American Standard UV05 User Manual

Operation Maintenance Manual OM 751-1
MicroTech II® Unit Ventilator Controls
for AAF®-HermanNelson® Classroom Unit Ventilators
Group: Applied Systems
Part Number: OM 751
Date: November 2006
DX Cooling Only-
Software Model UV05
Used with AAF-HermanNelson Classroom Unit Ventilator
Model AVV - Floor Mounted
Model AHV - Ceiling Mounted
Model AZV, AZU - Floor Mounted Self Contained Air Conditioner
IMPORTANT
Before unit commissioning, please read this publication in its entirety.
Develop a thorough understanding before starting the commissioning procedure.
This manual is to be used by the commissioner as a guide. Each installation is unique, only general topics are covered.
The order in which topics are covered may not be those required for the actual commissioning.
© 2006 McQuay International
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Acronyms/Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Using the Keypad/Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Display Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Keypad Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Using the Keypad/Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Menu Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Description of Operation . . . . . . . . . . . . . . . . . . . . 12
State Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
UVC Unit Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OFF Mode (State 9) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Night Purge Mode (State 8) . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fan Only Mode (State A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Emergency Heat Mode (Super State) . . . . . . . . . . . . . . . . . . . 16
Auto Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cool Mode (Super State) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Special Purpose Unit Modes. . . . . . . . . . . . . . . . . . . . . . . . . . 21
Unit Mode Priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Occupancy Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Occupied Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Unoccupied Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Additional Occupancy Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Networked Occupancy Sensor Capability. . . . . . . . . . . . . . . . 25
Unit-Mounted Time-Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit-Mounted Tenant Override Switch . . . . . . . . . . . . . . . . . . 25
Remote Wall-Mounted Sensor Tenant Override Switch . . . . . 25
Remote Wall-Mounted Sensor Status LED. . . . . . . . . . . . . . . 25
Space Temperature Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Networked Set Point Capability. . . . . . . . . . . . . . . . . . . . . . . . 26
Networked Set Point Offset Capability . . . . . . . . . . . . . . . . . . 26
Networked Set Point Shift Capability . . . . . . . . . . . . . . . . . . . 26
Networked Space Temperature Sensor Capability . . . . . . . . . 26
Remote Wall-Mounted Sensor with +/–3°F
Adjustment (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Remote Wall-Mounted Sensor with 55°F to 85°F
Adjustment (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Effective Set Point Calculations . . . . . . . . . . . . . . . . . . . . . . .27
Proportional Integral (PI) Control Loops . . . . . . . . . . . . . . . . . . . . . 29
Discharge Air Temperature Control . . . . . . . . . . . . . . . . . . . . 29
PI Control Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Proportional Band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Integral Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Indoor Air Fan Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Auto Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Occupied, Standby, and Bypass Operation . . . . . . . . . . . . . .31
Unoccupied Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Cycle Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Off Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Outdoor Air Damper Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Minimum Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Economizer Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Networked Space Humidity Sensor Capability . . . . . . . . . . . 34
Networked Outdoor Humidity Sensor Capability . . . . . . . . . . 34
Demand Controlled Ventilation (optional) . . . . . . . . . . . 34
CO
2
Networked Space CO
ASHRAE Cycle II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Compressor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Compressor Envelope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Compressor Cooling Lockout . . . . . . . . . . . . . . . . . . . . . . . . 35
Compressor Minimum On and Off Timers . . . . . . . . . . . . . . . 36
Compressor Start Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Outdoor Air Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Floating-Point Actuator Auto-Zero, Overdrive and Sync . . . . . . . . 36
External Binary Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
External Binary Input 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
External Binary Input 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
External Binary Input 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
External Binary Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
External Binary Output 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
External Binary Output 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
External Binary Output 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Sensor Capability . . . . . . . . . . . . . . . 34
2
UVC Input and Output Table . . . . . . . . . . . . . . . . . 40
Diagnostics and Service. . . . . . . . . . . . . . . . . . . . . 41
Alarm and Fault Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Space Temp Sensor Failure (F0). . . . . . . . . . . . . . . . . . . . . . 42
DX Pressure Fault (F1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Compressor Envelope Fault (F2) . . . . . . . . . . . . . . . . . . . . . . 42
Discharge Air DX Cooling Low Limit Indication (F3) . . . . . . . 42
Condensate Overflow Indication (optional) (F4). . . . . . . . . . . 43
Space Coil DX Temp Sensor Failure (F5) . . . . . . . . . . . . . . . 43
Outdoor Temp Sensor Failure (F6) . . . . . . . . . . . . . . . . . . . . 43
Discharge Air Temp Sensor Failure (F7) . . . . . . . . . . . . . . . . 43
Outdoor Coil DX Temp Sensor Failure (F8). . . . . . . . . . . . . . 43
Space Humidity Sensor Failure (optional) (FA) . . . . . . . . . . . 44
Outdoor Humidity Sensor Failure (optional) (Fb) . . . . . . . . . . 44
Space CO2 Sensor Failure (optional) (FC). . . . . . . . . . . . . . . 44
Change Filter Indication (FF) . . . . . . . . . . . . . . . . . . . . . . . . . 44
EPROM Memory Indicator (EE) . . . . . . . . . . . . . . . . . . . . . . . 44
Configuration Display (--) . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Troubleshooting Temperature Sensors . . . . . . . . . . . . . . . . . . . . . 44
Troubleshooting Humidity Sensors . . . . . . . . . . . . . . . . . . . . . . . . 45
Troubleshooting Carbon Dioxide (CO
) Sensors. . . . . . . . . . . . . . 46
2
UVC Configuration Parameters . . . . . . . . . . . . . . . 47

Introduction

Introduction
This manual provides information on the MicroTech II® control system used in the AAF®-
®
HermanNelson
Unit Ventilator product line. It describes the MicroTech II components, input/
output configurations, field wiring options and requirements, and service procedures.
For installation and general information on the MicroTech II Unit Ventilator Controller, refer to IM 747, MicroTech II Unit Ventilator Controller.
For installation, commissioning instructions, and general information on a particular unit ventilator model, refer to the appropriate manual (Table 1), as well as accompanying software operating instruction manual (Table 4), and possible accessory manuals that may pertain to the unit (Table 3).
For installation and maintenance instructions on a plug-in communications card, refer to the appropriate protocol-specific installation and maintenance manual (Table 2). For a description of supported network variables for each protocol, refer to Protocol Data Packet bulletin ED
15065.
Table 1: Model-specific unit ventilator installation literature
Description Manual #
Air Source Heat Pump IM 502 X DDC Control Components AED-Q-MTII-811 X Self-Contained IM 503 X X X X X X Self-Contained DDC Control Components Vertical Split-system IM 817-1 X X X X Horizontal Split-system IM 830 X X X X X X X X Ceiling Vent AH IM 830 X X X X
AZS Q V U R MII 810
AEQ
AER
AHF
AHB
AHR
AVF
AVB
AHV
AVS
AVH
AVV
AVR
AZS
AZB
AZR
AZU
XXXXX
AZV
AZQ
ARQ
ERQ
Table 2: Protocol-specific communication card installation literature and protocol data
Description Manual #
Unit Ventilator Unit Controller LonWorks® Communications Module
Unit Ventilator Unit Controller JCI N2 Open® Communications Module
Unit Ventilator Unit Controller BACnet® Communications Module
Protocol Data Packet ED-15065
IM 729
IM 730
IM 731
Table 3: Accessory-specific installation literature
Description Manual #
MTII Unit Ventilator Controls Installation IM 747 Room Temperature Sensors Installation IM 629-1 ATS Service Cable Installation for Unit Ventilators IM 762-0
McQuay OM 751 3
Introduction
Table 4: Software program literature
Description Manual #
Air Source Heat Pump with Electric Heat (Software Model 00) OM 748 Water Source Heat Pump with Electric Heat (Software Model 02) Water Source Heat Pump without Electric Heat (Software Model 03) DX Cooling with Electric Heat (Software Model 04) OM 750 DX Cooling Only (Software Model 05) OM 751 Electric Heat Only (Software Model 06) OM 752 DX Cooling with Hydronic Heat - Valve Control (Software Model 07) DX Cooling with Hydronic Heat - F&BP Damper Control (Software Model 08) 2-Pipe Hydronic Heat Only - Valve Control (Software Model 09) 2-Pipe Hydronic Heat Only - F&BP Damper Control (Software Model 10) 2-Pipe Chilled Water Cooling and Hot Water Heat - Valve Control (Software Model 11) 2-Pipe Chilled Water Cooling and Hot Water Heat - F&BP Damper Control (Software Model 12) 4-Pipe Chilled Water Cooling and Hydronic Heat - Valve Control (Software Model 13) 4-Pipe Chilled Water Cooling and Hydronic Heat - F&BP Damper Control (Software
Model 14) 2-Pipe Chilled Water Cooling Only - Valve Control (Software Model 15)
2-Pipe Chilled Water Cooling Only - F&BP Damper Control (Software Model 16) 2-Pipe Chilled Water Cooling with Electric Heat - Valve Control (Software Model 17)
2-Pipe Chilled Water Cooling with Electric Heat - F&BP Damper Control (Software Model 18)
OM 749
OM 753
OM 754
OM 755
OM 756
OM 757
OM 758
NOTICE
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against detrimental interference when the equipment is operated in a commercial environment. Operation of this equipment in a residential area is likely to cause detrimental interference in which case users are required to correct the interference at their own expense. McQuay International disclaims any liability resulting from any
interference or for the correction thereof.
WARNING
Electric shock hazard. Can cause personal injury or equipment damage.
This equipment must be properly grounded. Connections and service to the MicroTech II control panel must be performed only by personnel that are knowledgeable in the operation of the equipment being controlled.
CAUTION
Extreme temperature can damage system components.
The MicroTech II controller is designed to operate in ambient temperatures from -20°F to 125°F. It can be stored in ambient temperatures from -40°F to 140°F. It is designed to be stored and operated in relative humidity up to 95% (non-condensing).
CAUTION
Static sensitive components. A static discharge while handling electronic circuit boards can damage components.
Discharge any static electrical charge by touching the bare metal inside the main control panel before performing any service work. Never unplug any cables, circuit board terminal blocks, relay modules, or power plugs while power is applied to the panel.
4 McQuay OM 751
Introduction

Acronyms/Abbreviations

The following table list acronyms and abbreviations that may or may not be used within this manual. Other abbreviations for keypad displays and parameters can be found in Table 8 on page 14 and Table 26 on page 47.
Table 5: Acronyms and abbreviations
Description
Air Fan AF Auxiliary Heat End Differential AHED Auxiliary Heat Start Differential AHSD American Standard Code for Information Interchange ASCII American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc Compressorized Cooling Lockout CCLO Spac e C O Chilled Water CW Chilled Water Valve Position CWVP Discharge Air DA Discharge Air High Limit DAHL Discharge Air Temperature DAT Discharge Air Temperature Setpoint DATS Demand Controlled Ventilation DX Cooling Discharge Air Low Limit DXLL Economizer Compare Differential ECD Economizer IA/OA Enthalpy Differential EED Economizer OA Enthalpy Setpoint EES Emergency Heat Setpoint EHS Exhaust Interlock OAD Min Position Setpoint EOAD Outdoor Air Temperature Setpoint EOAT End-of-Cycle EOC EOC OAT Low Setpoint EOCS Outdoor Air Humidity Output EORH Space Humidity Setpoint ERH Economizer IA/OA Temp Differential ETD Economizer OA Temp Setpoint ETS Source (water in) Temperature EWIT Face and Bypass Damper Position FBDP Federal Communications Commission FCC Face and Bypass F & BP Heating, Ventilating, Air Conditioning Refrigeration HVACR Heating EOC Valve Setpoint HEOC Hot Water HW Indoor Air IA Indoor Air Fan IAF Indoor Air Temperature IAT Light Emitting Diode LED Local User Interface LUI Mixed Air Low Limit MALL Mechanical Cooling Low Limit Setpoint MCLL National Electric Code NEC Outside Air OA Outside Air Dampers OAD Energize Exhaust Fan OAD Setpoint OADE OAD Min Position High-Speed Setpoint OADH OAD Min Position Low-Speed Setpoint OADL OAD Min Position Med-Speed Setpoint OADM Outdoor Air Damper Position OADP OAD Lockout Setpoint OALS OAD Max Position Setpoint OAMX Outside Air Temperature OAT
Setpoint CO2S
2
Acronym/
ASHRAE
DCV
Abr.
McQuay OM 751 5
Introduction
Description
Occupied Cooling Setpoint OCS Occupied Heating Setpoint OHS Occupancy Override Input OOI Occupancy Sensor Input OSI Proportional Integral PI Parts Per Million PPM Positive Temperature Coefficient PTC Relative Humidity RH Space Humidity Setpoint Read Only RO Read Write RW Standby Cooling Setpoint SCS Standby Heating Setpoint SHS Thermal Expansion Valve TXV Unoccupied Cooling Setpoint UCS Unoccupied Heating Setpoint UHS Unit Ventilator UV Unit Ventilator Controller UVC UVC (Heat/Cool) Mode Output UVCM UVC State Output UVCS Wet Heat Valve Position VALP Ventilation Cooling Low Limit Setpoint VCLL Ventilation Cooling Lockout VCLO Ventilation Cooling Setpoint VCS Wet Heat WH Source (water in) Temperature Differential WITD
Acronym/
RHS
Abr.
6 McQuay OM 751

Getting Started

Getting Started
The MicroTech II Unit Vent Controller (UVC) is a self-contained device that is capable of complete, stand-alone operation. Information in the controller can be displayed and modified by using the keypad/display (local user interface). The following sections describe how to use the keypad/display.
Note – Many UVC parameters are accessible both through the keypad/display and the network
interface. The shared keypad/display and the network interface variables have a “last­change-wins” relationship.

Using the Keypad/Display

The keypad/display shown in Figure 1 is provided with all MicroTech II Applied Unit Ventilator unit controllers. With the keypad/display, operating conditions, system alarms, and control parameters can be monitored. Set points and other parameters also can be modified.
Figure 1: Keypad/display
MicroTechTMII
FAN ONLY
COOL
HEAT
AUTO
MODE FAN
HIGH
MED
LOW
AUTO
FUNC
ON /
STOP

Display Format

The keypad/display’s 2-digit, 7-segment display normally shows the effective heating or cooling temperature set point (Effective Set Point Output). The display also is used to view and modify UVC parameters as explained in the following sections.
Note – When the UVC is in the OFF mode, the effective heating set point appears in the display.
All other LEDs are switched off.

Keypad Functions

Security Levels
The keypad/display provides a 4-level password security feature that can be used to restrict access. The available security levels are shown in Table 6.
Note – All unit ventilator controllers ship with the lowest security (level 0) enabled. To change
security levels, see Figure 2. Once a security level is changed, the keypad/display remains at that security level until the next time it is changed.
Why can’t I use the MODE or FAN key or adjust Set Point Offset?
Most likely this is due to the security feature being used. If the security feature is set higher than level 0, then some keypad/display functionality is locked out. To ensure this is not the problem, enter the level 0 password then try to use the keypad/display again.
McQuay OM 751 7
Getting Started
Table 6: Keypad/display security levels
Level Display What is restricted? Password
0
1
2
3
U0
Default level (access all) 10 Does not allow set point offset changes;
U1
also locks out keypad/display menu access.
Does not allow set point offset changes nor MODE key changes; also locks out
U2
keypad/display menu access. Does not allow set point offset changes
U3
nor MODE and FAN key changes; also locks out keypad/display menu access.
21
32
43
Figure 2: Changing keypad/display security levels
ON/STOP Key and LED
Use the ON/STOP key to toggle the UVC between OFF mode and running (Application Mode Input). The ON/STOP LED is off when the UVC is in the OFF mode.
Note – When the UVC is in the OFF mode, the effective heating set point appears in the display.
All other LEDs are switched off.
– The UVC archives each change to the keypad/display FAN and MODE keys. When the
ON/STOP key is used to bring the unit out of OFF mode, the UVC implements the last active fan and unit modes.
– Each time the UVC power cycles, the UVC is in the auto fan and auto unit modes when
power is returned.
WARNING
Off mode is a “stop” state for the unit ventilator. It is not a “power off” state. Power may still be provided to the unit.
FAN Key
Use the FAN key to toggle through each of the fan speeds (Fan Speed Command Input): Auto, Low, Medium, and High.
MODE Key
Use the MODE key to toggle through the keypad/display accessible unit modes (Heat/Cool Mode Input): Auto, Heat, Cool, and Fan Only.
Arrow Keys
Use the arrow keys to scroll between parameters and to adjust parameters.
FUNC Key
Use the Func key to view the actual space temperature or to confirm selection and changes to user-adjustable parameters.
8 McQuay OM 751
Getting Started

Using the Keypad/Display

Viewing Actual Indoor Air Temperature (IAT)
Normally, the effective set point temperature appears on the keypad/display. You also can use the keypad/display to view the indoor air temperature (IAT). See Figure 3.
Note – When the actual indoor air temperature (Effective Space Temp Output) equals the
effective set point temperature (Effective Set Point Output), you there is no change to the keypad/display when you view space temperature.
Figure 3: Viewing indoor air temperature
70 71 70
Effective set point
Changing Set Points
The keypad/display can be used to make a +/–5°F (+/–3°C) offset adjustment to the effective temperature set point. See Figure 4. Also see “Space Temperature Set Points” on page 26 to learn more about temperature set points.
Figure 4: Adjusting the set point offset
FUNC
Enter
(5-sec)
Actual space temperature
Effective set point
-1
Flash value
FUNC
Enter
0
0
Current
offset
So 69
Effective set point
70
Effective set point
-1
Adjusted
offset
FUNC
Save
change
So
Set point
offset
Note – The set point offset clears whenever UVC power is cycled. When you change the set point
offset after a power cycle, or for the very first time, this cleared value shows as the highest allowed value (5°F/3°C) but is not an actual offset value.
– When using the +/–3°F (+/–1.7°C) remote wall sensor, any set point offset adjustment
made at the keypad/display causes the UVC to override and ignore the remote wall sensor set point adjustment knob. To use the remote wall sensor set point adjustment knob after you changed the set point offset on the keypad/display, clear the keypad/ display set point offset by cycling UVC power.
– When using the 55°F to 85°F remote wall sensor, the UVC ignores any LUI set point offset
adjustments.

Menu Reference

The keypad/display menu eases troubleshooting and simplifies UVC configuration. The user can access the most common parameters and system status values without a PC or network interface.
The keypad/display menu is accessed via an unmarked, hidden key. This hidden key is located approximately behind the letter “h” in the MicroTech II logo on the keypad/display face.
The keypad/display menu consists of two levels. The first level is the keypad/display Menu Item List containing alphanumeric characters representing each parameter. The second level is where the parameter’s value is viewed and adjusted if the parameter is adjustable. After 15­seconds, an inactivity timer automatically causes the display to back out of the menu levels, returning to the effective set point display.
McQuay OM 751 9
Getting Started
Figure 5: Changing a keypad/display menu item
Table 7: Keypad/display menu item list
Display Keypad menu item list Abr. Description
Reset Alarm Input Enter 1 to clear alarms (clears all inactive alarms, except filter alarm). To enable
rA
UVC (Heat/Cool) Mode
HC
Output UVC State Output
St
Discharge Air Temp Set
d0
point Output Discharge Air Temp
d1
Output Ventilation Cooling Low
d2
Limit set point Mechanical Cooling Low
d3
Limit set point Slave Type Configuration Set slave type: 0 = Independent (slave uses own sensors), 1 = Dependent (slave
SL
Effective Occupancy
Eo
Output Occupancy Override Input
o(
Occupied Cooling set
(o
point Standby Cooling Set
(S
point Unoccupied Cooling Set
(U
point Occupied Heating Set
ko
point Standby Heating Set
kS
point Unoccupied Heating Set
kU
point Wall Sensor Type
rS
Outside Air Damper
o1
Position Output OAD Min Position High-
o2
Speed Set point OAD Min Position Med­Speed Set point OADM
o3
OAD Min Position Low­Speed Set point OADL
o4
the alarm again, enter 0. Display current UVC mode. 1 = Heat, 3 = Cool, 4 = Night Purge, 6 = Off, 8 = Emerg.
UVCM
Heat, 9 = Fan Only Display current UVC state. 1 = EconMech, 2 = Mech, 3 = Econ, 4 = DA Heat, 5 = Heat, 6 = ActiveDehum, 7 = Full Heat, 8 = Night Purge, 9 = Off, 10 = Fan Only, 11
UVCS
= Heat Mode Cant Heat, 12 = CantCool, 13 = Emerg Heat Mode Cant Heat, 14 = Heat Mode Low Limit, 15 = Cool Mode Low Limit
DATS Display current DA temperature set point. RO x
DAT Display current DA temperature. RO x
VCLL Adjust economizer cooling DA temperature low limit. RW x
MCLL Adjust mechanical cooling DA temperature low limit. RW x
follows master). This feature requires a network over which the master and slave UVCs can communicate.
Display current occupancy. RO x
Set occupancy: 0 = occupied, 1 = unoccupied, 2 = bypass, 3 = standby. Adjusting this variable is intended only for troubleshooting. Once you are done, cycle unit power to clear this variable and return the UVC to normal operation.
OCS Adjust occupied cooling set point. RW x
SCS Adjust standby cooling set point. RW x
UCS Adjust unoccupied cooling set point. RW x
OHS Adjust occupied heating set point. RW x
SHS Adjust standby heating set point. RW x
UHS Adjust unoccupied heating set point. RW x
Set wall sensor type: 0 = +/–3F, 1 = 55°F to 85°F. RW x 0
OADP Display OA damper position. RO x
Adjust OA damper minimum position with IAF at high speed. (This variable is
OADH
factory set to 5% open when the unit is ordered with optional Adjust OA damper minimum position with IAF at medium speed. (This variable is not used when the optional damper minimum regardless of fan speed.) Adjust OA damper minimum position with IAF at low speed. (This variable is not used when the optional damper minimum regardless of fan speed.)
CO2 DCV is enabled. Only OADH is active as the OA
CO2 DCV is enabled. Only OADH is active as the OA
CO2 DCV.)
RO
05
1
RW
RW x
RO x
RO x
RW x 0
RW x
RW x 20%
RW x 25%
RW x 30%
Default
//
54°F
(12°C)
45°F
(7°C)
//
73.4°F (23°C)
77°F
(25°C)
82.4°F (28°C)
69.8°F (21°C)
66.2°F (19°C)
60.8°F (16°C)
2
2
10 McQuay OM 751
Display Keypad menu item list Abr. Description
Exhaust Interlock OAD
o5
Min Position set point Energize Exhaust Fan
o6
OAD Set point OAD Max Position Set
o7
point
OAD Lockout Enable
o8
OAD Lockout Set point OALS
o9
Economizer Enable Set economizer status: 0 = disable, 1 = enable. RW x 1
E1
Economizer OA Temp
E2
Set point Economizer IA/OA Temp
E3
Differential Economizer OA Enthalpy
E5
Set point Economizer IA/OA
E6
Enthalpy Differential
Space Humidity Output ERH Display room humidity (optional). 00 = No sensor connected. RO x
r1
Outdoor Air Humidity
r3
Output
Outdoor Air Temp Output EOAT Display OA temperature. RO x
ot
Emergency Heat Enable Set emergency heat status: 0 = disable, 1 = enable. RW x 1
k1
Emergency Heat Set
k2
point Emergency Heat
k3
Shutdown Configuration Auxiliary Heat Start
A1
Differential Auxiliary Heat End
A2
Differential Auxiliary Heat
A3
Configuration External BI-3
b3
Configuration External BO-3
b6
Configuration Fan Cycling
(F
Configuration
Filter Alarm Enable Set filter alarm status: 0 = disable, 1 = enable. RW x 0
(E
Reset Filter Alarm Input Enter 1 to clear filter alarm. RW x
(r
Compressor Enable Set compressor status: 0 = disable, 1 = enable. RW x 1
(1
Compressor Cooling
(2
Lockout Set point
Compressor Heating
(3
Lockout Set point
Compressor Start Delay
(6
Space Temp Sensor
SP
Offset
Keypad/display
Un
Temperature Units
1. RW = read and write capable, RO = read only.
2. If a menu value is greater than 2-digits (higher than 99), then
Adjust OA damper position above which the exhaust fan output will be energized.
EOAD
There is a fixed –5% differential associated with this set point. Adjust OA damper minimum position when the exhaust interlock input is
OADE
energized.
OAMX Adjust OA damper maximum position. RW x 99%
Set OA damper lockout feature status: 0 = disable, 1 = enable. (This variable is factory set to 1 when the unit is ordered as a recirc unit with no OAD.) Adjust OA temperature below which the OA damper closes if the OA damper lockout is enabled. (This variable is factory set to –99°C when the unit is ordered as a recirc unit with no OAD.)
Adjust economizer OA temperature set point. DO NOT lower this set point below
ETS
CCLO or you risk creating a deadband where no cooling occurs.
ETD Adjust economizer IA/OA temperature differential. RW x 1.8°F (1°C)
EES Adjust economizer OA enthalpy set point. RW x
EED Adjust economizer IA/OA enthalpy differential. RW x
EORH Display OA humidity (optional). 00 = No sensor connected. RO x
EHS Adjust emergency heat set point. RW x
Set emergency heat operation during shutdown, 0 = no emergency heat during shutdown: 1 = allow emergency heat during shutdown.
AHSD Adjust auxiliary heat start differential. RW x 1.8°F (1°C)
AHED Adjust auxiliary heat stop differential. RW x 1.8°F (1°C)
Set auxiliary heat type: 0 = N.O. device, 1 = N.C. device. RW x 0
Set the function external binary Input 3: 0 = ventilation lockout, 1 = exhaust interlock.
Set the function of external binary output 3: 0 = exhaust fan on/off signal, 1 = auxiliary heat.
Set space fan cycles (switches off) during occupied, bypass, and standby mode: 2 = continuous, 3 = cycling.
Adjust compressor cooling lockout set point. When the OA temperature falls below this set point, compressor cooling is not allowed. DO NOT make this setting lower
CCLO
than the factory default. There is a fixed +3.6°F (2°C) differential associated with this set point.
Adjust compressor heating lockout set point. When the OA temperature falls below
CHLO
this set point, compressor heating is not allowed and only electric heat will be used. Adjust compressor start delay. Where several units (inductive loads) are
connected to the same electrical supply, make this set point unique for every UVC to prevent multiple compressors from energizing at the same time after a power failure or occupancy change.
Adjust this setting to bias the UVC measured space temperature. RW x 0
Set keypad/display temperature units in English or SI. This set point also effects which unit types displayed over Metasys N2 and BACnet MS/TP networks using the appropriate optional communications modules.
// will be displayed on the keypad/display.
Getting Started
RO
05
1
RW
RW x 99%
RW x 12%
RW x 0
RW x
RW x
RW x 0
RW x 0
RW x 0
RW x 2
Default
35.6°F (2°C)
68°F
(20°C)
25 Btu/lb
(58 kJ/kg)
1.3 Btu/lb (3 kJ/kg)
53.6°F (12°C)
//
RW x
RW x
RW x 0 sec
RW x F
63.5°F
(17.5°C)
25°F
(-4°C)
2
McQuay OM 751 11

Description of Operation

Description of Operation

State Programming

The MicroTech II UVC takes advantage of “state” machine programming to define and control unit ventilator operation. “State” defines specific states or modes of operation for each process within the unit ventilator (e.g., heating, cooling, etc.) and contain the specific logic for each state. This eliminates some of the most common problems associated with control sequences such as the possibility of simultaneous heating and cooling, rapid cycling, etc.
State machine programming, and the unique nature of state diagrams, can be easily used to describe operation. It can simplify sequence verification during unit commissioning, as well as simplify troubleshooting. With the unique combination of state machine programming and the keypad/display’s ability to allow a technician to easily determine the active UVC state, troubleshooting the UVC can be very simple.
The state diagrams presented in the following sections consist of several “elements” including super states, states, conditional jumps (also called transitions) and transition points. Super states are used as a means to group two or more related states into a single control function such as cooling, or heating, etc. States are where all the actual work takes place, within each state the UVC enables PI-loops and other logic sequences required to control unit ventilator operation within that particular state, while other functions and PI-loops not needed during that state may be disabled. Conditional jumps, or transitions, are the logic paths used by the UVC to determine which state should be made active, these are the “questions” the UVC continually considers. The transition point is simply a point through which a number of conditional jumps meet. Think of it as a point where a number of questions must be considered from which the UVC then determines which path is followed and which state is then made active.
The UVC states and super states are used to define the “normal” unit modes, such as Off, Night Purge, Fan Only, Emergency Heat, Auto, Cool, and Heat. The UVC also supports several “special purpose” unit modes such as Purge, Pressurize, De-pressurize, and Shutdown, which can be forced via a network connection and override typical UVC operation.
Note – Not all states or modes are available for all UV configurations, and some states (such as
Active Dehum) are optional.
– In the state descriptions below the terms, saturated high and saturated low, indicate that
the heating or cooling function being described has reached 100% or 0%, respectively.
12 McQuay OM 751
Figure 6: Complete UVC—state diagram
Description of Operation
CantHeat
B
EmergencyHeat
ModeSuperState
FullHeat
7
CantHeat
D
HeatMode
SuperState
Off
Heat
5
LowLimit
E
NightPurge
Econ
Mech
8
FanOnly
A
AutoMode
3
1
2
DAHeat
4
LowLimit
F
9
CoolMode
SuperState
CantCool
C
EconMech

UVC Unit Modes

The UVC provides several “normal” modes of unit operation. These include: Off, Night Purge, Fan Only, Cool, Emergency Heat, Auto, Heat, and Cool.
Normal UVC modes can contain a single state or several states depending upon the functionality required for each particular mode. Each UVC state is assigned a number, which can be very helpful when trying to understand which state is currently active within the UVC. To view the current UVC state number, use the keypad/display.
McQuay OM 751 13
Description of Operation
F
Table 8: UVC state names and numbers
Normal UVC modes State names
OFF OFF 9 9 57
Night purge Night Purge 8 8 56
Fan only Fan Only 10 A 65
Emergency heat
Heat
Auto
Cool
Full Heat 7 7 55
Cant Heat 13 D 68
Heat 5 5 53 Cant Heat 11 B 66 Low Limit 14 E 69
EconMech 1 1 49
Mech 2 2 50
Econ 3 3 51
DA Heat 4 4 52 Cant Cool 12 C 67 Low Limit 15 F 70
Decimal ASCII Hex
State numbers
WARNING
Off mode is a “stop” state for the unit ventilator. It is not a “power off” state. Power may still be provided to the unit.

OFF Mode (State 9)

Off mode is provided so that the UVC can be forced into a powered OFF condition. OFF mode is a “stop” state for the unit ventilator; it is not a power off state. OFF mode consists of a single UVC state: OFF [9].
When OFF mode becomes active, the UVC stops all normal heating, cooling, and ventilation (OA damper is closed), and fan operation ends. The UVC continues to monitor space conditions, indicate faults, and provide network communications (if connected to a network) in the OFF mode while power is maintained to the unit.
While in OFF mode, the UVC does not maintain DA temperatures. If the space temperature drops below EHS while in the OFF mode, the UVC is forced into the Emergency Heat mode (see “Emergency Heat Mode (Super State)” on page 16).
The space lighting output continues to operate based upon the current occupancy mode.
Note – Special purpose unit modes such as Purge, Pressurize, and De-pressurize can force the
UVC to perform “special” functions during which the display appears to be in the OFF mode.
Figure 7: Off state diagram
OFF
9
UVC Mode
UVC Mode ≠ OFF
=
OF
Transition
point
14 McQuay OM 751
Description of Operation

Night Purge Mode (State 8)

Night Purge mode is provided as a means to more easily and quickly ventilate a space. Night purge can be useful in helping to remove odor build up at the end of each day, or after cleaning, painting, or other odor generating operations occur within the space. Night Purge mode consists of a single UVC state: Night Purge [8].
Night Purge is a full ventilation with exhaust mode, during which room comfort is likely to be compromised. Therefore, McQuay strongly recommends using Night Purge only when the space is unoccupied.
When Night Purge mode becomes active, the UVC stops all normal heating and cooling. Since any new energy used to treat the incoming air would be wasted in the purge process. In the Night Purge mode, the space fan is set to high speed, the OA damper is set to 100% open, and the Exhaust Fan binary output (see “External Binary Outputs” on page 38) is set to ON. If the UVC is not set to another mode within 1 hour (fixed), the UVC automatically switches to the Fan Only mode (see “Fan Only Mode (State A)” on page 15).
While in Purge mode, the UVC does not maintain DA temperatures. If the space temperature drops below the EHS, the UVC is forced into the Emergency Heat mode (see “Emergency Heat Mode (Super State)” on page 16).
Figure 8: Night purge state diagram
Night Purge
8
UVC Mode ≠
Night purge
=
Transition
point
UVC Mode
Night purge

Fan Only Mode (State A)

The Fan Only mode is provided so that the UVC can be forced into a Fan Only operation via a keypad/display or a network connection. Fan Only mode consists of a single UVC state: Fan Only [A].
When Fan Only mode becomes active, the UVC stops all normal heating and cooling.
While in Fan Only mode, the UVC does not maintain DA temperatures. If the space temperature drops below the EHS, the UVC is forced into the Emergency Heat mode (see “Emergency Heat Mode (Super State)”).
Figure 9: Fan only state diagram
UVC Mode ≠
Fan Only
Fan Only
A
Transition
point
UVC Mode
Fan Only
=
McQuay OM 751 15
Description of Operation

Emergency Heat Mode (Super State)

The Emergency Heat mode is provided for situations where the UVC is in a mode that does not normally allow heating, such as OFF, Cool, Night Purge, or Fan Only. If Emergency Heat mode is enabled, the UVC can automatically force itself into the Emergency Heat mode from OFF, Cool, Night Purge, Fan Only, Purge, Pressurize, De-pressurize, and Shutdown. Emergency Heat mode consists of UVC states: Full Heat [7] and Cant Heat [D].
Software model 05 does not have the primary or secondary heating devices. The UVC uses auxiliary heat (if field provided and field connected) when emergency heat is required.
When the Emergency Heat mode becomes active, the UVC automatically determines which state to make active, Full Heat [7], or Cant Heat [D], based on the transitions for each of those states.
Figure 10: Emergency heat state diagram
Emergency Heat Mode
Super State
Full Heat
Heat
Available
7
Heat
Available
UVC Mode
Emergency Heat
=
UVC Mode ≠
Emergency Heat
=
Transition
point
Cant Heat
D
Full Heat State (State 7)
The Full Heat [7] state is the “normal” state that the UVC goes into when Emergency Heat mode is active. It is activated when the space temperature is lower than the EHS.
When Emergency Heat mode becomes active, the UVC goes into 100% heating until the space temperature raises to the EHS plus a fixed differential (5.4°F/3°C). In the Emergency Heat mode, the space fan is set to high speed, and the OA damper operates normally.
If the UVC automatically forces itself into the Emergency Heat mode from another mode (e.g., Cool, Fan Only, etc.), then the UVC returns to the appropriate unit mode once the space temperature rises to the EHS plus a fixed differential (5.4°F/3°C).
The UVC monitors the DAT to ensure it does not exceed DAHL. If the DAT does exceed DAHL, then heating is set to 0% for a minimum of 2-minutes (fixed) and until the DAT drops 36°F (20°C) fixed differential below DAHL.
Cant Heat State (State D)
The Cant Heat [D] state is a “non-normal” state that the UVC can go into when Emergency Heat mode is active. An IAT or DAT sensor fault during Emergency Heat mode causes the UVC to make this state active.
When the Cant Heat state becomes active, the space fan remains at high speed as set during the Full Heat state.
The UVC will remain in the Cant Heat state until heat becomes available.
16 McQuay OM 751
Description of Operation

Auto Mode

Auto mode is provided so that the UVC can be set to automatically determine if heating or cooling is required. Auto mode is the default power-up UVC mode. Auto mode is made up of the Heat and Cool modes. When the UVC is set to auto mode, the UVC automatically determines which mode (Heat or Cool) to use.
Heat Mode (Super State)
When in Heat mode, the UVC will use auxiliary heat (if field provided and field connected to the unit) as needed to maintain the effective heating setpoint (see “Space Temperature Set Points” on page 26). The keypad/display or a network connection can be used to force the unit into the Heat mode. Additionally, the UVC when set to Auto mode can automatically force the unit into the Heat mode as needed. When the UVC is in Auto mode, it is “normal” for the UVC to “idle” in Heat mode when there is no need to switch to another mode.
The Heat mode super state consists of UVC states: Heat [5], Low Limit [E], and Cant Heat [B].
When the Heat mode super state becomes active, the UVC automatically determines which of the Heat Mode states to make active based upon the transitions for each state.
Figure 11: Heat mode super state diagram
Transition
point
UVC Mode = Heat
OR
=
Space
Auto AND
Warm
UVC Mode ≠ Heat AND
UVC Mode
UVC Mode
Warm AND Heat Pl = Sat Low
Auto
OR
=
Auto AND Space =
Heat Mode
Super State
UVC Mode
Heat
Cant Heat
B
Heat
Available
Heat = Available
AND
Low Limit = Inactive
Heat = Available
AND
Low Limit = Inactive
Available
Heat Pl = Sat Hi
(2 minutes)
DAT<VCLL
AND
DAT<(VCLL + 1.8F)
Low Limit
Heat
5
LLPl = Sat Lo
(2 minutes)
AND
E
Heat State (State 5)
The Heat state is the “normal” state during Heat mode. When the Heat state becomes active, the UVC will (within State) continually calculate the DATS (“Discharge Air Temperature Control” on page 29) required to maintain the effective heat setpoint (see “Space Temperature Set Points” on page 26). The calculated DATS will not be allowed to go above DAHL. The UVC will use auxiliary heat (if field provided and field connected to the unit) as needed to maintain the current DATS.The auxiliary heat binary output will be used as needed. The Heat Timer (3-minutes fixed) will begin counting. The CO will be active, if the unit is equipped for CO
control (see “CO2 Demand Controlled
2
demand controlled ventilation function
2
Ventilation (optional)” on page 34), and the OA damper will be adjusted as needed to maintain the CO
setpoint. The UVC will remain in this state until one of the transition out conditions
2
become true, or until one of the super state transition out conditions becomes true.
McQuay OM 751 17
Description of Operation
Note – The OAD is considered to be in “alarm” when the OAD is forced below the active minimum
position in the Low Limit state. This is not an actual unit “alarm” or “fault” condition, but only a condition used for the purpose of transition arguments.
Low Limit State (State E)
The Low Limit state is a “non-normal” state the UVC can go into while Heat mode is active when the unit reaches 100% heating and still cannot meet the current DATS (see “Discharge Air Temperature Control” on page 29) required to maintain the effective heating set point (see “Space Temperature Set Points” on page 26). This is likely to occur only if the OA temperature is very cold, the OA damper minimum position is set too high, the unit ventilator is oversized for the application, or if the electric heating has failed, or is set incorrectly.
When the Low Limit state becomes active, the Low Limit PI-loop can override the OA damper position (see “Outdoor Air Damper Operation” on page 32) and adjust the OA damper toward closed as necessary to maintain the current DATS (see “Discharge Air Temperature Control” on page 29).
Cant Heat State (State B)
The Cant Heat state is a “non-normal” state the UVC can go to when Heat mode is active. An IAT or DAT sensor fault during the Heat mode causes the UVC to make this state active.
When the Cant Heat state becomes active, no heating or ventilation takes place. The OA damper goes to the minimum position unless it is forced closed by other functions such as freezestat (T6) or morning warm-up.

Cool Mode (Super State)

When in Cool mode the UVC uses primary cooling (economizer) and secondary cooling (mechanical, DX) as needed to maintain the effective cooling set point (see “Space Temperature Set Points” on page 26). The keypad/display or network connection can be used to force the unit into the Cool mode. When the UVC is in Auto mode, it is “normal” for the UVC to “idle” in Cool mode when there is no need to switch to another mode. The Cool mode super state consists of the following UVC states: Econ Mech [1], Mech [2], Econ [3], DA Heat [4], Low Limit [F], and Cant Cool [C].
When the Cool mode super state becomes active, the UVC will automatically determine which UVC state to make active based upon the transitions for each state.
If the space temperature drops below EHS, and the Emergency Heat function is enabled, the UVC will be forced into the Emergency Heat mode (see “Emergency Heat Mode (Super State)” on page 16).
18 McQuay OM 751
Figure 12: Cool mode super state diagram
Econ
EconMech
Mech
3
1
2
CantCool
C
CoolMode
SuperState
DAHeat
LowLimit
4
F
LLPI=SatLow (2min)
AND
DAT>(VCLL+1.8F)
HeatPI=SatHi(2min)
AND DAT<VCLL
Space≠HighCO2
AND
HeatPI=SatLow
AND
DAT>VCLL
Space=HighCO2
OR
DAT<VCLL
UVCMode≠Cool AND UVCMode≠Auto
OR
UVCMode=Auto AND Space=Cold AND
MechPI=SatLow(3min) AND
EconPI=SatLow
UVCMode=Cool
OR
UVCMode=Auto AND Space=Warm
Econ≠Available
AND
MechCool
Available
Econ = Available
AND
MechCool
Available
Econ≠Available
AND
MechCool=Available
MechPI=SatLow (3min) AND
EconMechTimer=Expired
(3 minutes) OR
MechCool
Available
Econ≠Available
Econ=Available
MechCool≠Available
Econ≠Available
AND
MechCool=Available
Transition
Point
EconTimer=Expired
(3 minutes) AND
EconPI=SatHi AND
MechCool=Available
Description of Operation
Econ State (State 3)
The Econ state is a “normal” state during Cool mode. The Econ state typically is active in the Cool mode when primary cooling (economizer) is available and adequate to meet the cooling requirements.
When the Econ state becomes active, the UVC uses economizer cooling (see “Economizer Operation” on page 32) as needed to maintain the effective cooling set point (see “Space Temperature Set Points” on page 26). If cooling is not required while in the Econ state, the UVC can “idle” in the Econ state until cooling is required or until there is a call to switch to another mode or state.
The UVC monitors the DAT to ensure it does not fall below VCLL.
The CO Controlled Ventilation (optional)” on page 34) and the OA damper is adjusted as needed to maintain the CO
demand controlled ventilation function (optional) will be active (see “CO2 Demand
2
set point.
2
McQuay OM 751 19
Description of Operation
Figure 13: Econ state operation (occupied mode and auto fan)
Econ Mech State (State 1)
The Econ Mech state is a “normal” state during Cool mode. The Econ Mech state typically is active in the Cool mode when primary cooling (economizer) alone is not adequate to meet the cooling requirements and both primary cooling and secondary cooling (compressor) are available.
When the Econ Mech state becomes active, the OA damper is set to 100% open, and the UVC uses the units mechanical cooling capabilities as needed to maintain the effective cooling set point (see “Space Temperature Set Points” on page 26).
The UVC monitors the DAT to ensure it does not fall below MCLL.
Figure 14: Econ mech state operation (occupied mode and auto fan)
Mech State (State 2)
The Mech state is a “normal” state during Cool mode. The Mech state typically is active in the Cool mode when primary cooling (economizer) is not available and secondary cooling (compressor) is available.
When the Mech state becomes active, the UVC uses the unit’s mechanical cooling capabilities as needed to maintain the effective cooling set point (see “Space Temperature Set Points” on page 26). If cooling is not required while in the Mech state, the UVC can “idle” in the Mech state until cooling is required or until there is a call to switch to another mode or state.The UVC monitors the DAT to ensure it does not fall below MCLL.
20 McQuay OM 751
Description of Operation
The CO2 demand controlled ventilation function (optional) is active (see “CO2 Demand Controlled Ventilation (optional)” on page 34), and the OA damper is adjusted as needed to maintain the CO
Figure 15: Mech state operation (occupied mode and auto fan)
set point.
2
Discharge Air (DA) Heat State (State 4)
The DA Heat state is a “normal” state during Cool mode. The DA Heat state typically is active when reheat is required to maintain DATS while maintaining the required OA damper position. The DA Heat state can also be made active if the optional CO provided and CO
levels are high, requiring the OA damper to open beyond what is required
2
DCV feature is
2
for economizer cooling.
When DA Heat state is active, the UVC uses the units heating capability as needed to maintain VCLL. The CO Demand Controlled Ventilation (optional)” on page 34), and the OA damper is adjusted as needed to maintain the CO
demand controlled ventilation function (optional) is active (see “CO2
2
set point.
2
Low Limit State (State F)
The Low Limit state is a “non-normal” state during Cool mode. The Low Limit state typically follows the DA Heat state when the UVC reaches 100% heat and still cannot maintain VCLL.
When the Low Limit state becomes active, the Low Limit PI-loop overrides the OAD minimum position (see “Outdoor Air Damper Operation” on page 32) and adjusts the OAD toward closed as necessary to maintain the DAT set point (see “Discharge Air Temperature Control” on page 29).
Cant Cool State (State C)
The Cant Cool state is a “non-normal” state during Cool mode. The Cant Cool state typically becomes active when both primary (economizer) and secondary (compressor) cooling are not available (or they are disabled) or when an IAT, DAT or OAT sensor failure occurs.
When the Cant Cool state becomes active, no cooling is available.

Special Purpose Unit Modes

There are some additional UVC modes that are considered special purpose unit modes. These special purpose modes include Pressurize, Depressurize, Purge, Shutdown, and Energy Hold Off. These modes force the UVC to perform very specific and limited functions. Use these with caution and only for short periods as needed.
McQuay OM 751 21
Description of Operation
In each of these special purpose UVC modes, if the space temperature drops below EHS and the Emergency Heat function is enabled, the UVC is forced into the Emergency Heat mode (see “Emergency Heat Mode (Super State)” on page 16) and then return once the Emergency Heat function is satisfied.
Table 9: Actions during special purpose unit modes
Action
Pressurize High 100% Open Off
Depressurize Off Closed On
Purge High 100% Open On
Shutdown Off Closed Off
Energy hold off Off Closed Off
Indoor air fan
(IAF)
Outdoor air
damper (OAD)
Exhaust fan
output
Pressurize Mode
When in Pressurize mode, the UVC uses the IAF, OAD, and exhaust output as needed to pressurize the space. The UVC stops all normal heating and cooling but does allow emergency heat if required. The pressurize mode can only be accessed via a network connection.
Depressurize Mode
When in Depressurize mode the UVC will use the IAF, OAD, and exhaust output as needed to depressurize the space. The UVC stops all normal heating and cooling but does allow emergency heat if required. The de-pressurize mode can only be accessed via a network connection or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).
Purge Mode
When in Purge mode, the UVC uses the IAF, OAD, and exhaust output as needed to purge the space. The UVC stops all normal heating and cooling but does allow emergency heat if required. The purge mode can only be accessed via a network connection or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).
Shutdown Mode
Shutdown mode is the equivalent of the Off mode, but is an Off mode forced by a network connection. When in Shutdown mode, the UVC stops all normal heating, cooling, ventilation (OA damper is closed), and fan operation. By default emergency heat is not be used during the shutdown mode, however, the UVC can be configured (Emergency Heat Shutdown Configuration) to allow emergency heat operation during shutdown mode. The shutdown mode can be accessed via a network connection, a binary input to the UVC, or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).
WARNING
Shutdown mode and energy hold off mode are a “stop” state for the unit ventilator. It is not a “power off” state.
Energy Hold Off Mode
The UVC supports an energy hold off state, which when active forces the UVC to stop all normal heating, cooling and ventilation. Typically used by a network connection to force the UVC to cease heating, cooling and ventilation when conditions exist where heating, cooling and ventilation are not required or desired. Energy hold off mode is very similar to shutdown mode except that energy hold off always allows emergency heat if required. The energy hold off mode can only be accessed via a network connection or with ServiceTools for MicroTech II Applied Terminal Unit Controllers (ATS).
22 McQuay OM 751
Description of Operation

Unit Mode Priority

The UVC uses the network variables and binary inputs listed in Table 10 and Table 11 to determine the current unit mode. Special purpose UVC unit modes have higher priority than the normal UVC unit modes as shown in the tables.
Each table lists the highest priority items on the left to the lower priority items to the right. The right-most columns indicate unit operation as a result of the left-most columns. The term “Don’t care” in these tables implies that another network variable or binary input to the left has a higher priority.
Table 10: Special purpose UVC unit mode priority
Priority result
Emergency override
input
Normal
1
3
Pressurize Don’t care Don’t care Don’t care Off Pressurize
De-pressurize Don’t care Don’t care Don’t care Off De-pressurize
Purge Don’t care Don’t care Don’t care Off Purge
Shutdown Don’t care Don’t care Don’t care Off Off
1. Network input.
2. Network output.
3. Normal indicates the UVC power-up condition.
4. De-energized indicates that the contacts connected to this binary input are open.
5. Energized indicates that the contacts connected to this binary input are closed.
Remote shutdown
binary input
De-energized
Energized
4
5
Energy hold
off input
1
Normal Normal
Energy hold
off output
2
Unit mode
output
2
See the normal
UVC mode priority (Table 11)
Energy hold off Energy hold off Off Off
Don’t care Energy hold off Off Off
Actual UVC action
Table 11: Normal UVC mode priority
Priority result
Application override
input
1
Normal (Auto)
Heat Don’t care Heat Cool Don’t care Cool
Night purge Don’t care Night purge
Off Don’t care Off
Emergency heat Don’t care Emergency heat
Fan only Don’t care Fan only
1. Network input.
2. Network output.
3. Normal (Auto) is the normal UVC power-up state.
Unit mode override
Normal (Auto)
3
Night purge Night purge
Emergency heat Emergency heat
input
1
Unit mode output
3
Heat
Cool
Emergency heat
Heat Heat
Cool Cool
Off Off
Fan only Fan only
2
McQuay OM 751 23
Description of Operation

Occupancy Modes

The UVC is provided with four occupancy modes: Occupied, Standby, Unoccupied, and Bypass. The occupancy mode affects which heating and cooling temperature set points are used, affects IAF operation, and affects OAD operation. The Manual Adjust Occupancy and Networked Occupancy Sensor network variables, along with the Unoccupied and Tenant Override binary inputs, are used to determine the Effective Occupancy. The term “Don’t care” in Table 12 implies that another network variable or binary input to the left has a higher priority.
Note – The Occupancy Override Input is provided as a way for a network connection to manually
force the UVC into a particular occupancy mode. The Occupancy Override Input can override the tenant override feature. For example, if the network uses the Occupancy Override Input to force the unit into unoccupied mode, then the tenant override switch does not operate as expected. Therefore, McQuay strongly recommends using the Occupancy Sensor Input to control occupancy modes over a network and only using the Occupancy Override Input if there is reason to ensure tenant override does not occur.
Table 12: Occupancy mode priority
Priority result
Occupancy
Override input
Occupied Don’t care Don’t care Occupied
Unoccupied Don’t care Don’t care Unoccupied
Bypass
Standby Don’t care Don’t care Standby
Null (default)
1. Network input.
2. Network output.
3. Typical operation is defined in this row of the table.
4. The tenant override switch (unit or wall sensor mounted) can be used here to force the UVC into bypass.
Occupancy
sensor input
Occupied Don’t care Occupied
Unoccupied Don’t care Bypass
Null (default)
Occupied Don’t care Occupied
Unoccupied Don’t care Unoccupied
3
Null (default)
Unoccupied binary input
1
Contacts open (Occupied) Occupied
Contacts Closed (Unoccupied) Bypass
Contacts open (Occupied) Occupied
Contacts closed (Unoccupied) Unoccupied
Effective
occupancy
output
2
4
4

Occupied Mode

The occupied mode is the normal day time mode of UVC operation. During occupied mode the UVC uses the occupied heating and cooling set points, the OAD operates normally, and by default the IAF remains on.

Unoccupied Mode

The unoccupied occupancy mode is the normal night time mode of UVC operation. During unoccupied mode the UVC uses the unoccupied heating and cooling set points, the OAD remains closed, and the IAF cycles as needed for heating or cooling. The IAF remains off when there is no need for heating or cooling.

Standby Mode

The standby mode is a special purpose daytime mode of UVC operation. During standby, mode the UVC uses the standby heating and cooling set points, the OAD remains closed, and by default the IAF remains on.
24 McQuay OM 751
Description of Operation

Bypass Mode

The bypass mode (also called Tenant Override) is the equivalent of a temporary occupied mode. Once the bypass mode is initiated, it remains in effect for a set period of time (120 minutes, default). During the bypass mode, the UVC uses the occupied heating and cooling set points, the OAD operates normally, and by default the IAF remains on.

Additional Occupancy Features

Networked Occupancy Sensor Capability

A networked occupancy sensor can be interfaced with the Occupancy Sensor Input variable to select occupancy modes. When the Occupancy Sensor Input variable is used, it automatically overrides any hard-wired unoccupied binary input signal.

Unit-Mounted Time-Clock

An optional unit-mounted factory-installed electronic 24-hour/7-day time clock can be provided on stand-alone unit ventilator configurations. It is factory wired to the UVC unoccupied binary input and can be set to automatically place the unit into occupied and unoccupied modes based upon its user configured schedule.

Unit-Mounted Tenant Override Switch

A tenant override switch is factory installed in all floor mounted units and is located near the LUI on the unit. This switch provides a momentary contact closure that can be used by room occupants to temporarily force the UVC into the bypass occupancy mode from unoccupied mode.
Note – The Occupancy Override Input can override the tenant override feature. For example, if
the network uses the Occupancy Override Input to force the unit into unoccupied mode, then the unit-mounted tenant override switch does not operate as expected. Therefore, McQuay strongly recommends using the Occupancy Sensor Input to control occupancy modes over a network and only using the Occupancy Override Input if there is reason to ensure tenant override does not occur.

Remote Wall-Mounted Sensor Tenant Override Switch

The optional remote wall-mounted sensors include a tenant override switch. This switch provides a momentary contact closure that can be used by room occupants to temporarily force the UVC into the bypass occupancy mode from unoccupied mode.
Note – The Occupancy Override Input can override the tenant override feature. For example, if
the network uses the Occupancy Override Input to force the unit into unoccupied mode, then the wall sensor tenant override switch does not operate as expected. Therefore, McQuay strongly recommends using the Occupancy Sensor Input to control occupancy modes over a network and only using the Occupancy Override Input if there is reason to ensure tenant override does not occur.

Remote Wall-Mounted Sensor Status LED

The optional remote wall-mounted sensors each include a UVC status LED. This status LED aids diagnostics by indicating the UVC occupancy mode and fault condition.
Table 13: Remote wall-mounted sensor status LED
Indication LED operation
Occupied On continually
Unoccupied On 1 second/off 9 seconds
Bypass On continually
Standby On 9 seconds/off 1 second
Fault On 5 seconds/off 5 seconds
McQuay OM 751 25
Description of Operation

Space Temperature Set Points

The UVC uses the six occupancy-based temperature set points as the basis to determine the Effective Set point Output. The effective set point is calculated based on the unit mode, the occupancy mode, and the values of several network variables. The effective set point then is used as the temperature set point that the UVC maintains.
Table 14: Default occupancy-based temperature set points
Temperature set point Abbreviation Defaults
Unoccupied cool UCS 82.4°F (28.0°C)
Standby cool SCS 77.0°F (25.0°C)
Occupied cool OCS 73.4°F (23.0°C)
Occupied heat OHS 69.8°F (21.0°C)
Standby heat SHS 66.2°F (19.0°C)
Unoccupied heat UHS 60.8°F (16.0°C)

Networked Set Point Capability

The Space Temp Setpoint Input variable is used to allow the temperature set points for the occupied and standby modes to be changed via the network; the unoccupied set points are not affected by this variable.

Networked Set Point Offset Capability

The Networked Set Point Offset Input variable is used to shift the effective occupied and standby temperature set points by adding the value of the Setpoint Offset Input variable to the current set points; the unoccupied points are not affected by this variable. This variable is typically set bound to a supervisory network controller or to a networked wall module having a relative set point knob.
Use the keypad/display to make adjustments to the value of the Setpoint Offset Input variable. See “Changing Set Points” on page 9.
Note – The keypad/display and the network both affect the Set Point Offset Input variable. Keep
in mind that changes to this variable are last-one-wins.

Networked Set Point Shift Capability

The Set Point Shift Input variable is used to shift the effective heat/cool set points. It typically is bound to a networked supervisory controller or system that provides functions such as outdoor air temperature compensation. All occupied, standby, and unoccupied set points are shifted upward (+) or downward (
) by the corresponding value of the Set Point Shift Input
variable.
Note – The Set Point Shift Input capability is not available through the BACnet® interface.

Networked Space Temperature Sensor Capability

A networked space temperature sensor can be interfaced with the Space Temp Input variable. When the Space Temp Input variable is used (valid value), it automatically overrides the hard­wired space temperature sensor.
26 McQuay OM 751
Description of Operation
Remote Wall-Mounted Sensor with +/–3°F Adjustment (optional)
When the optional remote wall-mounted sensor with +/–3°F adjustment dial is used, the UVC effectively writes the value of the set point adjustment dial to the Set Point Offset Input variable.
Note – If a network connection is used to adjust the Set Point Offset Input variable, you must not
use the optional remote wall-mounted sensor with +/–3°F adjustment.
– If the keypad/display is used by room occupants to adjust the Set Point Offset, do not use
the optional remote wall-mounted sensor with +/–3°F adjustment. If you have the optional remote wall-mounted sensor with +/–3°F adjustment and an occupant uses the keypad to make Set Point Offset adjustments, this overrides any +/–3°F adjustment on the optional remote wall-mounted sensor since the keypad/display has higher priority. If you find that changes to the +/–3°F adjustment on the remote wall­mounted sensor have no effect, it is likely that an occupant used the keypad/display to make a Set Point Offset change. Cycle unit power to clear this situation and restore the ability to change the Set Point Offset from the +/–3°F adjustment on the remote wall-mounted sensor.
Remote Wall-Mounted Sensor with 55°F to 85°F Adjustment (optional)
When the optional remote wall-mounted sensor with 55°F to 85°F adjustment dial is used, the UVC will effectively write the value of the set point dial to the Space Temp Set Point Input variable.
Note – If a network connection is using the Space Temp Set Point Input variable, do not use the
optional remote wall-mounted sensor with 55°F to 85°F adjustment.
– If it is intended that the LUI will be used by room occupants to adjust the Setpoint Offset,
then you must not use the optional remote wall-mounted sensor with 55 adjustment. When using the optional remote wall-mounted sensor with 55 adjustment, the UVC will ignore any Setpoint Offset changes made at the LUI.
°F to 85°F
°F to 85°F

Effective Set Point Calculations

The UVC calculates the effective set point (Effective Set Point Output) based on several factors. These factors include the six occupancy set points for heating and cooling (Occupancy Temperature Set Point), occupancy mode, the value of the network variables Space Temp Set Point Input, Set Point Offset Input, and the Set Point Shift Input as well as the optional wall­mounted sensor’s set point adjustment knob. As always, network inputs have priority over hardwired connections.
The UVC determines if heating or cooling is required based on the current unit mode (Heat/ Cool Mode Output) and then calculates the required set point for heating or cooling. After calculating, the Effective Set Point Output network variable is set equal to the calculated set point. The Effective Set Point Output is the temperature set point that the UVC maintains, which normally appears on the keypad/display.
McQuay OM 751 27
Description of Operation
Figure 16: Effective set point calculations
Occupancy Temperature Setpoints (network configuration variables)
Occupied Cooling Set Point (OCS)
Standby Cooling Set Point (SCS)
Unoccupied Cooling Set Point (UCS)
Occupied Heating Set Point (OHS)
Standby Heating Set Point (SHS)
Unoccupied Heating Set Point (UHS)
Space Temp Set Point Input (network input)
WallSensorType
Config. Value
Set Point
Offset Input
(network input)
SetptShift (network inputs)
Occupied Cooling Set Point Shift (OCSS)
Standby Cooling Set Point Shift (SCSS)
Unoccupied Cooling Set Point Shift (UCSS)
Occupied Heating Set Point Shift (OCSS)
Standby Heating Set Point Shift (SHSS)
Unoccupied Heating Set Point Shift (UHSS)
Network Value
55°F/85°F
Wall Sensor
1
0
+3°F/–3°F
Wall Sensor
Local User
Interface
+5°F/–5°F
Network Value
Set Point
SetptOffset
Effective Set Point Calculations for each Occupancy Mode
AbsOffsetOccupied = Setpoint - (OCS + OHS)/2 AbsOffsetStandby = Setpoint - (SCS + SHS)/2
Occupied and Bypass Modes EffectiveCoolSetpoint = OCS + AbsOffsetOccupied + SetptOffset + OCSS EffectiveHeatSetpoint = OHS + AbsOffsetOccupied + SetptOffset + OHSS
Standby Mode EffectiveCoolSetpoint = SCS + AbsOffsetStandby + SetptOffset + SCSS EffectiveHeatSetpoint = SHS + AbsOffsetStandby + SetptOffset + SHSS
Unoccupied Mode EffectiveCoolSetpoint = UCS + UCSS EffectiveHeatSetpoint = UHS + UHSS
If both entering paths have valid values, then the network value has priority.
If both entering paths have valid values, then the keypad/display value has priority.
Table 15: Set point calculation examples
Given
OccupancyMode = Occupied or BypassHeat/CoolMode = Heat
SpaceTempSetpoint = (not used)
SetpointOffset = (not used) = 0.0°F
SetpointShift = (not used) = 0.0°F
OHS = 69.8°F
Example A
Effective set point calculations
EffectiveSetpoint = OHS + SetpointOffset + SetpointShift = 69.8 + 0.0 + 0.0 = 69.8°F
Given
OccupancyMode = Occupied or BypassHeat/CoolMode = Heat
SpaceTempSetpoint = 71.0°F
SetpointOffset = -1.0°F (occupant adjustment on remote wall sensor, or LUI)
SetpointShift = (not used) = 0.0°F
OCS = 73.4°F, OHS = 69.8F
Effective set point calculations
Example B
AbsoluteOffset = (OCS – OHS) / 2 =(73.4°F – 69.8°F) / 2 = 1.8°F
EffectiveSetpoint = SpaceTempSetpoint – AbsoluteOffset + SetpointOffset + SetpointShift = 71.0 -
1.0 - 1.0 + 0.0 = 68.2°F
28 McQuay OM 751

Proportional Integral (PI) Control Loops

The MicroTech II UVC uses PI-loop control for heating, cooling and ventilation processes
within the unit ventilator. Numerous PI algorithms can be used depending upon the unit
ventilator configuration. The UVC uses “single” and “cascading” PI loops where needed.
Table 16: PI loop list
PI loops PI loop type Set point
PI-1 Space Temperature
PI-2 Primary Cooling (Economizer)
PI-3 Secondary Cooling
PI-4 Primary Heating
PI-5
PI-6 Low Limit Single
CO2 (optional) Single Effective CO2 Setpoint Space CO
Cascading
Effective Heating or Cooling
Temperature Setpoint
Calculated Discharge Air Temperature
Setpoint Output
Calculated Discharge Air Temperature
Setpoint Output
Calculated Discharge Air Temperature
Setpoint Output
Calculated Discharge Air Temperature
Setpoint
Feedback
(controlled
variable)
Space Temperature
Discharge Air
Temperature
Discharge Air
Temperature
Discharge Air
Temperature
2
Discharge Air
Temperature
Description of Operation
Output
Calculated Discharge Air
Temperature Setpoint Output
Position the OA Damper
Operate the Compressor
Position the Wet Heat Valve or
F&BP Damper
Position the OA Damper
Position the OA Damper
Figure 17: PI loop graphic for CO
CO
Effective
2
set point
+
-
Space CO
sensor
PI - 5
2
2
Position the OA damper

Discharge Air Temperature Control

The UVC uses two “cascading” PI loops to aid in providing very stable space temperature
control. The Space Temperature PI-loop is used to calculate the Discharge Air Temperature
Setpoint Output required to meet the Effective Temperature Setpoint Output. A second PI-loop
(Primary Cooling, Secondary Cooling, or Primary Heating) is then activated to control the
heating or cooling device required to achieve the calculated Discharge Air Temperature
Setpoint Output.
Figure 18: Cascading PI loop graphic 1 (primary heat)
Figure 19: Cascading PI loop graphic 2 (primary cool—economizer)
McQuay OM 751 29
Description of Operation

PI Control Parameters

Associated with each PI loop is a set of two adjustable parameters: Proportional Band and Integral Time. When the unit ventilator is properly sized for the space, the factory settings for these parameters provides the best and most robust control action (see Figure 20).
If field problems arise, first ensure these parameters are set back to the factory default settings. If adjustment is required, only make small adjustments to one parameter at a time. After each adjustment, allow enough time for the system to stabilize before making further adjustments. If you do not have the means to graph the space performance, record the actual measured value and set point for several minutes and then plot the results using a spreadsheet to determine the correct action to change the PI parameter.
CAUTION
Adjusting PI parameters can cause erratic unit operation, and potentially damage the equipment.
PI control parameters should only be adjusted by trained personnel having a complete understanding of how these parameters affect system operation. Generally these parameters do not need to be adjusted from the factory default settings.
Figure 20: Optimized PI loop control

Proportional Band

The proportional band, or proportional action, causes the controlled output to changes in proportion to the magnitude of the difference between the sensor value and set point.
A proportional band setting that is too small (see Figure 21) causes control oscillations that go fully above and below the set point.
Figure 21: Proportional bands
A proportional band setting that is too large (see Figure 21) causes an offset between the actual measured oscillation center and the set point. A small offset is not necessarily a problem since most systems have a small “natural” offset and the integral function automatically works to eliminate or reduce this effect.
30 McQuay OM 751
Description of Operation
In general, it is best to start with a relatively large proportional band setting (the factory
default setting is best) and adjust to smaller values.
If you want the system to respond strongly to small changes in the space, adjust the
proportional band to a higher setting.
If you want the system to react weakly to small changes in the space, adjust the proportional
band to a higher setting.

Integral Time

The integral time, or integral action, causes the controlled output to change in proportion to
time difference between the sensor value and set point. The difference over time between the
actual value and set point forms an “area under the curve” (see Figure 22). The integral action
works to reduce this “area under the curve” and to eliminate any natural system offset.
Figure 22: Integral time
Area Under The Curve
Too Small
The smaller the integral time, the faster the output ramps up or down with small changes in the
space. The smaller the integral time, the quicker the system reacts to small changes in the
space. If the Integral Time is set too small, long oscillations occur (see Figure 22).
In general, it is best to start with a relatively large integral time setting (the factory default
setting is best) and adjust to smaller values. If you want the system respond strongly to small
changes in the space, lower the integral time. If you want the system to react weakly to small
changes in the space, adjust the integral time to a higher setting.

Indoor Air Fan Operation

The UVC supports a three-speed indoor air (IA) fan; low, medium, and high. The UVC
calculates the effective fan speed and operation based on the unit mode, the occupancy mode,
and the values of several network variables.

Auto Mode

The UVC is provided with a user selectable auto fan mode feature. When in auto fan mode,
the UVC uses the space temperature PI loop to automatically adjust the fan speed as needed to
maintain space temperature. This ensures that the UVC maintains the lowest and quietest fan
speeds whenever possible. When in auto fan mode, a maximum of six fan speed changes per
hour is allowed (by default). This prevents frequent automatic fan speed changes from
disturbing room occupants.

Occupied, Standby, and Bypass Operation

During occupied standby and bypass modes, the IA fan, by default, remains On.
McQuay OM 751 31
Description of Operation

Unoccupied Operation

During unoccupied mode, the IA fan typically remains off and cycles with calls for heating and cooling.

Cycle Fan

The UVC is provided with a Fan Cycling Configuration variable that can be used to force the IA fan to cycle with calls for heating and cooling during the occupied, standby, and bypass occupancy modes. When the fan is off, the OA damper is closed. McQuay recommends using this feature only when it is acceptable that normal ventilation is not required.
When the IA fan is set to cycle, the UVC is configured to continue fan operation for a time period after heating or cooling is complete.

Off Delay

When the UVC is placed into off mode or shutdown mode, the UVC is configured to continue fan operation for a short time period and then shutdown.

Outdoor Air Damper Operation

The UVC is configured for an OA damper operated by a floating-point actuator. The OA damper actuator contains a spring that ensures the OA damper is closed upon loss of power. The floating-point actuator is driven by the UVC using two binary (Triac) outputs. The OA damper typically is open to the current minimum position during the occupied and bypass occupancy modes and closed during the unoccupied and standby occupancy modes.
A Triac output is best tested under load using a 24 V relay for verification. To verify:
1 Put a relay across the Triac outputs.
2 Cycle the power.
3 Verify the relay’s closed contacts during calibration.

Minimum Position

The UVC is configured to maintain three OA damper minimum positions based on the operation of the IAF fan. This allows each unit to be field configured to provide the amount of fresh air required to the space at each of the three IA fan speeds.
Table 17: Default OA damper minimum positions
IAF speed Without CO
High 20% 5%
Medium 25% 5%
Low 30% 5%
Note – If the CO2 Demand Controlled Ventilation (DCV) option is used, the UVC only uses the IA
fan high speed OA damper minimum position regardless of fan speed. The DCV function adjusts the OA damper above this minimum as needed to maintain CO
2
With CO
2
set point.
2

Economizer Operation

The economizer function is used by the UVC to determine if the OA is adequate for economizer (primary) cooling. When both the economizer and mechanical cooling are available, the economizer is used as primary cooling and the UVC adds mechanical cooling only if the economizer is not adequate to meet the current cooling load (e.g., the OA damper reaches 100% and cooling is still required).
The UVC supports three economizer functions:
Basic (default)—Temperature Comparison Economizer
32 McQuay OM 751
Description of Operation
Expanded (optional)—Temperature Comparison with OA Enthalpy Setpoint Economizer (Strategy 1)
Leading Edge (optional)—Temperature Comparison with Enthalpy Comparison Economizer (Strategy 2)
Temperature Comparison Economizer (default)
If the default Basic economizer function is selected, the unit ventilator is provided from the factory without the optional IA and OA humidity sensors. In this case, the UVC is factory set for Economizer Strategy 1—the UVC automatically detects that no OA humidity sensor is present and adjusts to use the Temperature Comparison Economizer function.
Temperature Comparison with OA Enthalpy Setpoint Economizer (optional)
If the optional Expanded economizer function is selected, the unit ventilator is provided from the factory with the optional OA humidity sensor, which is used along with the OA temperature sensor to calculate OA enthalpy. In this case, the UVC is factory set for Economizer Strategy 1 and uses the Temperature Comparison with OA Enthalpy Setpoint Economizer function.
Note – Temperature Comparison with OA Enthalpy Setpoint Economizer requires an optional OA
humidity sensor.
Temperature Comparison with Enthalpy Comparison Economizer (optional)
If the optional Leading Edge economizer function is selected, the unit ventilator is provided from the factory with both the IA humidity and OA humidity sensors, which are used along with the IA temperature and OA temperature sensors to calculate IA enthalpy and OA enthalpy. In this case, the UVC is factory set for Economizer Strategy 2 and uses the Temperature Comparison with Enthalpy Comparison Economizer function.
Note – Temperature Comparison with Enthalpy Comparison requires both an optional OA
humidity sensor and an optional IA humidity sensor.
Table 18: Economizer enable/disable tests defined
Economizer
Tests
enable/disable tests
A OA temp set point EffectiveOATemp < (EconOATempSetpt – EconTempDiff) EffectiveOATemp >= EconOATempSetpt B IA/OA differential temp EffectiveOATemp < (EffectiveSpaceTemp – 3.6°F – EconTempDiff) EffectiveOATemp >= (EffectiveSpaceTemp – 3.6°F)
C OA enthalpy set point
IA/OA differential
D
enthalpy
EffectiveOAEnthalpy < (EconOAEnthalpySetpt –
EffectiveOAEnthalpy < (EffectiveSpaceEnthalpy –
Table 19: How economizer enable/disable tests are selected
Economizer
strategy
All
Basic
Expanded Reliable Reliable Don’t care Reliable
Leading Edge
Space temp sensor OA temp sensor
Unreliable Don’t care Don’t care Don’t care OA damper closed
Don’t care Unreliable Don’t care Don’t care OA damper closed
Reliable Reliable Don’t care Unreliable Test B Reliable Reliable Don’t care Reliable Test C
Reliable Reliable Reliable Reliable Test D and Test B Reliable Reliable Unreliable Reliable Test B Reliable Reliable Reliable Unreliable Test B Reliable Reliable Unreliable Unreliable Test B
Note: The hard-wired sensor and the equivalent input must both be unreliable for the value to be considered
unreliable.
Enable test Disable test
EconEnthalpyDiff)
EconEnthalpyDiff)
Space humidity
sensor
EffectiveOAEnthalpy >= EconOAEnthalpySetpt
EffectiveOAEnthalpy >= EffectiveSpaceEnthalpy
OA humidity sensor
Economizer enable/
disable tests
Test C and Either
Tes t B or Te s t A
McQuay OM 751 33
Description of Operation

Networked Space Humidity Sensor Capability

A networked space humidity sensor can be network interfaced with the Space Humidity Input variable. When the Space Humidity Input variable is used (valid value), it automatically overrides the hard-wired space humidity sensor (if present).

Networked Outdoor Humidity Sensor Capability

A networked outdoor humidity sensor can be network interfaced with the Outdoor Humidity Input variable. When the Outdoor Humidity Input variable is used (valid value), it automatically overrides the hard-wired outdoor humidity sensor (if present).

CO2 Demand Controlled Ventilation (optional)

Ventilation equipment typically uses fixed damper positions to determine the amount of OA for proper ventilation within the space. Most commonly, the fixed position of the OA damper is based on the maximum number of occupants the space is designed to accommodate. However, this fixed OA damper operation ignores the fact that most spaces during the day have varying occupancy levels and may only rarely reach maximum design occupancy levels. This type of fixed damper control for ventilation is energy wasteful since you are treating OA not actually needed for ventilation during low occupancy levels.
People produce CO
when they breath; the CO2 level within the space has a direct relationship
2
with the number of people within that space.
The UVC can optionally be factory configured to provide CO Ventilation (DCV). The CO
DCV function is useful in saving the energy typically wasted in
2
-based Demand Controlled
2
treating OA not actually needed for ventilation within a space during occupancy levels below maximum design. The CO above the minimum position as needed to maintain the Space CO
DCV function uses a PI-loop control to adjust the OA damper
2
Setpoint (1200 PPM
2
default).
The minimum damper position used with CO minimum position that would be used without CO damper position typically is 20% then when using CO
DCV typically can be set at ~20% of the
2
DCV. For example, if the minimum OA
2
DCV, you could set the new minimum
2
OA damper position as low as 4% (e.g., 20% × 0.20 = 4%). This new, smaller minimum OA damper position then should provide enough ventilation to keep odors in check within the space for most applications.
Note – The CO2 DCV function can increase the OA damper position past that required by the
economizer and vice versa.
– If odors within the space become a problem, increase the OA damper minimum position
as needed to eliminate these odors. It may be necessary with new construction or after renovation to raise the minimum position for some time period to help reduce odor build­up due to the out-gassing of new construction material and then return the minimum OA damper position at a later date.
– If the CO
fan high speed OA damper minimum position regardless of fan speed. The DCV function adjusts the OA damper above this minimum as needed. In this case, the IA fan high speed OA damper minimum position is factory set at 5%.
Demand Controlled Ventilation (DCV) option is used, the UVC only uses the IA
2

Networked Space CO2 Sensor Capability

A networked space CO2 sensor can be network interfaced with the Space CO2 Input variable. When the Space CO wired space CO
34 McQuay OM 751
Input variable is used (valid value), it automatically overrides the hard-
2
sensor (if present).
2
Description of Operation
)

ASHRAE Cycle II

The UVC supports ASHRAE Cycle II operation. The basis of ASHRAE Cycle II is to maintain the required minimum amount of ventilation whenever possible, which can be increased during normal operation for economizer cooling or CO
DCV control or reduced to
2
prevent excessively cold discharge air temperatures.
A discharge air temperature sensor is installed in all unit ventilators. If necessary, the ASHRAE II control algorithm overrides room control and modifies the heating, ventilating, and cooling functions (as available) to prevent the discharge air temperature from falling below the VCLL set point.

Compressor Operation

The UVC is configured to operate the compressor as secondary (mechanical) cooling when the economizer is available. When the economizer is not available and the compressor is available, the UVC uses the compressor when cooling is required.

Compressor Envelope

The compressor envelope protects the compressor from adverse operating conditions that can cause damage and or shortened compressor life by ending compressor operation if coil temperatures exceed the defined operating envelope.
For self-contained units, the UVC is configured to monitor both the inside air/refrigerant and outside air/refrigerant coil temperatures to prevent compressor operation under adverse conditions.
For split-system units, the UVC is configured at the factory to only monitor the inside air/ refrigerant coil as part of the compressor envelope function.
Figure 23: Compressor envelope in self-contained units
DX cooling
160˚F (71.1˚C)
2
40˚F (4.4˚C)
(indoor air coil)
Evaporator temperature
Condenser temperature
Area for compressor operation envelope.
1 Area where liquid slugging could occur.
2
Area where starving could occur.
1
28˚F (-2.2˚C) 120˚F (48.9˚C
(outdoor air coil)

Compressor Cooling Lockout

The UVC is configured to lockout compressor cooling when the OA temperature falls below the Compressor Cooling Lockout set point (63.5°F/17.5°C). Below this point, only economizer cooling is available.
McQuay OM 751 35
Description of Operation

Compressor Minimum On and Off Timers

The UVC is provided with minimum On (3-minute default) and minimum Off (5-minute default) timers to prevent adverse compressor cycling.

Compressor Start Delay

The UVC is provided with a Compressor Start Delay configuration variable, which is intended to be adjusted as part of the start-up procedure for each unit. This variable is used to delay compressor operation each time the compressor is required.
Note – To prevent strain on a building’s electrical supply system from multiple unit compressors
all starting at the same time after a power failure or after an unoccupied-to-occupied changeover, McQuay strongly recommends configuring each unit or groups of units at start-up with different start delays.

Outdoor Air Fan Operation

The UVC is configured with a fan on delay that delays OA fan operation for a time period (10 seconds, default) after the compressor starts. The OA fan stops with the compressor.

Floating-Point Actuator Auto-Zero, Overdrive and Sync

The UVC at power-up auto-zeros all floating-point actuators (OA damper) before going into normal operation to ensure proper positioning. During auto-zero, the unit remains off. The actuators all open approximately 30% and then are driven full closed. The overdrive feature then is used to continue forcing the actuators closed for one full stroke period. Once the zeroing process is complete, normal unit operation begins.
The UVC is configured such that whenever a floating-point actuator is commanded to go to 0% or 100%, the UVC overdrives the actuator one full stroke period past the 0% or 100% position to ensure proper positioning.
Additionally, the UVC is configured to sync all floating-point actuators once every six hours of operation. To do this, the UVC forces the actuator to the closest rail position (0% or 100%), uses the overdrive feature, and then returns to the required position. For example, if the actuator is at 20% when the six-hour limit is reached, the UVC then forces the actuator to 0%, overdrive for one full stroke and then returns to the 20% position.
36 McQuay OM 751
Description of Operation

External Binary Inputs

The UVC is provided with three binary inputs that provide the functions described below.
Figure 24: Binary inputs
Binary Inputs
3 sets of dry contacts to signal UVC
Input 1: Unoccupied (default)
Input 2: Remote shutdown
Input 3: Ventilation lockout (default)
or
Exhaust interlock system
These inputs each allow a single set of dry contacts to be used as a signal to the UVC. Multiple units can be connected to a single set of dry contacts. For wiring examples, see MicroTech II Unit Ventilator Controller IM 747.
Note – Not all of the functions listed can be used at the same time. The UVC is provided with
configuration parameters that can be adjusted to select which function is used for these inputs where multiple functions are indicated below.

External Binary Input 1

This input can be configured as an unoccupied (default) or dew point/humidity signal.
Unoccupied Input Signal
This input allows a single set of dry contacts to be used to signal the UVC to go into unoccupied or occupied mode. When the contacts close, the UVC goes into unoccupied mode. When the contacts open, the UVC goes into occupied mode. Additional variables can effect occupancy mode and override this binary input. See “Occupancy Modes” on page 24.

External Binary Input 2

This input can only be used for remote shutdown.
Remote Shutdown Input Signal
This input allows a single set of dry contacts to be used to signal the UVC to go into shutdown mode. When the contacts close (shutdown), the UVC goes into shutdown mode. When the contacts open. the UVC returns to normal operation. See “Special Purpose Unit Modes” on page 21.

External Binary Input 3

This input can be configured as a ventilation lockout (default) or exhaust interlock signal.
Ventilation Lockout Input Signal
This input allows a single set of dry contacts to be used to signal the UVC to close the OA damper. When the contacts close (ventilation lockout signal), the UVC closes the OA damper. When the contacts open, the UVC returns to normal OA damper operation.
McQuay OM 751 37
Description of Operation
Exhaust Interlock Input Signal
This input allows a single set of dry contacts to be used to signal the UVC that an exhaust fan within the space is energized. The UVC repositions the OA damper to a user adjustable minimum position (Exhaust Interlock OA Damper Min Position Setpoint). When the contacts close (exhaust fan on signal), the UVC uses the value defined by the Exhaust Interlock OA Damper Min Position Setpoint as the new minimum OA damper position regardless of IA fan speed. When the contacts open, the UVC returns to normal OA damper operation.

External Binary Outputs

The UVC is provided with three binary outputs that provide the functions described below.
Figure 25: Binary outputs
Binary Outputs
3 relay type outputs w/signal voltage
Output 1: Relay output for light signal
Output 2: Fault signal
Output 3: Exhaust fan operation (default)
or
Auxiliary heat device
These outputs are relay type outputs that are intended to be used with signal level voltages (24 VAC maximum) only. For wiring examples, see MicroTech II Unit Ventilator Controller IM
747.
Note – Not all of the functions listed can be used at the same time. The UVC is provided with
configuration parameters that can be adjusted to select which function will be used for these outputs when multiple functions are indicated below.

External Binary Output 1

This output can only be used as a signal for space lights.
Lights On/Off Signal
This relay output provides one set of Normally Open dry contacts that can be used to signal the operation of the space lights. When the UVC is in occupied, standby, or bypass occupancy modes, the relay output signals the lights ON (contacts closed). When the UVC is in unoccupied occupancy mode, the relay output signals the lights OFF (contacts open).

External Binary Output 2

This output can only be used as a fault signal.
Fault Signal
This relay output provides Normally Open, Normally Closed, and Common connections that can be used to signal a fault condition. When a fault exists, the UVC energizes this relay output. When the fault or faults are cleared, the UVC de-energizes this relay output.

External Binary Output 3

This output can only be used to signal exhaust fan operation (default) or operate an auxiliary heat device.
38 McQuay OM 751
Description of Operation
Exhaust Fan ON/OFF Signal
This relay output provides one set of Normally Open dry contacts that can be used to signal the operation of an exhaust fan. When the OA damper opens more than the Energize Exhaust Fan OA Damper set point, then the relay output signals the exhaust fan ON (contacts closed). When the OA damper closes below this set point, the relay output signals the exhaust fan OFF (contacts open).
Auxiliary Heat Signal
This relay output provides one set of Normally Open dry contacts that can be used to operate an auxiliary heat device. The UVC by default is configured to operate a Normally Open auxiliary heat device (de-energize when heat is required), such as a wet heat valve actuator with a spring setup to open upon power failure. However, the Auxiliary Heat Configuration variable can be used to set the UVC to use a Normally Closed auxiliary heat device (energize when heat is required), such as electric heat.
Table 20: Auxiliary heat start/stop calculation
Start/Stop Calculation
Auxiliary heat starts when:
Auxiliary heat stops when:
Primary Heat PI-Loop = saturated high (100%) for more than two minutes AND
EffectiveSpaceTemp AuxiliaryHeatStartDifferential EffectiveSpaceTemp ≥ (EffectiveSetpoint – AuxiliaryHeatStartDifferential) + AuxiliaryHeatStopDifferential
EffectiveSetpoint –
McQuay OM 751 39

UVC Input and Output Table

UVC Input and Output Table
All UVC input and output connections and their corresponding unit ventilator usage are shown in the following table.
Table 21: Inputs and outputs, software model 05—DX cooling only
I/O Description
BO-1 Inside Fan High BO-2 Inside Fan Medium BO-3 Electric Heat 1 BO-4 Electric Heat 2 BO-5 Electric Heat 3 BO-6 External Output Option 2: Fault Indication BO-7 BO-8 BO-9 Compressor
2
BI-1 Condensate Overflow BI-2 BI-3
External Input Option 3:Ventilation Lockout (default) or Exhaust
BI-4
Interlock
3
BI-5 External Input Option 2: Remote Shutdown BI-6 External Input Option 1: Unoccupied (default) BI-7 BI-8
BI-9 BI-10 BI-11 BI-12 DX Press Switch (NC)
4
AI-1 IA Temp. Sensor + T.O.
AI-2 Remote Setpt. Adjust. Pot.
AI-3 OA Coil DX Temp Sensor
5
AI-4 OA Temp Sensor
AI-5 IA Coil DX Temp Sensor
AI-6 DA Temp Sensor
Expansion board
xBO-1 External Output Option 1: Lights On/Off
xBO-2
External Output Option 3: Exhaust Fan On/Off (default) or Auxiliary Heat
1
xBO-3 OA Damper Open xBO-4 OA Damper Close xBO-5 xBO-6 xBO-7 Outdoor Fan xBO-8 Inside Fan Low
xAI-1 IA Humidity Sensor xAI-2 OA Humidity Sensor xAI-3 Indoor CO2 Sensor
5
6
6
6
xAI-4
1. Field selectable external output options (all possible options are shown).
2. This is the condensing unit on/off signal on split-systems.
3. Field selectable external input options (all possible options are shown).
4. DX pressures switch not installed on split-systems; this input is then wired for constant no-fault condition.
5. Not installed or wired on split-systems.
6. Optional.
1
3
1
40 McQuay OM 751

Diagnostics and Service

Diagnostics and Service
The most important aspect of troubleshooting unit ventilator controls is to isolate the source of the problem into one of two categories:
1 The problem resides within the UVC.
2 The problem is external to the UVC. Under most circumstances the problem is external to
the UVC.

Alarm and Fault Monitoring

The UVC is programmed to monitor the unit for specific alarm conditions. If an alarm condition exists, a fault occurs. When a fault exists, the following occurs:
The UVC indicates the fault condition by displaying the fault code on the keypad/display.
The remote wall-mounted sensor (optional) LED flashes a pattern indicating that a fault
condition exists.
The fault signal binary output energizes.
The fault performs the appropriate control actions as described for each fault.
Manual reset faults can be reset in one of three ways:
By cycling the unit power.
Via the keypad/display menu.
Via the network interface.
Table 22: Alarm and fault code summary
Priority Fault description Reset
1 Space Temp Sensor Failure Auto 2 DX Pressure Fault 2-Auto in 7 days, then Manual
Compressor Envelope Fault 2-Auto in 7 days, then
3
4 Discharge Air DX Cooling Low Limit Indication Auto 5 Condensate Overflow Indication Auto 6 Space Coil DX Temp Sensor Failure Auto 7 Outdoor Temp Sensor Failure Auto 8 Discharge Air Temp Sensor Failure Auto
9 Water Coil DX Temp Sensor Failure Auto 10 Water-out Temp Sensor Failure Auto 11 Space Humidity Sensor Failure Auto 12 Outdoor Humidity Sensor Failure Auto 13 Space CO2 Sensor Failure Auto 14 Not used 15 Not used 16 Change Filter Indication Manual 17 EPROM Memory Indicator Replace conroller board 18 Configuration Display Download file
* Rev 1_27 has auto reset
Manual*
Keypad/
display fault
codes
F0 F1
F2
F3 F4 F5 F6 F7 F8 F9 FA Fb FC Fd FE FF EE
--
McQuay OM 751 41
Diagnostics and Service

Space Temp Sensor Failure (F0)

The Space Temp Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
Space fan de-energizes (unless in emergency heat mode).
Compressor immediately de-energizes.
Outdoor fan (if present) de-energizes.
Outside air damper is forced closed.
Electric heat stages are de-energized.
Fault is indicated.

DX Pressure Fault (F1)

The DX Pressure Fault occurs when the UVC detects a switch open condition from the refrigerant pressure switch.
Effect:
Compressor immediately de-energizes.
Outdoor fan (if present) de-energizes.
Fault is indicated.

Compressor Envelope Fault (F2)

The UVC monitors refrigerant temperatures. The Compressor Envelope Fault occurs when the UVC detects compressor operation that exceeded the allowed operating parameters.
Effect:
Compressor immediately de-energizes.
Outdoor fan (if present) de-energizes.
Fault is indicated.
Cause:
Poor air or water flow through the refrigerant coils. Check fans for proper rpm. Check air filters.
If the unit has a three-phase scroll compressor, check for proper electrical phasing.
Refrigerant circuit component failure or improper adjustment. Check refrigerant pressures
and TXV adjustment.
Coil sensors may have lost proper contact with the refrigerant coil. Check coil sensors.

Discharge Air DX Cooling Low Limit Indication (F3)

The Discharge Air DX Cooling Low Limit Indication fault occurs when the UVC detects a low discharge air temperature (DAT < MCLL) during compressor cooling.
Effect:
Compressor immediately de-energizes.
Outdoor fan (if present) de-energizes.
Fault is indicated (on earlier software versions).
42 McQuay OM 751
Diagnostics and Service

Condensate Overflow Indication (optional) (F4)

The Condensate Overflow Indication fault will occur when the UVC detects high condensate levels within the units indoor coil drain pan.
Effect:
Compressor is immediately de-energized if in cooling.
Outdoor fan (if present) is de-energized.
Fault is indicated.

Space Coil DX Temp Sensor Failure (F5)

The Space Coil DX Temp Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
Compressor immediately de-energizes.
Outdoor fan (if present) de-energizes.
Fault is indicated.

Outdoor Temp Sensor Failure (F6)

The Outdoor Temp Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
Outside air damper is forced closed.
Compressor immediately de-energizes.
Fault is indicated.

Discharge Air Temp Sensor Failure (F7)

The Discharge Air Temp Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor. Emergency heat mode is available during this fault condition.
Effect:
Space fan is immediately de-energized (unless in emergency heat mode).
Outside air damper is forced closed.
Electric heat stages are de-energized.
Compressor immediately de-energizes.
Outdoor fan (if present) immediately de-energizes.
Fault is indicated.

Outdoor Coil DX Temp Sensor Failure (F8)

The Outdoor Coil DX Temp Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
Compressor immediately de-energizes.
Outdoor fan (if present) de-energizes.
Fault is indicated.
McQuay OM 751 43
Diagnostics and Service

Space Humidity Sensor Failure (optional) (FA)

The Space Humidity Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
IA/OA Enthalpy comparison economizer (if used) is disabled.
Dehumidification function (optional) is disabled.
Fault is indicated.

Outdoor Humidity Sensor Failure (optional) (Fb)

The Outdoor Humidity Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
IA/OA Enthalpy comparison or OA Enthalpy economizer (if used) is disabled.
Fault is indicated.

Space CO2 Sensor Failure (optional) (FC)

The Space CO2 Sensor Failure fault occurs when the UVC detects open or short conditions from the sensor.
Effect:
CO
Demand Controlled Ventilation function is disabled.
2
Fault is indicated.

Change Filter Indication (FF)

The Change Filter Indication fault occurs when the UVC calculates that the total fan run time has exceeded the allowed number of hours since the last filter change.
Effect:
Fault is indicated.

EPROM Memory Indicator (EE)

The EPROM Memory Indicator occurs when an unusual electrical event has scrambled the EPROM memory within the controller board. In the event that this happens, the controller board must be replaced.

Configuration Display (--)

The Configuration Display occurs when the display file “**.cfg” is incorrect or has not been downloaded with the appropriate file from service tools.

Troubleshooting Temperature Sensors

The UVC is configured to use passive positive temperature coefficient (PTC) sensor whose resistance increases with increasing temperature. The element has a reference resistance of 1035 ohms at 77°F (25°C). Each element is calibrated according to the tables shown.
Use the following procedure to troubleshoot a suspect sensor.
1 Disconnect both sensor leads from the UVC.
2 Using some other calibrated temperature sensing device, take a temperature reading at the
sensor location.
44 McQuay OM 751
Diagnostics and Service
3
Use the temperature reading from Step 2 to determine the expected sensor resistance from Table 23 .
4 Using a calibrated ohmmeter, measure the actual resistance across the two sensor leads.
5 Compare the expected resistance to the actual resistance.
6 If the actual resistance value deviates substantially (more than 10%) from the expected
resistance, replace the sensor.
Table 23: Temperature versus resistance
°F (°C) Resistance in ohms °F (°C) Resistance in ohms
–40 (–40) 613 113 (45) 1195 –31 (–35) 640 122 (50) 1237 –22 (–30) 668 131 (55) 1279 –13 (–25) 697 140 (60) 1323
–4 (–20) 727 149 (65) 1368
5 (–15) 758 158 (70) 1413
14 (–10) 789 167 (75) 1459
23 (–5) 822 176 (80) 1506
32 (0) 855 185 (85) 1554
41 (5) 889 194 (90) 1602 50 (10) 924 203 (95) 1652 59 (15) 960 212 (100) 1702 68 (20) 997 221 (105) 1753 77 (25) 1035 230 (110) 1804 86 (30) 1074 239 (115) 1856 95 (35) 1113 248 (120) 1908
104 (40) 1153

Troubleshooting Humidity Sensors

The UVC is configured to use a 0–100% RH, 0–5 VDC, capacitive humidity sensor. Each sensor is calibrated according to the table shown.
CAUTION
The humidity sensor is not protected against reversed polarity. Check carefully when connecting the device or damage can result.
Use the following procedure to troubleshoot a suspect sensor:
1 Disconnect the sensors output voltage lead from the UVC analog input.
2 Using some other calibrated humidity sensing device, take a humidity reading at the sensor
location.
3 Use the humidity reading from Step 2 determine the expected sensor voltage from
Table 24 .
4 Using a calibrated multi-meter, measure the actual voltage across the yellow and white
sensor leads. Wire color definitions:
White = ground
Yellow = output VDC
Blue = supply VDC
5 Compare the expected voltage to the actual voltage.
6 If the actual voltage value deviates substantially (more than 10%) from the expected
voltage, replace the sensor.
McQuay OM 751 45
Diagnostics and Service
Table 24: Humidity versus voltage.
RH (%) VDC (mV) RH (%) VDC (mV)
10 1330 55 2480 15 1475 60 2600 20 1610 65 2730 25 1740 70 2860 30 1870 75 2980 35 1995 80 3115 40 2120 85 3250 45 2235 90 3390 50 2360 95 3530

Troubleshooting Carbon Dioxide (CO2) Sensors

The UVC is configured to use a 0–2000 PPM, 0–10 VDC, single beam absorption infrared gas sensor. Each sensor is calibrated according to the table shown.
Use the following procedure to troubleshoot a suspect sensor.
1 Disconnect the sensors output voltage lead from the UVC analog input (xAI-3).
2 Using some other calibrated CO
3 Use the CO
reading from Step 2 to determine the expected sensor voltage from Table 25.
2
4 Using a calibrated multi-meter, measure the actual voltage across the lead removed from
xAI-3 and ground.
5 Compare the expected voltage to the actual voltage.
6 If the actual voltage value deviates substantially (more than 10%) from the expected
voltage, replace the sensor.
sensing device, take a CO2 reading at the sensor location.
2
In the unlikely event that the CO
sensor requires calibration, consult the factory for
2
information on obtaining calibration equipment and instructions.
Table 25: CO2 versus voltage table
CO2 (PPM) VDC (V) CO2 (PPM) VDC (V)
300 1.5 1200 6.0 400 2.0 1300 6.5 500 2.5 1400 7.0 600 3.0 1500 7.5 700 3.5 1600 8.0 800 4.0 1700 8.5 900 4.5 1800 9.0
1000 5.0 1900 9.5
46 McQuay OM 751

UVC Configuration Parameters

UVC Configuration Parameters
The UVC is been provided with a number of configuration variables as listed in the following table. These configuration variables are stored in UVC non-volatile memory. For a description of supported network variables for each protocol, refer to Protocol Data Packet bulletin ED
15065.
Table 26: UVC configuration parameters (OM 751)
Configuration Parameter Name Abr. Notes Default
Occupied Cooling Setpoint
Standby Cooling Setpoint
Unoccupied Cooling Setpoint
Occupied Heating Setpoint
Standby Heating Setpoint
Unoccupied Heating Setpoint
Local Bypass Time Tenant override
Spac e C O
Space Humidity Setpoint
Emergency Heat Enable 0 = disable, 1 = enable (uses auxiliary heat where primary heat is
Emergency Heat Setpoint
Emergency Heat Shutdown Configuration Wall Sensor Type
Slave Type Configuration2 0 = independent slave, 1 = dependent slave
OAD Min Position High-Speed Setpoint
OAD Min Position Med-Speed Setpoint
OAD Min Position Low-Speed Setpoint
Exhaust Interlock OAD Min Position Setpoint
Energize Exhaust Fan OAD Setpoint
OAD Max Position Setpoint
OAD Lockout Enable 0 = disable, 1 = enable (this variable will be factory set to 1 when
OAD Lockout Setpoint
Economizer Enable 0 = disable, 1 = enable
Economizer OA Temp Setpoint
Economizer IA/OA Temp Differential
Economizer OA Enthalpy Setpoint
Economizer IA/OA Enthalpy Differential
External BI-3 Configuration 0 = Ventilation Lockout, 1 = Exhaust Interlock
External BO-3 Configuration 0 = Exhaust Fan On/Off, 1 = Auxiliary Heat
Filter Alarm Enable 0 = disable, 1 = enable
Filter Change Hours Setpoint fan run hours between filter change alarms
Setpoint
2
2
2
2
OCS 73°F (23°C)
SCS 77°F (25°C)
UCS 82°F (28°C)
OHS 70°F (21°C)
SHS 66°F (19°C)
UHS 61°F (16°C)
120 min
CO2S 1200 PPM
used with both active (reheat) and passive dehumidification
RHS
sequences
not applicable)
EHS 54°F (12°C)
0 = no emergency heat during shutdown, 1 = emergency heat available during shutdown 0 = +/- 3°F, 1 = 55°F to 85°F
(this variable will be factory set to 5% open when the unit is ordered
OADH
with optional CO (this variable is ignored when the unit is ordered with optional CO2
OADM
DCV) (this variable is ignored when the unit is ordered with optional CO2
OADL
DCV) OA damper minimum position when the exhaust interlock input is
EOAD
energized defines position above which exhaust fan output will be energized
OADE
OAMX 99% open
the unit is ordered as a recirc unit with no OAD) OA temperature below which the OA damper will remain closed
OALS
(this variable will be factory set to –99°C when the unit is ordered as a recirc unit with no OAD)
ETS 68°F (20°C)
ETD 2°F (1°C)
EES 25 btu/lb (58 kJ/kg)
EED 1.3 btu/lb (3 kJ/kg)
DCV)
2
60% Rh
20% open
25% open
30% open
99% open
12% open
36°F (2°C)
700 hrs
LUI Menu
1
Item
Co C5 CU Ho H5 HU
1
H1
H2
0
0
0
H3
r5 SL
o2
o3
o4
o5
o6 o7
0
o8
o9
1
E1 E2 e3 e5 e6
0
0
0
B3 B6 CE
McQuay OM 751 47
UVC Configuration Parameters
Configuration Parameter Name Abr. Notes Default
Primary Cool Proportional Band
Primary Cool Integral Time
Secondary Cool Proportional Band
Secondary Cool Integral Time
Discharge Air Temp Proportional Band
Discharge Air Temp Integral Time
CO2 Proportional Band2
CO2 Integral Time2
Ventilation Cooling Low Limit Setpoint
Mechanical Cooling Low Limit Setpoint
Discharge Air High Limit
Space Fan Off Delay
Fan Cycling Configuration space fan operation during occupied, standby and bypass
Space Fan Speed Changes Per Hour example: 6/60min = 10min (maximum of 1 fan speed change every
Space Fan Run Time Reset reset total run time: 1 = reset (you must return the variable back to
Compressor Run Time Reset reset total run time: 1 = reset (you must return the variable back to
Compressor Enable 0 = disable, 1 = enable
Compressor Minimum On Time
Compressor Minimum Off Time
Compressor Cooling Lockout Setpoint
Compressor Envelope Cool Max In
Compressor Envelope Cool Min In
Compressor Envelope Cool Max Out
Compressor Envelope Cool Min Out
Compressor Envelope Cool Max Ratio
Compressor Envelope Cool Max Offset
Compressor Envelope Cool Min Ratio
Compressor Envelope Cool Min Offset
Auxiliary Heat Start Differential
Auxiliary Heat End Differential
Auxiliary Heat Configuration 0 = normally open heat device (hot water valve, etc.),
Space Humidity Sensor Enable
Outdoor Humidity Sensor Enable
2
2
discharge air low limit during ventilation or economizer cooling
VCLL
discharge air low limit during mechanical (compressor) cooling
MCLL
DAHL 140°F (60°C)
occupancy modes: 2 = continuous, 3 = cycle
10min when fan in auto)
0 after reset)
0 after reset)
OA temperature below which compressor cooling is not allowed
CCLO
degrees above auxiliary heat start point where auxiliary heat ends
AHSD
degrees above auxiliary heat start point where auxiliary heat ends
AHED
1 = normally closed heat device (electric heat, etc.) 0 = disable, 1 = enable (this variable will be factory set to 1 when the unit is ordered with optional humidity sensor) 0 = disable, 1 = enable (this variable will be factory set to 1 when the unit is ordered with optional humidity sensor)
18°F (10°C)
180 sec
18°F (10°C)
600 sec
4°F (2.22°C)
300 sec
100 PPM
600 sec
54°F (12°C)
45°F (7°C)
30 sec
180 sec
300 sec
63.5°F (17.5°C)
120°F (48.89°C)
28°F (-2.22°C)
160°F (71.11°C)
40°F (4.44°C)
88°F (48.89°C)
-4°F (-2.22°C)
2°F (1°C)
2°F (1°C)
2
6
0
0
1
0.00
0.0
0
0
0
LUI Menu
1
Item
d2 d3
CF
C!
A1 A2
A3
48 McQuay OM 751
UVC Configuration Parameters
Configuration Parameter Name Abr. Notes Default
OAD Stroke Time
Split-System OA/DX Coil Temp used on split-system units only to partially disable the compressor
envelope by setting the outside DX coil temperature to a fixed valid value, enter 122°F (50°C) on split-systems, use 327.67 for self­contained units (327.67 = invalid)
Application Name and Version Label
Compressor Start Delay adjust the compressor delay used to prevent multiple compressor
units from starting simultaneously (each unit or group of units should have a different delay setting)
Outdoor Fan Delay
1. Indicates parameters accessible through the keypad/display.
2. Requires optional equipment.
90 sec
327.76
0 sec
10 sec
LUI Menu
1
Item
C6
McQuay OM 751 49
McQuay Training and Development
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
© 2006 McQuay International • www.mcquay.com • 800-432-1342
Loading...