The following symbols and labels are used throughout this manual
to indicate immediate or potential safety hazards. It is the
owner’s and installer’s responsibility to read and comply with all
safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of
personal injury , property damage, and/or product damage.
S
HIPPING INSPECTION
HIGH VOLTAGE!
D
ISCONNECT
ULTIPLE POWER SOURCES MAY BE PRESENT
M
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH
ALL
POWER BEFORE SERVICING
.
WARNING
.
. F
AILURE
Always keep the unit upright; laying the unit on its side or top
may cause equipment damage. Shipping damage, and subsequent investigation is the responsibility of the carrier. Verify
the model number, specifications, electrical characteristics,
and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
C
ODES
& R
EGULATIONS
This product is designed and manufactured to comply with
national codes. Installation in accordance with such codes and/
or prevailing local codes/regulations is the responsibility of the
installer. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations. Rated
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR
REPAIR (HEREINAFTER
SHOULD SERVICE THE EQUIPMENT
FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVI CE OR
SERVICE PROCEDURES
FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT
SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE
EQUIPMENT
THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST
SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER
TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH
, “
SERVICE
”)
THE EQUIPMENT SPECIFIED IN THIS MANUAL
. THE
MANUFACTURER WILL NOT BE RESPONSIBLE
. IF
YOU SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY
. IN
ADDITION, IN
. I
MPROPER INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF
.
,
performance is achieved after 72 hours of operation. Rated performance is delivered at the specified airflow. See out door unit
specification sheet for split system models or product specification sheet for packaged and light commercial models.
Specification sheet s can be found at www.goodmanmfg.com
for Goodman® brand products or www.amana-hac.com for
Amana® brand products. Within either website, please select
S
CROLL EQUIPPED UNITS SHOULD NEVER BE USED TO EVACUATE THE AIR
CONDITIONING SYSTEM
ELECTRICAL ARCING RESULTING IN A DAMAGED OR FAILED
COMPRE SSOR
.
. V
CAUTION
ACUUM S THIS LOW CAN CAUSE INTERNAL
the residential or commercial products menu and then select
the submenu for the type of product to be installed, such as
air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
“IMPORTANT – This product has been designed and manufactured to meet
ENERGY STAR criteria for energy efficiency when matched with appropriate
coil components. However, proper refrigerant charge and proper air flow
are critical to achieve rated capacity and efficiency. Installation of this
product should follow the manufacturer’s refrigerant charging and air
flow instructions. Failure to confirm proper charge and airflow may reduceenergy efficiency and shorten equipment life.”
is a registered trademark of Maytag Corporation or its related companies and is used under
license to Goodman Company, L.P., Houston, TX. All rights reserved.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction
and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the
imposition of substantial fines. Should you have any questions please contact the local office of the EPA.
If replacing a condensing unit or air handler, the system must be manufacturer approved and Air Conditioning, Heating and
Refrigeration Institute (AHRI) matched. NOTE: Installation of unmatched systems is strongly discouraged.
Outdoor units are approved for operation above 55°F in cooling mode. Operation below 55°F in cooling mode requires the use
of an approved low ambient kit.
Damage to the unit caused by operating the unit in a structure that is not complete (either as part of new construction or
renovation) is not covered by the warranty.
F
EATURES
This heat pump is a part of the ComfortNet™ family of products. It may be installed as part of a “legacy” system using a
standard 24 VAC thermostat. However, with the CTK0* ComfortNet™ thermostat kit, this heat pump may be installed as part of
a digitally communicating system. The ComfortNet system provides enhanced setup features, and enhanced diagnostics. It
also reduces the number of thermostat wires to a maximum of four
and a minimum of two.
I
NSTALLATION CLEARANCES
Special consideration must be given to location of the condensing
unit(s) in regard to structures, obstructions, other units, and any/
all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; how-
NOT
RECOMMENDED
OK!
B
OK!
ever, if vertical conditions require placement beneath an obstruction there should be a minimum of 60 inches between the top
BBB
of the unit and the obstruction(s). The specified dimensions
meet requirements for air circulation only. Consult all appropriate
AAAAA
regulatory codes prior to determining final clearances.
Another important consideration in selecting a location for the unit(s)
is the angle to obstructions. Either side adjacent the valves can be
placed toward the structure provided the side away from the struc-
AA
C
AA
C
AA
OK!
OK!
OK!
OK!
ture maintains minimum service clearance. Corner installations
are strongly discouraged.
A
AA
AA
CC
This unit can be located at ground floor level or on flat roofs. At
ground floor level, the unit must be on a solid, level foundation
that will not shift or settle. To reduce the possibility of sound
transmission, the foundation slab should not be in contact with
or be an integral part of the building foundation. Ensure the foundation is sufficient to support the unit. A concrete slab raised
Model TypeABCAA
Residential
Light Commercial
Minimum Airflow Clearance
10"10"18"20"
12"12"18"24"
above ground level provides a suitable base.
R
OOFTOP INSTALLATIONS
If it is necessary to install this unit on a roof structure, ensure the roof structure can support the weight and that proper
consideration is given to the weather-tight integrity of the roof. Since the unit can vibrate during operation, sound vibration
transmission should be considered when installing the unit. Vibration absorbing pads or springs can be installed between the
condensing unit legs or frame and the roof mounting assembly to reduce noise vibration.
NOTE: These units require special location consideration in areas of heavy snow accumulation and/or areas with prolonged
continuous subfreezing temperatures. Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost
accumulation. Situate the unit to permit free unobstructed drainage
of the defrost water and ice. A minimum 3” clearance under the
outdoor coil is required in the milder climates.
Design TemperatureSuggested Minimum Elevation
+15° and above2 1/2"
-5° to +14°8"
below -5°12"
2
WARNING
R
EFRIGERANTS ARE HEAVIER THAN AIR
OXYGEN IN YOUR LUNGS OR IN ANY ENCLOSED SPACE
POSSIBLE DIFFICULTY IN BREATHING OR DEATH
EVER PURGE REFRIGE RANT INTO AN ENCLOSED ROOM OR SPACE
• N
LAW, ALL REFRIGE RANTS MUST BE RECLAIMED
F AN INDOOR LEAK IS SUSPECTED, THOROUGHLY VENTILATE THE AREA
• I
BEFORE BEGINNING WORK
IQUID REFRIGERANT CAN BE VERY COLD
• L
OR BLINDNESS, AVOID CONTACT AND WEAR GLOVES AND GOGGLES
LIQUID REFRIGERANT DOES CONTACT YOUR SKIN OR EYES, SEEK MEDICAL
HELP IMMEDIATELY
LWAYS FOLLOW
• A
OISONOUS GAS WILL BE PRODUCED
P
EPA
.
.
REGULATIONS
. T
HEY CAN “PUSH OUT” THE
. TO
AVOID
:
.
. TO
AVOID POSSIBLE FROST BITE
. N
EVER BURN REFRIGE RANT, AS
.
. BY
. IF
In more severe weather locations, it is recommended that the
unit be elevated to allow unobstructed drainage and air flow.
The elevation minimums at right are recommended:
S
AFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation,
they should serve as a useful guide.
R
EFRIGERANT LINES
WARNING
TO
AVOID POSSIBLE EXPLOSION
• N
EVER APPLY FLAME OR STEAM TO A REFRIGERANT CYLINDER
MUST HEAT A CYLINDER FOR FASTER CHARGING, PARTIALLY IMMERSE IT
IN WARM WATER
EVER FILL A CYLINDER MORE THAN
• N
EVER ADD ANYTHING OTHER THAN
• N
TO AN
410A
BE LISTED OR CERTIFIED FOR THE TYPE OF REFRIGERANT USED
TORE CYLINDERS IN A COOL, DRY PLACE
• S
LATFORM OR A ROLLER
P
.
R-410A
CYLINDER
.
:
80%
FULL OF LIQUID REFRIGERANT
R-22 TO AN R-22
. THE
SERVICE EQUIPMENT USED MUST
. N
EVER USE A CYLINDER AS A
. IF
YOU
CYLINDER OR
.
R-
W ARNING
TO
AVOID POSSIBLE INJURY, EXPLOSION OR DEATH, PRACTICE SAFE
HANDLING OF REFRIGERANTS
.
W ARNING
TO
AVOID POSSIBLE EXPLOSION, USE ONLY RETURNA BLE (NOT
DISPOSABLE) SERVICE CYLINDERS WHEN REMOVING REFRIGERANT FROM
A SYSTEM
• E
• E
• E
W
.
NSURE THE CYLINDER IS FREE OF DAMAGE WHICH COULD LEAD TO A
LEAK OR EXPLOSION
NSURE THE HYDROSTATIC TEST DATE DOES NOT EXCEED
NSURE THE PRESSURE RATIN G MEETS OR EXCEEDS
HEN IN DOUBT, DO NOT USE CYLINDER
.
400
.
5
PSIG
YEARS
.
.
.
Use only refrigerant grade (dehydrated and sealed) copper tubing to connect the condensing unit with the indoor evaporator.
After cutting the tubing, install plugs to keep refrigerant tubing
clean and dry prior to and during installation. Tubing should
always be cut square keeping ends round and free from burrs.
Clean the tubing to prevent contamination.
Do NOT let refrigerant lines come in direct contact with plumbing, ductwork, floor joists, wall studs, floors, and walls. When
running refrigerant lines through a foundation or wall, openings
should allow for sound and vibration absorbing material to be
placed or installed between tubing and foundation. Any gap
between foundation or wall and refrigerant lines should be filled
with a pliable silicon-based caulk, RTV or a vibration damping
material. A void suspending refrigerant tubing from joist s and
studs with rigid wire or straps that would come in contact with
the tubing. Use an insulated or suspension type hanger. Keep
both lines separate and always insulate the suction line.
These sizes are suitable for line lengths of 79 feet or less. If a
run of more than eighty feet is required, refer to Remote Cooling Service Manual, or TP-106 Long Line Set Application R-22,
or TP-107 Long Line Set Application R-410A or contact your
distributor for assistance.
CAUTION
THE
COMPRESSOR
SUSCEPTIBLE TO MOISTURE ABSORPTION AND COULD CAUS E
COMPRE SSOR FAILURE
ANY LONGER THAN NECESSARY FOR INSTALLATION
POE
OIL FOR
R-410A
. DO
NOT LEAVE SYSTEM OPEN TO ATMOSPHERE
UNITS IS EXTREMELY
.
RECOMMENDED INTERCONNECTING TUBING (Ft)
Cond
Unit
0-2425-49 50-79*
Line Di ameter ( In. OD)
TonsSuctLiqSuctLiqSuctLiq
1 1/25/81/43/43/83/43 / 8
25/81/43/43/83/43/8
2 1/25/81/43/43/87/83 / 8
33/43/87/83/81 1/83/8
3 1/27/83/81 1/83/81 1/83/8
47/83/81 1/83/81 1/83/8
57/83/81 1/83/81 1/83/8
* Lines greater than 79 feet in length or vertical elevation
changes more than 50 feet
Service Manual or contact your distributor for assist ance.
refer to the R emote Cooling
Insulation is necessary to prevent condensation from forming
and dropping from the suction line. Armaflex (or satisfactory equivalent) with 3/8” min. wall thickness is recommended. In
severe conditions (hot, high humidity areas) 1/2” insulation may be required. Insulation must be installed in a manner which
protects tubing from damage and contamination.
3
Where possible, drain as much residual compressor oil from existing systems, lines, and traps; pay close attention to low areas
where oil may collect. NOTE: If changing refrigerant types, ensure the indoor coil and metering device is compatible with the
type of refrigerant being used: otherwise, the indoor coil must be
replaced.
B
URYING REFRIGERANT LINES
If burying refrigerant lines can not be avoided, use the following
checklist.
1. Insulate liquid and suction lines separately .
2. Enclose all underground portions of the refrigerant lines in
waterproof material (conduit or pipe) sealing the ends where
tubing enters/exits the enclosure.
3. If the lines must pass under or through a concrete slab, ensure
lines are adequately protected and sealed.
R
EFRIGERANT LINE CONNECTIONS
IMPORTANT
T o avoid overheating the service valve, TXV valve, or filter
drier while brazing, wrap the component with a wet rag,
or use a thermal heat trap compound. Be sure to follow
the manufacturer’s instruction when using the heat trap compound. Note: Remove Schrader valves from service
valves before brazing tubes to the valves. Use a brazing alloy of 2% minimum silver content. Do not use flux.
T orch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size
require less heat to bring the tube to brazing temperature before adding brazing alloy . Applying too much heat
to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube
being brazed. NOTE: The use of a heat shield when brazing is recommended to avoid burning the serial plate
or the finish on the unit.
1. The ends of the refrigerant lines must be cut square, deburred, cleaned, and be round and free from nicks or dents. Any
other condition increases the chance of a refrigerant leak.
2. “Sweep” the refrigerant line with nitrogen or inert gas during brazing to prevent the formation of copper-oxide inside the
refrigerant lines. The POE oils used in R-410A applications will clean any copper-oxide present from the inside of the
refrigerant lines and spread it throughout the system. This may cause a blockage or failure of the metering device.
3. After brazing, quench the joints with water or a wet cloth to prevent overheating of the service valve.
4. Ensure the filter drier paint finish is intact after brazing. If the paint of the steel filter drier has been burned or chipped,
repaint or treat with a rust preventative. This is especially important on suction line filter driers which are continually wet
when the unit is operating.
NOTE: Be careful not to kink or dent refrigerant lines. Kinked or dented lines will cause poor performance or compressor
damage.
Do NOT make final refrigerant line connection until plugs
are removed from refrigerant tubing.
NOTE: Before brazing, verify indoor TXV is correct for R410A
and proper size.
TO
AVOID POSSIBLE EXPLOSION, THE LINE FROM THE NITROGEN
CYLINDER MUST INCLUDE A PRESSURE REGULATOR AND A PRESSURE
RELIEF VALVE
NO MORE THAN
. THE
PRESSURE RELIEF VALVE MUST BE SET TO OPEN AT
150
PSIG
WARNING
.
L
EAK TESTING
Pressure test the system using dry nitrogen and soapy water to
locate leaks. If you wish to use a leak detector, charge the
(N
ITROGEN OR NITROGEN-TRACED
)
WARNING
TO
AVOID THE RISK OF FIRE OR EXPLOSION, NEVER USE OXYGEN, HIGH
PRESSURE AIR OR FLAMMABLE GASES FOR LEAK TESTING OF A
REFRIGERATION SYSTEM
4
.
system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure then
apply the detector to suspect areas. If leaks are found, repair
them. After repair, repeat the pressure test. If no leaks exist,
proceed to system evacuation.
S
YSTEM EVACUATION
Condensing unit liquid and suction valves are closed to contain
the charge within the unit. The unit is shipped with the valve
stems closed and caps installed. Do not open valves until
the system is evacuated.
REFRIGERANT UNDER PRESSURE!
F
AILURE TO FOLLOW PROPER PROCEDURES MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH
P
ROLONGED OPERATION AT SUCTION PRESSURES LESS THAN
FOR MORE THAN
SCROLLS AND PERMANENT DAMAGE TO THE SCROLL TIPS, DRIVE
BEARINGS AND INTERNAL SEAL
5
SECONDS WILL RESULT IN OVERHEATING OF THE
WARNING
.
CAUTION
.
20
PSIG
NOTE: Scroll compressors should never be used to evacuate or
pump down a heat pump or air conditioning system.
5000
1. Connect the vacuum pump with 250 micron capability to
the service valves.
2. Evacuate the system to 250 microns or less using suction
and liquid service valves. Using both valves is necessary
as some compressors create a mechanical seal separating
the sides of the system.
3. Close pump valve and hold vacuum for 10 minutes. Typically
pressure will rise during this period.
•If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to
startup.
4500
4000
3500
MICRONS
3000
IN
2500
ACUUM
2000
V
1500
1000
500
0 1 2 3 4 5 6 7 8 9
CONDENSIBLES OR SMALL
LEAK PRESENT
NO LEAKS
NO CONDENSIBLES
MINUTES
LEAK(S)
PRESENT
10
•If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or noncondensibles
may be present or the system may have a small leak.
Return to step 2: If the same result is encountered check
for leaks as previously indicated and repair as necessary
then repeat evacuation.
•If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as
necessary then repeat evacuation.
E
LECTRICAL CONNECTIONS
The condensing unit rating plate lists pertinent electrical data
HIGH VOLTAGE!
D
ISCONNECT
ULTIPLE POWER SOURCES MAY BE PRESENT
M
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH DUE TO ELECTRIC SHOCK
MUST CONFORM WITH
CODES
EQUIPMENT PERFORMANCE, EQUIPMENT DAMAGE OR
FIRE
ALL
POWER BEFORE SERVICING
NEC OR CEC
. U
NDERSIZED WIRES COULD CAUSE POOR
.
WARNING
. W
AND ALL LOCAL
.
. F
AILURE
IRING
necessary for proper electrical service and overcurrent protection. Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit.
Consult the NEC, CEC, and all local codes to determine the
correct wire gauge and length.
TO
AVOID THE RISK OF FIRE OR EQUIPMENT DAMAGE, USE COPPER
CONDUCTORS
.
WARNING
Local codes often require a disconnect switch located near the
unit; do not install the switch on the unit. Refer to the installation instructions supplied with the indoor furnace/air handler for
specific wiring connections and indoor unit configuration. Likewise, consult the instructions packaged with the thermostat for
mounting and location information.
O
VERCURRENT PROTECTION
The following overcurrent protection devices are approved for use.
•Time delay fuses
•HACR type circuit breakers
These devices have sufficient time delay to permit the motor-compressor to start and accelerate its load.
5
H
IGH VOLTAGE CONNECTIONS
Route power supply and ground wires through the high voltage port
and terminate in accordance with the wiring diagram provided inside the control panel cover.
LOW V
Condensing unit control wiring requires a nominal 24 V AC (+/- 6
V AC), 60 Hz, minimum 25 V A service from either the indoor or an
optional outdoor transformer. Low volt age wiring for the condensing units depends on the thermostat used. The unit is designed to
work as part of a fully communicating HV AC system utilizing the
ComfortNet™ CTK0* thermostat, ComfortNet™ compatible indoor
unit, and up to four wires.
The unit also has legacy 24 V AC inputs to support non-communicating systems. Route control wires through the low voltage port andterminate in accordance with the wiring diagram provided inside the controlpanel
cover.
NOTE: For two-stage units, refer to the Installation Instructions suppliedwith the
variable speed indoor units for field wiring connections.
NOTE: If the heat pump unit is wired in the communicating modetogether
with a compatible communicating indoor unit and CTK0* communicating
thermostat, then the communicating thermostat is able to search andidentify
the condensing unit when power is applied to the system. Refer to the
Installation Manual of the optional communicating thermostat for more
information.
OL TAGE CONNECTIONS
60
60
30 Min ut e s
60
60
90 Minutes
Voltage Ports
60
30
0
60
60
30
60
0
60 Minutes
120 Minutes
HIGH
VOLTAGE
PORT
LOW
VOLTAGE
PORT
30
0
30
0
Use the dipswitch to select defrost time interval (30, 60, 90, 120
minutes; see chart below).
Factory default setting is 30 minutes. The maximum defrost
cycle time is 10 minutes.
Dipswitch Settings for Selection
of Defrost Time
CAUTION
S
YSTEM START UP
NOTE: Power must be supplied to the 18 SEER outdoor units
containing ECM motors before the power is applied to the indoor
unit. Sending a low voltage signal without high voltage power
present at the outdoor unit can cause malfunction of the control module on the ECM motor.
Adequate refrigerant charge for the matching evaporator coil or air handler and 15 feet of lineset is supplied with the condensing unit. If using evaporator coils or air handlers other than HSVTC coil it maybe necessary to add or remove refrigerant to attain
proper charge. If line set exceeds 15 feet in length, refrigerant should be added at .6 ounces per foot of liquid line.
NOTE: Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped
indoor coil to verify proper charge.
Open the suction service valve first! If the liquid service valve is opened first, oil from the compressor may be drawn into the indoor
coil TXV , restricting refrigerant flow and affecting operation of the system.
When opening valves with retainers, open each valve only until the top of the stem is 1/8” from the retainer . To avoid loss of
refrigerant, DO NOT apply pressure to the retainer . When opening valves without a retainer remove service valve cap and insert
a hex wrench into the valve stem and back out the stem by turning the hex wrench counterclockwise. Open the valve until it
contacts the rolled lip of the valve body .
NOTE: These are not back-seating valves. It is not necessary to force the stem tightly against the rolled lip.
After the refrigerant charge has bled into the system, open the liquid service valve. The service valve cap is the secondary seal
for the valve and must be properly tightened to prevent leaks. Make sure cap is clean and apply refrigerant oil to threads and
POSSIBLE REFRIGERANT LEAK!
TO
AVOID A POSSIBLE REFRIGERANT LEAK, OPEN THE SERVICE VALVES
UNTIL THE TOP OF THE STEM IS
1/8”
FROM THE RETAINER
.
6
sealing surface on inside of cap. Tighten cap finger-tight and then tighten additional 1/6 of a turn (1 wrench flat) to properly seat
the sealing surfaces.
Do not introduce liquid refrigerant from the cylinder into the crankcase of the compressor as this may damage the
compressor.
1. Break vacuum by fully opening liquid and suction base valves.
2. Set thermostat to call for cooling. Check indoor and outdoor
fan operation and allow system to stabilize for 10 minutes
for fixed orifices and 20 minutes for expansion valves.
C
HARGE VERIFICA TION
CAUTION
USE
REFRIGE RANT CERTIFIED TO
COMPRE SSOR DAMAGE, AND DAMAGE CAUSED BY USED REG RIGERA NT IS NOT
COVERE D UNDER THE WARRANTY
REFRIGE RANT TO MEET
AHRI
AHRI
STANDA RDS
. M
OST PORTABLE MACHINES CANNO T CLEAN USED
STANDA RDS
. U
SED REFRIGE RANT MAY CAUSE
.
NOTICE
V
IOLATION OF
PENALTIES
EPA
REGULATIONS MAY RESULT IN FINES OR OTHER
.
REFRIGERANT UNDER PRESSURE!
• DO
NOT OVERCHARGE SYSTEM WITH REFRIGERANT
O NOT OPERATE UNIT IN A VACUUM OR AT NEGATIVE PRESSURE
• D
AILURE TO FOLLOW PROPER PROCEDURES MAY CAUSE PROPERTY
F
DAMAGE, PERSONAL INJURY OR DEATH
O
PERATING THE COMPRE SSOR WITH THE SUCTION VALVE CLOSED MAY
The outdoor temperature must be 60°F or higher . Set the room
thermostat to COOL, fan switch to AUTO, and set the temperature control well below room temperature.
After system has stabilized per startup instructions, check
subcooling and superheat as detailed in the following section.
E
XPANSION VALVE SYSTEM
NOTE: Units matched with indoor coils equipped with non-adjustable TXV should be charged by subcooling only.
Run the unit on low stage cooling for 10 minutes until refrigerant pressures stabilize. Use the following guidelines and methods
to check unit operation and ensure that the refrigerant charge is within limits. Charge the unit on low stage.
1. Purge gauge lines. Connect service gauge manifold to base-valve service ports. Run system at least 10 minutes to allow
pressure to stabilize.
2. T emporarily inst all a thermometer on the liquid line at the liquid line service valve and 4-6" from the compressor on the
suction line. Ensure the thermometer makes adequate contact and is insulated for best possible readings. Use liquid line
temperature to determine subcooling and vapor temperature to determine superheat.
3. Check subcooling and superheat. Systems with TXV application should have a subcooling of 5 to 7°F and superheat of
7 to 9 °F.
a.If subcooling and superheat are low, adjust TXV to 7 to 9 ºF superheat, then check subcooling.
NOTE: T o adjust superheat, turn the valve stem clockwise to increase and counter clockwise to decrease.
b.If subcooling is low and superheat is high, add charge to raise subcooling to 5 to 7 °F then check superheat.
c.If subcooling and superheat are high, adjust TXV valve to 7 to 9 ºF superheat, then check subcooling.
d.If subcooling is high and superheat is low, adjust TXV valve to 7 to 9 ºF superheat and remove charge to lower the
subcooling to 5 to 7 ºF.
TO
PREVENT PERSONAL INJURY, CAREFULLY CONNECT AND DISCONNECT
MANIFOLD GAUGE HOSES
BURNS
. DO
NOT VENT REFRIGERANT INTO THE ATMOSPHERE
ALL REFRIGERANT DURING SYSTEM REPAIR AND BEFORE FINAL UNIT
DISPOSAL
.
CAUTION
. E
SCAPING LIQUID REFRIGE RANT CAN CAUSE
. R
ECOVER
NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge.
4. Disconnect manifold set, installation is complete.
SUBCOOLING FORMULA = SAT. LIQUID TEMP. - LIQUID LINE TEMP.
NOTE: Check the Schrader ports for leaks and tighten valve cores if necessary . Install cap s finger-tight.
H
EAT PUMP
The proper method of charging a heat pump in the heat mode is by weight with the additional charge adjustments for line size,
line length, and other system components. For best results on outdoor units with TXVs, superheat should be 2-5° at 4-6" from
the compressor. Make final charge adjustment s in the cooling cycle.
- H
EATING CYCLE
ADDITIONAL NOTES
1. There are (3) 7-segment LED displays on the PCB. Refer to the Troubleshooting chart at the end of this manual for
definitions of the LED status.
2. “TERM” dip switch is used for communications bus configuration. Leave the settings to the factory default position.
3. “LEARN” push button is used to reset the communications between the equipment. Used only for troubleshooting
purposes.
4. Press “TEST” push button, during system “Standby” mode to turn on both the compressor and outdoor fan for five
seconds.
5. The “RECALL” push button is used to retrieve the six most recent faults. The control must be in Standby Mode (no
thermostat inputs) to use the feature. Depress the push button for approximately two seconds and less than five seconds.
The 7-segment LED displays will then display the six most recent faults beginning with the most recent fault and
decrementing to the least recent fault. The faults may be cleared by depressing the button for greater than five seconds.
Consecutively repeated faults are displayed a maximum of three times. Refer to the fault code definitions at the end of
this manual for more details.
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.