The PTAC Hydronic Kit is an enclosure kit that provides
complete coverage of all PTAC plumbing and coils while still
allowing access to controls. The kit can only be installed
where there is a central boiler for heating the water. It does
not affect unit heating and cooling operations. The hydronic
kit chassis slides out for service without removing any
hydronic plumbing. The electrical connections are plug-in
type to assist in kit installation.
NOTE: Heat pump models will operate on heat pump
function down to the switchover temperature before operating on hydronic heat.
Freeze Protection
For PTAC Hydronic Coil freeze protection on hot water
systems, the hydronic system should use an antifreeze
AND
HWK03E
I
NSTRUCTIONS
solution. However, the addition of antifreeze will reduce the
capacity of the hydronic coil and affect system sizing. The
higher the antifreeze concentration, the greater the capacity
reduction. Therefore, for optimum unit performance, only use
an antifreeze concentration that will protect to the lowest
ambient temperature expected. A 20% solution will protect
to approximately 15°F. A 50% solution protect to -35°F.
Use an antifreeze that is formulated for hydronic use. DO
NOT USE AUTOMOTIVE OR PETROLEUM BASED PRODUCTS.
Tools Required
1/4 Inch Electric Drill
1/8 Inch Diameter Drill Bit
Center Punch and Hammer
6 Foot Rule
Combination Square
1/4 Inch Nut Driver or Socket
5/16 Inch Nut Driver or Socket
Torch, Solder, Flux, etc.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This
includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention
to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is
more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to
instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific
good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices.
However, if there is a direct conflict between existing practices and the content of this manual, the
Before installing the hydronic kit, determine the following:
•Whether a 2-way or 3-way normally open or normally
closed valve is required.
•If an end switch is required to control the circulating
pump. (Information relating to U.L. approved valves
and current loads is shown on the kit label and is
repeated in the following figure).
NOTE: WHEN HYDRONIC HEAT IS USED, DISREGARD THE MINIMUM CIRCUIT AMPACITY AND MAXIMUM
FUSE SIZE SHOWN ON THE AUXILIARY NAMEPLATE FOR FIELD INSTALLED HEATERS. USE VALVES
SHOWN ON THE MASTER UNIT NAMEPLATE.
ERIE MANUFACTURING CO. 654C0507EA01 654C0407EA01 UNIT VOLTAGE RATING230/208 265
CAUTION: VOLTAGE RATING OF VALVE IS 24VAC AND DOES NOT CORRESPOND TO
THIS KIT MAY BE USED WITH ONE OF THE
FOLLOWING ELECTRIC CONTROL VALVES:
VOLTAGE RATING ON THE UNIT NAMEPLATE.
HOT WATER
654C0527EA01 654C0427EA01 FAN MOTOR AMPS.6.6
654C0509EA01 VS2212G14A02A MOTORIZED VALVE, WATTS6.56.5
NOTE: WHEN HYDRONIC HEAT KIT IS
EMPLOYED, THE FOLLOWING LOADS
OPERATE CONCURRENTLY:
E
F
A
C
BARBER-COLMANVA-1403-201VA-9224-201 MAX. WATER TEMPERATURE 200° F
HONEYWELLV8043A
VA-1403-301VA-9214-201 MAX. WATER PRESSURE200 PSIG
VA-3403-201MAX. STEAM PRESSURE5.0 PSIG
V8043BV8043J
V8044A
Also, ensure that the following steps are completed and a
hydronic model chassis is installed before installation.
NOTE: The hydronic chassis MUST have a model
number in which the 10th, 11th, 12th or 13th digit
is H.
1. Wall sleeve is installed and completely sealed.
It must extend at least 3” and no more than 3-1/8” past
the finished interior wall in order to properly install the
hydronic kit.
2. All plumbing stub-outs are completed.
3. Unit chassis is uncrated, uninstalled, and not yet
connected to an electrical source.
INSTALLATION
The installation and servicing of the equipment referred to in this booklet should be performed by qualified, experienced technicians.
Be sure to engage the services of a qualified water
treatment specialist to determine what water treatment, if any, is needed. The manufacturer will not
assume responsibility for equipment failures resulting
from untreated or improperly treated water.
B
D
This Installation kit includes:
ItemQ tyDescription
A1Transition
B1Hydronic Skirt
C1Hydronic Top Assy
D1Hydronic Front Assy
E2Support Brackets
F1Bag Assembly containing:
1. Drill two 1/8” diameter holes on both sides of wall sleeve
as shown (Figure 1).
NOTE: If there is not enough room to drill holes from the
side then drill holes from inside the wall sleeve.
Wall
3-1/4"
Sleeve
5"
2-1/4"
1/8" Holes
Indoor
Right
Side
Wall
Sleeve
1/8" Holes
3-1/4"
5"
2-1/4"
Indoor
Left
Figure 1
2. Remove the hydronic kit from its packaging. Recycle the
cardboard packaging material.
3. Mount the two support brackets to the bottom of the
hydronic top (Figure 2) with four (4) 3/8-inch #8 supplied
screws.
On HVK03E Hydronic Steam Kits, do not use 1/4 inch head,
3/8 inch long, #8 screws to attach the left support bracket
to the hydronic top. Use the provided two 5/16 inch painted
head, 1/4 inch long, #8 screws in place of these longer
screws. (Figure 3)
NOTE: Failure to use the 1/4 inch long screws instead
of the 3/8 inch long screws may result in leaks of the
hydronic steam coil.
Figure 3
4. Mount the transition to the chassis with two 1/2-inch #8
supplied screws (Figure 4).
1/2" #8 Screw
(May be covered
by gasket)
Transition
1/2" #8 Screw
(May be covered
by gasket)
Figure 4
5. Position the hydronic top with support brackets to the
wall sleeve and fasten the support brackets to the drilled
holes in the wall sleeve with four 1/2-inch #10 supplied
screws. (Figure 5)
Slide Brackets Before Tightening Screws
Figure 2
Move the brackets to the left so that screws are located
in right side of slot and tighten screws (Figure 3).
Figure 5
6. Place the chassis back into the wall sleeve and secure
chassis to wall sleeve.
7. Measure the actual distance “D” (Figure 6) from the
bottom of the chassis basepan to the finished floor to
determine how far to extend the skirt below the metal
front. If the distance is less than two inches, trim the
skirt per Figure 7 so that it will not interfere with the
gasket or block the inlet air on the front. In Figure 7, “Y”
dimension equals 2” minus actual “D” dimension.
3
Hydronic Front
(Inside Surface)
W
A
L
L
S
k
i
r
t
Basepan
D = 1/2" to 3-3/4"
Floor
6
2
-
3
/
4
"
8
"
Figure 6
Y
=
2
Figure 7
3/8" #8 Screws
(Two On Each Side)
Figure 9
9. Remove the six screws from the top of the hydronic top.
Lift the hydronic top straight up and set aside along with
the six screws (Figure 10).
"
-
D
Exterior
Wall
Figure 10
Skirt
Between 0" to 3"
Hydronic
Front
Finished
Floor
Wall
Sleeve
Figure 8
8. Mount the skirt to the metal front with the four remaining
3/8” #8 supplied screws (Figure 9).
NOTE: Skirt is attached to front of top piece during shipping.
10. Position the wires from the freeze thermostat found on
the left side of the hydronic top so the wires slide through
the slot opening in the hydronic top.
Place all wires into the supplied snap bushing (Figure
11.
SNAP BUSHING
Figure 11
11. Snap the grommet into the hydronic top and pull the
wires forward to take out the slack in the wires (Figure
12).
4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.