Amana AMH80403ANBA, AMH80403ANBB, AMH80403AXBA, AMH80403AXBB, AMH80603ANBA User Manual

...
Service Instructions
®
Goodman® & Amana® Brand
AMH8, GMH8, GDH8, ADSH8
& Accessories
This manual is to be used by qualified, professionally trained HV AC technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person. The material in this manual does not supercede manufacutrer's installation and operation instructions.
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
Copyright © 2006-2014, 2016 Goodman Manufacturing Company, L.P.
RS6612007r3
August 2016
TABLE OF CONTENTS
IMPORTANT INFORMATION........................2 - 3
PRODUCT IDENTIFICATION ..................... 4 - 10
ACCESSORIES ................................... 11 - 15
OPERATING INSTRUCTIONS .................... 16 - 18
PRODUCT DESIGN............................... 19 - 39
TROUBLESHOOTING ............................ 41 - 42
MAINTENANCE .................................. 43 - 46
SERVICING ....................................... 47 - 63
SERVICING TABLE OF CONTENTS .................. 49
WIRING DIAGRAMS/SCHEMATICS .................. 64
SYSTEM OPERATION ................................. 40
IMPORTANT INFORMATION
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate service manual. REVIEW ALL SERVICE
INFORMATION IN THE APPROPRIATE SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SER VICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR REPAIR (HEREINAFTER MANUAL SHOULD SERVICE THE EQUIPMENT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT
. IN
LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
, “
SERVICE
”)
THE EQUIPMENT SPECIFIED IN THIS
. THE
MANUFACTURER WILL NOT
. IF
YOU SERVICE THIS UNIT, YOU
ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE
. I
MPROPER
.
2
WARNING
HIGH VOLTAGE D
ISCONNECT ALL POWER BEFORE SERVICING OR
INSTALLING THIS UNIT. BE PRESENT . DAMAGE, PERSONAL INJ URY OR DEATH.
F
MULTIPLE POWER SOURCES MAY
AILURE TO D O SO MAY CAUSE PROPE RTY
WARNING
T
O PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH, DO NOT STORE COMBUSTIBLE MATE RIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
IMPORTANT INFORMATION
CO can c aus e serious il lness inc lu d i ng pe r m a n ent br a in damage or death.
B10259-216
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this product. For further assistance, please contact:
CONSUMER INFORMATION LINE
GOODMAN® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
customerservice@goodmanmfg.com
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
CONSUMER INFORMATION LINE
AMANA® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
hac.consumer.affairs@amanahvac.com
fax us at: (731) 856-1821
(Not a technical assistance line for dealers.)
Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
Las emisiones de monóxido de carbono p ueden circular a través del aparato cu and o se ope ra en cua lqu i e r mo do .
El monó x id o de carbono puede causar en fermed ades seve ras como daño cerebral per m a n e n te ó muerte.
RISQUE D'EM POISO N NE ME NT AU
Cette ventilation est nécessaire pour éviter le danger d'intoxication au CO po uv an t su rv enir si un appareil produisant du monoxyde de carbone continue de fonctionner au sein de la zone confinée.
MONOXYDE DE CARBONE
B10259-216
Outside the U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your
telephone company will bill you for the call.
B10259-216
3
PRODUCT IDENTIFICA TION
Good
(13 Digits)
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
man Furnace Nomenclature
GMH80 060 3AN AA 12345 678 910111213
Brand Minor Revision G - Goodman A - Initial Release A- Amana® Brand B - 1st Revision
Configuration M - Upflow/H orizontal Major Revision C - Downflow/H orizon tal A - Initial Release K - Dedicated Upflow B - 1st Revision D - Dedicated Downflow
Gas Vale / Motor N - Natural Gas E- Convertible 2 Stage / High Efficiency X - Low NOx H - Convertible 2 Stage / Single Speed S - Single Stage / Single Speed Cabinet Width
AFUE B - 17.5" 97 - 97% AFUE C - 21" 80 - 80% AFUE D - 24.5"
MBTU/h Maximum CFM 40 - 40,000 3 - 1200 CFM 60 - 60,000 4 - 1600 CFM 80 - 80,000 5 - 2000 CFM 100 - 100,000 120 - 120,000 140 - 140,000
Nox
A - 14"
Am an a® B rand Furnace Nomenclature (14 Digits)
A D S H 80 060 3 B N A A 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Brand Minor Revision A- Amana® Brand A - Initial Rele ase
Configur ation M - Up flow/ H or izontal Major Revision C - Downflow /Horizontal A - Initial Re le ase K - Dedicated Upflow B - 1st Revis ion D - Dedicated Downflow
Motor N - Natural G as V - Variable Speed/ComfortNet X - Low NOx E - High Efficiency S - Single Speed Cabinet Width
Gas Valve B - 17.5" M - Modulating C - 21" C - 2 Stage D - 24.5" H - Convertible 2 Stage S - Single Stage Maximum CFM
AFUE 4 - 1600 CFM 97 - 97% AFUE 5 - 2000 CFM 80 - 80% AFUE
MBTU/h 40 - 40,000 60 - 60,000 80 - 80,000 100 - 100,000 120 - 120,000
4
B - 1st Revis ion
Nox
A - 14"
3 - 1200 CFM
PRODUCT IDENTIFICA TION
MODEL# MFG.# DESCRIPTION
GDH8**CA
GDH8***CB
GDH8***AA
GDH8***BA
GDH8***BB
GDH80453A* GDH80703A* GDH80904B* GDH81155C*
GDH80453A* GDH80703A* GDH80904B* GDH81155C*
GDH80403A* GDH80603A* GDH80804B* GDH81005C*
GDH80403A* GDH80603A* GDH80804B* GDH81005C*
GDH80403A* GDH80603A* GDH80804B* GDH81005C*
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, Dedicated down flo w installa ti on , 3 3 3/8" tall, Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and 21" wide.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, Dedicated down flo w installa ti on , 3 3 3/8" tall, Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and 21" wide. "CB" revisions went to a Honeywell gas valve.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, New model nomenclature, fi re d at 23,000 BTUH per burner. Dedicated down flow installation, 33 3/8" tall, Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and 21" wide.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTU H per burner. Dedicated down flow installation, 33 3/8" tall, Induced draft, Two stage gas valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and 21" wide. "BA" revisions have a standard rated altitude of 4,500 ft.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTU H per burner. Dedicated down flow installation, 33 3/8" tall, Induced draft, Two stage gas valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and 21" wide. "BB" revisions have a standard rated altitude of 5,500 ft.
GDH8***BC
GDH80403B* GDH80603B*
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTU H per burner. Dedicated down flow installation, 33 3/8" tall, Induced draft, Two stage gas valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis size is 14" wide. "BC" revisions are equipped with a Broad Ocean motor.
5
PRODUCT IDENTIFICA TION
MODEL # MFG.# DESCRIPTION
GMH80453A*
GMH8**CA
GMH80703A* GMH80704B* GMH80903B* GMH80904C* GMH80905C* GMH81155C* GMH81405D*
Goodman® Brand 80% Modified Two-Stage Gas Furnace
installation, 33 3/8" tall, Induced draft, Two stage gas Valv e , Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide.
, Upflow/Horizontal Left and Right
GMH80453A* GMH80703A* GMH80704B*
GMH8***CB
GMH8***CC
GMH8***CD GMH81405D*
GMH8***AA
GMH80903B* GMH80904C* GMH80905C* GMH81155C* GMH81405D*
GMH80453A* GMH80703A* GMH80704B* GMH80903B* GMH80904C* GMH80905C* GMH81155C* GMH81405D*
GMH80403A* GMH80603A* GMH80604B* GMH80803B* GMH80804C* GMH80805C* GMH81005C* GMH81205D*
Goodman® Brand 80% Modified Two-Stage Gas Furnace
,Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage gas Valv e , Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. CB revision changed to a rotatable inducer (clockwise).
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage gas Valv e , Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. CC revision changed to a Honeywell gas valve.
Goodman®Brand 80% Modified Two-Stage Gas Furnace
.Upflow/Horizontal Left and right installation, 33 3/8" tall, Induced draft, Two stage gas Valv e , Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. Chassis size 24.5" wide. "CD" revision has a standard rated altittude of 5,500 ft.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, New model nomenclature, fired at 23,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Alulinized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and
24.5" wide.
GMH8***BA
GMH8***BB
GMH8***BC
6
GMH80403A* GMH80603A* GMH80604B* GMH80803B* GMH80804C* GMH80805C* GMH81005C* GMH81205D*
GMH80403A* GMH80603A* GMH80604B* GMH80803B* GMH80804C* GMH80805C* GMH81005C*
GMH80403A* GMH80603A* GMH80803B*
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. "BA" revisions have a standard rated altitude of 4,500 ft
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage gas valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. "BB" revisions and GMH81205D*BA have a standard rated altitude of 5,500 ft.
Goodman® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Induced draft, Two stage gas valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Aluminized steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14" & 17.5" wide. "BC" revisions are equipped with a Broad Ocean motor.
PRODUCT IDENTIFICA TION
MODEL# MFG.# DESCRIPTI O N
AMH80453A*
AMH8**CA
AMH8***CB
AMH8***CC
AMH80703A* AMH80704B* AMH80903B* AMH80904C* AMH80905C* AMH81155C* AMH81405D*
AMH80453A* AMH80703A* AMH80704B* AMH80903B* AMH80904C* AMH80905C* AMH81155C* AMH81405D*
AMH80453A* AMH80703A* AMH80704B* AMH80903B* AMH80904C* AMH80905C* AMH81155C* AMH81405D*
Amana® Brand 80% Modified Two-Stage Gas Furnace
installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide.
Amana® Brand 80% Modified Two-Stage Gas Furnace
installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time.Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. CB revision changed to a ro tatable inducer (clockwise).
Amana® Brand 80% Modified Two-Stage Gas Furnace
installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. CC revision changed to a Honeywell gas valve.
, Upflow/Horizontal Left and Right
, Upflow/Horizontal Left and Right
, Upflow/Horizontal Left and Right
AMH8**CE AMH81405D*
AMH80403A* AMH80603A* AMH80604B*
AMH8***AA
AMH8***BA
AMH8***BB
AMH80803B* AMH80804C* AMH80805C* AMH81005C* AMH81205D*
AMH80403A* AMH80603A* AMH80604B* AMH80803B* AMH80804C* AMH80805C* AMH81005C* AMH81205D*
AMH80403A* AMH80603A* AMH80604B* AMH80803B* AMH80804C* AMH80805C* AMH81005C*
Amana® Brand 80% Modified Two-Stage Gas Furnace,
Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time.Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" model is low NOx. Chassis size is 24.5" wide. "CE" revision has a standard rated altitude of 5,500 ft.
Amana® Brand 80% Modified Two-Stage Gas Furnace
, New mode l n o men clature, fired at 23,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide.
Amana® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. "BA" revisions have a standard rated altitude of 4,500 ft.
Amana® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" 21, and 24.5" wide. "BB" revisions and AMH81205D*BA have a standard rated altitude of 5,500 ft
AMH8***BC
AMH80403A* AMH80603A* AMH80803B*
Amana® Brand 80% Modified Two-Stage Gas Furnace
, fired at 20,000 BTUH per burner. Upflow/Horizontal Left and Right installation, 33 3/8" tall, Two tone painted cabinet. Induced draft, Two stage gas Valve, I ntegrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC blower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" wide. "BC" revisions are equipped with a Broad Ocean motor.
7
PRODUCT IDENTIFICA TION
MODEL# MF G.# DESCRIPTION
ADSH80***AA
ADSH80***AB
ADSH800403AX* ADSH800603AX* ADSH800804CX* ADSH801005CX*
ADSH800403AX* ADSH800603AX*
Amana® Brand 80% Modified Two-Stage Gas Furnace
tall, Two tone painted cabinet. Induced draft, Two stage gas Val v e , Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC b lower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis sizes are 14", 17.5" and 21" wide. Standard rated altitude of 5,500 ft
Amana® Brand 80% Modified Two-Stage Gas Furnace,
tall, Two tone painted cabinet. Induced draft, Two stage gas Val v e , Integrated circuit board controlling 2nd stage gas valve by time. Left or right side gas entry. Stainless steel heat exchanger. PSC b lower motor. 115 volt silicon nitride igniter. "X" models are low NOx. Chassis size is 14" wide. Standard rated altitude of 5,500 ft. "AB" revisions are equipped with a Broad Ocean motor.
, Dedicated down flow installation, 33 3/8"
Dedicated down flow installation, 33 3/8"
8
PRODUCT IDENTIFICA TION
MODEL # MFG # DESCRIPTION
AFE18-60A
EFR01
FTK 04
HANG20
HANG21
N/A
P1221001
P1221002F
FTK04
N/A
N/A
Fossil Fuel Kit.
above/downstream of a gas or fossil fuel furnace when used with a heat pump. I t will operate with single and two stage heat pumps and single and two stage furnaces. The AFE18-60A control will turn the heat pump unit off when the furnace is turned on. An anti-short cycle feature initiates a 3 minute timed off delay when the compressor goes off.
External Filter Rack Kit
is intended to provide a location, external to the furnace casing, for installation of a permanent filter. The rack is mounted over the indoor air blower compartment area of either side panel, and provide filter retention as well as a location for attaching return air ductwork.
Furnace Twinning Kit
furnaces to operate at the same time from a single thermostat. The two furnaces to be "twinned" must be the exact same model with their circulating air blowers set to deliver the same air flow at the same time. This kit cannot be used to control more than two furnaces.
High Altitude Natural Gas Kit.
fired at 20,000 Btu's per cell for higher altitudes. This kit is required when installing these furnaces above their maximum rated altitude.
High Altitude Natural Gas Kit.
fired at 20,000 Btu's per cell for higher altitudes. This kit is required when installing these furnaces above their maximum rated altitude.
The AFE18-60A control is designed for use where the indoor coil is located
. For use with Goodman® and Amana® Brand upflow furnaces. This kit
. This kit allows Goodman® or Amana® Brand single stage 80% gas
The kit is designed to convert 80% gas furnace models
The kit is designed to convert 80% gas furnace models
HA02
N/A
High Altitude Natural Gas Kit.
furnace models fired at 22,500 BTU's per cell for higher altitudes. This kit is required when installing these furnaces above their maximum rated altitude. This kit contains # 43-49, 55-58 gas orifices. The orifices in the kit have been selected as a result of testing with the American Gas Association. The y will provide appropriate derating at the altitu de listed in the High Altitude Charts as shown in the installation instructions of the kit.
The kit is designed to convert Goodman®, Amana® Brand gas
9
PRODUCT IDENTIFICA TION
MODEL # MFG # DESCRIPTION
AFE18-60A
EFR01
FSRKA-14 FSRKA-17 FSRKA-21 FSRKA-24
FSRKG-14 FSRKG-17 FSRKG-21
FSRGA-24
FTK04
N/A
P1221001
P1221002F
"A " Width Cab.
"B" Width Cab "C" Width Cab "D" Width Cab
"A " Width Cab.
"B" Width Cab "C" Width Cab "D" Width Cab
FTK04
Fossil Fuel Kit.
The AFE18-60A control is designed for use where the indoor coil is located above/downstream of a gas or fossil fuel furnace when used with a heat pump. It will operate with single and two stage heat pumps and single and two stage furnaces. The AFE18-60A control will turn the heat pump unit off when the furnace is turned on. An anti-short cycle feature initiates a 3 minute timed off delay when the compressor goes off.
External Filter Rack Kit
. For use with Goodman® and Amana® Brand upflow furnaces. This kit is intended to provide a location, external to the furnace casing, for installation of a permanent filter. The rack is mounted over the indoor air blower compartment area of either side panel, and provide filter retention as well as a location for attaching return air ductwork.
Furnace Sound Reduction Kits.
For use with Amana® Brand 33" chassis, 80% furnaces.
When installed, these kits could help to reduce the sound level be apprximatley two decibels.
Furnace Sound Reduction Kits.
For use with Goodman® Brand 33" chassis, 80% furnaces.
When installed, these kits could help to reduce the sound level be apprximatley two decibels.
Furnace Twinning Kit
. This kit allows Goodman® or Amana® Brand single stage 80% gas furnaces to operate at the same time from a single thermostat. The two furnaces to be "twinned" must be the exact same model with their circulating air blowers set to deliver the same air flow at the same time. This kit cannot be used to control more than two furnaces.
HANG20
HANG21
HA02
N/A
N/A
N/A
High Altitude Natural Gas Kit.
The kit is designed to convert 80% gas furnace models fired at 20,000 Btu's per cell for higher altitudes. This kit is required when installing these furnaces above their maximum rated altitude.
High Altitude Natural Gas Kit.
The kit is designed to convert 80% gas furnace models fired at 20,000 Btu's per cell for higher altitudes. This kit is required when installing these furnaces above their maximum rated altitude.
High Altitude Natural Gas Kit.
The kit is designed to convert Goodman®, Amana® Brand gas furnace models fired at 22,500 BTU's per cell for higher altitudes. This kit is required when installing these furnaces above their maximum rated altitude. This kit contains # 43-49, 55-58 gas orifices. The orifices in the kit have been selected as a result of testing with the American Gas Association. They will provide appropriate derating at the altitude listed in the High A ltitude Charts as shown in the installation instructions of the kit.
10
ACCESSORIES
MODEL
NUMBER
EFR01
AFE180-60A
GOODM AN® BRAND "H" Model Fu rnace Accessories
HA02
SBT14
SBT17
SBT21
AMU / G M U
ASAS / GSAS
LPM-06
FTK04
LPLP02 LPLP03
HANG20
HANG21
MVK-01
MVK-02
FSRKG14
FSRKG17
FSRKG21
FSRKG24
Description
GMH80403A**
GMH80603A**
GMH80604B**
GMH80803B**
GMH80804B**
GMH80805C**
GMH81005C**
GMH81205D**
GMH81405DNC*
GDH80403A**
GDH80603A**
GDH80804B**
GDH81005C**
14"
Dual Fuel Bo ar d
EFR External Filter Rack
Media Ai r Cl ean ers
Downflow Subbase
Electro n i c Ai r Cl ean er
····
····
····
····
····
····
····
····
····
····
····
··· ·
··· ·
·
21"
17.5"
Downflow Subbase
not approved for this model
approved for this model
(1) W/R & HW 2 stg valve (2) BA REV 4,500 - 10,000 FT (excluding GMH81205D*BA) (3) BB REV 5,500 - 10,000 FT (4) AA Rev (5) GMH81205D*BA and GMH81405D*CD 5,500 FT - 10,000 FT
Propane Gas
Downflow Subbase
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Off Kit
Conversio n Ki t
Twinning Kit
LP Low P r essur e S h ut
··
··
··
··
··
··
··
··
···
··
··
··
··
W/Pressu r e S witch
High Al ti tu de O rifices
High Altitude Orifice Kit
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (5)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(5)
High Al ti tu de O rifices
Masonry Vent Ki t
W/Pressu r e S witch
·
·
·
·
·
·
·
Masonry Vent Ki t
Sound Reduction Kit
Sound Reduction Kit
Sound Reduction Kit
Sound Reduction Kit
(4)
(4)
(4)
(4)
(4)
(4)
(4)
·
(4)
··
11
ACCESSORIES
MODEL
NUMBER
EFR01
AFE180-60A
AMANA® BRAND "H" Model Furnace Accessories
HA02
SBT14
SBT17
SBT21
AMU / GMU
ASAS / GSAS
LPM-06
FTK04
LPLP02 LPLP03
MVK-01
HANG20
HANG21
MVK-02
FSRKA14
FSRKA17
FSRKA21
FSRKA24
Description
AMH80403A**
AMH80603A**
AMH80604B**
AMH80803B**
AMH80804B**
AMH80805C**
AMH81005C**
AMH81205D**
AMH81405DNC*
ADSH800403A**
ADSH800603A**
ADSH800804B**
ADSH801005C**
14"
Dual F u e l Board
EFR External Filter Rack
Media Ai r Cleane r s
Downflow Subbase
Electronic Air Cl eaner
····
····
····
····
····
····
····
····
····
····
····
··· ·
··· ·
·
21"
17.5"
Downflow Subbase
not approved for this model approved for this model (1) W/R & HW 2 stg valve (2) BA REV 4,500 - 10,000 FT (excluding GMH81205D*BA) (3) BB REV 5,500 - 10,000 FT
(4) AA Rev
(5) GMH81205D*BA 5,500 FT - 10,000 FT
Prop ane Gas
Downflow Subbase
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
(1)
Off Kit
Conversion Kit
Twinning Ki t
LP Low Pressure Shut
··
··
··
··
··
··
··
··
W/Pressure Switch
High Altitude Orifices
High Altitude Orifice Kit
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (2) (3)
(4) (5)
W/Pressure Switch
High Altitude Orifices
·····
·· ·
·· ·
·· ·
·· ·
Mason r y V e nt Ki t
Mason r y V e nt Ki t
Sound Reduction Kit
Sound Reduction Kit
Sound Reduction Kit
Sound Reduction Kit
·
·
·
·
·
·
·
(4)
(4)
(4)
(4)
(4)
(4)
(4)
·
(4)
12
ACCESSORIES
EXTERNAL FILTER RACK KIT
( EFR01 )
SLOTS IN FILTER CLEAR SCREWS
ON UNIT
UNIT SIDE
PANEL
BLOWER DECK
SCREWS
FRONT
OF UNIT
BASE
OF UNIT
RETURN AIR
CUTOUT AREA
LOWER EDGE
SCREW
EFR01 EXTERNAL FILTER RACK KIT
Used on 80% Upfl ow Model Furnaces
FILTER RACK ASSEMBLY
(FACE FILTER OPENING
TOWARDS FRONT
OF UNIT)
13
ACCESSOR Y WIRING DIAGRAMS
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
POWER SUPPLY INPUT
FURNACE DEMAND OUTPUT
BLOWER FAN DEMAND OUTPUT
POWER SUPPLY INPUT (COMMON)
SECOND STAGE FURNACE DEMAND OUTPUT
COMPRESSOR OUTPUT
SECOND STAGE COMPRESSOR OUTPUT
REVERSING VALVE OUTPUT
POWER SUPPLY OUT TO THERMOSTAT
CALL FOR REVERSING VALVE
CALL FOR COMPRESSOR
CALL FOR EMERGENCY HEAT
CALL FOR BLOWER FAN
CALL FOR FURNACE HEAT
POWER SUPPLY COMMON OUT TO THER MOSTAT
CALL FOR 2ND STAGE FURNACE HEAT
CALL FOR 2ND STAGE COMPRESSOR
POWER SUPPLY OUT TO HP CONTROL
HP CALL FOR FURNACE (DURING DEFROST)
REVERSING VALVE OUTPUT
COMPRESSOR CONTACTOR OUTPUT
POWER SUPPLY COMMON OUT TO HP C ON TR OL
ODT (OUTDOOR THERMOSTAT)
2ND STAGE C OMPRESSOR DEMAND OUTPUT
F U R N A C E
T H E R M O S T A T
H E A T
P U M P
R W1 G C W2 Y Y2 O
R O Y E G W1 C W2 Y2
R W2 O Y
C OT-NO OT-NC OT-C
Y2
P1-8
P1-7
P1-4
P1-6
P1-5
P1-2
P1-3
P1-1
P2-2
P2-1
P2-7
P2-8
P2-5
P2-9
P2-3
P2-4
P2-6
P3-9
P3-8
P3-7
P3-2
P3-6
P3-3
P3-1
P3-4
P3-5
24VAC
24VAC
F1
3A
C
C
24VAC
C
POWER SUPPLY
1.0K
6.8K
6.8K
+5VDC
E/W1
O
Y
+VDC +5VDC
+VDC
K1
K2
Q1
MICROPROCESSOR
24VAC
+VDC
K4
Q2
W1-FURN W2-HP
G-STAT
G-FURN
Y2-HP
Y2-STAT Y2-FURN
Y-STAT Y-FURN
Y-HP
K3
14
BREAK FOR ODT
1 2
ALL FUEL SYSTEM CONTROL BOARD - AFE18-60A
This wiring diagram is for reference only. Not all wiring is as shown above.
Refer to the appropriate wiring diagram for the unit being serviced.
(For use with Heat Pumps in conjunction with 80% or 90% Single-Stage or Two-Stage Furnaces)
ACCESSOR Y WIRING DIAGRAMS
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FURNACE TWINING KIT - FTK04 (UTEC Control Board)
This wiring diagram is for reference only. Not all wiring is as shown above.
Refer to the appropriate wiring diagram for the unit being serviced.
(For use only with 80% or 90% Single-Stage Furnaces)
15
OPERA TING INSTRUCTIONS
FOR Y OUR S AFETY READ BE FORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.
B. BEFORE OPERATING smell around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electric switch; do not use any telephone in your building. Immediately call your supplier from a neighbor's phone. Follow the gas suppliers instructions.
If you cannot reach your gas supplier,
call the fire department.
C. Use only your hand to move the gas control switch or knob. Never use tools. If the gas control switch or knob will not operate, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an automatic ignition system which automatically lights the burners. Do not try to light the burners by hand.
5. Remove control access panel.
6. Move the gas control switch or knob to "OFF ".
GAS CONTROL SWITCH SHOWN IN "ON" POSITION
7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP!above on this label. Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step.
8. Move the gas control switch or knob to "ON".
9. Replace control access panel.
10. Turn on all electric power to the appliance.
11. Set the thermostat to the desired setting.
12. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to its lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control access panel.
4. Move the gas control switch or knob to "OFF". Do not force.
5. Replace control access panel.
WARNING: Improper alteration, service or
maintenance can cause injury or property damage.
Refer to the user's information manual provided with this
consult a qualified or the gas supplier.
This furnace must be
instructions and local codes. In the absence of local codes, follow the National Fuel Gas
Code, ANSI Z223.1.
For indoor installation.
PGB & PGJ For outdoor installation only .
If notWARNING:
installed, operated and maintained in accordance with the manufacturer's instru ctions, this product could expose you to substances in fuel combustion which can cause death or serious illness and which are known to the State of California to cause cancer, birth defects or other reproductive harm. This product contains fiberglass insulation. Fiberglass insu la tion contains a chemical
California to cause cancer.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
16
0140F00001P
OPERA TING INSTRUCTIONS
CONSIGNES DE SECURITE - LIRE
AVANT D'ALLUMER L'APP AREIL
AVERTISSEMENT: Le non-respect des inst r uct i ons qui suivent peut
^
entrainer un r i sque d'incendi e ou d'explosion causant des dommages, des blessures ou la mort.
A. Cet appareil comporte pas de veilleuse. Il est muni d'un mecanisme qui allume automatiquement le bruleur. N
B. Sentir tout autour de l'appariel AVANT D'ALLUMER afin de deceler toute fuite de gaz. Assurez-vous de sentir tout pres du plancher car certains gaz sont plus lourds que l'air et se deposeront sur le plancher.
SI VOUS SENTEZ UNE ODEUR DE GAZ: Ne tentez d'allumer aucun appariel.
Ne touchez pas aux interrupteurs elec triques; n'utiliser aucun telephone dans l'edifice ou vous vous trouvez. Appelez immediatement votre fournisseur de gaz en utilisant le telephone d'un voisin et suivez les instructions du fournisseur. Appelez les pompiers si vous ne parvenez pas a rejoindre votre fournisseur de gaz.
C. N'utiliser que votre main pour pousser ou tourner le commande du gaz. N'utilisez jamais d'outils. Si vous ne parvenez pas a pousser ou a tourner la commande, ne tentez pas de la reparer; appelez un reparateur qualifie. Forcer la commande ou essayer de la reparer peut entrainer un risque d'incendie ou d'explosion.
D. N'utilisez pas cet appareil si l'une de ses parties a ete dans l'eau. Si cela se produit, demandez immediatement a un reparateur qualifie d'insp ecter l'appareil et de remplacer toute piece du systeme de controle et toute commande de gaz ayant ete dans l'eau.
^^
'allumez paz le bruleur manuellement.
^
^
0140F00002P
1. UN INSTANT! Lisez d'abord les consignes
INSTRUCTIONS DE SERVICE
de s e cu rite ci-des su s.
2. Reglez le thermostat a son point le plus bas.
3. Coupez l'alimentation electrique de l'appareil.
4. Cet appareil est muni d'un mecanisme qui allume automatiquement le bruleur. Ne tentez pas d'allumer le bruleur manuellement.
5. Retirez le panneau d'acces de la commande.
6. Mettez la commande de gaz a la position
^
ARRET ("OFF").
7. Attendez cinq (5) minutes afin de permettre a tout gaz present d'etre evacue. Si vous sentez une odeur de gaz a ce moment, ARRETEZ! et suivez les consignes de securit e donnees au paragraphe B ci-dessus. Si vous ne sentez pas de gaz, passez a l'etape suivante.
8. Mettez la commande de gaz a la position MARCHE ("ON").
9. Remettez la panneau d'acces de la commande en place.
10. Retablissez l'alimenation electrique de l'appareil.
11. Reglez le thermost at a le temperature desiree.
12. Si l'appareil ne fonctionne pas, suivez les instructions intitulees "Arret du gaz" et appelez un reparateur qualifie ou votre fourniss eur de gaz.
1. Reglez le thermostat a son point le plus bas.
2. Coupez l'alimentation electrique de l'appareil si vous devez effectuer un entretien.
3. Retirez le panneau d'acces de la commande.
4. Mettez la commande de gaz a la position ARRET ("OFF").
5. Remettez le panneau d'acces de la commande en place.
^
^
^
^
^
^
ARRET DU GAZ
^
Commande de gaz en position
"MARCHE"
17
OPERA TING INSTRUCTIONS
A
O
R
T
I
G
B
N
N
U
M
A
O
"
/
N
S
A
G
T
E
L
N
I
E
E
V
R
I
R
A
Z
A
U
D
G
M L
N
I
M
G
A
L
N
U
A
A
R
E
V
E
H
S
O
O
"
P
S
"
N
O
Z
E
A
,
L
N
O
E
E
P
A
S
W
S
"
E
R
H
C
N
18
PRODUCT DESIGN
Safety
Please adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or oper­ating the furnace.
WARNING
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERATI ON, SERV ICE OR MAINTENANCE, R EFER TO THI S MANUAL. QUALIFIED INSTALLE R, SERVICE AGENCY OR THE GAS SUPPLIER.
OR ADDITIONAL ASSISTANCE OR INFORMATION, CONSULT A
F
WARNING
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
T
MAY CAUSE SERI OUS ILLNESS OR DEATH AN D WHICH ARE KNOWN TO THE
S
TATE OF CALIFORNIA TO CAUSE CANCER, BI RTH DEFECTS OR OTHER
REPRODUCTIVE HARM.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
DUE TO ELECTRICAL SHOCK, THE FURNACE MUST BE LOC ATED TO PROTECT THE ELEC TRICA L COMPON ENTS FROM WA TER.
Charge (ESD) Precautions NOTE: Discharge body’s static electricity before touch-
ing unit. An electrostatic discharge can adversely affect electrical components.
Use the following precautions during furnace installa­tion and servicing to protect the integrated control mod­ule from damage. By putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure is ap­plicable to both installed and uninstalled (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s elec­trostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the furnace near the control. Any tools held in a person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wir­ing following the discharge process in Step 2. Use caution not to recharge your body with static elec­tricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat Step 2 before touching control or wires.
4. Discharge any static electricity from your body to ground before removing a new control from its con­tainer. Follow Steps 1 through 3 if installing the con-
trol on a furnace. Return any old or new controls to their containers before touching any ungrounded ob­ject.
Product Application
This product is designed for use as a residential home gas furnace. It is not designed or certified for use in mobile home, trailer, or recreational vehicle applica­tions.
This furnace can be used in the following non-industrial commercial applications: Schools, Office buildings, Churches,
Retail stores, Nursing homes, Hotels/motels, Common or office areas. In such applications, the furnace must be installed
with the
Goodman® & Amana
installation instructions.
®
Brand 80% furnaces are ETL certi­fied appliances and are appropriate for use with natural or propane gas. (NOTE: If using propane gas, a propane conversion kit is required).
IMPORTANT NOTE: The 80% furnace cannot be in­stalled as a direct vent (i.e.., sealed combustion) fur­nace. The burner box is present only to help reduce sound transmission from the burners to the occupied space.
To ensure proper installation, operation and servicing, thoroughly read the installation and service manuals for specifics pertaining to the installation, servicing and application of this product.
WARNING
OSSIBLE PROPERTY D AMAGE, PERSONAL INJ URY OR DEATH DUE TO FIRE,
P
EXPLOSION, SMOKE, S OOT, CONDENSTAION, E LECTRICAL SHOCK OR C ARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION, RE PAIR, OPERATI ON, OR MAINTENANCE OF THI S PRODUCT.
WARNING
T
O PREVENT PROPERTY DAMAGE, PERSONAL INJ URY OR DEATH D UE TO FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR RECREATIONAL VEHICLE.
To ensure proper furnace operation, install, operate, maintain and service the furnace in accordance with the installation, operation and service instructions, all lo­cal building codes and ordinances. In their absence, fol­low the latest edition of the National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or CAN/CGA B149 Installa­tion Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI
Z223.1) can be obtained from any of the following:
American National Standards Institute 25 West 43rd Street, 4th Floor New York, NY 10036
19
PRODUCT DESIGN
National Fire Protection Association 1 Batterymarch Park Quincy, MA 02269-7471
CSA International 8501 East Pleasant Valley Cleveland, OH 44131
A copy of the CAN/CGA B149 Installation Codes can be obtained from:
CSA International 178 Rexdale Boulevard Etobicoke, Ontario, Canada M9W, 1R3
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Contractors of America.
Location Requirements and Considerations
WARNING
O PREVENT POSSIBLE E QUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FOLLOWING BULLET P OINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.
Follow the instructions listed below when selecting a furnace location. Refer also to the guidelines provided in the Combustion and Ventilation Air Requirements sec­tion in this manual or the installation instructions for details.
Centrally locate the furnace with respect to the proposed or existing air distribution system.
Ensure the temperature of the return air entering the furnace is between 55°F and 100°F when the furnace is heating.
If the furnace is installed in an application where the typical operating sound level of a furnace is deemed objectionable, an optional sound reduc­tion kit is available. Consult your local distribu­tor for more details.
Provide provisions for venting combustion prod­ucts outdoors through a proper venting system. Special consideration should be given to vent/flue pipe routing and combustion air intake pipe when applicable.
80% Furnaces: All installations must be vented in accordance with National Fuel Gas Code, NFPA 54/ ANSI Z223.1 - lateset edition. In Canada the fur­naces must be vented in accordance with the Na­tional Standard of Canada, CAN/CGA B149.
Ensure upflow or horizontal furnaces are not in­stalled directly on carpeting, or any other com­bustible material. The only combustible material allowed is wood.
A special accessory subbase must be used for up­right counterflow unit installations over any com­bustible material (including wood). Refer to sub­base instructions for installation details. (NOTE: A subbase will not be required if an air condition­ing coil is located beneath the furnace between the supply air opening and the combustible floor.
Exposure to contaminated combustion air will re­sult in safety and performance-related problems. Do not install the furnace where the combustion air is exposed to the following substances:
chlorinated waxes or cleaners chlorine-based swimming pool chemicals water softening chemicals deicing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions (such as perchloroethylene) printing inks paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials
Seal off a non-direct vent furnace if it is installed near an area frequently contaminated by any of the above substances. This protects the non-di- rect vent furnace from airborne contaminants. To ensure that the enclosed non-direct vent furnace has an adequate supply of combustion air, vent from a nearby uncontaminated room or from out­doors. Refer to the Combustion and Ventilation Air Requirements section in this manual or the in­stallation instructions for details.
If the furnace is used in connection with a cooling unit, install the furnace upstream or in parallel with the cooling unit coil. Premature heat ex­changer failure will result if the cooling unit coil is placed ahead of the furnace.
If the furnace is installed in a residential garage, position the furnace so that the burners and igni­tion source are located not less than 18 inches (457 mm) above the floor. Protect the furnace from physical damage by vehicles.
20