These furnaces comply with requirements embodied in
the American National Standard / National Standard of
Canada ANSI Z21.47·CSA-2.3 Gas Fired Central Furnaces.
ATTENTION INST ALLING PER SONNEL
As a professional installer, you have an obligation to know the
product better than the customer. This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with
this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair, it is possible to place
yourself in a position which is more hazardous than when the
unit is in operation.
Remember, it is your responsibility to install the product safely
and to know it well enough to be able to instruct a customer in
its safe use.
Safety is a matter of common sense...a matter of thinking before
acting. Most dealers have a list of specific, good safety
practices...follow them.
The precautions listed in this Installation Manual are intended
as supplemental to existing practices. However, if there is a
direct conflict between existing practices and the content of
this manual, the precautions listed here take precedence.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION
NOTE: Please contact your distributor or our website listed
below for the applicable Specification Sheet referred to in this
manual.
Honeywell Gas Valve .......................................................4 4
2
W ARN ING
G
OODMAN
DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES
F YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME
I
RESPONSIBI LITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE
WHICH MAY RESULT
INSTALL OR SERVICE HEATING AND AIR CONDITIONING EQU IPMENT
S
AFETY
Adhere to the following warnings and cautions when installing,
adjusting, altering, servicing, or operating the furnace. To ensure
proper installation and operation, thoroughly read this manual
for specifics pertaining to the installation and application of this
product.
This furnace is manufactured for use with natural gas. It may be
field converte d to oper a t e on L.P. gas by using the appropriate L.P.
conversion kit liste d in the
LATIONS section of this manual
Install this furnace only in a location and position as specified in
LOCATION REQUIREMENTS & CONSIDERATIONS section and INSTALLATION POSITIONS section of this manual.
Provide adequate combustion and ventilation air to the furnace
as specified in COMBUSTION & VENTILATION AIR REQUIREMENTS
section of this manual.
Combustion products must be discharged to the outdoors. Connect this furnace to an approved vent system only, as specified in
CATEGORY 1 VENTING section of this manual.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections, as specified in GAS SUPPLY ANDPIPING section of this manual.
Always install a furnace to operate within the furnace’s intended
temperature-rise range with a duct system which has external
static pressure within the allowable range, as specified on the
furnace rating plate and OPERATIONAL CHECKS section of these
instructions.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to
the furnace casing and terminating outside the space containing
the furnace.
A gas-fired furnace for installation in a residential garage must
be installed as specified in the LOCATION REQUIREMENTS AND
CONSIDERATIONS section of this manual.
WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY
. M
ANY JURISD ICTIONS REQ UIRE A LICENSE TO
C
ONSIDERA TIONS
PROPANE GAS/HIGH ALTITUDE INSTAL-
.
.
WARNING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER
INSTALLATION, ADJUSTMENT, ALTERA TI ON, SERVICE OR MAINTENANCE
REFER TO THIS MANUAL
INFORMATIO N, CONSULT A QUALIFIED INSTALLER, SERVICER AGENCY OR
THE GAS SUPPLIER
. FOR
ADDITIONAL ASSISTANCE OR
.
WARNING
IF
THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION MAY RESU LT CAUSING PROPERTY
DAMAGE
,
PERSONAL INJURY OR LOSS OF LIFE
DO
NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE
.
.
WHAT TO DO IF YOU SMELL GAS:
D
O NOT TRY TO LIGHT ANY APPLIANCE
D
O NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE
IN YOUR BUILDING
I
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S
PHONE
. F
I
F YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE
DEPARTMENT
I
NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED
INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER
.
OLLOW THE GAS SUPPLIER’S INSTRUCTIONS
.
.
.
.
WARNING
T
HIS PRODUCT CONTAI NS OR PRODUCES A CHEMICAL OR CHEMICALS
WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE
KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH
DEFECTS OR OTHER REPRODUCTIV E HARM
.
WARNING
H
EATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE
ROUT INE, INSPECTION, MAINTENANCE AND SUPERVISION
BUILDING IN WHICH ANY SUCH DEVICE IS LOCATED WILL BE VACAN T
CARE SHOULD BE TAKEN THAT SUCH DEVICE IS ROUT INELY INSPECTED
MAINTAINED AND MONITORED. IN THE EVENT THAT THE BUILDING
MAYBE EXPOSED TO FREEZING TEMPERATURES AND WILL BE VACAN T
ALL WATER-BEARING PIPES SHOULD BE DRAINED, THE BUILDING SHOULD
BE PROPERLY WINTERIZED, AND THE WATER SOURCE CLOSED. IN THE
EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING
TEMPERATURES AND WILL BE VACAN T, ANY HYDRONIC COIL UNITS
SHOULD BE DRAINED AS WELL AND, IN SUCH CASE, ALTERNATIVE HEAT
SOURCES SHOULD BE UTILIZED
.
. IF
THE
,
,
,
,
WARNING
TO
PREVENT POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH DUE TO ELECTRICAL SHOCK, THE FURNACE MUST BE LOCATED TO
PROTECT THE ELECTRICAL COMPONENTS FROM WATER
.
,
This furnace may be used as a construction site heater only if
certain conditions are met. These conditions are listed in the PROD-UCT APPLICATIONsection of this manual.
3
Advertenci a e spe cia l p ara la instalación de calent adores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
RISQUE D'E MPO ISO N NEM EN T AU
MONOXYDE DE CARBONE
Las emis ion es de monóxido de carbono pue de n c irc ular a través
del aparat o c uando se opera en cualquier modo.
CO can cause serious illness including permanent brain
damag e or death.
B10259-216
El monóx i do de carbono puede causar e nfermedades se ve ras
como daño cerebral permanente ó muerte.
WARN ING
S
HOULD OVERHEAT ING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF
TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE
FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY
.
WARN ING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO
FIRE, EXPLOSION, SMOKE, SOOT, COND E NSATION, ELECTRICAL SHOCK
OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION
REPAIR OPERATION, OR MAINTENANCE OF THIS PRODUCT
.
WARN ING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER
INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE
REFER TO THIS MANUAL
INFORMATIO N, CONSULT A QUALIFIED INSTALLER, SERVICER AGENCY OR
THE GAS SUPPLIER
. FOR
ADDITIONAL ASSISTANCE OR
.
WARN ING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION, THIS
FURNACE MUST BE CATEGORY
ATEGORY
C
P
ROVIS IONS MUST BE MADE FOR VENTI NG COMBUSTION PRODUCTS
OUTDOORS THROUGH A PROPER VENTI NG SYSTEM
FLUE PIPE COUL D BE A LIMITING FACTOR IN LOCATING THE FURNACE
III
VENTI NG
I
VENTED
. DO
NOT VENT USING
.
. THE
LENGTH OF
ADDITIONAL SAFETY CONSIDERATIONS
•This furnace is approved for Category I Venting only.
•Provisions must be made for venting combustion
products outdoors through a proper venting system. The
length of flue pipe could be a limiting factor in locating
the furnace.
Cett e v entilation es t nécessaire po ur év iter le danger d ' intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbon e continue de fonctionne r au sei n de la zone confi né e .
B10259-216
Le monoxyde de
des
dommages permanents au cerveau et meme la mort.
carbone peut causer des maladies graves telles que
B10259-216
SHIPPING INSPECTION
All units are securely packed in shipping containers tested ac-
,
cording to International Safe Transit Association specifications.
The carton must be checked upon arrival for external damage. If
damage is found, a request for inspection by carrier’s agent must
be made in writing immediately.
.
The furnace must be carefully inspected on arrival for damage
and bolts or screws which may have come loose in transit. In the
event of damage the consignee should:
,
1. Make a notation on delivery receipt of any visible damage
to shipment or container.
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notified as soon
as possible - preferably within five days.
,
4. File the claim with the following support documents within
a nine month statute of limitations.
•Original or certified copy of the Bill of Lading, or
indemnity bond.
•Original paid freight bill or indemnity in lieu thereof.
•Original or certified copy of the invoice, showing trade
and other discounts or reductions.
•Copy of the inspection report issued by carrier’s
represen tative at the time damage is reported to carrier.
The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
Keep this literature in a safe place for future reference.
4
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge body’ s st atic electricity bef or e touching unit. An
electrostatic discharge can adversely affect electrical components.
Use the following precautions during furnace installation and ser-
vicing to protect the integrated control module from damage. By
putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure
is applicable to both installed and non-installed (ungrounded)
furnaces.
1. Disconnect all power to the furnace. Do not touch the
integrated control module or any wire connected to the
control prior to discharging your body’s electrostatic
charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnaces near the control. Any tools held in a person’s
hand during grounding will be discharged.
3. Service integrated control module or connecting wiring
following the discharge process in step 2. Use caution not
to recharge your body with static electricity; (i.e., do not
move or shuffle your feet, do not touch ungrounded objects,
etc.). If you come in contact with an ungrounded object,
repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new
control from its container. Follow steps 1 through 3 if
installing the control on a furnace. Return any old or new
controls to their containers before touching any ungrounded
object.
TO THE INSTALLER
Before installing this unit, please read this manual thoroughly to
familiarize yourself with specific items which must be adhered to,
including but not limited to: unit maximum external static pressure, gas pressures, BTU input rating, proper electrical connections, circulating air temperature rise, minimum or maximum CFM,
and motor speed connections, and venting. These furnaces are
designed for Category I venting only.
WARN ING
TO
PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO
FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR
RECREATIONAL VEHICL E
P
RODUCT APPLICA TION
This furnace is primarily designed for residential home-heating
applications. It is NOT designed or certified for use in mobile
homes, trailers or recreational vehicles. Neither is it designed or
certified for outdoor applications. The furnace must be installed
indoors (i.e., attic space, crawl space, or garage area provided the
garage area is enclosed with an operating door).
This furnace can be used in the following non-industrial commercial applications:
Nursing homes, Hotels/motels, Common or office areas
.
In such applications , the furnace must be installed with the following stipulations:
•It must be installed per the installation instructions
provided and per local and national codes.
•It must be installed indoors in a building constructed on
site.
•It must be part of a ducted system and not used in a free
air delivery application.
•It must not be used as a “make-up” air unit.
•All other warranty exclusions and restrictions apply.
This furnace may be used as a construction sit e he a ter ONLY if the
following conditions are met:
•The vent system is permanently installed per these
installation instructions.
•A room thermostat is used to control the furnace. Fixed
jumpers that provide continuous heating CANNOT be used
and can cause long term equipment damage. Bi-metal
thermostats, or any thermostat affected by vibration must
not be used during construction.
•Return air ducts are provided and sealed to the furnace.
•A return air temperature range between 60ºF (16ºC) and
80ºF (27ºC) is maintained.
•Air filters are installed in the system and replaced daily
during construction and upon completion of
construction.
•The input rate and temperature rise are set per the furnace
rating plate.
•100% outside air must be used for combustion during
construction. Temporary ducting may be used to supply
outside air to the furnace for combustion – do not connect
this duct directly to the furnace. Size this duct according
to NFPA 54/ANSI Z223.1 section for Combustion and
Ventilation Air.
•The furnace heat exchanger, components, duct system,
air filters and evaporator coils are thoroughly cleaned
following final construction clean up by a qualified
person.
•All furnace operating conditions (including ignition,
input rate, temperature rise and venting) are verified by
a qualified person according to these installation
instructions.
•Furnace doors must be in place on the furnace while the
furnace is operating in any mode.
Damage or repairs due to failure to comply with these requirements are not cov ere d under the w arr an ty.
NOTE: The Commonwealth of Massachusetts requires that the
following additional requirements must also be met:
•Gas furnaces must be installed by a licensed plumber or
gas fitter.
•A T-handle gas cock must be used.
•If the unit is to be installed in an attic, the passageway to
and the service area around the unit must have flooring.
5
WARN ING
TO
PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO
FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR
RECREATIONAL VEHICL E
.
WARNING
TO
PREVENT POSSIBLE EQUIPM EN T DAMAGE, PROPERTY DAMAGE
PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE
OBSERVED WHEN INSTALLING THIS UNIT
.
,
T o ensure proper furnace oper ation, install, opera te and maintain
the furnace in accordance with these installation and operation
instructions, all local building codes and ordinances. In their ab-
sence, follow the lates t edition of the National Fuel Gas Code (NFP A
54/ANSI Z223.1), and/or CAN/CSA B149 Installation Codes, local
plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFP A 54/ANSI Z223.1) can be
obtained from any of the following:
American National Standards Institute
25 West 43rd Street, 4th Floor
New Y ork, NY 10036
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
The rated heating capacity of the furnace should be greater than
or equal to the total heat loss of the area to be heated. The total
heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations”
published by the Air Conditioning Contractors of America.
In the USA, this furnace MUST be installed in accordance with the
latest edition of the ANSI Z223.1 booklet entitled “National Fuel
Gas Code” (NFPA 54), and the requirements or codes of the local
utility or other authority having jurisdiction. Additional helpful
publications available from the NFPA are, NFPA 90A - Installation
of Air Conditioning and Ventilating System and NFPA 90B - Warm
Air Heating and Air Conditioning System.
All venting shall be in accordance with the National Fuel Gas
Code, ANSI Z223.1, or applicable local building and/or air conditioning codes.
NOTE: Furnaces with NOx screens meet the California NOx emission standards and California seasonal efficiency standards. ANNUAL inspections of the furnace and its vent system is strongly
recommended.
L
OCATION REQUI
REMENTSAND CONSIDERATIONS
Your unit model type determines which installation procedures
must be used. For *MH8, *MS8, and GHS8 models, you must follow
instructions for Horizontal Left, Horizontal Right or Upflow installations only. These furnaces are not approved for Downflow installations.
Downflow models GD(H,S) ARE NOT APPRO VED FOR HORIZONT ALOR UPFLOW INSTALLATIONS. For these models, use only the instructions for downflow installation only.
Follow the instructions listed below when selecting a furnace location. Refer also to the guidelines provided in Combustion and
Ven tilation Air Requirements.
•Centrally locate the furnace with respect to the proposed
or existing air distribution system.
•Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace is
heating.
•If the furnace is installed in an application where the
typical operating sound level of a furnace is deemed
objectionable, an optional sound reduction kit is
available. Consult your local distributor for more details.
•Provisions must be made for venting combustion
products outdoors through a proper venting system. The
length of flue pipe could be a limiting factor in locating
the furnace.
•Ensure adequate combustion air is available for the
furnace. Improper or insufficient combustion air can
expose building occupants to gas combustion products
that could include carbon monoxide. Refer to Combustion
and Vent ilation Air Requirements.
•The furnace must be level. If the furnace is to be set on a
floor that may become wet or damp at times, the furnace
should be supported above the floor on a concrete base
sized approximately 1-1/2" larger than the base of the
furnace.
•Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible material.
The only combustible material allowed is wood.
•Exposure to contaminated combustion air will result in
safety and performance-related problems. Do not install
the furnace where the combustion air is exposed to the
following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
•If the furnace is used in connection with a cooling unit,
install the furnace upstream or in parallel with the
cooling unit coil. Premature heat exchanger failure will
result if the cooling unit coil is placed ahead of the
furnace.
6
For vertical (upflow or downflow) applications, the
V
minimum cooling coil width shall not be less than furnace
width minus 1”. Additionally, a coil installed above an
upflow furnace or under a counterflow furnace may be
the same width as the furnace or may be one size larger
than the furnace. Example: a “C” width coil may be
installed with a “B” width furnace.
For upflow applications, the front of the coil and furnace
must face the same direction.
•If the furnace is installed in a residential garage, position
the furnace so that the burners and ignition source are
located not less than 18 inche s (457 mm) abov e the floor.
Protect the furnace from physical damage by vehicles.
•If the furnace is installed horizon t ally, the furnace access
doors must be vertical so that the burners fire horizontally
into the heat exchanger. Do not install the unit with the
access doors on the “up/top” or “down/bottom” side of
the furnace.
•Do not connect this furnace to a chimney flue that serves
a separate appliance designed to burn solid fuel.
•For counterflow installations, the air conditioning coil
must be downstream from the heat exchanger of the
furnace.
• Counterflow installation over a noncombustible floor.
Before setting the furnace over the plenum opening,
ensure the surface around the opening is smooth and
level. A tight seal should be made between the furnace
base and floor by using a silicon rubber caulking
compound or cement grout.
•Counterflow installation over a combustible floor. If
installation over a combustible floor become s necessary,
use an accessory subbase (see Specification Sheet
applicable to your model for details). A special accessory
subbase must be used for upright counterflow unit
installations over any combustible material including
wood. Follow the instructions with the subbase for proper
installations. Do not install the furnace directly on
carpeting, tile, or other combustible material other than
wood flooring. (NOTE: The subbase will not be required
if an air conditioning coil is installed between the supply
air opening on the furnace and the floor.
ent Pipe Clearance to Combustibles6" using Single Wall Connector or 1"
using B-1 vent.
Top - 1"
Back - 0"
•Adequate combustion/ventilation air must be supplied
to the closet.
•Furnace must be completely sealed to floor or base.
Combustion/ ventilation air supply pipes must terminate
12" from top of closet and 12" from floor of closet. DO
NOT remove solid base plate for side return.
•Return air ducts must be completely sealed to the furnace
and terminate outside the enclosure surfaces.
CLEARANCESAND ACCESSIBILITY
Unobstructed front clearance of 24" for servicing is recommended.
VENT
B1-VENT SINGLE
1"6"1"3"0"1"
Top clearance for horizontal configuration - 1"
SIDESFRONTBACK
INSTALLATION POSITIONS
An upflow furnace may be installed in an upright position or horizontal on either the left or right side panel. Do not install this
furnace on its back. For vertically installed upflow furnaces, return air ductwork may be attached to the side panel(s) and/or
basepan. For horizontally installed upflow furnaces, return air
ductwork must be attached to the basepan. For counterflow fur-
naces, return ductwork must be attached to the top end of the
blower compartment.
NOTE: Ductwork must never be attached to the back of the furnace.
HORIZONTAL INSTALLATION
horizontal installations,
For
insert the
#8 x 5/8 screw
from the
literature package.
TOP
(PLENUM)
Side
Clearance - 1"
Line contact to framing is permitted when installed in the horizontal configuration. Line contact is defined as the portion of the
cabinet that is formed by the intersection of the top and side.
ACCESSIBILITY CLEARANCE, WHERE GREA TER, SHOULD T AKE PRECE DENCE OVER MINIMUM FIRE PROTECTION CLEARANCE. A gas-fired
furnace for installation in a residential garage must be installed
Front Clearance - 3"
7
so that the ignition source and burners are located not less than
eighteen inches (18") above the floor and is protected or located to
prevent physical damage by vehicles. A gas furnace must not be
installed directly on carpeting, tile, or other combustible materials other than wood flooring.
FURNACE SUSPENSION
If suspending the furnace from rafters or joist, use 3/8" threaded
rod and 2”x2”x3/8” angle iron as shown below. The length of rod
will depend on the application and the clearances necessary.
Suspended Furnace
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting system
serving other appliances, the venting system may be too large to
properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the Ameri-
can National Standard/National Standard of Canada for Gas-Fired
Central Furnaces ANSI Z21.47-Latest Edition, CSA-2.3-Latest Edition Section 1.23.1. The following steps shall be followed with
each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system
are not in operation:
a.Seal any unused openings in the venting system;
b.Inspect the venting system for proper size and horizontal
pitch, as required by the National Fuel Gas Code, ANSI
Z223.1 or the CAN/CSA B149 Installation Codes and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition;
c.In so far as practical, close all building doors and
windows and all doors between the space in which the
appliance(s) connected to the venting system are located
and other spaces of the building. Turn on clothes dryers
and any appliance not connected to the venting system.
Turn on any exhaust fans, such as range hoods and
bathroom exhausts, so they shall operate at maximum
speed. Do not operate a summer exhaust fan. Close
fireplace dampers;
d.Follow the lighting instructions. Place the appliance being
inspected in operation. Adjust thermostat so appliance
shall operate continuously;
e.Test for draft hood equipped appliance spillage at the
draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle;
f.After it has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows, exhaust
fans, fireplace dampers and any other gas burning
appliance to their previous conditions of use;
g.If improper venting is observed during any of the above
tests, the common venting system must be corrected.
Corrections must be in accordance with the latest edition of the
National Fuel Gas Code NFP A 54/ANSI Z223.1 and/or CAN/CSA B149
Installation Codes.
If resizing is required on any portion of the venting system, use the
appropriate table in the latest edition of the National Fuel Gas
Code ANSI Z223.1 and/or CAN/CSA B149 Installation Codes.
THERMOSTAT LOCATION
In an area having good air circulation, locate the thermostat about
five feet high on a vibration-free inside wall. Do not install the
thermostat where it may be influenced by any of the following:
•Drafts, or dead spots behind doors, in corners, or under
cabinets.
•Hot or cold air from registers.
•Radiant heat from the sun.
•Light fixtures or other appliances.
•Radiant heat from a fireplace.
•Concealed hot or cold water pipes, or chimneys.
•Unconditioned areas behind the thermostat, such as an
outside wall.
Consult the instructions packaged with the thermostat for mounting instructions and further precautions.
C
OMBUSTION AND VENTILA TION AIR REQUIREMENTS
WARN ING
TO
AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
SUFFICIEN T FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF
FLUE GASES MUST BE SUPPLIED
SUPPLIED INTO THE FURNACE AREA
. M
OST HOMES REQUIRE OUTSIDE AIR BE
.
Improved construction and additional insulation in buildings have
reduced heat loss by reducing air infiltration and escape around
doors and windows. These changes have helped in reducing heating/cooling costs but have created a problem supplying combustion and ventilation air for gas fired and other fuel burning appliances. Appliances that pull air out of the house (clothes dryers,
exhaust fans, fireplaces, etc.) increase the problem by starving
appliances for air.
House depressurization can cause back drafting or improper combustion of gas-fired appliances, thereby exposing building occupants to gas combustion products that could include carbon monoxide.
,
8
If this furnace is to be installed in the same space with other gas
appliances, such as a water heater, ensure there is an adequate
supply of combustion and ventilation air for all appliances. Refer
to the latest edition of the National Fuel Gas Code NFPA 54/ANSI
Z223.1 or CAN/CSA B149 Installation Codes or applicable provisions of the local building codes for determining the combustion
air requirements for the appliances.
This furnace must use indoor air for combustion. It cannot be installed as a direct vent (i.e., sealed combustion) furnace.
Most homes will require outside air be supplied to the furnace
area by means of ventilation grilles or ducts connecting directly
to the outdoors or spaces open to the outdoors such as attics or
crawl spaces.
C
ATEGORY
I V
ENTING
(V
ERTICAL VENTING
)
WARN ING
TO
PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO
ASPHYXIATION, THIS FURNACE MUST BE CATEGORY
VENT USING CATEGORY
III
VENTI NG
.
I
VENTED
. DO
NOT
Category I V enting is venting a t a non-positive pre ssure. A furnace
vented as Category I is considered a fan-assisted appliance and
the vent syst em does not have to be “ ga s tight. ” NOTE: Single st age
gas furnaces with induced draft blowers draw products of combustion through a heat exchanger allowing, in some instances,
common venting with natural draft appliances (i.e. water heaters). All installations must be vented in accordance with National
Fuel Gas Code NFP A 54/ANSI Z223.1 - lat est e dition. In Cana da, the
furnaces must be vented in accordance with the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions and amendments.
NOTE: Masonry vent kit (MVK-01 and MVK-02) is to only be used
on interior masonry chimneys or qualifying exterior masonry
chimney applications identified in the MVK kit installation
instructions. To ensure safe and reliable operation, use only the
kit listed for your model.
KitInp ut KBTU RangeL imit Sett i ng
MVK-0140-100250°F
MVK-02120-140290°F
This kit is for use on Amana
Note :
33” tall “H” and “S” model furnaces installed in the upflow position only.
®
brand and Goodman® brand 80% AF UE,
NOTE: The vertical height of the Category I venting system must be
at least as great as the horizontal length of the venting system.
WARNING
TO
PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO
ASPHYXIATION, COMMON VENTI NG WITH OTHER MANUFACTURER’S
INDUCED DRAFT APPLIANCES IS NOT ALLOWED
.
The minimum vent diameter for the Category I venting system is as
shown:
MODEL
404 Inch4 Inch
604 Inch4 Inch
804 Inch4 Inch
1005 Inch5 Inch
1205 InchN/A
1405 InchN/A
UPFLOWCOUNTERFLOW
MINIMUM VENT
Under some conditions, larger vents than those shown above may
be required or allowed. When an existing furnace is removed froma venting system serving other appliances, the venting system may
be too large to properly vent the remaining attached appliances.
Upflow or Horizontal units are shipped with the induced draft
blower discharging from the top of the furnace. (“T op” is as viewed
for an upflow installation.) The induced draft blower can be rotated 90 degrees with the (0270F01119) chimney transition bottom kit for Category I venting. For upflow models installed vertically or horizontally, a four inch single wall pipe can be used to
extend the induced draft blower outlet 1/2” beyond the furnace
cabinet. THIS PRODUCT IS NOT DESIGNED FOR COUNTERCLOCK-
WISE INDUCED DRAFT BLOWER ROT A TION.
Vent the furnace in accordance with the National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest edition.
Venting - F urnace Installed in Horiz ont al Position
THIS FURNACE IS NOT DESIGN CERTIFIED TO BE HORIZONTALLY
VENTED THROUGH AN EXTERIOR SIDE W ALL.
The following describes an optional venting procedure when the
furnace is installed in the horizontal left discharge position.
To rotate the induced draft blower clockwise, you will need to
purchase one (0270F01119) chimney transition bottom kit.
1. Disconnect electrical power from the furnace.
2. Disconnect the induced draft blower power leads, flue pipe,
and pressure switch tubing.
3. Remove the round cutout fr om the right side of the wrapper.
4. Remove and save the four screws that fasten the induced
draft blower to the flue collector box.
5. Remove and save the three screws that hold the chimney
assembly to the induced draft blower.
6. Remove and save the four screws that fasten the chimney
top to the chimney bottom.
9
7. Remove the chimney transition bottom from the transition
bottom kit.
8. Install the chimney top with the four screws retained from
step 6 onto the new chimney transition bottom from the
transition bottom kit.
9. Remove the induced draft blower and install the new
chimney assembly to it using the three screws retained
from step 5.
10. Rotate the induced draft blower 90 degrees to the right,
feed the flue pipe through the round cutout from the outside
of the wrapper, and fit onto the chimney top assembly.
Secure the pipe to the chimney top from the front, top, and
bottom using (3) screws and rotating the induced draft
blower to properly orient the assembly. NOTE: If the pipe
section is less than 18” , then att ach it directly to the chimney
top on 3 sides and feed it through the round cutout from the
inside of the wrapper.
11. Reattach the induced draft blower using the (4) screws
retained from step 3. Ensure the gasket located between
the induced draft blower and collector box is rotated
accordingly.
12. Reconnect the induced draft blower power leads. NOTE: If
the wires are not long enough, pull extra wire from the wire
bundle in the blower compartment.
13. Reconnect the remaining flue pipe, and the pressure switch
tubing. Ensure that all wires and the pressure switch tubing
is at least one inch from the flue pipe, or any other hot
surface.
14. Restore power to furnace.
NOTE: In a horizontal installation the air conditioning coil must
be adequately supported by proper brackets and supports.
Inadequate coil support can result in furnace cabinet distortion
and air leakage.
Counterflow units are shipped with the induced draft blower discharging from the top of the furnace. (“T op” a s viewed for a counterflow installation.)
Vent the furnace in accordance with the National Fuel Gas Code
NFPA54/ANSI Z223.1-latest edition.
WARNING
P
OSSIBILITY OF PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
DAMAGING COND ENSATION CAN OCCUR INSIDE MASONRY CHIMNEYS
WHEN A SINGLE FAN-ASSISTED CATEGORY
FURNACE) IS VENTED WITHOUT ADEQUATE DILUTION AIR
CONNECT AN
FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPED
APPLIANCE OR THE CHIMNEY IS LINED WITH A METAL LINER OR TYPE
METAL VENT
SIZED IN ACCORDANCE WITH THE APPROPRIATE VENTI NG TABLES
80%
APPLIANCE, THE POTENTIAL FOR COND E NSATION DAMAGE MAY STILL
EXIST WITH EXTREMELY COLD CONDITION S, LONG VENT CONNECTORS
EXTERIOR CHIMNEYS, OR ANY COMBIN ATIO N OF THESE CONDITIONS
HE RISK OF COND ENSATION DAMAGE IS BEST AVOIDED BY USING
T
MASONRY CHIMNEY AS A PATHWAY FOR PROPERLY SIZED METAL LINER
OR TYPE
80%
FURNACE TO A MASONRY CHIMNEY UNLESS THE
. ALL
INSTALLATIONS USING MASONRY CHIMNEYS MUST BE
FURNACE IS COMMON VENTED WITH A DRAFT HOOD EQUIPPE D
B
METAL VENT
Clean Out
Typical Multiple Flue Clay Tile Chimney
Throat
Damper
Breech
.
Clay Tile Size: 8" x 8" x12 "
I
APPLIANCE
Wash
(Each x 24" Length)
1/2" to 1" Air Space
F.A .F. Vent
Connector
Fan Assisted
Forced Air
Furnace
Roof Line
Attic Floor
Second Floor
First Floor
Water Heater
Vent Connector
Natural Draft
Water Heater
Basement Floor
(80% AFUE
. DO
NOT
CHECKLIST SUMMARY
B
. IF AN
,
.
WARN ING
N
EVER ALLOW THE PRODUCTS OF COMBUSTION, INCLUDING CARBON
MONOXIDE, TO ENTER THE RETURN DUCTWORK OR CIRCULATION AIR
SUPPLY
.
EXTERIOR MASONRY CHIMNEYS (CATE GORY I FURNACES ONL Y)
An exterior masonry chimney is defined as a “Masonry” chimney
exposed to the outdoors on one or more side s below the roof line. ”
The ability to use a clay lined masonry chimney depends on a
parameter not associated with interior chimneys. This variable is
the geographic location of the installation. Researchers have discovered that the winter design temperatures have a direct impact
on the suitability of this type of venting. In most situations, the
existing masonry chimneys will require a properly sized metallic
liner.
This checklist serves as a summary of the items to be checked
before venting an 80+ furnace into a masonry chimney. In addition, we recommend that a qualified serviceman use this checklist
to perform a yearly inspection of the furnace venting system.
This checklist is only a summary. For detailed information on
each of the procedures mentioned, see the paragraph referenced
with each item.
10
Proper Chimney
Termination?
(Check 1)
If the chimney does not meet these termination requirements, but
all other requirements in the checklist can be met, it may be possible for a mason to extend the chimney. If this will not be practical, see Fix 1.
10' or Less
Chimney channel
free of solid and
liquid fuel
appliances?
(Check 2)
Crown in good
condition
(Check 3)
Cleanout free of
debris?
(Check 4)
Liner in good
condition?
(Check 5)
Change venting
arrangements
(Fix 2)
Rebuild crown
(Fix 3)
and/or Reline
(Fix 4)
Reline
(Fix 4)
Reline
(Fix 4)
2' Min.
Termination 10 Feet Or Less From Ridge, Wall or Parapet
2' Min.
Wall o r
Parapet
Chimney
10' or Less
2' Min.
Chimney
More than 10’
3' Min.
3' Min.
3’ Min.
Dilution air
available?
(Check 6)
Reline
(Fix 4)
Complete the
installation.
(Check 7)
CHECK 1 - PROPERCHIMNEYTERMINATION.
A masonry chimney used as a vent for gas fired equipment must
extend at least three feet above the highest point where it passes
through the roof. It must extend at least two feet higher than any
portion of a building within a horizontal distance of 10 feet. In
addition, the chimney must terminate at least 3 feet above any
forced air inlet located within 10 feet. The chimney must extend at
least five feet above the highest connected equipment draft hood
outlet or flue collar.
NOTE:
No Height
above parapet
Wall or
Parapet
Ridge
Termination More Than 10 Feet From Ridge, Wall or Parapet
required when distance
from walls or parapet is
more than 10 feet.
More than 10’
Chimney
10’
2” Min.
Chimney
Height above any
roof surface within
10 feet horizontally.
Solid fuel appliances include fireplaces, wood stoves, coal furnaces, and incinerators.
Liquid fuel appliances include oil furnaces, oil-fired boilers and
oil-fired water heaters.
CHANNEL
11
Appliances which burn propane (sometimes referred to as LP (liquefied petroleum)) gas are considered gas-fired appliances.
CHECK 3 - CHIMNEY CROWN CONDITION.
Damage from condensate usually shows up first in the crown. If
any of the following trouble signs are present, the condition of the
crown is not satisfactory:
a) Crown leaning
b) Bricks missing
c) Mortar missing
d) T ile liner cracked
e) No tile liner
f) Salt staining at mortar joints. (White stains, and mortar
becomes sandy and/or erodes.)
For problems a, b, or c, see Fix 3. If problems d, e, or f are present,
see Fix 4. IMPORT ANT : It may be nece ssary to follow both Fix 3 and
Fix 4.
CHECK 4 - DEBRISIN CLEANOUT
A cleanout (dropleg) must be present such that the upper edge of
the cleanout cover is at least 12 inches below the lower edge of the
lowest chimney inlet opening.
A chimney without a cleanout could become partially blocked by
debris. If no cleanout is present, the chimney must be relined (Fix
4). Remove the cleanout cover, and examine the cleanout for debris. If significant amounts of any of the following are found:
•Fuel oil residue
•Bricks
•Mortar or sand
•Pieces of the tile liner
•Rusted pieces of the metallic liner - reline the chimney
(Fix 4).
CHECK 5 - LINER CONDITION.
If a metal liner is present, it must be checked. It cannot be assumed that all existing metal liners are correctly installed and in
good condition.
Remove the lowe st existing ven t connector , and e xamine the inside
of the elbow or tee at the base of the liner. A small amount of soot
may be considered acceptable, provided the installer vacuums it
away. If rusted pieces of the liner have collected here, the metal
liner must be removed and replaced (Fix 4).
Next, gently tap the inside of the liner with a Phillips screwdriver.
If the screwdriver perforates the liner, or if the tapping does not
sound like metal hitting metal, the liner must be removed and
replaced (Fix 4).
Remember that all appliances must be vented inside the liner.
Venting one appliance inside the liner and another appliance outside the liner is not acceptable.
Next, use a flashlight and small mirror to sight up the liner. B vent
must be supported so as to not come into direct contact with the
chimney walls or tile liner. If it is not, it can probably be rehung so
as to be acceptable. A thimble or fire stop may be helpful here.
Flexible liners should be hung straight or nearly straight. If it is
spiraled in the chimney and in good condition, it should be rehung.
To do this, break the top seal; pull up and cut off the excess liner
length, and refit the top seal. Use caution when doing this, as the
cut edges of flexible liners may be sharp.
The surfaces of the liner must be physically sound. If gaps or holes
are present, the metal liner must be removed and replaced (Fix 4).
Finally, confirm that the metal liner is the correct size for the
appliances to be installed. Use the GAMA tables and rules.
If a metal liner is not present, a clay tile liner must be present, or
the chimney must be lined (Fix 4).
Use a flashlight and small mirror at the cleanout or vent connector to inspect the clay tile liner. If any of the following problems
are present:
•T ile sections misaligned
•T ile sections missing
•Gaps between tile sections
•Signs of condensate drainage at the cleanout or vent
connectors
•Mortar protruding from between tile sections
•Use of sewer pipe or drainage pipe rather than an
approved fire clay tile reline the chimney (Fix 4).
Next, measure the size of the liner. It may be possible to do this
from the cleanout. The liner must be at least as large as the minimum size established by the tables in National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest edition and in the National Standard
of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest editions
and amendments. If the liner is too small or too large, then the
chimney must be relined (Fix 4).
CHECK 6 - DILUTION AIR.
If gas-fired appliances are to be vented into a clay tile liner, a
source of dilution air is required.
Dilution air cannot be obtained through:
•Induced draft appliances
•Natural draft appliances with vent dampers
Sufficient dilution air can ordinarily be obtained through the draft
hood of a natural draft appliance only if the appliance’s vent
connector does not include a vent damper. If dilution air wi ll not
be available, the chimney must be relined (Fix 4).
CHECK 7 - COMPLETETHE INSTALLATION.
If Checks 1 through 6 have been satisfactory, and the liner is an
acceptable size as determined by the tables in National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition and in the National
Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest
editions and amendments, then the clay tile liner can probably be
used as a vent for the gas appliances. However, the installer must
keep in mind the following factors which may render the tile liner
unsuitable for use as a vent:
12
•Extremely cold weather
•Long vent connectors
•Masonry chimneys with no air gap between the liner and
the bricks. (In practice, this can be difficult to detect.)
•Exterior chimneys (The tables in National Fuel Gas Code
NFPA 54/ANSI Z223.1 - latest edition and in the National
Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2
- latest editions and amendments assume interior
chimneys.)
If, in the judgment of the local gas utility, installer, and/or local
codes; one or more of the above factors is likely to present a
problem, the chimney must be relined (Fix 4).
FIX 1 - LINER TERMINATION
Any cap or roof assembly used with a liner must be approved by
the liner manufacturer for such use. The liner and cap/roof assembly must then terminate above the roof in accordance with the
manufacturer’s instructions.
In some cases, a shorter extension above the roof may be possible
with a liner than would be required with a masonry chimney.
For further information on relining, see Fix 4.
FIX 2 -CHANGE VENTING ARRANGEMENTS
If the masonry chimney has more than one channel, it may be
possible to vent the gas appliances into one channel and vent the
solid or liquid fuel appliance(s) into another channel(s). Do not
vent an 80+ Furnace inside of a metal liner with other appliances
vented outside the liner.
Alternatively, the homeowner may agree to discontinue use of the
fireplace (solid fuel appliance). If so, the tile liner must be cleaned
to remove creosote buildup. The fireplace opening must then be
permanently sealed.
If oil-fired appliance(s) are being replaced by gas-fired
appliance(s), the tile liner must first be cleaned to remove the fuel
oil residue.
If none of the above options is practical, the furnace may need to
be vented vertically with a B Vent.
Under some conditions, a 90%+ furnace could be installed rather
than an 80% furnace. The 90%+ furnace can be vented horizontally
or vertically through PVC pipe.
FIX 3 - REBUILDTHE CROWN
If the chimney crown is damaged, a qualified mason must repair it
in accordance with nationally recognized building codes or standards. One such standard which may be referenced is the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, ANSI/NFPA 211.
FIX 4 - RELINING
Relining options include B vent and flexible liners.
If the chimney has diagonal offsets, B vent probably cannot be
used.
If B vent is to be used, it must be supported adequately. Supports
(such as fire stops or thimbles) must be used to prevent the B vent
from coming into direct contact with the tile liner or chimney
walls. Direct contact would result in higher heat loss, with an
increased possibility of poor venting system performance.
It is not acceptable to vent one appliance inside the B vent and
other appliances outside. The excess space between the B vent and
the chimney walls must be covered at the top of the chimney by a
weatherproof, corrosion resistant flashing.
The B vent should then be topped with a listed vent cap. The listed
vent cap will, when installed per the manufacturer ’s instructions,
prevent problems due to rain, birds, or wind effects.
A B-vent installed as described in this section is considered to be
an enclosed vent system, and the sizing tables in National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National
Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest
editions and amendments may be used.
If a flexible liner is to be used, it must be made of the proper
materials:
•For most residential applications, an aluminum liner
should be acceptable.
•If the combustion air supplied to the furnace will be
contaminated with compounds containing chlorine or
fluorine, a liner of AL 29-4C stainless steel should be
used. Common sources of chlorine and fluorine
compounds include indoor swimming pools and chlorine
bleaches, paint strippers, adhesives, paints, varnishes,
sealers, waxes (which are not yet dried) and solvents
used during construction and remodeling. Various
commercial and industrial processes may also be sources
of chlorine/fluorine compounds.
•Heavier gauge 300 and 400 series stainless steel liners
were developed for use with oil or solid fuel appliances.
They are not suitable for use with gas-fired appliances.
Flexible liners specifically intended and tested for gas
applications are listed in the UL “Gas and Oil Equipment
Directory”. (UL Standard 1777).
For sizing of flexible liners, see the tables in the National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition and in the National
Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2 - latest
editions and amendments.
To install the liner, read and follow the liner manufacturer’s instructions and your local codes. Excess liner length should be
pulled out of the chimney and cut off . U se caution when doing this,
as the cut edges of flexible liners may be sharp. Do not spiral
excess liner inside of the chimney. Support the liner as recommended by the liner manufacturer.
Some manufacturers of flexible liners offer an insulation sleeve
designed to be added to the liner before it is installed in the chimney. (Poured insulation, either vermiculite or other materials, is
no longer recommended.) Insulation will need to be added to the
flexible liner if:
•It is required by the liner manufacturer’s instructions.
13
•The previous liner was properly sized and installed, and
suffered from condensation damage.
•It is required by your local building codes.
Even if none of those three conditions exist which require additional liner insulation, the installer may wish to consider it if:
•The local climate is very cold.
•The chimney is very tall.
•The vent connectors used are very long or have a large
number of elbows.
•Local experience indicates that flexible liners installed
without insulation are likely to have condensation
problems.
Insulation must be selected and installed in accordance with the
liner manufacturer’s instructions.
Finally, cap the chimney and terminate the liner in accordance
with the liner manufacturer’s instructions.
E
LECTRICAL CONNECTIONS
115 VOLT LINE CONNECTIONS
Before proceeding with electrical connections, ensure that the supply voltage, frequency, and phase correspond to that specified on
the unit rating plate. Power supply to the furnace must be NEC
Class 1, and must comply with all applicable codes. The furnace
must be electrically grounded in accordance with local codes or,
in their absence, with the latest edition of The National Electric
Code, ANSI NFP A 70 and/ or The Canadian Electric Code CSA C22.1.
Use a separate fused branch electrical circuit containing properly
sized wire, and fuse or circuit breaker. The fuse or circuit breaker
must be sized in accordance with the maximum overcurrent protection specified on the unit rating plate. An electrical disconnect
must be provided at the furnace location.
Line voltage wiring must enter into the junction box provided with
the furnace.
NOTE: Line polarity must be observed when making field
connections.
FOSSIL FUEL APPLICATIONS
WARN ING
HIGH VOLTAGE !
TO
AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO
THE UNIT MUST BE POLARIZED AND GROUNDED
.
WARN ING
HIGH VOLTAGE !
TO
AVOID PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER
BEFORE SERVICING OR CHANGING ANY ELECTRICAL
WIRING
.
CAUTION
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS
OPERATION
. W
IRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
. V
ERIFY PROPER OPERATION AFTER SERVICING
WARN ING
HIGH VOLTAGE !
TO
AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR
DEATH, THE FURNACE MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN
THEIR ABSENCE, WITH THE LATEST EDITION OF THE
N
ATIONAL ELECTRIC CODE
.
This furnace can be used in conjunction with a heat pump in a
fossil fuel application. A fossil fuel application refers to a combined gas furnace and heat pump installation which uses an outdoor temperature sensor to determine the most cost efficient means
of heating heat pump or gas furnace.
A heat pump thermostat with two stages of heat is required to
properly use a furnace in conjunction with a heat pump. Refer to
the fossil fuel kit installation instructions for additional thermostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit installation instructions. All furnace connections must be made to the
furnace integrated control module and the FURNACE terminal strip
on the fossil fuel control board.
JUNCTION BOX RELOCATION
.
E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
Line voltage connections can be made through either the right or
left side panel. The furnace is shipped configured for a right side
electrical connection. To make electrical connections through the
opposite side of the furnace, the junction box must be relocated to
the left side prior to making electrical connections. To relocate
the junction box, perform the following steps.
WARNING
.
. USE
GLOVES AS A
WIRING HARNESS
The wiring harness is an integral part of this furnace. Field alteration to comply with electrical codes should not be r equired. Wires
are color coded for identification purposes. Refer to the wiring
diagram for wire routings. If any of the original wire as supplied
with the furnace must be replaced, it must be replaced with wiring
material having a temperature rating of at least 105° C. Any replacement wiring must be a copper conductor.
WARNING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK
DISCONNECT ELECTRICAL POWER BEFORE INSTALLING OR SERVICING THIS
UNIT
.
1. Remove both doors from the furnace.
2. Remove and save the screws holding the junction box to
the right side of the furnace.
14
,
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.