Altronix OLS180220 Installation Manual

OLS180220 Off-Line Switching Power Supply/Charger
Overview:
The OLS180220 is a power supply/charger that converts 220VAC (working range 198VAC-256VAC), 50/60Hz input into a 12VDC or 24VDC @ 6A of continuous supply current (see specifications).
Specifications:
Input:
• 220VAC (working range 198VAC-256VAC), 50/60Hz,
0.8A.
Output:
• 12VDC or 24VDC selectable output.
• 6A continuous supply current.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current 0.5A.
Voltage Output Selection Table:
Output VDC Switch Position Max. Load DC
12VDC SW 1 - ON 6A 24VDC SW1 - OFF 6A
Supervision:
• AC fail supervision (form “C” contacts).
• Battery presence and low battery supervision (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Features:
• Power ON/OFF switch.
• Includes battery leads.
Board Dimensions (L x W x H):
7.25” x 4.5” x 1.75” (184.1mm x 114.3mm x 44.45mm).
Installation Instructions:
1. Mount the OLS180220 in the desired location/enclosure.
2. Slide [Power ON/OFF] switch to OFF position.
3. Set the OLS180220 to the desired DC output voltage via SW1 (Voltage Output Selection Table).
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
4. Connect AC power to the terminals marked [L & N], connect ground to the terminal marked [G]. Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
5. Measure output voltage before connecting devices. This helps avoiding potential damage.
6. Connect devices to be powered to the terminals marked [– DC + ].
7. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
8. Connect appropriate signaling notification devices to AC Fail and Low Battery supervisory relay outputs marked [NC, C, NO].
9. Slide [Power ON/OFF] switch to ON position.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output. Short circuit or thermal overload condition. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal Legend Function/Description
L, G, N Connect 220VAC to these terminals: L to Hot, N to Neutral, G to ground. – DC + 12VDC / 24VDC @ 6A continuous output. AC FAIL
NC, C, NO
Low Battery NC, C, NO
– BAT + Stand-by battery connections. Maximum charge rate 0.5A.
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC, 24VDC output threshold set @ approximately 21VDC.
ON
OFF - 24V ON - 12V
OFF ON
5A 250V
LG N
DC
AC
AC FAIL
NC C NO NC C NO
LOW BAT
--- BAT + --- DC +
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 website: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A. IIOLS180220 - Rev. 010704 H25P