the power
supply transitions into CV mode or into CC mode, depending on the
foldback mode settings. This feature is particularly useful for protecting
current or voltage sensitive loads. Foldback can be set to trigger a switch
when transitioning from CV to CC mode or from CC to CV mode.
To set the foldback protection and foldback delay time:
1. Turn the 9-position mode control to the FLD position or press the
rotary Adjust/Enter control if the 9-position mode control is already
at the FLD position.
2. Select the type of crossover that will cause foldback to trigger by
using the rotary Adjust/Enter control.
If the mode selected is CC or CV mode, the foldback delay timer will
start on a transition into the selected mode. If the mode selected is
none, foldback is not enabled.
3. Press the rotary Adjust/Enter control when the desired mode has been
selected.
The FLD LED will illuminate and DELA will be displayed in the
output voltage display.
4. Adjust the desired d elay time using the rotary Adjust/Enter control.
The range can be set from 0.50 seconds to a maximum of 50 seconds.
The step size is in increments of 0.05 seconds when setting from 0.50
to 5 seconds and then in 1 second increments from 5 seconds to 50
seconds.
5. Once the desired foldback delay time has been selected, press the
rotary Adjust/Enter control to commit the foldback delay setting.
To disable foldback protection:
1. Turn the 9-position mode control to the FLD position or press the
rotary Adjust/Enter control if the control knob is already at the FLD
position.
2. FLd is displayed on the output voltage display and the output current
display shows the current foldback trigger mode.
3. Turn the rotary Adjust/Enter control until nonE is displayed in the
output current display.
3-24M370185-01
Page 67
Setting Foldback Mode
4. Press the rotary Adjust/Enter control to commit the setting once the
desired value has been set.
5. The green FLD LED will turn off and the display will return to the
select is the same as the current operating mode, the foldback timer will begin
counting immediately after the delay time has been set.
If you set foldback while the output is enabled and the trigger you
Resetting Activated Foldback Protection
To reset activated and latched foldback protection, press and hold the
rotary Adjust/Enter control for approximately 3 seconds.
The SCPI command (s) for these instructions are:
[:]OUTPut[<channel>]:PROTection:CLEar
3
M370185-013-25
Page 68
Local Operation
Using Over Voltage Protection (OVP)
The OVP circuit protects the load in the even t of an analog programming
error, an incorrect voltage control adjustment, or a power supply failure.
The OVP circuit monitors the output voltage at the output of the power
supply and will disable the output whenever a preset voltage set point is
exceeded. You can set the preset voltage trip point by using the 9-position
mode control on the front panel or via one of the remote programming
interfaces.
To prevent accidental tripping of the OVP while setting up, the firmware
will prevent the OVP set point from being less than 105% of the voltage
set point when in local set point control mode. When the XTR is in VAP
mode for defining voltage set point the set point limitation will be based
on the VAP input signal level. The user should note it is possible to trip
OVP in this mode if the OVP is configured when the analog program ming
source is off.
When the user attempts to configure an OVP setpoint that is less than
105% of the voltage set point via the front panel the set point will stop
allowing the value to decrement. If the user attempts to configure an OVP
set point that is less than 105% of the voltage set point via SCPI a -221,
"settings conflict error" will be pushed onto the error queue.
3-26M370185-01
Page 69
Defining the OVP Set Point
To define the OVP set point:
1. Turn the power supply On.
Ensure the voltage is lower than the desired set point.
2. Set the output to the desired voltage.
OVP can be set without setting desired output voltage first.
3. Turn the 9-position mode control to the PRT position.
Pro OUP is displayed.
4. Press the rotary Adjust/Enter control.
5. Turn the rotary Adjust/Enter control to set the upper limit protection.
Using Over Voltage Protection (OVP)
See “Coarse and Fine Adjustment Modes” on page 3–3.
Important:
The OVP range is variable from V
+5% to V
SET
MAX
+25%.
6. Once the desired value has been set, press the rotary Adjust/Enter
UVP will not be active for voltage set points that are less than 1%
The UVP prevents voltage settings below a set value. The UVP lets you
create a voltage window of operation when used in conjunction with the
OVP setting. The UVP range is variable from 0 V to OVP
SET
–10%.
The UVP is a protection that becomes active after the output is enabled
and a period of time has passed to allow the output to reach its set point
value before the UVP protection begins monitoring. As with OVP if the
voltage set point is determined by analog control (VAP) and the voltage
strays to within 5% of the UVP set point then UVP Safe will trigger to
warn the user that they are about to trigger the UVP alarm.
The period of time before the UVP monitoring is active after the output is
enabled is determined by the rise-time delay for the model as listed in
Table C-2, “Remote Operation” on page C–4 on the row called Up-prog
Response Time, 0 - Vmax. Since the rise time is based on a purely
resistive load the user should be aware that UVP triggering might be
possible in capacitive or rectifier loads due to the rise time being longer.
In these cases it is recommended that the user mask the UVP alarm until
the rise time has elapsed and then unmask the alarm to allow UVP
protection to be enabled during operation.
3-28M370185-01
Page 71
Defining the UVP Set Point
To define the UVP set point:
1. Turn the power supply On.
2. Set the output to the desired voltage.
3. Turn the 9-position mode control to the PRT position.
PRo OUP is displayed.
4. Turn the rotary Adjust/Enter control until PRo UUP is displayed.
5. Press the rotary Adjust/Enter control to select the UVP for setting up.
6. Set up the lower limit protection using the rotary Adjust/Enter
control.
Over Current Protection (OCP)
Important:
7. Once the desired value has been set, press the rotary Adjust/Enter
control to commit the setting.
See “Coarse and Fine Adjustment Modes” on page 3–3.
The OCP alarm is a firmware alarm that is only configurable using the
SCPI interface. The OCP triggers if the output current exceeds the OCP
set point. Because the OCP alarm is a firmware based alarm it has a
latency before detection of the condition can occur. The user should be
aware of this latency and take this into consideration when relying on
OCP to protect a sensitive load. The maximum period for detecting an
OCP condition is 300 ms.
OCP is fixed at 110% of rated current.
SET
–10%.
3
M370185-013-29
Page 72
Local Operation
Using Over Temperature Protection Lock (OTP)
The OTP lock protects the power supply in the event of an over
temperature alarm. This alarm could be caused by ventilation restriction
or overheating due to fan failure.
Two modes are available:
•Auto recovery (OTP OFF) where the power supply turns on again
after cooling down.
•Latch mode (OTP ON) where you will need to reset the unit by
turning the front panel power switch to Off and then On again.
If the OTP is activated, the main output will turn off and PRO O7P (over
temperature protection) will blink on the display. The OTP alarm is an
alarm that will auto recover when the temperature falls back into normal
bounds.
Defining the OTP Mode
To define the OTP lock:
1. Turn the 9-position mode control to the PRT position.
PrO OUP is displayed.
2. Turn the rotary Adjust/Enter control until PRO O7P is displayed.
3. Press the rotary Adjust/Enter control to display O7P ON or OFF.
4. Turn the rotary Adjust/Enter control to change to On or Off.
5. Press the rotary Adjust/Enter control.
The SCPI command (s) for these instructions are:
[:]SYSTem[<channel(s)>]:PROTection:LATCh
Resetting in Latch Mode
To reset the power supply if the OTP alarm is tripped and the OTP mode
is set to On (latching enabled), press and hold the rotary Adjust/Enter
control for approximately 3 seconds.
Use the external shutdown function to enable or disable the output of the
power supply via a logic level signal. When the external shutdown is
triggered, the power supply will display SD POL on the output voltage and
current displays. The external shutdown is useful for making adjustments
to either the load or the power supply without shutting off the power
supply or for using the power supply as part of a larger test system in
which digital or analog control is required.
Activating the External Shutdown Function
To activate the external shutdown function, use the AUX output supply
provided on the Analog Programming Connector J3. This input has a user
selectable polarity with logic low input from 0.0V to 1.2V and logic high
from 2.0V to 15V. The control signal for this input must be capable of
sinking 10mA minimum. This input is also compatible with the use of dry
contacts, where a short is logic low and an open is logic high. The input
lines of the shutdown circuit are fully optically isolated. See page C–4 for
specifications.
Once the External Shutdown has been triggered, the display will blink the
SD POL.
3
Controlling the External Shutdown Function
The external shutdown circuit accepts a voltage or dry contact control
(high or low logic level) to enable or disable the power supply output.
Make connections for the signals at the AUX Output and Isolated Analog
Programming Connector on the rear panel. (See “AUX Output and
Isolated Analog Programming (ISOL) Connector” on page 4–20 for more
information.)
To activate the shutdown function:
Connect the control signal source to the Shutdown pin (J3.1 2) on th e Aux
Output and Isolated Analog Programming Connector with the control
circuit ground connected to Isolated Ground pin (J3.6).
The External Shutdown pin is pulled high internally (normally high).
Therefore, if this feature is not used, the polarity should be set to 1 to
avoid false triggering. (See “Defining the Polarity of the External
Shutdown Signal” on page 3–32 for instructions.)
M370185-013-31
Page 74
Local Operation
Defining the Polarity of the External Shutdown Signal
1. Turn the 9-position mode control to the PRT position or press the
rotary Adjust/Enter control if the control knob is already at the PRT
position.
PrO OUP is displayed on the output voltage display.
2. Turn the rotary Adjust/Enter control until PrO SD is displayed.
3. Press the rotary Adjust/Enter control to display SD 0 (shutdown on
logic 0) or SD1 (shutdown on logic 1).
4. Press the rotary Adjust/Enter control to commit the desired polarity
setting.
For example: If you set the shutdown logic to 1 (SD1) and apply a
logic high (greater than 1.2 Vdc) to pin J3.12 relative to pin J3.6 on
the ISOL connector, the power supply will shut down. Conversely, if
you set the shutdown logic to 0 (SD0), the power supply will only
operate when you have a logic h igh (gre ater th an 1 .2 Vd c) to pin J3.2
relative to pin J3.6.
Important:
the shutdown polarity should be set to 0 if it is not being used.
There is an internal pullup resistor inside the shutdown circuit so
The SCPI command (s) for these instructions are:
[:]OUTPut[<channel>]:POLarity
3-32M370185-01
Page 75
Interlock Function
The Interlock function can be used to wire an external shutoff switch that
can be used to enable or disable the power supply output. When the
switch is closed the power supply will operate normally. If the switch is
opened, the power supply will trigger the interlock alarm. The output will
be disabled, the display will blink In Loc, and the ALARM LED will
illuminate. This alarm will automatically clear when the switch closes
again, and the output will automatically be restored to its pre-alarm state
(either enabled or disabled). The interlock function can be enabled or
disabled using a SCPI command. Common applications include an
emergency shutoff switch or a door switch.
Connect the switch between pins J3.14 and J3.15 on the AUX Output and
Isolated Analog Programming Connector.
Defining the Interlock Mode
The Interlock mode is controlled via SCPI commands. There is no front
panel access for enabling or disabling the Interlock functionality. See
“Interlock Enable/Disable” on page 5–66.
Interlock Function
3
The SCPI command for setting the Interlock mode to On and Off is:
[:]SENSe[<channel>]:PROTection:INTerlock[:STATe]
Output Protection
The output voltage and the output current can be programmed (preset) to
automatically start at zero Volts and zero Amps upon power-up and upon
output enable. Also, each can be reprogrammed to disable the autotmatic
reset to zero.
Note: With the M10 Option, the power supply voltage output is
preset to 0 Volts.
Programming Voltage Output Preset
To Enable/Disable automatic reset to 0 Volts:
1. Turn the rotary Adjust/Enter control to PRT and press.
2. Turn again until Pr0 0U7P is displayed.
3. Press to display 0U7P U0L.
M370185-013-33
Page 76
Local Operation
4. Turn to display U0L 0n or U0L OFF.
5. Press to commit the selected setting.
Important:
This single front panel operation affects both power on and
output enable. However, when using SCPI, there is a separate command
for each.
The SCPI command to query or enable/disable the 0 Voltage Output
Preset at power-on is:
[:]SYSTem[<channel>]:PON:VOLTage {?|ON|OFF}
The SCPI command to query or enable/disable the 0 Voltage Output
Preset upon output enable is:
Power On Status signal indicates a fault condition in the power supply.
Power On Status signal is a TTL output signal at Pin J2.13 with reference
to COM_ISOLATED (Pin J2.2 or Pin J2.6).
During normal operation, the Power On Status signal will be high. If the
output is disabled for any reason, the Power On Status signal will go low.
The following conditions will set the Power On Status to a low level:
•AC fail
•Over Voltage protection (OVP)
•Under Voltage Protection (UVP)
•Over Current Protection (OCP)
•Over Temperature protection (OTP)
•Foldback protection
•Interlock
•Output Off
•Shutdown activated (rear panel shutdown).
•Internal hardware malfunction
•Fan failure
Hardware Malfunction Alarms
3
Hardware Malfunction Alarms
The power supply will turn off the output. An error message will be
displayed in the event that:
•OVP trips
•Voltage deviation in CV mode reaches more than ±5% from the set
1
level.
•Current deviation in CC mode reaches more than ±5% from the set
1
level.
1.These two forms of hardware malfunction are only monitored in the
corresponding APG mode.
M370185-013-35
Page 78
Local Operation
Current Configuration Memory Settings
The power supply will save the unit settings at the time of power down.
These settings will be loaded when the power is restored to the unit or the
power supply is powered up again. Table 3-7 lists the settings that are
saved and recalled on a power cycle event.
Table 3-7
Voltage Setpoint
Current Setpoint
Voltage Output Protection
Current Output Protection
Over Voltage Protection (OVP)
Under Voltage Protection (UVP)
Over Temperature Protection (OTP)
Autostart OUTPUT ENABLE Main
Autostart OUTPUT ENABLE Aux
Foldback Mode
Foldback Delay
Shutdown Logic
Voltage Analog Programming (VAP) Mode
Voltage Analog Programming (VAP) Level
Current Analog Programming (CAP) Mode
Current Analog Programming (CAP) Level
Remote Programming Interface
Local Lock
PSU (Power Supply) Address
Data Rate (BPS)
Alarm Latches
Front Panel Timeout
Power Cycle Saved/Recalled Settings
3-36M370185-01
Page 79
User Setting Memory Locations
There are three user setting memory locations available for storing
frequently used configurations. These user setting memory locations help
to facilitate multiple users of an XTR power supply who have different
setups or when multiple loads are used that have different requirements.
Table 3-8 lists the values that are stored in each user setting memory
location.
User Setting Memory Locations
Table 3-8
Voltage Setpoint
Current Setpoint
Voltage Output Protection
Current Output Protection
Over Voltage Protection (OVP)
Over Temperature Protection (OTP)
Autostart OUTPUT ENABLE Main
Autostart OUTPUT ENABLE Aux
Foldback Mode
Foldback Delay
Shutdown Logic
Voltage Analog Programming (VAP) Mode
Voltage Analog Programming (VAP) Level
Current Analog Programming (CAP) Mode
Current Analog Programming (CAP) Level
Current Sharing Mode
Alarm Latches
Front Panel Timeout
User Accessible Saved/Recalled Settings
3
Saving User Setting Memory Locations
To save user setting memory locations:
1. Turn the 9-position mode control to the SAV position.
M370185-013-37
SAUE is displayed on the output voltage display with a number
indicating a preset position which is displayed on the output current
display.
Page 80
Local Operation
2. Turn the rotary Adjust/Enter control to select a preset position from 1
to 3.
3. Press the rotary Adjust/Enter control.
SAuE done is displayed on the output voltage display.
4. The setting has now been saved to the selected user setting memory
location.
The SCPI command (s) for these instructions are:
*SAV <setting_location>
or
[:]SYSTem[<channel>]:SAVE <setting_location>
Recalling User Setting Memory Locations
This feature recalls settings that were previously saved.
To load user setting memory locations:
1. Turn the 9-position mode control to the RCL position.
RCL is displayed on the output voltage display with a number
indicating a preset position on the output current display.
2. Turn the rotary Adjust/Enter control to select a preset position from 1
to 3.
3. Press the rotary Adjust/Enter control.
rCL done is displayed on the output voltage display.
The settings in the selected user setting memory locations have now
been applied to the power supply.
The SCPI command (s) for these instructions are:
*RCL <setting_location>
or
[:]SYSTem[<channel>]:RECall <setting_location>
Three user setting memory locations are available and one user setting
memory location is saved automatically before AC power shutdown. This
user setting memory location will be loaded after AC power is restored.
3-38M370185-01
Page 81
Local Lockout
Local lockout is a feature that allows the front panel to be locked so that
accidental button presses are ignored. This feature is often used to lockout
the front panel when you are controlling the power supply from a remote
location. When in local lockout mode, the front panel will display LOCL Loc whenever a button is pressed or a knob is turned.
Enabling Local Lockout
To enable local lockout:
1. Turn the 9-position mode control to the PGM position or press the
rotary Adjust/Enter control if the control knob is already at the PGM
position.
The display will show rE in the output voltage display and the
selected remote interface in the output current display.
2. Turn the rotary Adjust/Enter
3. Press the rotary Adjust/Enter control.
4. Turn the rotary Adjust/Enter control until the display shows LOCL On.
5. Press the rotary Adjust/Enter control.
Local lockout has been enabled.
control until the
Local Lockout
3
display shows LOCLLoc.
The SCPI command (s) for these instructions are:
[:]SYSTem:REMote:STATe
Disabling Local Lockout
To disable local lockout:
1. Turn the 9-position mode control to the PGM position or press the
rotary Adjust/Enter control if the control knob is already at the PGM
position.
The display will show rE in the output voltage display and the
selected remote interface in the output current display.
2. Turn the rotary Adjust/Enter control until the display shows LOCL Off.
3. Press the rotary Adjust/Enter control.
Local lockout will be disabled after power-cycling the power supply.
The SCPI command (s) for these instructions are:
[:]SYSTem[<channel(s)>]:REMote:STATe
M370185-013-39
Page 82
Local Operation
Resetting the Power Supply
The reset is used to clear the parameters to the factory default values.
Soft ResetThe soft reset is used to set the parameters (see Table 3-9) to the default
values, but it does not reset the calibration constants
To perform a soft reset:
1. Turn the power supply to Off then On.
When the unit is powering on, 8888 8888 is displayed on the output
voltage and current displays.
2. Press the key combination of both OUTPUT ENABLE Main button
and OUTPUT ENABLE Aux button and hold continuously for 3
seconds in order to execute.
If the flash fail alarm triggers, it is also possible to reset the power
supply. The front panel should display P5U S rS.
3. Once a reset has been triggered, the output voltage display shows P5U CLr for 1 second.
The model number will be displayed for 1 second and then return to
normal mode.
After executing a reset, the power supply’s settings are restored to the
default settings but retain the calibration data. Table 3-9 lists the default
settings.
Table 3-9
ParameterSetting
Address1
Data rate (Kbps)9.6
Communication mode RS-232
Vout setting0 V
Iout setting0 A
OutputOff
AUX OutOff
TriggerOff
Ext. On/Off PolarityNegative
Auto start modeOff
AUX Auto start modeOff
OVPMaximum
3-40M370185-01
Power Supply Default Settings
Page 83
Resetting the Power Supply
Table 3-9
ParameterSetting
UVP0 V
Foldback triggerNone
Foldback delay0.5 s
Current Share ModeController
Alarm Output Latches263 (0 × 107, all latches enabled)
Alarms Mask2047 (0 × 7FF, all enabled)
InterlockDisabled
Voltage Analog ProgrammingOff
Voltage APG Scale10 V
Current Analog ProgrammingOff
Current APG Scale10 V
Voltage Output ProtectionOff
Current Output ProtectionOff
Power Supply Default Settings
(except M10 Option: always On)
(except M10 Option: always On)
3
M370185-013-41
Page 84
Local Operation
Using Multiple Power Supplies
WARNING: Shock hazard
There is a shock hazard at the load when using a power supply at an output of
greater than 40V or a combined output of greater than 40V. To protect personnel
against accidental contact with hazardous voltages created by a series
connection, ensure that the load, including connections, has no live parts which
are accessible. Also ensure that the insulation rating of the load wiring and
circuitry is greater than or equal to the maximum or combined output voltage of
the power supply.
CAUTION: Equipment damage
Do not connect power supplies from different manufacturers in parallel or in
series.
CAUTION: Equipment damage
The remote programming inputs are internally referenced to the power supply's
negative output. Do not connect remote programming ground lines to the power
supply's positive output.
You can operate power supplies of the same model with the outputs in
series to obtain increased load voltage or with the outputs in parallel to
obtain increased current, also called current sharing. Split supply
operation gives you two positive outputs, or a positive and a negative
output. See Figure 3-5 on page 3–43. When using multiple supplies in
series or parallel, they will not meet the single unit specifications in this
Manual.
3-42M370185-01
Page 85
Power Supply
Power Supply
Using Multiple Power Supplies
V
Common
Load
V
3
Figure 3-5
Split Supply Operation
M370185-013-43
Page 86
Local Operation
–
–
Configuring Multiple Supplies for Series Operation
A maximum of two power supplies of the same rating can be connected in
series to increase the output voltage.
CAUTION: Equipment damage
When two power supplies are connected in series, they should be programmed to
the same output voltage to prevent damage to the lower voltage supply at short
circuit condition.
Connecting to the Load in Local Sensing Mode
Connect the negative (–) output terminal of one power supply to the
positive (+) output terminal of the next power supply. See Figure 3-6 for a
representation of series operation.
J1.2
+LS
J1.1
+S
Power Supply
J1.5
-LS
J1.2
+LS
Power Supply
J1.5
-LS
Figure 3-6
+
J1.6
-S
J1.1
+S
+
–
J1.6
-S
Series Operation
+
LOAD
3-44M370185-01
Page 87
Connecting to the Load in Remote Sensing Mode
Connect the negative (–) output terminal of one power supply to the
positive (+) output terminal of the next power supply. The more positive
supply’s positive sense line should connect to the positive terminal of the
load (or distribution point). Its return sense line should connect to the
connection between the two units at the same spot as the negative
supply’s positive sense line. The return sense line of the negative supply
should be connected to the return of the load. See Figure 3-7.
CAUTION: Equipment damage
Do not connect sense lines through relays.
Using Multiple Power Supplies
3
Figure 3-7
M370185-013-45
Load Connections in Remote Sensing Mode
Page 88
Local Operation
Configuring Multiple Supplies for Current Sharing Operation (APG
Method)
Up to four power supplies can be connected in parallel to increase the
output current. One of the units will operate as the master unit and the
remaining units will operate as slave units controlled by the master unit.
The master unit uses the analog programming lines to set the output
voltages and currents of the slave units to match its output.
In remote digital operation, only the master unit can be programmed
remotely while the slave units that are connected remotely will only
provide voltage, current and status readback information.
In APG current sharing topologies, only the master unit can be
programmed using any of the input methods (front panel, remote digital,
or analog programming control). The slave unit(s) voltage and current
output(s) are determined by the master unit through the REF_I input to
each slave unit. The readback using any of the monitoring methods (front
panel display, user monitor lines or SCPI measure commands) of each
unit (master or slave) will provide individual unit status, not system
status.
Important:
configured as a controller. Failure to do so will result in unpredictable
operation.
Setting up the Controller Unit
Set the output voltage of the master unit to the desired voltage. Program
the current set point of the master unit to the desired load current set point
divided by the number of parallel units. During operation, the master unit
operates in Constant Voltage mode, regulating the load voltage at the
programmed output voltage. Send the Current share SCPI command or
use the following instructions to program front panel current share setup:
1. With the 9-position mode control at the PGM position, press the
rotary Adjust/Enter control.
rE is displayed on the output voltage display.
2. Turn the rotary Adjust/Enter control to select CurrShAr and press the
Adjust/Enter control.
C5hr is displayed on the output voltage display.
3. Turn the rotary Adjust/Enter control to select Con7 in the output
current display.
If current sharing is not being used, the unit must be
3-46M370185-01
Page 89
4. Press the rotary Adjust/Enter control to commit the setting.
The SCPI command (s) for these instructions are:
[[:]SOURce[<channel>]]:COMBine:CSHare[:MODE]
Setting up the Slave Units
The output voltage and current of the slave units should be programmed
to maximum value. During parallel operation, the slave units operate as
a controlled current source following the controller unit’s output current.
All slave units must be configured with the SCPI command to enable
current sharing, or use the following instructions to program front panel
current share setup:
1. With the 9-position mode control at the PGM position, press the
rotary Adjust/Enter control.
rE is displayed on the output voltage display.
2. Turn the Adjust/Enter conrol to select “CurrShAr” and press the
Adjust/Enter control.
C5hr is displayed on the output voltage display.
3. Turn the rotary Adjust/Enter control to select SlA in the output
current display.
Using Multiple Power Supplies
3
4. Press the rotary Adjust/Enter control to commit the setting.
The SCPI command (s) for these instructions are:
[[:]SOURce[<channel>]]:COMBine:CSHare[:MODE]
Important:
interface slave described in chapter 5.
The slave unit discussed here is not the same as the remote
Setting Over Voltage Protection (OVP)
The master unit’s OVP should be programmed to the desired OVP level.
The OVP of the slave units should be programmed to a higher value
than the master OVP. When the controller unit shuts down, it will
program the outputs of the slave units to zero volts. If a slave unit shuts
down, only that unit would shut down and the remaining slave units
would supply all the load current if possible.
M370185-013-47
Page 90
Setting Foldback Protection
Foldback protection is only available on the master units as the slaves
operate in constant current mode. They should never crossover into
constant voltage mode. If foldback is triggered on the master unit, when
its output shuts down, it will program the slave unit’s output to zero
volts.
3-48
Page 91
Using Multiple Power Supplies
Connecting to the Load in Local Sensing Mode (Parallel Control
Method)
Connect the power supplies in parallel to obtain a single output supply
with a higher output current set point. Set all of the outputs to the same
voltage before connecting the positive (+) and negative (–) terminals in
parallel. The total current available is the sum of the maximum currents
of each power supply.
3
Figure 3-8
M370185-013-49
Load Connections in Local Sensing Mode
Page 92
Local Operation
Connecting to the Load in Remote Sensing Mode (Parallel Control
Method)
Figure 3-9
3-50M370185-01
Load Connections in Remote Sensing Mode (Parallel Control Method)
Page 93
Using Multiple Power Supplies
3
M370185-013-51
Page 94
Local Operation
3-52M370185-01
Page 95
Analog
4
Programming (APG)
and Isolated Analog
Programming (ISOL)
Chapter 4, Analog Programming (APG) and Isolated
Analog Programming (ISOL), provides information and
procedures for analog and isolated analog programming of
the power supply.
Page 96
Analog Programming (APG) and Isolated Analog Programming (ISOL)
Introduction
The rear panel connectors J1 and J3 provide an option to control and
monitor the output of the power supply with analog signals. Connector J1
provides a non-isolated analog interface where all signals are referenced
to the negative output terminal of the power supply. Connector J3 is an
isolated interface and also provides an isolated auxiliary voltage output to
aid analog programming.
Analog Programming (APG) of Output Voltage and Output Current
Analog programming allows control of the power supply’s output
voltage, output current or both to be controlled from analog inp ut sources.
As the programming source is varied within the configured analog
programming range (2–10
varies proportionally over its output range. For example, if you set the
programming scale to 10
programming pins, the power supply will be programmed to 50% of the
output capability for your power supply.
While analog programming mode is configured, you will not be able to
make adjustments to the set points from the front panel or through the
remote interfaces.
volts/kΩ max), the power supply’s output
V voltage source and apply 5 V to the
The front panel will display AnPr in the output current display when the
9-position mode control is turned to VOLTS or AMPS positions for the
parameter(s) that are configured to be controlled by analog programming.
If an adjustment of a parameter controlled by APG is attempted using a
SCPI command, a “-221 Settings Conflict” error will be pushed onto the
error queue.
Using analog programming requires that you make connections to the
Isolated Analog Programming Connector or Analog Programming
Connector on the rear panel of the power supply. Depending on your
model, see
4-2M370185-01
“Rear Panel Connectors” on page 1–6 or “” on page 1–7.
Page 97
Remote Programming Options
Analog Monitor Signals
There are four monitor lines for analog programming the pin name and
the related APG mode, which are listed in
provided to give analog feedback. The output from these monitor lines is
a value scaled to the Analog Programming level set for the corresponding
analog programming type. For example, the voltage monitor and isolated
voltage monitor lines are both scaled to the analog programming level
that is set in the VAP mode.
Introduction
T able 4-1. All of these lines are
Table 4-1
Related APG ModeReference Line
Non-Isolated Voltage Analog Programming VOL_MONJ1.13
Isolated Voltage Analog ProgrammingIS_MON_VOLJ3.5
Non-Isolated Current Analog Programming CUR_MONJ1.14
Isolated Current Analog ProgrammingIS_MON_CURJ3.10
Important:
supply even when the unit is not set to operate in analog programming mode.
Important:
programming modes are used for the respective voltage and current control. If
local (front panel) control is used or non-isolated APG is used, these values will
be inaccurate and should not be used for monitoring. Conversely, if isolated APG
is used, the non-isolated monitor lines will be inaccurate.
Monitor Lines
Connector
Name
Analog control monitor lines will reflect the output of the power
Isolated monitor lines are only valid when isolated analog
4
M370185-014-3
Page 98
Analog Programming (APG) and Isolated Analog Programming (ISOL)
Auxiliary Outputs
The auxiliary outputs are an additional isolated source. The auxiliary
output has two outputs: +5
The auxiliary output operates independently of the main output. It is
enabled or disabled from the front panel by pressing the OUTPUT
ENABLE Aux button. When the Aux output is enabled, the OUTPUT
ENABLE Aux button is illuminated. Like the main output of the power
supply , the Aux also has the ability to Autostart at power up. See
Auto Start Mode (Auto Restart)” on page 3–17 and “Auxiliary Auto Start
Mode” on page 3–18 for details on controlling this feature.
Table 4-2 provides a summary of the options available for programming
output voltage and current set point using an analog source.
V output on J3.9 and a +15 V output on J3.1 1.
“Output
Table 4-2
Control of…Programming Scale
Output voltage2–10 V Voltage source (adjustable)See page 4–10.
Current set point 2–10 V Voltage source (adjustable)See page 4–12.
Output voltage2–10 kΩ Resistive source (adjustable)See page 4–15.
Current set point 2–10 kΩ Resistive source (adjustable)See page 4–17.
1.The resolution can be adjusted in increments of 0.1 volts.
Remote Programming Options
1
For more info…
4-4M370185-01
Page 99
Analog Programming (APG) Connector J1
The APG connector is an 18-pin connector. See Figure 4-1.
The APG connector provides access to the following functions:
J1.7COM Analog CommonSame as power supply negative sense (–SNS)
J1.8COM Analog CommonSame as power supply negative sense (–SNS)
M370185-014-5
Local Sense}Jumper. Factory default condition.
Sense
Page 100
Analog Programming (APG) and Isolated Analog Programming (ISOL)
Table 4-3
APG Pins and Functions J1
PinReferenceFunction
J1.9VOL_PRAnalog Voltage Programming Input
J1.10CUR_PRAnalog Current Programming Input
J1.11VOL_RES_PRVoltage Resistive Programming Input
J1.12CUR_RES_PRCurrent Resistive Programming Input
J1.13
VOL_MON
1
Voltage Monitor. The scale of this output is set by the APG
voltage input range selected (see Important note below).
J1.14
CUR_MON
1
Current Monitor. The scale of this output is set by the APG
current input range selected (see Important note below).
J1.15EXT_CC_CVExternal CC/CV. Indicates the state of the operate mode. When
in CV mode, logic high is output and when in CC mode, logic
low is output. Logic is TTL/CMOS compatible.
J1.16CSHCurrent Share. Used to hook up units for current sharing. Output
from master unit. Slave units should be left open.
J1.17REF_ICurrent Reference Input. Slave input from current share output
on the master unit.
J1.18NC
1.Important: Non-isolated monitor lines are only valid in local control, digital remote and nonisolated analog programming modes for the respective voltage and current control. If isolated
analog programming is used, the isolated monitor lines should be used as the non-isolated
monitoring lines will not accurately reflect the output state of the power supply.
4-6M370185-01
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.