AMETEK M133 User Manual

Page 1
M133 / M135 / M136
Disconnect Polarity Relay
and
M9 / M130 Remote
Programming
©2004 by AMETEK Programmable Power
This document contains information proprietary to AMETEK Inc. The information contained herein is not to be duplicated or transferred in any manner without prior written permission from AMETEK.
March, 2015 Document No. M362809-01 Rev C
SORENSEN Power Supplies AMETEK Programmable Power 9250 Brown Deer Road San Diego, CA 92121-2294 Tel: (858) 450-0085 Fax: (858) 458-0267 Email: sales.ppd@ametek.com
www.programmablepower.com
Page 2
Page 3
Sorensen DCS Series Manual Addendum
1.1 INTRODUCTION
This addendum covers the M133, M135 and M136 option operation, a M9 or M130 remote programming option for the DCS series power supply with an Isolation Relay and Reverse Polarity Relays PCB. The Isolation Relay PCB is an assembly which is attached to the DCS externally; when installed it adds 3” to the length (see Figure 1). This
option allows the user to fully isolate the DCS output from it’s load as
well as provide local or remote sense control.
1.2 FEATURES AND FUNCTIONS
All features remain as described in the DCS-E 1KW Series manual and Section 1 of the M9C GPIB (P/N M361667-01) or M130 Ethernet programming manual (P/N M362797-03). See section 2.2 of this
document for sense connection differences from base model.
1.2.1 Additional Features and Functions
Output voltage isolation from output load. Output local or remote sense operation. Relay hot-switch lock-out; ensures that the voltage across
the relay contacts and the current through them is zero prior to changing relay states.
Relay automatic disconnect; relays automatically latch open
when a shutdown occurs.
1.3 PROGRAMMABLE FUNCTIONS
All programmable functions remain as described in Section 1 of the M9 or M130 manual.
1.3.1 Additional Programmable Functions
Remote Isolation Relay control Remote Local/Remote Sense Relay control Remote Reverse Polarity Control
1.3.2 Readback Functions
All readback functions remain as described in Section 1 of the M9 or M130 manual.
M133 / M135 / M136 Operation, Remote Programming 1
Page 4
Manual Addendum Sorensen DCS Series
Molex Pin
Description
1
Isolated Remote Sense (+)
2
Isolated Remote Sense (-)
3&4
Not Used
5
Non-Isolated DCS output Voltage +
6
Non-Isolated DCS output Voltage -
2.1 CONFIGURATION
The M9 (GPIB) or M130 (LXI Ethernet) and the Relay PCB options are installed at the factory. Use the setup procedure described in the M9 or M130 programming manual section 2 to configure the M9 or M130 and Relay PCB for your system and application.
2.2 EXTERNAL SIGNAL CONTROL USER CONNECTOR
The control signals accessible at connector J5 are the M9 signals extended thru the relay PCB from the M9 external user control signals are as described in paragraph 2.3 of the M9 programming manual.
The control signals accessible at connector J3 are the DCS 1KW J3 signals extended thru the relay PCB from the DCS 1KW rear panel are as described in paragraph 2.4.2 – 2.4.3 of the DCS 1KW Operation
Manual. NOTE: Do not use the sense connections at J312
and J3-13 – Sense connection must be made at the J9 Pins 1 and 2.
A 6-pin Molex J9 provides access to the isolated remote sense signals J9-1 and J9-2. The mating receptacle for the 6-pin connector is Molex 43025-0600. Remote sense J9-1 connects to the +side of the load and J9-2 to the –side. Also accessible is the non-isolated DCS output voltage on J9-5 (+) and J9-6 (-).
3.1 IEEE 488.2 or Ethernet and SCPI COMMAND OPERATION
The M9 and Relay PCB operation by remote programming using the M9 IEEE-488.2 and SCPI command sets are as described in section 3 of the M9 programming manual.
2 M133 / M135 / M136 Operation, Remote Programming
Table 1 External User Connector J9
Page 5
Sorensen DCS Series Manual Addendum
3.1.1 Output SCPI Commands Relay PCB
3.1.1.1 Calibration SCPI Commands
CAL:INIT:VOLT <VALUE> ; Stores fixed output voltage at power up CAL:INIT:VOLT:PROT <VALUE> ; Sets over voltage protection level CAL:INIT:CURR <VALUE> ; Stores fixed output current at power up CAL:UNLOCK “6867” ; Security code store unlock CAL:STORE ; Stores calibration parameters CAL:LOCK ; Locks calibration parameters
3.1.3.2 Output SCPI Commands
OUTP:ISOL OFF ; Sets the isolation relay control signal off OUTP:POL NORM ; Sets normal polarity or OUTP:POL INV ; Reverses output polarity OUTP:ISOL ON ; Sets the isolation relay control signal ON OUTP:SENS ON ; Sets the sense relay signal open or closed
M133 / M135 / M136 Operation, Remote Programming 3
Page 6
Manual Addendum Sorensen DCS Series
Figure 1. Top and Side Views
4 M133 / M135 / M136 Operation, Remote Programming
Page 7
Sorensen DCS Series Manual Addendum
Figure 2. Rear View – GPIB
M133 Operation, M9 Remote Programming 5
Page 8
Manual Addendum Sorensen DCS Series
Figure 3. Rear View – Ethernet
6 M133 / M135 / M136 Operation, Remote Programming
Loading...