Amana AMH80403ANBA, AMH80403ANBB, AMH80403AXBA, AMH80403AXBB, AMH80603ANBA Installation Manual

...
INSTALLATION INSTRUCTIONS FOR
TABLE OF CONTENTS
*M(H,S)8 / GD(H,S)8 / GHS8 / GME8 ADS(H,S)8 / AMEH8 G
(CA TEGOR Y I )
These furnaces comply with requirements embodied in the American National Standard / National Standard of Canada ANSI Z21.47·CSA-2.3 Gas Fired Central Furnaces.
ATTENTION INST ALLING PER SONNEL
As a professional installer, you have an obligation to know the product better than the customer. This includes all safety pre­cautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warn­ings. Often during installation or repair, it is possible to place yourself in a position which is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific, good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION
NOTE: Please contact your distributor or our website listed below for the applicable Specification Sheet referred to in this manual.
AS FURNACE
Installer: Affix all manuals
adjacent to the unit.
PRODUCT APPLICATION............................................................5
LOCA TION REQUIREMENTS AND CONSIDERATIONS .................. 6
COMBUSTION AND VENTILA TION AIR REQUIREMENTS............. 8
CA TEGORY I VENTING (VERTICAL VENTING) ..............................9
EXTERIOR MASONRY CHIMNEYS
ELECTRICAL CONNECTIONS.....................................................14
GAS SUPPL Y AND PIPING ........................................................16
Safety Considerations......................................................3
Additional Safety Considerations ....................................4
Shipping Inspection .......................................................... 4
Electrostatic Discharge (ESD) Precautions ....................... 5
To The Installer..................................................................5
Clearances and Accessibility ...........................................7
Installation Positions .......................................................7
Horizontal Installation .....................................................7
Furnace Suspension .......................................................... 8
Existing Furnace Removal.................................................8
Thermostat Location .........................................................8
(CA TEGORY I FURNACES ONL Y) .........................................10
Checklist Summary ..........................................................10
Check 1 - Proper chimney termination ..........................11
Check 2 - Any solid or liquid fuel appliances
vented into this chimney channel ..............................11
Check 3 - Chimney Crown Condition...............................12
Check 4 - Debris in Cleanout...........................................1 2
Check 5 - Liner Condition. ...............................................12
Check 6 - Dilution Air . .....................................................12
Check 7 - Complete the Installation................................12
Fix 1 - Liner Termination .................................................13
Fix 2 -Change Venting Arr angemen t s ..............................13
Fix 3 - Rebuild the Crown ................................................13
Fix 4 - Relining ................................................................13
Wiring Harness ............................................................... 14
115 Volt Line Connections ..............................................14
Fossil Fuel Applications .................................................14
Junction Box Relocation .................................................1 4
24 Volt Thermostat W iring .............................................15
GME8 & AMEH8 Furnaces
with 2-Stage Condenser Field Wiring ........................1 5
Setting the Heat Anticipator............................................16
115 Volt Line Connection of Accessories ........................16
Electronic Air Cleaner .....................................................16
24 Vac Humidifier ...........................................................16
High Altitude Derate........................................................17
Propane Gas Conversion ................................................17
Gas Piping Connections..................................................17
Upflow Installations .......................................................18
Counterflow Installations ..............................................18
Gas Piping Checks...........................................................18
Propane Gas Tanks and Piping.......................................19
IO-446C 11/2015
5151 San Felipe Suite 500 • Houston, TX 77056
www.goodmanmfg.com • www .amana-hac.com
© 2011 - 2015 Goodman Manufacturing Company, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
CIRCULA TING AIR AND FILTERS ...............................................20
Ductwork - Air Flow.........................................................20
Filters - Read This Section Before
Installing The Return Air Ductwork ................................20
Upright Installations ......................................................20
Circulation Air Filters .....................................................20
Horizontal Installations .................................................21
SEQUENCE OF OPERA TION
(INTEGRA TED IGNITION CONTROL)..................................... 21
Power Up .........................................................................21
Heating Mode ..................................................................22
(Mode DIP switch is set to “1 STG” position) .................22
(Mode DIP Switch is set to “2 STG” position) .................22
Cooling Mode ..................................................................22
Fan Only Mode................................................................22
ST ART -UP PROCEDURE AND ADJUS TMENT ..............................23
Furnace Operation..........................................................23
Furnace Start-up .............................................................23
Furnace Shutdown ..........................................................23
Gas Supply Pressure Measurement................................23
Gas Manifold Pressure Measurement and Adjustment.2 5
Gas Input Rate Measurement (Natural Gas Only)..........27
T empera ture Rise.............................................................27
Circulator Blower Speed Adjustment..............................27
Circulator Blower Fan T iming Adjustment .....................28
Setting Furnace Operating Mode
(GDH8, GME8, *MH8, AMEH8 & ADSH8 models only) 28
OPERA TIONAL CHECKS............................................................28
Checking Duct Static .......................................................28
Burner Flame...................................................................29
SAFETY CIRCUIT DESCRIPTION................................................ 29
General............................................................................29
Integrated Control Module .............................................29
Primary Limit ...................................................................29
Auxiliary Limit .................................................................29
Rollout Limits ..................................................................29
Pressure Switches ...........................................................29
Flame Sensor...................................................................30
TROUBLESHOOTING ...............................................................30
Electrostatic Discharge (ESD) Precautions .....................30
Diagnostic Chart .............................................................30
Fault Recall .....................................................................30
(Furnaces equipped with
PCBBF132 Control Board only) ...................................30
Resetting From Lockout ...................................................30
MAINTENANCE........................................................................30
Annual inspection ...........................................................30
Filters ..............................................................................31
Filter Maintenance..........................................................31
Filter Removal .................................................................31
Induced Draft and Circulator Blower Motors ................31
Flame Sensor (Qualified Servicer Only) .........................31
Igniter (Qualified Servicer Only) ....................................31
Burners............................................................................31
CLEANING (QUALIFIED SERVICER ONL Y)..................................31
BEFORE LEA VING AN INST ALLA TION ........................................32
REP AIR AND REPLACEMENT PARTS..........................................32
Component ID..................................................................33
APPENDIX D TROUBLESHOOTING CHART ...............................34
PCBBF134 & PCBBF132 CONTROL BOARDS .................34
BLOWER PERFORMANCE DA T A ...............................................37
*M(H/S)8 .........................................................................37
GDS8/ADSS8 ....................................................................38
GHS8 ................................................................................38
GDH8 / ADSH8 .................................................................39
GME8 ...............................................................................40
AMEH8.............................................................................41
*(M, D, H)S8 / ADSS8 Wiring Diagram ..................................42
GME8 / AMEH8 Wiring Diagram ...........................................43
Honeywell Gas Valve .......................................................4 3
*(M,D)H8 / ADSH8 Wiring Diagram ......................................44
Honeywell Gas Valve .......................................................4 4
2
W ARN ING
G
OODMAN
DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES
F YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME
I
RESPONSIBI LITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH MAY RESULT INSTALL OR SERVICE HEATING AND AIR CONDITIONING EQU IPMENT
S
AFETY
Adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the furnace. To ensure proper installation and operation, thoroughly read this manual for specifics pertaining to the installation and application of this product.
This furnace is manufactured for use with natural gas. It may be field converte d to oper a t e on L.P. gas by using the appropriate L.P. conversion kit liste d in the LATIONS section of this manual
Install this furnace only in a location and position as specified in
LOCATION REQUIREMENTS & CONSIDERATIONS section and INSTAL­LATION POSITIONS section of this manual.
Provide adequate combustion and ventilation air to the furnace as specified in COMBUSTION & VENTILATION AIR REQUIREMENTS
section of this manual.
Combustion products must be discharged to the outdoors. Con­nect this furnace to an approved vent system only, as specified in CATEGORY 1 VENTING section of this manual.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in GAS SUPPLY AND PIPING section of this manual.
Always install a furnace to operate within the furnace’s intended temperature-rise range with a duct system which has external static pressure within the allowable range, as specified on the furnace rating plate and OPERATIONAL CHECKS section of these instructions.
When a furnace is installed so that supply ducts carry air circu­lated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
A gas-fired furnace for installation in a residential garage must be installed as specified in the LOCATION REQUIREMENTS AND
CONSIDERATIONS section of this manual.
WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY
. M
ANY JURISD ICTIONS REQ UIRE A LICENSE TO
C
ONSIDERA TIONS
PROPANE GAS/HIGH ALTITUDE INSTAL-
.
.
WARNING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERA TI ON, SERVICE OR MAINTENANCE REFER TO THIS MANUAL INFORMATIO N, CONSULT A QUALIFIED INSTALLER, SERVICER AGENCY OR THE GAS SUPPLIER
. FOR
ADDITIONAL ASSISTANCE OR
.
WARNING
IF
THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESU LT CAUSING PROPERTY DAMAGE
,
PERSONAL INJURY OR LOSS OF LIFE
DO
NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE
.
.
WHAT TO DO IF YOU SMELL GAS:
D
O NOT TRY TO LIGHT ANY APPLIANCE
D
O NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE
IN YOUR BUILDING
I
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S
PHONE
. F
I
F YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE
DEPARTMENT
I
NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED
INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER
.
OLLOW THE GAS SUPPLIER’S INSTRUCTIONS
.
.
.
.
WARNING
T
HIS PRODUCT CONTAI NS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIV E HARM
.
WARNING
H
EATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE ROUT INE, INSPECTION, MAINTENANCE AND SUPERVISION BUILDING IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VACAN T CARE SHOULD BE TAKEN THAT SUCH DEVICE IS ROUT INELY INSPECTED MAINTAINED AND MONITORED. IN THE EVENT THAT THE BUILDING MAYBE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACAN T ALL WATER-BEARING PIPES SHOULD BE DRAINED, THE BUILDING SHOULD BE PROPERLY WINTERIZED, AND THE WATER SOURCE CLOSED. IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACAN T, ANY HYDRONIC COIL UNITS SHOULD BE DRAINED AS WELL AND, IN SUCH CASE, ALTERNATIVE HEAT SOURCES SHOULD BE UTILIZED
.
. IF
THE
,
,
,
,
WARNING
TO
PREVENT POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, THE FURNACE MUST BE LOCATED TO PROTECT THE ELECTRICAL COMPONENTS FROM WATER
.
,
This furnace may be used as a construction site heater only if certain conditions are met. These conditions are listed in the PROD- UCT APPLICATION section of this manual.
3
Advertenci a e spe cia l p ara la instalación de calent adores ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
RISQUE D'E MPO ISO N NEM EN T AU
MONOXYDE DE CARBONE
Las emis ion es de monóxido de carbono pue de n c irc ular a través del aparat o c uando se opera en cualquier modo.
CO can cause serious illness including permanent brain damag e or death.
B10259-216
El monóx i do de carbono puede causar e nfermedades se ve ras como daño cerebral permanente ó muerte.
WARN ING
S
HOULD OVERHEAT ING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY
.
WARN ING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, EXPLOSION, SMOKE, SOOT, COND E NSATION, ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION, OR MAINTENANCE OF THIS PRODUCT
.
WARN ING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE REFER TO THIS MANUAL INFORMATIO N, CONSULT A QUALIFIED INSTALLER, SERVICER AGENCY OR THE GAS SUPPLIER
. FOR
ADDITIONAL ASSISTANCE OR
.
WARN ING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION, THIS FURNACE MUST BE CATEGORY
ATEGORY
C P
ROVIS IONS MUST BE MADE FOR VENTI NG COMBUSTION PRODUCTS OUTDOORS THROUGH A PROPER VENTI NG SYSTEM FLUE PIPE COUL D BE A LIMITING FACTOR IN LOCATING THE FURNACE
III
VENTI NG
I
VENTED
. DO
NOT VENT USING
.
. THE
LENGTH OF
ADDITIONAL SAFETY CONSIDERATIONS
This furnace is approved for Category I Venting only.
Provisions must be made for venting combustion products outdoors through a proper venting system. The length of flue pipe could be a limiting factor in locating the furnace.
Cett e v entilation es t nécessaire po ur év iter le danger d ' intoxication au CO pouvant survenir si un appareil produisant du monoxyde de carbon e continue de fonctionne r au sei n de la zone confi né e .
B10259-216
Le monoxyde de des
dommages permanents au cerveau et meme la mort.
carbone peut causer des maladies graves telles que
B10259-216
SHIPPING INSPECTION
All units are securely packed in shipping containers tested ac-
,
cording to International Safe Transit Association specifications. The carton must be checked upon arrival for external damage. If damage is found, a request for inspection by carrier’s agent must be made in writing immediately.
.
The furnace must be carefully inspected on arrival for damage and bolts or screws which may have come loose in transit. In the event of damage the consignee should:
,
1. Make a notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notified as soon as possible - preferably within five days.
,
4. File the claim with the following support documents within a nine month statute of limitations.
Original or certified copy of the Bill of Lading, or indemnity bond.
Original paid freight bill or indemnity in lieu thereof.
Original or certified copy of the invoice, showing trade and other discounts or reductions.
Copy of the inspection report issued by carrier’s represen tative at the time damage is reported to carrier.
The carrier is responsible for making prompt inspection of dam­age and for a thorough investigation of each claim. The distribu­tor or manufacturer will not accept claims from dealers for trans­portation damage.
Keep this literature in a safe place for future reference.
4
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge body’ s st atic electricity bef or e touching unit. An
electrostatic discharge can adversely affect electrical components. Use the following precautions during furnace installation and ser-
vicing to protect the integrated control module from damage. By putting the furnace, the control, and the person at the same elec­trostatic potential, these steps will help avoid exposing the inte­grated control module to electrostatic discharge. This procedure is applicable to both installed and non-installed (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the furnaces near the control. Any tools held in a person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
TO THE INSTALLER
Before installing this unit, please read this manual thoroughly to familiarize yourself with specific items which must be adhered to, including but not limited to: unit maximum external static pres­sure, gas pressures, BTU input rating, proper electrical connec­tions, circulating air temperature rise, minimum or maximum CFM, and motor speed connections, and venting. These furnaces are designed for Category I venting only.
WARN ING
TO
PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR RECREATIONAL VEHICL E
P
RODUCT APPLICA TION
This furnace is primarily designed for residential home-heating applications. It is NOT designed or certified for use in mobile homes, trailers or recreational vehicles. Neither is it designed or certified for outdoor applications. The furnace must be installed indoors (i.e., attic space, crawl space, or garage area provided the garage area is enclosed with an operating door).
This furnace can be used in the following non-industrial commer­cial applications:
Schools, Office buildings, Churches, Retail stores,
Nursing homes, Hotels/motels, Common or office areas
.
In such applications , the furnace must be installed with the fol­lowing stipulations:
It must be installed per the installation instructions provided and per local and national codes.
It must be installed indoors in a building constructed on site.
It must be part of a ducted system and not used in a free air delivery application.
It must not be used as a “make-up” air unit.
All other warranty exclusions and restrictions apply.
This furnace may be used as a construction sit e he a ter ONLY if the following conditions are met:
The vent system is permanently installed per these installation instructions.
A room thermostat is used to control the furnace. Fixed jumpers that provide continuous heating CANNOT be used and can cause long term equipment damage. Bi-metal thermostats, or any thermostat affected by vibration must not be used during construction.
Return air ducts are provided and sealed to the furnace.
A return air temperature range between 60ºF (16ºC) and 80ºF (27ºC) is maintained.
Air filters are installed in the system and replaced daily during construction and upon completion of construction.
The input rate and temperature rise are set per the furnace rating plate.
100% outside air must be used for combustion during construction. Temporary ducting may be used to supply outside air to the furnace for combustion – do not connect this duct directly to the furnace. Size this duct according to NFPA 54/ANSI Z223.1 section for Combustion and Ventilation Air.
The furnace heat exchanger, components, duct system, air filters and evaporator coils are thoroughly cleaned following final construction clean up by a qualified person.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) are verified by a qualified person according to these installation instructions.
Furnace doors must be in place on the furnace while the furnace is operating in any mode.
Damage or repairs due to failure to comply with these require­ments are not cov ere d under the w arr an ty.
NOTE: The Commonwealth of Massachusetts requires that the following additional requirements must also be met:
Gas furnaces must be installed by a licensed plumber or gas fitter.
A T-handle gas cock must be used.
If the unit is to be installed in an attic, the passageway to and the service area around the unit must have flooring.
5
WARN ING
TO
PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR RECREATIONAL VEHICL E
.
WARNING
TO
PREVENT POSSIBLE EQUIPM EN T DAMAGE, PROPERTY DAMAGE PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THIS UNIT
.
,
T o ensure proper furnace oper ation, install, opera te and maintain the furnace in accordance with these installation and operation instructions, all local building codes and ordinances. In their ab-
sence, follow the lates t edition of the National Fuel Gas Code (NFP A 54/ANSI Z223.1), and/or CAN/CSA B149 Installation Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFP A 54/ANSI Z223.1) can be obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New Y ork, NY 10036
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in ac­cordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Contractors of America.
In the USA, this furnace MUST be installed in accordance with the latest edition of the ANSI Z223.1 booklet entitled “National Fuel Gas Code” (NFPA 54), and the requirements or codes of the local utility or other authority having jurisdiction. Additional helpful publications available from the NFPA are, NFPA 90A - Installation of Air Conditioning and Ventilating System and NFPA 90B - Warm Air Heating and Air Conditioning System.
All venting shall be in accordance with the National Fuel Gas Code, ANSI Z223.1, or applicable local building and/or air condi­tioning codes.
NOTE: Furnaces with NOx screens meet the California NOx emis­sion standards and California seasonal efficiency standards. AN­NUAL inspections of the furnace and its vent system is strongly recommended.
L
OCATION REQUI
REMENTS AND CONSIDERATIONS
Your unit model type determines which installation procedures must be used. For *MH8, *MS8, and GHS8 models, you must follow instructions for Horizontal Left, Horizontal Right or Upflow instal­lations only. These furnaces are not approved for Downflow in­stallations. Downflow models GD(H,S) ARE NOT APPRO VED FOR HORIZONT AL OR UPFLOW INSTALLATIONS. For these models, use only the in­structions for downflow installation only.
Follow the instructions listed below when selecting a furnace lo­cation. Refer also to the guidelines provided in Combustion and
Ven tilation Air Requirements.
Centrally locate the furnace with respect to the proposed or existing air distribution system.
Ensure the temperature of the return air entering the furnace is between 55°F and 100°F when the furnace is heating.
If the furnace is installed in an application where the typical operating sound level of a furnace is deemed objectionable, an optional sound reduction kit is available. Consult your local distributor for more details.
Provisions must be made for venting combustion products outdoors through a proper venting system. The length of flue pipe could be a limiting factor in locating the furnace.
Ensure adequate combustion air is available for the furnace. Improper or insufficient combustion air can expose building occupants to gas combustion products that could include carbon monoxide. Refer to Combustion
and Vent ilation Air Requirements.
The furnace must be level. If the furnace is to be set on a floor that may become wet or damp at times, the furnace should be supported above the floor on a concrete base sized approximately 1-1/2" larger than the base of the furnace.
Ensure upflow or horizontal furnaces are not installed directly on carpeting, or any other combustible material. The only combustible material allowed is wood.
Exposure to contaminated combustion air will result in safety and performance-related problems. Do not install the furnace where the combustion air is exposed to the following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
If the furnace is used in connection with a cooling unit, install the furnace upstream or in parallel with the cooling unit coil. Premature heat exchanger failure will result if the cooling unit coil is placed ahead of the furnace.
6
For vertical (upflow or downflow) applications, the
V
minimum cooling coil width shall not be less than furnace width minus 1”. Additionally, a coil installed above an upflow furnace or under a counterflow furnace may be the same width as the furnace or may be one size larger than the furnace. Example: a “C” width coil may be installed with a “B” width furnace.
For upflow applications, the front of the coil and furnace must face the same direction.
If the furnace is installed in a residential garage, position the furnace so that the burners and ignition source are located not less than 18 inche s (457 mm) abov e the floor. Protect the furnace from physical damage by vehicles.
If the furnace is installed horizon t ally, the furnace access doors must be vertical so that the burners fire horizontally into the heat exchanger. Do not install the unit with the access doors on the “up/top” or “down/bottom” side of the furnace.
Do not connect this furnace to a chimney flue that serves a separate appliance designed to burn solid fuel.
For counterflow installations, the air conditioning coil must be downstream from the heat exchanger of the furnace.
Counterflow installation over a noncombustible floor. Before setting the furnace over the plenum opening, ensure the surface around the opening is smooth and level. A tight seal should be made between the furnace base and floor by using a silicon rubber caulking compound or cement grout.
Counterflow installation over a combustible floor. If installation over a combustible floor become s necessary, use an accessory subbase (see Specification Sheet applicable to your model for details). A special accessory subbase must be used for upright counterflow unit installations over any combustible material including wood. Follow the instructions with the subbase for proper installations. Do not install the furnace directly on carpeting, tile, or other combustible material other than wood flooring. (NOTE: The subbase will not be required if an air conditioning coil is installed between the supply air opening on the furnace and the floor.
ent Pipe Clearance to Combustibles­6" using Single Wall Connector or 1" using B-1 vent.
Top - 1"
Back - 0"
Adequate combustion/ventilation air must be supplied to the closet.
Furnace must be completely sealed to floor or base. Combustion/ ventilation air supply pipes must terminate 12" from top of closet and 12" from floor of closet. DO NOT remove solid base plate for side return.
Return air ducts must be completely sealed to the furnace and terminate outside the enclosure surfaces.
CLEARANCES AND ACCESSIBILITY
Unobstructed front clearance of 24" for servicing is recommended.
VENT
B1-VENT SINGLE
1" 6" 1" 3" 0" 1"
Top clearance for horizontal configuration - 1"
SIDES FRONT BACK
INSTALLATION POSITIONS
An upflow furnace may be installed in an upright position or hori­zontal on either the left or right side panel. Do not install this furnace on its back. For vertically installed upflow furnaces, re­turn air ductwork may be attached to the side panel(s) and/or basepan. For horizontally installed upflow furnaces, return air ductwork must be attached to the basepan. For counterflow fur- naces, return ductwork must be attached to the top end of the blower compartment.
NOTE: Ductwork must never be attached to the back of the furnace.
HORIZONTAL INSTALLATION
horizontal installations,
For
insert the
#8 x 5/8 screw
from the
literature package.
TOP
(PLENUM)
Side Clearance - 1"
Line contact to framing is permitted when installed in the horizon­tal configuration. Line contact is defined as the portion of the cabinet that is formed by the intersection of the top and side. ACCESSIBILITY CLEARANCE, WHERE GREA TER, SHOULD T AKE PRECE ­DENCE OVER MINIMUM FIRE PROTECTION CLEARANCE. A gas-fired furnace for installation in a residential garage must be installed
Front Clearance - 3"
7
so that the ignition source and burners are located not less than eighteen inches (18") above the floor and is protected or located to prevent physical damage by vehicles. A gas furnace must not be installed directly on carpeting, tile, or other combustible materi­als other than wood flooring.
FURNACE SUSPENSION
If suspending the furnace from rafters or joist, use 3/8" threaded rod and 2”x2”x3/8” angle iron as shown below. The length of rod will depend on the application and the clearances necessary.
Suspended Furnace
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting system
serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the Ameri-
can National Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI Z21.47-Latest Edition, CSA-2.3-Latest Edi­tion Section 1.23.1. The following steps shall be followed with
each appliance connected to the venting system placed in opera­tion, while any other appliances connected to the venting system are not in operation:
a. Seal any unused openings in the venting system; b. Inspect the venting system for proper size and horizontal
pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the CAN/CSA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition;
c. In so far as practical, close all building doors and
windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers;
d. Follow the lighting instructions. Place the appliance being
inspected in operation. Adjust thermostat so appliance shall operate continuously;
e. Test for draft hood equipped appliance spillage at the
draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle;
f. After it has been determined that each appliance
connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use;
g. If improper venting is observed during any of the above
tests, the common venting system must be corrected.
Corrections must be in accordance with the latest edition of the National Fuel Gas Code NFP A 54/ANSI Z223.1 and/or CAN/CSA B149 Installation Codes.
If resizing is required on any portion of the venting system, use the appropriate table in the latest edition of the National Fuel Gas Code ANSI Z223.1 and/or CAN/CSA B149 Installation Codes.
THERMOSTAT LOCATION
In an area having good air circulation, locate the thermostat about five feet high on a vibration-free inside wall. Do not install the thermostat where it may be influenced by any of the following:
Drafts, or dead spots behind doors, in corners, or under cabinets.
Hot or cold air from registers.
Radiant heat from the sun.
Light fixtures or other appliances.
Radiant heat from a fireplace.
Concealed hot or cold water pipes, or chimneys.
Unconditioned areas behind the thermostat, such as an outside wall.
Consult the instructions packaged with the thermostat for mount­ing instructions and further precautions.
C
OMBUSTION AND VENTILA TION AIR REQUIREMENTS
WARN ING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH SUFFICIEN T FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF FLUE GASES MUST BE SUPPLIED SUPPLIED INTO THE FURNACE AREA
. M
OST HOMES REQUIRE OUTSIDE AIR BE
.
Improved construction and additional insulation in buildings have reduced heat loss by reducing air infiltration and escape around doors and windows. These changes have helped in reducing heat­ing/cooling costs but have created a problem supplying combus­tion and ventilation air for gas fired and other fuel burning appli­ances. Appliances that pull air out of the house (clothes dryers, exhaust fans, fireplaces, etc.) increase the problem by starving appliances for air.
House depressurization can cause back drafting or improper com­bustion of gas-fired appliances, thereby exposing building occu­pants to gas combustion products that could include carbon mon­oxide.
,
8
If this furnace is to be installed in the same space with other gas appliances, such as a water heater, ensure there is an adequate supply of combustion and ventilation air for all appliances. Refer to the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 or CAN/CSA B149 Installation Codes or applicable provi­sions of the local building codes for determining the combustion air requirements for the appliances.
This furnace must use indoor air for combustion. It cannot be in­stalled as a direct vent (i.e., sealed combustion) furnace.
Most homes will require outside air be supplied to the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces.
C
ATEGORY
I V
ENTING
(V
ERTICAL VENTING
)
WARN ING
TO
PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION, THIS FURNACE MUST BE CATEGORY VENT USING CATEGORY
III
VENTI NG
.
I
VENTED
. DO
NOT
Category I V enting is venting a t a non-positive pre ssure. A furnace vented as Category I is considered a fan-assisted appliance and the vent syst em does not have to be “ ga s tight. ” NOTE: Single st age gas furnaces with induced draft blowers draw products of com­bustion through a heat exchanger allowing, in some instances, common venting with natural draft appliances (i.e. water heat­ers). All installations must be vented in accordance with National Fuel Gas Code NFP A 54/ANSI Z223.1 - lat est e dition. In Cana da, the furnaces must be vented in accordance with the National Stan­dard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest edi­tions and amendments.
NOTE: Masonry vent kit (MVK-01 and MVK-02) is to only be used on interior masonry chimneys or qualifying exterior masonry chimney applications identified in the MVK kit installation instructions. To ensure safe and reliable operation, use only the kit listed for your model.
Kit Inp ut KBTU Range L imit Sett i ng
MVK-01 40-100 250°F MVK-02 120-140 290°F
This kit is for use on Amana
Note :
33” tall “H” and “S” model furnaces installed in the upflow position only.
®
brand and Goodman® brand 80% AF UE,
NOTE: The vertical height of the Category I venting system must be at least as great as the horizontal length of the venting system.
WARNING
TO
PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION, COMMON VENTI NG WITH OTHER MANUFACTURER’S INDUCED DRAFT APPLIANCES IS NOT ALLOWED
.
The minimum vent diameter for the Category I venting system is as shown:
MODEL
40 4 Inch 4 Inch 60 4 Inch 4 Inch
80 4 Inch 4 Inch 100 5 Inch 5 Inch 120 5 Inch N/A 140 5 Inch N/A
UPFLOW COUNTERFLOW
MINIMUM VENT
Under some conditions, larger vents than those shown above may be required or allowed. When an existing furnace is removed from a venting system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
Upflow or Horizontal units are shipped with the induced draft blower discharging from the top of the furnace. (“T op” is as viewed for an upflow installation.) The induced draft blower can be ro­tated 90 degrees with the (0270F01119) chimney transition bot­tom kit for Category I venting. For upflow models installed verti­cally or horizontally, a four inch single wall pipe can be used to extend the induced draft blower outlet 1/2” beyond the furnace cabinet. THIS PRODUCT IS NOT DESIGNED FOR COUNTERCLOCK-
WISE INDUCED DRAFT BLOWER ROT A TION.
Vent the furnace in accordance with the National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition.
Venting - F urnace Installed in Horiz ont al Position
THIS FURNACE IS NOT DESIGN CERTIFIED TO BE HORIZONTALLY VENTED THROUGH AN EXTERIOR SIDE W ALL.
The following describes an optional venting procedure when the furnace is installed in the horizontal left discharge position.
To rotate the induced draft blower clockwise, you will need to purchase one (0270F01119) chimney transition bottom kit.
1. Disconnect electrical power from the furnace.
2. Disconnect the induced draft blower power leads, flue pipe, and pressure switch tubing.
3. Remove the round cutout fr om the right side of the wrapper.
4. Remove and save the four screws that fasten the induced draft blower to the flue collector box.
5. Remove and save the three screws that hold the chimney assembly to the induced draft blower.
6. Remove and save the four screws that fasten the chimney top to the chimney bottom.
9
7. Remove the chimney transition bottom from the transition bottom kit.
8. Install the chimney top with the four screws retained from step 6 onto the new chimney transition bottom from the transition bottom kit.
9. Remove the induced draft blower and install the new chimney assembly to it using the three screws retained from step 5.
10. Rotate the induced draft blower 90 degrees to the right, feed the flue pipe through the round cutout from the outside of the wrapper, and fit onto the chimney top assembly. Secure the pipe to the chimney top from the front, top, and bottom using (3) screws and rotating the induced draft blower to properly orient the assembly. NOTE: If the pipe section is less than 18” , then att ach it directly to the chimney top on 3 sides and feed it through the round cutout from the inside of the wrapper.
11. Reattach the induced draft blower using the (4) screws retained from step 3. Ensure the gasket located between the induced draft blower and collector box is rotated accordingly.
12. Reconnect the induced draft blower power leads. NOTE: If the wires are not long enough, pull extra wire from the wire bundle in the blower compartment.
13. Reconnect the remaining flue pipe, and the pressure switch tubing. Ensure that all wires and the pressure switch tubing is at least one inch from the flue pipe, or any other hot surface.
14. Restore power to furnace.
NOTE: In a horizontal installation the air conditioning coil must be adequately supported by proper brackets and supports. Inadequate coil support can result in furnace cabinet distortion and air leakage.
Counterflow units are shipped with the induced draft blower dis­charging from the top of the furnace. (“T op” a s viewed for a coun­terflow installation.)
Vent the furnace in accordance with the National Fuel Gas Code NFPA54/ANSI Z223.1-latest edition.
WARNING
P
OSSIBILITY OF PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DAMAGING COND ENSATION CAN OCCUR INSIDE MASONRY CHIMNEYS WHEN A SINGLE FAN-ASSISTED CATEGORY FURNACE) IS VENTED WITHOUT ADEQUATE DILUTION AIR CONNECT AN FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPED APPLIANCE OR THE CHIMNEY IS LINED WITH A METAL LINER OR TYPE METAL VENT SIZED IN ACCORDANCE WITH THE APPROPRIATE VENTI NG TABLES
80%
APPLIANCE, THE POTENTIAL FOR COND E NSATION DAMAGE MAY STILL EXIST WITH EXTREMELY COLD CONDITION S, LONG VENT CONNECTORS EXTERIOR CHIMNEYS, OR ANY COMBIN ATIO N OF THESE CONDITIONS
HE RISK OF COND ENSATION DAMAGE IS BEST AVOIDED BY USING
T
MASONRY CHIMNEY AS A PATHWAY FOR PROPERLY SIZED METAL LINER OR TYPE
80%
FURNACE TO A MASONRY CHIMNEY UNLESS THE
. ALL
INSTALLATIONS USING MASONRY CHIMNEYS MUST BE
FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPE D
B
METAL VENT
Clean Out
Typical Multiple Flue Clay Tile Chimney
Throat
Damper
Breech
.
Clay Tile Size: 8" x 8" x12 "
I
APPLIANCE
Wash
(Each x 24" Length)
1/2" to 1" Air Space
F.A .F. Vent Connector
Fan Assisted Forced Air Furnace
Roof Line
Attic Floor
Second Floor
First Floor
Water Heater Vent Connector
Natural Draft Water Heater
Basement Floor
(80% AFUE
. DO
NOT
CHECKLIST SUMMARY
B
. IF AN
,
.
WARN ING
N
EVER ALLOW THE PRODUCTS OF COMBUSTION, INCLUDING CARBON MONOXIDE, TO ENTER THE RETURN DUCTWORK OR CIRCULATION AIR SUPPLY
.
EXTERIOR MASONRY CHIMNEYS (CATE GORY I FURNACES ONL Y)
An exterior masonry chimney is defined as a “Masonry” chimney exposed to the outdoors on one or more side s below the roof line. ” The ability to use a clay lined masonry chimney depends on a parameter not associated with interior chimneys. This variable is the geographic location of the installation. Researchers have dis­covered that the winter design temperatures have a direct impact on the suitability of this type of venting. In most situations, the existing masonry chimneys will require a properly sized metallic liner.
This checklist serves as a summary of the items to be checked before venting an 80+ furnace into a masonry chimney. In addi­tion, we recommend that a qualified serviceman use this checklist to perform a yearly inspection of the furnace venting system.
This checklist is only a summary. For detailed information on each of the procedures mentioned, see the paragraph referenced with each item.
10
Proper Chimney
Termination?
(Check 1)
If the chimney does not meet these termination requirements, but all other requirements in the checklist can be met, it may be pos­sible for a mason to extend the chimney. If this will not be practi­cal, see Fix 1.
10' or Less
Chimney channel
free of solid and
liquid fuel
appliances?
(Check 2)
Crown in good
condition
(Check 3)
Cleanout free of
debris?
(Check 4)
Liner in good
condition?
(Check 5)
Change venting
arrangements
(Fix 2)
Rebuild crown
(Fix 3)
and/or Reline
(Fix 4)
Reline (Fix 4)
Reline (Fix 4)
2' Min.
Termination 10 Feet Or Less From Ridge, Wall or Parapet
2' Min.
Wall o r Parapet
Chimney
10' or Less
2' Min.
Chimney
More than 10’
3' Min.
3' Min.
3’ Min.
Dilution air available?
(Check 6)
Reline (Fix 4)
Complete the
installation.
(Check 7)
CHECK 1 - PROPER CHIMNEY TERMINATION.
A masonry chimney used as a vent for gas fired equipment must extend at least three feet above the highest point where it passes through the roof. It must extend at least two feet higher than any portion of a building within a horizontal distance of 10 feet. In addition, the chimney must terminate at least 3 feet above any forced air inlet located within 10 feet. The chimney must extend at least five feet above the highest connected equipment draft hood outlet or flue collar.
NOTE:
No Height
above parapet
Wall or Parapet
Ridge
Termination More Than 10 Feet From Ridge, Wall or Parapet
required when distance from walls or parapet is more than 10 feet.
More than 10’
Chimney
10’
2” Min.
Chimney
Height above any roof surface within 10 feet horizontally.
3’ Min.
CHECK 2 - ANY SOLID OR LIQUID FUEL APPLIANCES VENTED INTO THIS
CHIMNEY
Solid fuel appliances include fireplaces, wood stoves, coal fur­naces, and incinerators.
Liquid fuel appliances include oil furnaces, oil-fired boilers and oil-fired water heaters.
CHANNEL
11
Appliances which burn propane (sometimes referred to as LP (liq­uefied petroleum)) gas are considered gas-fired appliances.
CHECK 3 - CHIMNEY CROWN CONDITION.
Damage from condensate usually shows up first in the crown. If any of the following trouble signs are present, the condition of the crown is not satisfactory:
a) Crown leaning b) Bricks missing c) Mortar missing d) T ile liner cracked e) No tile liner f) Salt staining at mortar joints. (White stains, and mortar
becomes sandy and/or erodes.)
For problems a, b, or c, see Fix 3. If problems d, e, or f are present, see Fix 4. IMPORT ANT : It may be nece ssary to follow both Fix 3 and Fix 4.
CHECK 4 - DEBRIS IN CLEANOUT
A cleanout (dropleg) must be present such that the upper edge of the cleanout cover is at least 12 inches below the lower edge of the lowest chimney inlet opening.
A chimney without a cleanout could become partially blocked by debris. If no cleanout is present, the chimney must be relined (Fix
4). Remove the cleanout cover, and examine the cleanout for de­bris. If significant amounts of any of the following are found:
Fuel oil residue
Bricks
Mortar or sand
Pieces of the tile liner
Rusted pieces of the metallic liner - reline the chimney (Fix 4).
CHECK 5 - LINER CONDITION.
If a metal liner is present, it must be checked. It cannot be as­sumed that all existing metal liners are correctly installed and in good condition.
Remove the lowe st existing ven t connector , and e xamine the inside of the elbow or tee at the base of the liner. A small amount of soot may be considered acceptable, provided the installer vacuums it away. If rusted pieces of the liner have collected here, the metal liner must be removed and replaced (Fix 4).
Next, gently tap the inside of the liner with a Phillips screwdriver. If the screwdriver perforates the liner, or if the tapping does not sound like metal hitting metal, the liner must be removed and replaced (Fix 4).
Remember that all appliances must be vented inside the liner. Venting one appliance inside the liner and another appliance out­side the liner is not acceptable.
Next, use a flashlight and small mirror to sight up the liner. B vent must be supported so as to not come into direct contact with the chimney walls or tile liner. If it is not, it can probably be rehung so as to be acceptable. A thimble or fire stop may be helpful here.
Flexible liners should be hung straight or nearly straight. If it is spiraled in the chimney and in good condition, it should be rehung. To do this, break the top seal; pull up and cut off the excess liner length, and refit the top seal. Use caution when doing this, as the cut edges of flexible liners may be sharp.
The surfaces of the liner must be physically sound. If gaps or holes are present, the metal liner must be removed and replaced (Fix 4). Finally, confirm that the metal liner is the correct size for the appliances to be installed. Use the GAMA tables and rules.
If a metal liner is not present, a clay tile liner must be present, or the chimney must be lined (Fix 4).
Use a flashlight and small mirror at the cleanout or vent connec­tor to inspect the clay tile liner. If any of the following problems are present:
T ile sections misaligned
T ile sections missing
Gaps between tile sections
Signs of condensate drainage at the cleanout or vent connectors
Mortar protruding from between tile sections
Use of sewer pipe or drainage pipe rather than an approved fire clay tile reline the chimney (Fix 4).
Next, measure the size of the liner. It may be possible to do this from the cleanout. The liner must be at least as large as the mini­mum size established by the tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments. If the liner is too small or too large, then the chimney must be relined (Fix 4).
CHECK 6 - DILUTION AIR.
If gas-fired appliances are to be vented into a clay tile liner, a source of dilution air is required.
Dilution air cannot be obtained through:
Induced draft appliances
Natural draft appliances with vent dampers
Sufficient dilution air can ordinarily be obtained through the draft hood of a natural draft appliance only if the appliance’s vent connector does not include a vent damper. If dilution air wi ll not be available, the chimney must be relined (Fix 4).
CHECK 7 - COMPLETE THE INSTALLATION.
If Checks 1 through 6 have been satisfactory, and the liner is an acceptable size as determined by the tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments, then the clay tile liner can probably be used as a vent for the gas appliances. However, the installer must keep in mind the following factors which may render the tile liner unsuitable for use as a vent:
12
Extremely cold weather
Long vent connectors
Masonry chimneys with no air gap between the liner and the bricks. (In practice, this can be difficult to detect.)
Exterior chimneys (The tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2
- latest editions and amendments assume interior chimneys.)
If, in the judgment of the local gas utility, installer, and/or local codes; one or more of the above factors is likely to present a problem, the chimney must be relined (Fix 4).
FIX 1 - LINER TERMINATION
Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use. The liner and cap/roof as­sembly must then terminate above the roof in accordance with the manufacturer’s instructions.
In some cases, a shorter extension above the roof may be possible with a liner than would be required with a masonry chimney.
For further information on relining, see Fix 4.
FIX 2 -CHANGE VENTING ARRANGEMENTS
If the masonry chimney has more than one channel, it may be possible to vent the gas appliances into one channel and vent the solid or liquid fuel appliance(s) into another channel(s). Do not vent an 80+ Furnace inside of a metal liner with other appliances vented outside the liner.
Alternatively, the homeowner may agree to discontinue use of the fireplace (solid fuel appliance). If so, the tile liner must be cleaned to remove creosote buildup. The fireplace opening must then be permanently sealed.
If oil-fired appliance(s) are being replaced by gas-fired appliance(s), the tile liner must first be cleaned to remove the fuel oil residue.
If none of the above options is practical, the furnace may need to be vented vertically with a B Vent.
Under some conditions, a 90%+ furnace could be installed rather than an 80% furnace. The 90%+ furnace can be vented horizontally or vertically through PVC pipe.
FIX 3 - REBUILD THE CROWN
If the chimney crown is damaged, a qualified mason must repair it in accordance with nationally recognized building codes or stan­dards. One such standard which may be referenced is the Stan­dard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Ap­pliances, ANSI/NFPA 211.
FIX 4 - RELINING
Relining options include B vent and flexible liners. If the chimney has diagonal offsets, B vent probably cannot be
used.
If B vent is to be used, it must be supported adequately. Supports (such as fire stops or thimbles) must be used to prevent the B vent from coming into direct contact with the tile liner or chimney walls. Direct contact would result in higher heat loss, with an increased possibility of poor venting system performance.
It is not acceptable to vent one appliance inside the B vent and other appliances outside. The excess space between the B vent and the chimney walls must be covered at the top of the chimney by a weatherproof, corrosion resistant flashing.
The B vent should then be topped with a listed vent cap. The listed vent cap will, when installed per the manufacturer ’s instructions, prevent problems due to rain, birds, or wind effects.
A B-vent installed as described in this section is considered to be an enclosed vent system, and the sizing tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments may be used.
If a flexible liner is to be used, it must be made of the proper materials:
For most residential applications, an aluminum liner should be acceptable.
If the combustion air supplied to the furnace will be contaminated with compounds containing chlorine or fluorine, a liner of AL 29-4C stainless steel should be used. Common sources of chlorine and fluorine compounds include indoor swimming pools and chlorine bleaches, paint strippers, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/fluorine compounds.
Heavier gauge 300 and 400 series stainless steel liners were developed for use with oil or solid fuel appliances. They are not suitable for use with gas-fired appliances. Flexible liners specifically intended and tested for gas applications are listed in the UL “Gas and Oil Equipment Directory”. (UL Standard 1777).
For sizing of flexible liners, see the tables in the National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments.
To install the liner, read and follow the liner manufacturer’s in­structions and your local codes. Excess liner length should be pulled out of the chimney and cut off . U se caution when doing this, as the cut edges of flexible liners may be sharp. Do not spiral excess liner inside of the chimney. Support the liner as recom­mended by the liner manufacturer.
Some manufacturers of flexible liners offer an insulation sleeve designed to be added to the liner before it is installed in the chim­ney. (Poured insulation, either vermiculite or other materials, is no longer recommended.) Insulation will need to be added to the flexible liner if:
It is required by the liner manufacturer’s instructions.
13
The previous liner was properly sized and installed, and suffered from condensation damage.
It is required by your local building codes.
Even if none of those three conditions exist which require addi­tional liner insulation, the installer may wish to consider it if:
The local climate is very cold.
The chimney is very tall.
The vent connectors used are very long or have a large number of elbows.
Local experience indicates that flexible liners installed without insulation are likely to have condensation problems.
Insulation must be selected and installed in accordance with the liner manufacturer’s instructions.
Finally, cap the chimney and terminate the liner in accordance with the liner manufacturer’s instructions.
E
LECTRICAL CONNECTIONS
115 VOLT LINE CONNECTIONS
Before proceeding with electrical connections, ensure that the sup­ply voltage, frequency, and phase correspond to that specified on the unit rating plate. Power supply to the furnace must be NEC Class 1, and must comply with all applicable codes. The furnace must be electrically grounded in accordance with local codes or, in their absence, with the latest edition of The National Electric Code, ANSI NFP A 70 and/ or The Canadian Electric Code CSA C22.1.
Use a separate fused branch electrical circuit containing properly sized wire, and fuse or circuit breaker. The fuse or circuit breaker must be sized in accordance with the maximum overcurrent pro­tection specified on the unit rating plate. An electrical disconnect must be provided at the furnace location.
Line voltage wiring must enter into the junction box provided with the furnace.
NOTE: Line polarity must be observed when making field connections.
FOSSIL FUEL APPLICATIONS
WARN ING
HIGH VOLTAGE !
TO
AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO
THE UNIT MUST BE POLARIZED AND GROUNDED
.
WARN ING
HIGH VOLTAGE !
TO
AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING
.
CAUTION
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS OPERATION
. W
IRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
. V
ERIFY PROPER OPERATION AFTER SERVICING
WARN ING
HIGH VOLTAGE !
TO
AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR DEATH, THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE, WITH THE LATEST EDITION OF THE
N
ATIONAL ELECTRIC CODE
.
This furnace can be used in conjunction with a heat pump in a fossil fuel application. A fossil fuel application refers to a com­bined gas furnace and heat pump installation which uses an out­door temperature sensor to determine the most cost efficient means of heating heat pump or gas furnace.
A heat pump thermostat with two stages of heat is required to properly use a furnace in conjunction with a heat pump. Refer to the fossil fuel kit installation instructions for additional thermo­stat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit installa­tion instructions. All furnace connections must be made to the furnace integrated control module and the FURNACE terminal strip on the fossil fuel control board.
JUNCTION BOX RELOCATION
.
E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
Line voltage connections can be made through either the right or left side panel. The furnace is shipped configured for a right side electrical connection. To make electrical connections through the opposite side of the furnace, the junction box must be relocated to the left side prior to making electrical connections. To relocate the junction box, perform the following steps.
WARNING
.
. USE
GLOVES AS A
WIRING HARNESS
The wiring harness is an integral part of this furnace. Field alter­ation to comply with electrical codes should not be r equired. Wires are color coded for identification purposes. Refer to the wiring diagram for wire routings. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C. Any re­placement wiring must be a copper conductor.
WARNING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK DISCONNECT ELECTRICAL POWER BEFORE INSTALLING OR SERVICING THIS UNIT
.
1. Remove both doors from the furnace.
2. Remove and save the screws holding the junction box to the right side of the furnace.
14
,
Loading...
+ 30 hidden pages