ALTV2432 Series
CCTV Power Supplies
Installation Guide
Models Include:
• ALTV2432 • ALTV2432CB
- 24VAC @ 8 amp (200VA) - 24VAC @ 8 amp (200VA)
or 28VAC @ 7 amp. or 28VAC @ 7 amp.
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
• ALTV2432350 • ALTV2432350CB
- 24VAC @ 14 amp (350VA) - 24VAC @ 14 amp (350VA)
or 28VAC @ 12.5 amp (350VA). or 28VAC @ 12.5 amp (350VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
• ALTV2432600 • ALTV2432600CB
- 24VAC @ 28 amp (700VA) - 24VAC @ 28 amp (700VA)
or 28VAC @ 25 amp (700VA). or 28VAC @ 25 amp (700VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
Rev. 021704
![](/html/6f/6ff1/6ff1c332f7718e7da95fe29e769967abec7e119854ab6371f0092f88b951daa1/bg2.png)
Overview:
These Altronix CCTV Power Supplies provide 24VAC/28VAC distributed via thirty-two (32) fuse or PTC protected
outputs for powering CCTV Cameras, heaters and other video accessories.
Thirty-two (32) Output ALTV2432 Reference Chart:
Altronix
Model Number
Output Voltage
(Power)
Total Output Current
Outputs
Number of
PTC Protected Outputs
Outputs
Fuse Protected
(Class 2 power limited)
Output Current
(max per output)
50/60Hz Input
Current
115VAC
ALTV2432
ALTV2432CB
ALTV2432350
ALTV2432350CB
ALTV2432600
ALTV2432600CB
24VAC 8 amp
32 - x 3.5 amp 2.9 amp
28VAC 7 amp
24VAC 8 amp
32 x - 2.5 amp 2.9 amp
28VAC 7 amp
24VAC 14 amp
32 - x 3.5 amp 2.7 amp
28VAC 12.5 amp
24VAC 14 amp
32 x - 2.5 amp 2.7 amp
28VAC 12.5 amp
24VAC 28 amp
32 - x 3.5 amp 5.4 amp
28VAC 25 amp
24VAC 28 amp
32 x - 2.5 amp 5.4 amp
28VAC 25 amp
Specifications:
Ease of installation saves time & eliminates costly labor.
Surge suppression.
•
• AC power LED indicator.
wer ON/OFF switch / circuit-breaker.
o
P
•
• Unit maintains camera synchronization.
•
• Spare fuses included (on fuse protected models).
Enclosure Dimensions:
13"H x 13.5"W x 3.25"D
Installation Instructions:
Mount unit in desired location.
1.
2. Turn OFF main switch on unit
3. All units are factory set for 24VAC operation.
or 28VAC operation, adjust unit prior to mounting and applying power as follows: Change the wire position so that
F
the black wire [28V] is connected to the terminal marked [P] and the yellow wire [24V] is connected to the
termi nal marked [S]
4. Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1-3, pgs. 4-6), secure green lead to
round. Use 18 AWG or larger for all power connections.
th g
ear
5. Measure output v
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting
the output voltage.
6. Connect devices to terminals marked [1P - 1N through 16P - 16N] on PD16W/PD16WCB board
(Figs. 1-3, pgs. 4-6), carefully observing polarity. Terminals marked [1P - 16P] are of the same polarity.
.
oltage before connecting de
(Figs. 1-3, pgs. 4-6).
vices.
This helps avoid potential damage.
- 2 -
![](/html/6f/6ff1/6ff1c332f7718e7da95fe29e769967abec7e119854ab6371f0092f88b951daa1/bg3.png)
7. Turn main switch on unit to the ON (RESET) position (Figs. 1-3, pgs. 4-6).
8.
Green LED(s) will illuminate when unit is powered.
9.
Upon completion of wiring, secure enclosure door with screws (supplied).
Caution:
Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes
and in accordance with the National Electrical Code. Use 75 C or higher rated UL insulated wiring for
connecting the unit to the mains.
Terminal Identification:
PD16W - Power Distribution Module
1P - 16P AC output.
1N - 16N AC output.
- 3 -