OLS350, OLS350220
Offline Switching Power Supply/Charger
Overview:
This power supply/charger converts 115VAC / 60Hz or 220VAC / 50Hz input, into a 24VDC @ 12 amp of continuous
supply current (see specifications).
Specifications:
• 24VDC output.
• Input: OLS350 - 115V
OLS350220 - 220V
• Maximum charge current 0.7 amp.
• 12 amp continuous supply current at 24VDC.
• Filtered and electronically regulated outputs.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when
AC fails (zero voltage drop).
AC / 60Hz 5.0 amp or
AC / 50Hz 3.0 amp.
Installation Instructions:
Unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the unit in desired location/enclosure.
2. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G].
Use 18 AWG or larger for all power connections (Battery, DC output, AC input).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
3. Connect devices to be powered to terminals marked [--- DC +].
Note: It is important to measure output voltage before connecting devices. This helps avoid potential damage.
4. When the use of stand-by batteries are desired, they must be lead acid or gel type.
Connect batter
Note: When batteries are not used a loss of AC will result in the loss of output voltage.
5. Connect appropriate signaling notification devices to A
relay outputs marked [NC, C, NO].
y to terminals marked [--- BAT +] (battery leads included).
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
• Short circuit overload protection.
• Includes battery leads.
Board Dimensions: 4.5”W x 7.5”L x 1.75”H
Specified at 25˚ C ambient.
C Fail & Low battery supervisory
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal Legend Power Supply Status
L, G, N Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground.
--- D C + 24VDC @ 12 amp continuous output.
AC FAIL
NC, C, NO
Low Battery
NC, C, NO
--- BAT + Stand-by battery connections. Maximum charge rate 0.7 amp.
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present. Contact rating 1 amp @ 28VDC
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present.
Contact rating 1 amp @ 28VDC.
Low battery threshold: 24VDC output threshold set @ approximately 20.5VDC.
OLS 350
ALTRONIX CORP.
BKLYN, N.Y. 11220
MADE IN USA
LOW BAT
NC C NO NC C NO
--- BAT + --- DC +
AC DC
AC FAIL