This manual is to be used by qualified, professionally trained HV AC technicians only. Goodman does not assume any
responsibility for property damage or personal injury due to improper service procedures or services performed by an
unqualified person. The material in this manual does not supercede manufacutrer's installation and operation
instructions.
is a registered trademark of Maytag Corporation or its related companies and is used under license.
All rights reserved.
SYSTEM OPERATION ................................. 40
IMPORTANT INFORMATION
Pride and workmanship go into every product to provide our customers with quality products. It is possible,
however, that during its lifetime a product may require service. Products should be serviced only by a qualified
service technician who is familiar with the safety procedures required in the repair and who is equipped with
the proper tools, parts, testing instruments and the appropriate service manual. REVIEW ALL SERVICE
INFORMATION IN THE APPROPRIATE SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SER VICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR
REPAIR (HEREINAFTER
MANUAL SHOULD SERVICE THE EQUIPMENT
BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SERVICE OR SERVICE PROCEDURES
ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY
RESULT
. IN
LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY
LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT
INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF THE EQUIPMENT
SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR
REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER
TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH
, “
SERVICE
”)
THE EQUIPMENT SPECIFIED IN THIS
. THE
MANUFACTURER WILL NOT
. IF
YOU SERVICE THIS UNIT, YOU
ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE
. I
MPROPER
.
2
WARNING
HIGH VOLTAGE
D
ISCONNECT ALL POWER BEFORE SERVICING OR
INSTALLING THIS UNIT.
BE PRESENT .
DAMAGE, PERSONAL INJ URY OR DEATH.
F
MULTIPLE POWER SOURCES MAY
AILURE TO D O SO MAY CAUSE PROPE RTY
WARNING
T
O PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
DO NOT STORE COMBUSTIBLE MATE RIALS OR USE GASOLINE OR OTHER
FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
IMPORTANT INFORMATION
CO can c aus e serious il lness inc lu d i ng pe r m a n ent br a in
damage or death.
B10259-216
To locate an authorized servicer, please consult your
telephone book or the dealer from whom you purchased
this product. For further assistance, please contact:
CONSUMER INFORMATION LINE
GOODMAN® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
customerservice@goodmanmfg.com
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
CONSUMER INFORMATION LINE
AMANA® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
hac.consumer.affairs@amanahvac.com
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
Las emisiones de monóxido de carbono p ueden circular a través
del aparato cu and o se ope ra en cua lqu i e r mo do .
El monó x id o de carbono puede causar en fermed ades seve ras
como daño cerebral per m a n e n te ó muerte.
RISQUE D'EM POISO N NE ME NT AU
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO po uv an t su rv enir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.
MONOXYDE DE CARBONE
B10259-216
Outside the U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your
telephone company will bill you for the call.
B10259-216
3
PRODUCT IDENTIFICA TION
Good
(13 Digits)
The model and manufacturing number are used for positive identification of component parts used in manufacturing.
Please use these numbers when requesting service or parts information.
Configuration
M - Upflow/H orizontalMajor Revision
C - Downflow/H orizon talA - Initial Release
K - Dedicated UpflowB - 1st Revision
D - Dedicated Downflow
Gas Vale / MotorN - Natural Gas
E- Convertible 2 Stage / High EfficiencyX - Low NOx
H - Convertible 2 Stage / Single Speed
S - Single Stage / Single SpeedCabinet Width
BrandMinor Revision
A- Amana® Brand A - Initial Rele ase
Configur ation
M - Up flow/ H or izontalMajor Revision
C - Downflow /Horizontal A - Initial Re le ase
K - Dedicated Upflow B - 1st Revis ion
D - Dedicated Downflow
Motor N - Natural G as
V - Variable Speed/ComfortNet X - Low NOx
E - High Efficiency
S - Single SpeedCabinet Width
Gas Valve B - 17.5"
M - Modulating C - 21"
C - 2 Stage D - 24.5"
H - Convertible 2 Stage
S - Single StageMaximum CFM
, Dedicated down flo w installa ti on , 3 3
3/8" tall, Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd stage gas
valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor.
115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and 21" wide.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, Dedicated down flo w installa ti on , 3 3
3/8" tall, Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd stage gas
valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor.
115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and 21" wide.
"CB" revisions went to a Honeywell gas valve.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, New model nomenclature, fi re d at
23,000 BTUH per burner. Dedicated down flow installation, 33 3/8" tall, Induced draft, Two stage
gas Valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas
entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X"
models are low NOx. Chassis sizes are 14", 17.5" and 21" wide.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTU H per burner.
Dedicated down flow installation, 33 3/8" tall, Induced draft, Two stage gas valve, Integrated circuit
board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat
exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis
sizes are 14", 17.5" and 21" wide. "BA" revisions have a standard rated altitude of 4,500 ft.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTU H per burner.
Dedicated down flow installation, 33 3/8" tall, Induced draft, Two stage gas valve, Integrated circuit
board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat
exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis
sizes are 14", 17.5" and 21" wide. "BB" revisions have a standard rated altitude of 5,500 ft.
GDH8***BC
GDH80403B*
GDH80603B*
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTU H per burner.
Dedicated down flow installation, 33 3/8" tall, Induced draft, Two stage gas valve, Integrated circuit
board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat
exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis
size is 14" wide. "BC" revisions are equipped with a Broad Ocean motor.
installation, 33 3/8" tall, Induced draft, Two stage gas Valv e , Integrated circuit board
controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat
exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx.
Chassis sizes are 14", 17.5" 21, and 24.5" wide.
,Upflow/Horizontal Left and Right
installation, 33 3/8" tall, Induced draft, Two stage gas Valv e , Integrated circuit board
controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat
exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx.
Chassis sizes are 14", 17.5" 21, and 24.5" wide. CB revision changed to a rotatable inducer
(clockwise).
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, Upflow/Horizontal Left and Right
installation, 33 3/8" tall, Induced draft, Two stage gas Valv e , Integrated circuit board
controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat
exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx.
Chassis sizes are 14", 17.5" 21, and 24.5" wide. CC revision changed to a Honeywell gas
valve.
Goodman®Brand 80% Modified Two-Stage Gas Furnace
.Upflow/Horizontal Left and right
installation, 33 3/8" tall, Induced draft, Two stage gas Valv e , Integrated circuit board
controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat
exchanger. PSC blower motor. 115 volt silicon nitride igniter. Chassis size 24.5" wide. "CD"
revision has a standard rated altittude of 5,500 ft.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, New model nomenclature, fired
at 23,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall,
Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd stage gas valve
by time. Left or right side gas entry. Alulinized steel heat exchanger. PSC blower motor. 115
volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and
, fired at 20,000 BTUH per
burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage
gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right side
gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride
igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. "BA"
revisions have a standard rated altitude of 4,500 ft
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner.
Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage gas valve,
Integrated circuit board controlling 2nd stage gas valve by time. Left or right side
gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride
igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. "BB"
revisions and GMH81205D*BA have a standard rated altitude of 5,500 ft.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner.
Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage gas valve,
Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry.
Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are
low NOx. Chassis sizes are 14" & 17.5" wide. "BC" revisions are equipped with a Broad Ocean
motor.
installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated
circuit board controlling 2nd stage gas valve by time. Left or right side gas entry.
Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X"
models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide.
Amana® Brand 80% Modified Two-Stage Gas Furnace
installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated
circuit board controlling 2nd stage gas valve by time.Left or right side gas entry.
Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X"
models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. CB revision changed
to a ro tatable inducer (clockwise).
Amana® Brand 80% Modified Two-Stage Gas Furnace
installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated
circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat
exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes
are 14", 17.5" 21, and 24.5" wide. CC revision changed to a Honeywell gas valve.
Upflow/Horizontal Left and Right
installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated
circuit board controlling 2nd stage gas valve by time.Left or right side gas entry.
Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" model
is low NOx. Chassis size is 24.5" wide. "CE" revision has a standard rated altitude of 5,500
ft.
Amana® Brand 80% Modified Two-Stage Gas Furnace
, New mode l n o men clature, fired at
23,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted
cabinet. Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd
stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC
blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are
14", 17.5" 21, and 24.5" wide.
Amana® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner.
Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted cabinet. Induced draft,
Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time.
Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt
silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5"
wide. "BA" revisions have a standard rated altitude of 4,500 ft.
Amana® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner.
Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted cabinet. Induced draft,
Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right
side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X"
models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. "BB" revisions and
AMH81205D*BA have a standard rated altitude of 5,500 ft
AMH8***BC
AMH80403A*
AMH80603A*
AMH80803B*
Amana® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner.
Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted cabinet. Induced draft,
Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right
side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X"
models are low NOx. Chassis sizes are 14", 17.5" wide. "BC" revisions are equipped with a Broad
Ocean motor.
tall, Two tone painted cabinet. Induced draft, Two stage gas Val v e , Integrated circuit board controlling
2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC b
lower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and
21" wide. Standard rated altitude of 5,500 ft
Amana® Brand 80% Modified Two-Stage Gas Furnace,
tall, Two tone painted cabinet. Induced draft, Two stage gas Val v e , Integrated circuit board controlling
2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC b
lower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis size is 14" wide.
Standard rated altitude of 5,500 ft. "AB" revisions are equipped with a Broad Ocean motor.
, Dedicated down flow installation, 33 3/8"
Dedicated down flow installation, 33 3/8"
8
PRODUCT IDENTIFICA TION
MODEL # MFG #DESCRIPTION
AFE18-60A
EFR01
FTK 04
HANG20
HANG21
N/A
P1221001
P1221002F
FTK04
N/A
N/A
Fossil Fuel Kit.
above/downstream of a gas or fossil fuel furnace when used with a heat pump. I t will operate with
single and two stage heat pumps and single and two stage furnaces. The AFE18-60A control will
turn the heat pump unit off when the furnace is turned on. An anti-short cycle feature initiates a 3
minute timed off delay when the compressor goes off.
External Filter Rack Kit
is intended to provide a location, external to the furnace casing, for installation of a permanent
filter. The rack is mounted over the indoor air blower compartment area of either side panel, and
provide filter retention as well as a location for attaching return air ductwork.
Furnace Twinning Kit
furnaces to operate at the same time from a single thermostat. The two furnaces to be "twinned"
must be the exact same model with their circulating air blowers set to deliver the same air flow at
the same time. This kit cannot be used to control more than two furnaces.
High Altitude Natural Gas Kit.
fired at 20,000 Btu's per cell for higher altitudes. This kit is required when installing these
furnaces above their maximum rated altitude.
High Altitude Natural Gas Kit.
fired at 20,000 Btu's per cell for higher altitudes. This kit is required when installing these
furnaces above their maximum rated altitude.
The AFE18-60A control is designed for use where the indoor coil is located
. For use with Goodman® and Amana® Brand upflow furnaces. This kit
. This kit allows Goodman® or Amana® Brand single stage 80% gas
The kit is designed to convert 80% gas furnace models
The kit is designed to convert 80% gas furnace models
HA02
N/A
High Altitude Natural Gas Kit.
furnace models fired at 22,500 BTU's per cell for higher altitudes. This kit is required when
installing these furnaces above their maximum rated altitude. This kit contains # 43-49, 55-58 gas
orifices. The orifices in the kit have been selected as a result of testing with the American Gas
Association. The y will provide appropriate derating at the altitu de listed in the High Altitude Charts
as shown in the installation instructions of the kit.
The kit is designed to convert Goodman®, Amana® Brand gas
9
PRODUCT IDENTIFICA TION
MODEL # MFG #DESCRIPTION
AFE18-60A
EFR01
FSRKA-14
FSRKA-17
FSRKA-21
FSRKA-24
FSRKG-14
FSRKG-17
FSRKG-21
FSRGA-24
FTK04
N/A
P1221001
P1221002F
"A " Width Cab.
"B" Width Cab
"C" Width Cab
"D" Width Cab
"A " Width Cab.
"B" Width Cab
"C" Width Cab
"D" Width Cab
FTK04
Fossil Fuel Kit.
The AFE18-60A control is designed for use where the indoor coil is located
above/downstream of a gas or fossil fuel furnace when used with a heat pump. It will operate with
single and two stage heat pumps and single and two stage furnaces. The AFE18-60A control will
turn the heat pump unit off when the furnace is turned on. An anti-short cycle feature initiates a 3
minute timed off delay when the compressor goes off.
External Filter Rack Kit
. For use with Goodman® and Amana® Brand upflow furnaces. This kit
is intended to provide a location, external to the furnace casing, for installation of a permanent
filter. The rack is mounted over the indoor air blower compartment area of either side panel, and
provide filter retention as well as a location for attaching return air ductwork.
Furnace Sound Reduction Kits.
For use with Amana® Brand 33" chassis, 80% furnaces.
When installed, these kits could help to reduce the sound level be apprximatley two decibels.
Furnace Sound Reduction Kits.
For use with Goodman® Brand 33" chassis, 80% furnaces.
When installed, these kits could help to reduce the sound level be apprximatley two decibels.
Furnace Twinning Kit
. This kit allows Goodman® or Amana® Brand single stage 80% gas
furnaces to operate at the same time from a single thermostat. The two furnaces to be "twinned"
must be the exact same model with their circulating air blowers set to deliver the same air flow at
the same time. This kit cannot be used to control more than two furnaces.
HANG20
HANG21
HA02
N/A
N/A
N/A
High Altitude Natural Gas Kit.
The kit is designed to convert 80% gas furnace models
fired at 20,000 Btu's per cell for higher altitudes. This kit is required when installing these
furnaces above their maximum rated altitude.
High Altitude Natural Gas Kit.
The kit is designed to convert 80% gas furnace models
fired at 20,000 Btu's per cell for higher altitudes. This kit is required when installing these
furnaces above their maximum rated altitude.
High Altitude Natural Gas Kit.
The kit is designed to convert Goodman®, Amana® Brand gas
furnace models fired at 22,500 BTU's per cell for higher altitudes. This kit is required when
installing these furnaces above their maximum rated altitude. This kit contains # 43-49, 55-58 gas
orifices. The orifices in the kit have been selected as a result of testing with the American Gas
Association. They will provide appropriate derating at the altitude listed in the High A ltitude Charts
as shown in the installation instructions of the kit.
10
ACCESSORIES
MODEL
NUMBER
EFR01
AFE180-60A
GOODM AN® BRAND "H" Model Fu rnace Accessories
HA02
SBT14
SBT17
SBT21
AMU / G M U
ASAS / GSAS
LPM-06
FTK04
LPLP02 LPLP03
HANG20
HANG21
MVK-01
MVK-02
FSRKG14
FSRKG17
FSRKG21
FSRKG24
Description
GMH80403A**
GMH80603A**
GMH80604B**
GMH80803B**
GMH80804B**
GMH80805C**
GMH81005C**
GMH81205D**
GMH81405DNC*
GDH80403A**
GDH80603A**
GDH80804B**
GDH81005C**
14"
Dual Fuel Bo ar d
EFR External Filter Rack
Media Ai r Cl ean ers
Downflow Subbase
Electro n i c Ai r Cl ean er
····
····
····
····
····
····
····
····
····
····
····
····
····
·
21"
17.5"
Downflow Subbase
not approved for this model
approved for this model
(1) W/R & HW 2 stg valve
(2) BA REV 4,500 - 10,000 FT (excluding GMH81205D*BA)
(3) BB REV 5,500 - 10,000 FT
(4) AA Rev
(5) GMH81205D*BA and GMH81405D*CD 5,500 FT - 10,000 FT
Propane Gas
Downflow Subbase
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Off Kit
Conversio n Ki t
Twinning Kit
LP Low P r essur e S h ut
··
··
··
··
··
··
··
··
···
··
··
··
··
W/Pressu r e S witch
High Al ti tu de O rifices
High Altitude Orifice Kit
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(5)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(5)
High Al ti tu de O rifices
Masonry Vent Ki t
W/Pressu r e S witch
·
·
·
·
·
·
·
Masonry Vent Ki t
Sound Reduction Kit
Sound Reduction Kit
Sound Reduction Kit
Sound Reduction Kit
(4)
(4)
(4)
(4)
(4)
(4)
(4)
·
(4)
··
11
ACCESSORIES
MODEL
NUMBER
EFR01
AFE180-60A
AMANA® BRAND "H" Model Furnace Accessories
HA02
SBT14
SBT17
SBT21
AMU / GMU
ASAS / GSAS
LPM-06
FTK04
LPLP02 LPLP03
MVK-01
HANG20
HANG21
MVK-02
FSRKA14
FSRKA17
FSRKA21
FSRKA24
Description
AMH80403A**
AMH80603A**
AMH80604B**
AMH80803B**
AMH80804B**
AMH80805C**
AMH81005C**
AMH81205D**
AMH81405DNC*
ADSH800403A**
ADSH800603A**
ADSH800804B**
ADSH801005C**
14"
Dual F u e l Board
EFR External Filter Rack
Media Ai r Cleane r s
Downflow Subbase
Electronic Air Cl eaner
····
····
····
····
····
····
····
····
····
····
····
····
····
·
21"
17.5"
Downflow Subbase
not approved for this model
approved for this model
(1) W/R & HW 2 stg valve
(2) BA REV 4,500 - 10,000 FT (excluding GMH81205D*BA)
(3) BB REV 5,500 - 10,000 FT
(4) AA Rev
(5) GMH81205D*BA 5,500 FT - 10,000 FT
Prop ane Gas
Downflow Subbase
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Off Kit
Conversion Kit
Twinning Ki t
LP Low Pressure Shut
··
··
··
··
··
··
··
··
W/Pressure Switch
High Altitude Orifices
High Altitude Orifice Kit
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(2)(3)
(4)(5)
W/Pressure Switch
High Altitude Orifices
·····
···
···
···
···
Mason r y V e nt Ki t
Mason r y V e nt Ki t
Sound Reduction Kit
Sound Reduction Kit
Sound Reduction Kit
Sound Reduction Kit
·
·
·
·
·
·
·
(4)
(4)
(4)
(4)
(4)
(4)
(4)
·
(4)
12
ACCESSORIES
EXTERNAL FILTER RACK KIT
( EFR01 )
SLOTS IN FILTER
CLEAR SCREWS
ON UNIT
UNIT SIDE
PANEL
BLOWER DECK
SCREWS
FRONT
OF UNIT
BASE
OF UNIT
RETURN AIR
CUTOUT AREA
LOWER EDGE
SCREW
EFR01 EXTERNAL FILTER RACK KIT
Used on 80% Upfl ow Model Furnaces
FILTER RACK ASSEMBLY
(FACE FILTER OPENING
TOWARDS FRONT
OF UNIT)
13
ACCESSOR Y WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
POWER SUPPLY
INPUT
FURNACE DEMAND
OUTPUT
BLOWER FAN DEMAND
OUTPUT
POWER SUPPLY INPUT
(COMMON)
SECOND STAGE FURNACE
DEMAND OUTPUT
COMPRESSOR OUTPUT
SECOND STAGE
COMPRESSOR OUTPUT
REVERSING VALVE
OUTPUT
POWER SUPPLY OUT
TO THERMOSTAT
CALL FOR
REVERSING VALVE
CALL FOR
COMPRESSOR
CALL FOR
EMERGENCY HEAT
CALL FOR
BLOWER FAN
CALL FOR
FURNACE HEAT
POWER SUPPLY COMMON
OUT TO THER MOSTAT
CALL FOR 2ND STAGE
FURNACE HEAT
CALL FOR 2ND STAGE
COMPRESSOR
POWER SUPPLY OUT
TO HP CONTROL
HP CALL FOR FURNACE
(DURING DEFROST)
REVERSING
VALVE OUTPUT
COMPRESSOR
CONTACTOR OUTPUT
POWER SUPPLY COMMON
OUT TO HP C ON TR OL
ODT (OUTDOOR
THERMOSTAT)
2ND STAGE C OMPRESSOR
DEMAND OUTPUT
F
U
R
N
A
C
E
T
H
E
R
M
O
S
T
A
T
H
E
A
T
P
U
M
P
R
W1
G
C
W2
Y
Y2
O
R
O
Y
E
G
W1
C
W2
Y2
R
W2
O
Y
C
OT-NO
OT-NC
OT-C
Y2
P1-8
P1-7
P1-4
P1-6
P1-5
P1-2
P1-3
P1-1
P2-2
P2-1
P2-7
P2-8
P2-5
P2-9
P2-3
P2-4
P2-6
P3-9
P3-8
P3-7
P3-2
P3-6
P3-3
P3-1
P3-4
P3-5
24VAC
24VAC
F1
3A
C
C
24VAC
C
POWER
SUPPLY
1.0K
6.8K
6.8K
+5VDC
E/W1
O
Y
+VDC
+5VDC
+VDC
K1
K2
Q1
MICROPROCESSOR
24VAC
+VDC
K4
Q2
W1-FURN
W2-HP
G-STAT
G-FURN
Y2-HP
Y2-STAT
Y2-FURN
Y-STAT
Y-FURN
Y-HP
K3
14
BREAK FOR ODT
12
ALL FUEL SYSTEM CONTROL BOARD - AFE18-60A
This wiring diagram is for reference only. Not all wiring is as shown above.
Refer to the appropriate wiring diagram for the unit being serviced.
(For use with Heat Pumps in conjunction with 80% or 90% Single-Stage or Two-Stage Furnaces)
ACCESSOR Y WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FURNACE TWINING KIT - FTK04 (UTEC Control Board)
This wiring diagram is for reference only. Not all wiring is as shown above.
Refer to the appropriate wiring diagram for the unit being serviced.
(For use only with 80% or 90% Single-Stage Furnaces)
15
OPERA TING INSTRUCTIONS
FOR Y OUR S AFETY READ BE FORE OPERATING
If you do not follow these instructions exactly,
a fire or explosion may result causing property
damage, personal injury or loss of life.
A. This appliance does not have a pilot. It
is equipped with an ignition device which
automatically lights the burners. Do not
try to light the burners by hand.
B. BEFORE OPERATING smell around
the appliance area for gas. Be sure to
smell next to the floor because some gas
is heavier than air and will settle on the
floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch;
do not use any telephone in your
building.
Immediately call your supplier
from a neighbor's phone. Follow
the gas suppliers instructions.
If you cannot reach your gas supplier,
call the fire department.
C. Use only your hand to move the gas
control switch or knob. Never use
tools. If the gas control switch or knob
will not operate, don't try to repair it,
call a qualified service technician.
Force or attempted repair may result in
a fire or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call
a qualified service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the
appliance.
4. This appliance is equipped with an
automatic ignition system which
automatically lights the burners. Do not
try to light the burners by hand.
5. Remove control access panel.
6. Move the gas control switch or knob
to "OFF ".
GAS CONTROL
SWITCH SHOWN
IN "ON" POSITION
7. Wait five (5) minutes to clear out any
gas. If you then smell gas, STOP!above on this label.
Follow "B" in the safety information
above on this label. If you don't smell
gas, go to the next step.
8. Move the gas control switch or knob
to "ON".
9. Replace control access panel.
10. Turn on all electric power to the
appliance.
11. Set the thermostat to the desired
setting.
12. If the appliance will not operate,
follow the instructions "To Turn Off Gas
To Appliance" and call your service
technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to its lowest setting.
2. Turn off all electric power to the
appliance if service is to be performed.
3. Remove control access panel.
4. Move the gas control switch or knob
to "OFF". Do not force.
5. Replace control access panel.
WARNING: Improper
alteration, service or
maintenance can
cause injury or
property damage.
Refer to the user's
information manual
provided with this
consult a qualified
or the gas supplier.
This furnace must be
instructions and local
codes. In the absence
of local codes, follow
the National Fuel Gas
Code, ANSI Z223.1.
For indoor installation.
PGB & PGJ
For outdoor
installation only .
If notWARNING:
installed, operated
and maintained in
accordance with the
manufacturer's
instru ctions, this
product could expose
you to substances
in fuel combustion
which can cause
death or serious
illness and which
are known to the
State of California to
cause cancer, birth
defects or other
reproductive harm.
This product contains
fiberglass insulation.
Fiberglass insu la tion
contains a chemical
California to cause
cancer.
FOR YOUR SAFETY
Do not store or use gasoline or
other flammable vapors and liquids in the vicinity of this
or any other appliance.
16
0140F00001P
OPERA TING INSTRUCTIONS
CONSIGNES DE SECURITE - LIRE
AVANT D'ALLUMER L'APP AREIL
AVERTISSEMENT: Le non-respect des inst r uct i ons qui suivent peut
^
entrainer un r i sque d'incendi e ou d'explosion causant des dommages,
des blessures ou la mort.
A. Cet appareil comporte pas de veilleuse. Il est muni d'un mecanisme qui allume
automatiquement le bruleur. N
B. Sentir tout autour de l'appariel AVANT D'ALLUMER afin de deceler toute fuite de gaz.
Assurez-vous de sentir tout pres du plancher car certains gaz sont plus lourds que l'air
et se deposeront sur le plancher.
SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne tentez d'allumer aucun appariel.
Ne touchez pas aux interrupteurs elec triques; n'utiliser aucun telephone
dans l'edifice ou vous vous trouvez.
Appelez immediatement votre fournisseur de gaz en utilisant le telephone
d'un voisin et suivez les instructions du fournisseur.
Appelez les pompiers si vous ne parvenez pas a rejoindre votre fournisseur
de gaz.
C. N'utiliser que votre main pour pousser ou tourner le commande du gaz. N'utilisez
jamais d'outils. Si vous ne parvenez pas a pousser ou a tourner la commande, ne tentez
pas de la reparer; appelez un reparateur qualifie. Forcer la commande ou essayer de la
reparer peut entrainer un risque d'incendie ou d'explosion.
D. N'utilisez pas cet appareil si l'une de ses parties a ete dans l'eau. Si cela se produit,
demandez immediatement a un reparateur qualifie d'insp ecter l'appareil et de remplacer
toute piece du systeme de controle et toute commande de gaz ayant ete dans l'eau.
^^
'allumez paz le bruleur manuellement.
^
^
0140F00002P
1. UN INSTANT! Lisez d'abord les consignes
INSTRUCTIONS DE SERVICE
de s e cu rite ci-des su s.
2. Reglez le thermostat a son point le plus bas.
3. Coupez l'alimentation electrique de l'appareil.
4. Cet appareil est muni d'un mecanisme qui
allume automatiquement le bruleur. Ne tentez
pas d'allumer le bruleur manuellement.
5. Retirez le panneau d'acces de la commande.
6. Mettez la commande de gaz a la position
^
ARRET ("OFF").
7. Attendez cinq (5) minutes afin de permettre a
tout gaz present d'etre evacue. Si vous sentez
une odeur de gaz a ce moment, ARRETEZ! et
suivez les consignes de securit e donnees au
paragraphe B ci-dessus. Si vous ne sentez pas
de gaz, passez a l'etape suivante.
8. Mettez la commande de gaz a la position
MARCHE ("ON").
9. Remettez la panneau d'acces de la commande
en place.
10. Retablissez l'alimenation electrique de l'appareil.
11. Reglez le thermost at a le temperature desiree.
12. Si l'appareil ne fonctionne pas, suivez les
instructions intitulees "Arret du gaz" et appelez un
reparateur qualifie ou votre fourniss eur de gaz.
1. Reglez le thermostat a son point le plus bas.
2. Coupez l'alimentation electrique de l'appareil si vous devez effectuer un entretien.
3. Retirez le panneau d'acces de la commande.
4. Mettez la commande de gaz a la position ARRET ("OFF").
5. Remettez le panneau d'acces de la commande en place.
^
^
^
^
^
^
ARRET DU GAZ
^
Commande de
gaz en position
"MARCHE"
17
OPERA TING INSTRUCTIONS
A
O
R
T
I
G
B
N
N
U
M
A
O
"
/
N
S
A
G
T
E
L
N
I
E
E
V
R
I
R
A
Z
A
U
D
G
M
L
N
I
M
G
A
L
N
U
A
A
R
E
V
E
H
S
O
O
"
P
S
"
N
O
Z
E
A
,
L
N
O
E
E
P
A
S
W
S
"
E
R
H
C
N
18
PRODUCT DESIGN
Safety
Please adhere to the following warnings and cautions
when installing, adjusting, altering, servicing, or operating the furnace.
WARNING
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION,
ADJUSTMENT, ALTERATI ON, SERV ICE OR MAINTENANCE, R EFER TO THI S
MANUAL.
QUALIFIED INSTALLE R, SERVICE AGENCY OR THE GAS SUPPLIER.
OR ADDITIONAL ASSISTANCE OR INFORMATION, CONSULT A
F
WARNING
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
T
MAY CAUSE SERI OUS ILLNESS OR DEATH AN D WHICH ARE KNOWN TO THE
S
TATE OF CALIFORNIA TO CAUSE CANCER, BI RTH DEFECTS OR OTHER
REPRODUCTIVE HARM.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
DUE TO ELECTRICAL SHOCK, THE FURNACE MUST BE LOC ATED TO PROTECT
THE ELEC TRICA L COMPON ENTS FROM WA TER.
Charge (ESD) Precautions
NOTE: Discharge body’s static electricity before touch-
ing unit. An electrostatic discharge can adversely affect
electrical components.
Use the following precautions during furnace installation and servicing to protect the integrated control module from damage. By putting the furnace, the control,
and the person at the same electrostatic potential, these
steps will help avoid exposing the integrated control
module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded)
furnaces.
1. Disconnect all power to the furnace. Do not touch
the integrated control module or any wire connected
to the control prior to discharging your body’s electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of
the furnace near the control. Any tools held in a
person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring following the discharge process in Step 2. Use
caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do
not touch ungrounded objects, etc.). If you come in
contact with an ungrounded object, repeat Step 2
before touching control or wires.
4. Discharge any static electricity from your body to
ground before removing a new control from its container. Follow Steps 1 through 3 if installing the con-
trol on a furnace. Return any old or new controls to
their containers before touching any ungrounded object.
Product Application
This product is designed for use as a residential home
gas furnace. It is not designed or certified for use in
mobile home, trailer, or recreational vehicle applications.
This furnace can be used in the following non-industrial
commercial applications: Schools, Office buildings, Churches,
Retail stores, Nursing homes, Hotels/motels, Common or
office areas. In such applications, the furnace must be installed
with the
Goodman® & Amana
installation instructions.
®
Brand 80% furnaces are ETL certified appliances and are appropriate for use with natural
or propane gas. (NOTE: If using propane gas, a propane
conversion kit is required).
IMPORTANT NOTE: The 80% furnace cannot be installed as a direct vent (i.e.., sealed combustion) furnace. The burner box is present only to help reduce
sound transmission from the burners to the occupied
space.
To ensure proper installation, operation and servicing,
thoroughly read the installation and service manuals for
specifics pertaining to the installation, servicing and
application of this product.
WARNING
OSSIBLE PROPERTY D AMAGE, PERSONAL INJ URY OR DEATH DUE TO FIRE,
P
EXPLOSION, SMOKE, S OOT, CONDENSTAION, E LECTRICAL SHOCK OR C ARBON
MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION, RE PAIR, OPERATI ON,
OR MAINTENANCE OF THI S PRODUCT.
WARNING
T
O PREVENT PROPERTY DAMAGE, PERSONAL INJ URY OR DEATH D UE TO FIRE,
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR RECREATIONAL
VEHICLE.
To ensure proper furnace operation, install, operate,
maintain and service the furnace in accordance with the
installation, operation and service instructions, all local building codes and ordinances. In their absence, follow the latest edition of the National Fuel Gas Code
(NFPA 54/ANSI Z223.1), and/or CAN/CGA B149 Installation Codes, local plumbing or waste water codes, and
other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
19
PRODUCT DESIGN
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269-7471
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
A copy of the CAN/CGA B149 Installation Codes can be
obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W, 1R3
The rated heating capacity of the furnace should be
greater than or equal to the total heat loss of the area
to be heated. The total heat loss should be calculated
by an approved method or in accordance with “ASHRAE
Guide” or “Manual J-Load Calculations” published by the
Air Conditioning Contractors of America.
Location Requirements and Considerations
WARNING
O PREVENT POSSIBLE E QUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FOLLOWING BULLET P OINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.
Follow the instructions listed below when selecting a
furnace location. Refer also to the guidelines provided
in the Combustion and Ventilation Air Requirements section in this manual or the installation instructions for
details.
•Centrally locate the furnace with respect to the
proposed or existing air distribution system.
•Ensure the temperature of the return air entering
the furnace is between 55°F and 100°F when the
furnace is heating.
•If the furnace is installed in an application where
the typical operating sound level of a furnace is
deemed objectionable, an optional sound reduction kit is available. Consult your local distributor for more details.
•Provide provisions for venting combustion products outdoors through a proper venting system.
Special consideration should be given to vent/flue
pipe routing and combustion air intake pipe when
applicable.
80% Furnaces: All installations must be vented in
accordance with National Fuel Gas Code, NFPA 54/
ANSI Z223.1 - lateset edition. In Canada the furnaces must be vented in accordance with the National Standard of Canada, CAN/CGA B149.
•Ensure upflow or horizontal furnaces are not installed directly on carpeting, or any other combustible material. The only combustible material
allowed is wood.
•A special accessory subbase must be used for upright counterflow unit installations over any combustible material (including wood). Refer to subbase instructions for installation details. (NOTE:
A subbase will not be required if an air conditioning coil is located beneath the furnace between
the supply air opening and the combustible floor.
•Exposure to contaminated combustion air will result in safety and performance-related problems.
Do not install the furnace where the combustion
air is exposed to the following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
•Seal off a non-direct vent furnace if it is installed
near an area frequently contaminated by any of
the above substances. This protects the non-di-rect vent furnace from airborne contaminants. To
ensure that the enclosed non-direct vent furnace
has an adequate supply of combustion air, vent
from a nearby uncontaminated room or from outdoors. Refer to the Combustion and VentilationAir Requirements section in this manual or the installation instructions for details.
•If the furnace is used in connection with a cooling
unit, install the furnace upstream or in parallel
with the cooling unit coil. Premature heat exchanger failure will result if the cooling unit coil
is placed ahead of the furnace.
•If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition source are located not less than 18 inches
(457 mm) above the floor. Protect the furnace from
physical damage by vehicles.
20